HomeMy WebLinkAbout Energy Certificate7277 ZAN.P,,SVILLE RD
CARMEL,,, IN 46033
Builder: LENNAR HOMES
Model: MERIDIAN_111 Community: LEGACY PRAIRIE 804
Ceiling Attic, R-38
Above -Grade -Walls- R-1-6
Foundation Walls N/A
Framed Floor R-30
Slab R-10.0 Perimeter, R-0.0
Under
Infiltration 1586 CFM50 (4.87 ACH50)
Window U-Value: 0.33, SHGC: 0.28
Building' Features
Duct Supply R-8.0, Return R-8.0
Duct Leakage -to -Outside 1-28-CFM @ 25Pa-(5:49-/ 1-00-s.f )---- --
Total Duct Leakage 299 CFM @ 25Pa (Post -Construction)
Heating Furnace • Natural Gas • 95.5 AFUE
Cooling Air Conditioner • Electric • 13 SEER
Water Heating Water Heater • Electric • 0.93 Energy Factor
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5- If rating is Projected, I certify that the building design described herein is consistent with the
building plans, specifications, and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been inspected/tested and
that the mandatory provisions of the IECC have been installed to meet or exceed the intent of I the IECC or will be verified as such by another party.
Name: Michael Hill 'i Signature:
Organization: TSI Energy Solutions Digitally signed: 2/6/20 at 3:13 PM
Ekotrope RATER - Version 3.2.3.2351
2009 IECC compliance results calculated using Ekotrope RATER's energy and code compliance algorithm.
Ekotrope RATER is a RESNET Accredited HERS Rating Tool. All results are based on data entered by Ekotrope users.
Ekotrope disclaims all liability for the information shown on this report.
RESNET HOME ENERGY
RATING Standard Disclosure C",EneWSo`utions
For home(s) located at: 7277 ZANESVILLE RD, CARMEL, IN
Check the applicable disclosure(s) in accordance with the instructions on the reverse of this page:
M1. The Rater or the Rater's employer is receiving a fee for providing the rating on this home.
2. In addition to the rating, the Rater or the Rater's employer has also provided the following consulting services
for this home:
E]A. Mechanical system design
B. Moisture control or indoor air quality consulting
C. Performance testing and/or commissioning other than required for the rating itself
RID. Training for sales or construction personnel
0 E. Other(specify)
[]3. The Rater or the Rater's employer is:
[]A. The seller of this home or their agent
E] B. The mortgagor for some portion of the financed payments on this home
LIC. An employee, contractor, or consultant ofthe electric and/or natural gas utility serving this home
R14. The Rater or Rater's employer is a supplier or installer of products, which may include:
Products
HVAC systems
Installed in this home by
Rater Employer
OR is in the business of
Rater Employer
Thermal insulation systems
Rater
Employer
DRater
Employer
Air sealing of envelope or duct systems
Rater
VEmployer
Rater
Employer
Energy efficient appliances
Rater
Employer
Rater
Employer
Construction (builder, developer, construction contractor, etc)
Rater
Employer
Rater
Employer
Other (specify):
Rater
Employer
Rater
Employer
[]5. This home has been verified under the provisions of Chapter 6, Section 603 "Technical Requirements for
Sampling" of the Mortgage Industry National Home Energy Rating Standard as set forth by the Residential Energy
Services Network (RESNET). Rater Certification #: 9479271
Name: Michael Hill
Organization: TSI Energy Solutions
Signature:
Digitally signed: 2/6/20 at 3:13 PM
I attest that the above information is true and correct to the best of my knowledge. As a Rater or Rating
Provider I abide by the rating quality control provisions of the Mortgage Industry NationalHome Energy Rating
Standard as set forth by the Residential Energy Services Network(RESNET). The national rating quality
control provisions of the rating standard are contained inChapter One 4.C.8. of the standard and are posted at
http://resnet.us/standards/RESNET Mortgage_Industry_National_HERS_Standards.pdf
The Home Energy Rating Standard Disclosure for this home is available from the rating provider.
