HomeMy WebLinkAbout19.12.17-Bibibop The Bridges-Lighting COMcheckCOMcheck Software Version 4.1.1.0
Interior Lighting Compliance Certificate
Project Title:
90.1 (2007) Standard
Project Type:Alteration
Construction Site:
365 West 116th Street
Carmel, IN 46032
Owner/Agent:
Bibibop
Carmel, IN 46032
Designer/Contractor:
Chris Jenkins
Dunham Associates
50 South 6th Street
Suite 1100
Minneapolis, MN 55402
Project Information
Energy Code:
Bibibop
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1-Vestibule 101 (Common Space Types:Lobby)47 1.30 61
2-Dining 102 (Common Space Types:Dining Area - Family Restaurant)940 2.10 1974
3-Kitchen 103 (Common Space Types:Food Preparation)484 1.20 581
4-Scullery 104 (Common Space Types:Active Storage)134 0.80 107
5-Corridor 106 (Common Space Types:Corridor/Transition)289 0.50 144
8-Family 109 (Common Space Types:Restrooms)53 0.90 48
9-Family 110 (Common Space Types:Restrooms)53 0.90 48
6-Utility 107 (Common Space Types:Workshop): Exempt
7-Storage 108 (Common Space Types:Active Storage): Exempt
2963Total Allowed Watts =
Area Category Exemption Qualifications
Activity Area
# Fixtures
Repl./AddedPre-Alt.null
Total # Watts
Pre-Alt.Post-Alt.
Utility 107 ( Common Space Types:Workshop 39 sq.ft.)1 0
Exemption: Less than 50% fixture replacement.
72.000 72.000
Storage 108 ( Common Space Types:Active Storage 42
sq.ft.)
1 0
Exemption: Less than 50% fixture replacement.
72.000 72.000
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Vestibule 101 ( Common Space Types:Lobby 47 sq.ft.)
LED 1: C: 6" Round Downlight: Other:1 2 7 15
Dining 102 ( Common Space Types:Dining Area - Family Restaurant 940 sq.ft.)
LED 2: A: 9.5" Pendant: Other:1 3 10 30
LED 3: B: 14" Pendant: Other:1 9 10 90
LED 4: H: Surface Mount Directional: Other:1 9 13 117
LED 5: J: 6" Pendant: Other:1 7 13 91
Project Title:
Data filename:
Bibibop
P:\2020\0420995-119-00 Bibibop - The Bridges - Carmel, IN\03-Electrical\02-Lighting\0420995-
119-00 Bibibop Carmel IN.cck
12/17/19Report date:
61 ofPage
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Kitchen 103 ( Common Space Types:Food Preparation 484 sq.ft.)
LED 7: C: 6" Round Downlight: Other:1 24 7 175
LED 8: D: 4" Round Downlight: Other:1 4 7 29
LED 9: E: 4" Round Downlight: Other:1 4 7 28
LED 10: G: Pendant: Other:1 3 16 48
Scullery 104 ( Common Space Types:Active Storage 134 sq.ft.)
LED 11: F: 2x4 Troffer: Other:1 3 85 255
Corridor 106 ( Common Space Types:Corridor/Transition 289 sq.ft.)
LED 12: J: 6" Pendant: Other:1 6 13 78
Family 109 ( Common Space Types:Restrooms 53 sq.ft.)
LED 13: C: 6" Round Downlight: Other:1 2 7 15
Family 110 ( Common Space Types:Restrooms 53 sq.ft.)
LED 14: C: 6" Round Downlight: Other:1 2 7 15
Utility 107 ( Common Space Types:Workshop 39 sq.ft.): Exempt
Storage 108 ( Common Space Types:Active Storage 42 sq.ft.): Exempt
985Total Proposed Watts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting
systems have been designed to meet the 90.1 (2007) Standard requirements in COMcheck Version 4.1.1.0 and to comply with
any applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting PASSES
Project Title:
Data filename:
Bibibop
P:\2020\0420995-119-00 Bibibop - The Bridges - Carmel, IN\03-Electrical\02-Lighting\0420995-
119-00 Bibibop Carmel IN.cck
12/17/19Report date:
62 ofPage
Christopher Jenkins 12/17/2019
Inspection Checklist
Requirements: 100.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.1.1.0
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 90.1 (2007) Standard
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
4.2.2
[PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the lighting and
electrical systems and equipment and
document where exceptions to the
standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: Sheet E100 - Light Fixture Schedule
8.4.1.1,
8.4.1.2
[PR6]2
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the electrical systems
and equipment and document where
exceptions are claimed. Feeder
connectors sized in accordance with
approved plans and branch circuits
sized for maximum drop of 3%.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: Sheet E100 & E200 General notes
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Bibibop
P:\2020\0420995-119-00 Bibibop - The Bridges - Carmel, IN\03-Electrical\02-Lighting\0420995-
119-00 Bibibop Carmel IN.cck
12/17/19Report date:
63 ofPage
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
9.4.1.1
[EL1]2
Automatic controls to shut off all
building lighting installed in buildings
>5,000 ft2.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: Sheet E100
9.4.1.2
[EL2]2
Independent lighting controls installed
per approved lighting plans and all
manual controls readily accessible and
visible to occupants.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: Sheet E100
9.4.1.4
[EL4]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: Sheet E100
9.4.2
[EL5]3
Ballasted one and three lamp fixtures
with >30 W/lamp have two lamp
tandem wired ballasts when >=2
fixtures in same space on same
control.
Complies
Does Not
Not Observable
Not Applicable
Exception: Electronic high-frequency ballasts.
Location on plans/spec: NA
9.4.3
[EL6]1
Exit signs do not exceed 5 watts per
face.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: Sheet E100 - Light Fixture Schedule
9.6.2
[EL8]1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Location on plans/spec: NA
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Bibibop
P:\2020\0420995-119-00 Bibibop - The Bridges - Carmel, IN\03-Electrical\02-Lighting\0420995-
119-00 Bibibop Carmel IN.cck
12/17/19Report date:
64 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
8.7.1
[FI16]3
Furnished as-built drawings for
electric power systems within 30 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
8.7.2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.2.2.3
[FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Bibibop
P:\2020\0420995-119-00 Bibibop - The Bridges - Carmel, IN\03-Electrical\02-Lighting\0420995-
119-00 Bibibop Carmel IN.cck
12/17/19Report date:
65 ofPage
Project Title:
Data filename:
Bibibop
P:\2020\0420995-119-00 Bibibop - The Bridges - Carmel, IN\03-Electrical\02-Lighting\0420995-
119-00 Bibibop Carmel IN.cck
12/17/19Report date:
66 ofPage