RESNET Form 03001-2 -Amended April 24, 2007
l
Home Energy Rating Certificate
Final Report
Your Home's Estimated Energy Use:
Heating
Cooling
Hot Water
Lights/Appliances
Service Charges
Generation (e.g. Solar)
Total:
Existing
Homes
Reference
Home
Zero Energy
Home
More Energy
150
140
230
120
un
100
90
o
70
'0
so This Home
40
30
10
20
0
Lev Energy
Rating Date: 2020-02-06
Registry ID: 463975967
Ekotrope ID: Od4aaDYv
Use [MBtu]
Annual Cost
51.9
$338
2.4
$73
9.5
$285
21.2
$562
— -
$273
0.0
$0
85.1
$1,533
Home Feature Summary:
Home Type:
Townhouse, inside unit
Model:
MERIDIAN III
Community:
LEGACY PRAIRIE 804
Conditioned Floor Area:
2,330 ft2
Number of Bedrooms:
3
Primary Heating System:
Furnace • Natural Gas • 95.5 AFUE
Primary Cooling System:
Air Conditioner • Electric • 13 SEER
Primary Water Heating:
Water Heater • Electric • 0.93 Energy Factor
House Tightness:
1586 CFM50 (4.87 ACH50)
Ventilation:
None
Duct Leakage to Outside:
128 CFM @ 25Pa (5.49 / 100 s.f.)
Above Grade Walls:
R-16
Ceiling:
Attic, R-38
Window Type:
U-Value: 0.33, SHGC: 0.28
Foundation Walls:
N/A
C",Erergy Soluflons
This home meets or exceeds the
criteria of the following:
2009 International Energy Conservation Code
Rating Completed by:
Energy Rater:Michael Hill
RESNETID:9479271
Rating Company:TSI Energy Solutions
4650 Killarney Dr, Carmel IN 46082
317-846-4655
Rating Provider:TSI Energy Solutions
4650 Killarney Dr, Carmel IN 46082r
1�
317-846-4655
Michael Hill, Certified Energy Rater
Digitally signed: 2/6/20 at 3:13 PM
IECC 2009 Performance Compliance
Property Organization
7277 ZANESVILLE RD TSI Energy Solutions
CARMEL, IN 46033 317-846-4655
Model: MERIDIAN III Michael Hill
Community: LEGACY PRAIRIE 804
Builder
PRL804 (AS BUILT) LENNAR HOMES
LEGACY PRAIRIE 804_11004008
Design
Heating
Cooling
Water Heating
SubTofa_I - Used to determine- compliance
Lights & Appliances
Onsite generation
Inspection Status
2020-02-06
Rater ID (RTIN): 9479271
RESNET Registered
(Confirmed)
Annual Energy Cost
IECC 2009 Performance
$843
$122
$332
_ - $1,296,_
$559 -
$0
Total. _.... $1856
Requirements
C",EnergySolufions
As Designed
$667
$117
$332
$559
$0
405.3
Performance -based compliance passes by 13.9% "
R402.4.1.2
Air Leakage Testing Air sealing is 4.87 ACH at 50 Pa. It must not exceed 7-00 ACH at 50 Pa.
402.5
Area-wei hted average fenestration SHGC
9 9
®
_
402.5
Area -weighted average fenestration Ll-Factor
403.2.2
- ' Duct Testing_','.
®
Mandatory
Checklist Mandatory code requirements that are not
checked_by Ekotrope must be met
k405 2,
Duct InsLilationi.
Design exceeds requirements for IECC 2009 Performance compliance by 13.9%.
As a 3rd party extension of the code jurisdiction utilizing these reports, I certify that this energy code compliance document has been created in accordance with the requirements of
Chapter 4 of the adopted International Energy Conservation Code based on Climate Zone 5. If rating is Projected, I certify that the building design described herein is consistent with
the building plans, specifications, and other calculations submitted with the permit application. If rating is Confirmed, I certify that the address referenced above has been
inspected/tested and that the mandatory provisions of the IECC have been installed to meet or exceed the intent of the IECC or will be verified as such by another party.
Name:
Organization:
Michael Hill
TSI Energy Solutions
Signature: 40
Digitally signed: 2/6/20 at 3:13 PM
Ekotrope RATER - Version 3.2.3.2351
IECC 2009 Performance compliance results calculated using Ekotrope RATER's energy and code compliance algorithm.
Ekotrope RATER is a RESNET Accredited HERS Rating Tool. All results are based on data entered by Ekotrope users.
Ekotrope disclaims all liability for the information shown on this report