HomeMy WebLinkAboutPermit Plans_Robertson,Kevin_022620UMACINV MSPVICINITY MAP
ADDRESS:9860 CHAMBRAY DR,
INDIANAPOLIS, IN 46280
39°55'54.7"N 86°07'13.2"W
APN:291-407-303-027-000-018
DESIGNER/CHECKED BY:
CUSTOMER INFORMATION
SS/BH
NAME: KEVIN ROBERTSON
DATE:2/26/20
SCALE:AS NOTED REV:A
AHJ:IN- CITY OF INDIANAPOLIS
PRN NUMBER: GRN-008006
UTILITY:DUKE ENERGY
SHEET CATALOG
INDEX NO. DESCRIPTION
T-1 COVER PAGE
M-1 MOUNTING DETAIL
M-2 STRUCTURAL DETAIL
E-1 SINGLE LINE DIAGRAM
PL-1 WARNING PLACARDS
SS SPEC SHEET(S)
SITE PLAN LAYOUT
(E) MAIN SERVICE PANEL(INTERIOR)
(N) PV INVERTER (EXTERIOR)
PHOTOVOLTAIC ARRAY ON THE ROOF
·ELECTRIC CODE:IEC 2009
·FIRE CODE:IFC 2014
·BUILDING CODE:IBC 2014
·RESIDENTIAL CODE:IRC 2005
APPLICABLE CODES CHAMBRAY DR KEVIN ROBERTSON - 5.440kW DC, 3.800kW AC
COVER PAGE
T-1
1.MODULES ARE LISTED UNDER UL 1703 AND
CONFORM TO THE STANDARDS.
2.INVERTERS ARE LISTED UNDER UL 1741 AND
CONFORM TO THE STANDARDS.
3.DRAWINGS ARE DIAGRAMMATIC, INDICATING
GENERAL ARRANGEMENT OF THE PV SYSTEM AND
THE ACTUAL SITE CONDITION MIGHT VARY.
4.WORKING CLEARANCES AROUND THE NEW PV
ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN
ACCORDANCE WITH NEC 110.26.
5.ALL GROUND WIRING CONNECTED TO THE MAIN
SERVICE GROUNDING IN MAIN SERVICE PANEL/
SERVICE EQUIPMENT.
6.ALL CONDUCTORS SHALL BE 600V, 75°C
STANDARD COPPER UNLESS OTHERWISE NOTED.
7.WHEN REQUIRED, A LADDER SHALL BE IN PLACE
FOR INSPECTION IN COMPLIANCE WITH OSHA
REGULATIONS.
8.THE SYSTEM WILL NOT BE INTERCONNECTED BY
THE CONTRACTOR UNTIL APPROVAL FROM THE
LOCAL JURISDICTION AND/OR THE UTILITY.
9.ROOF ACCESS POINT SHALL BE LOCATED IN
AREAS THAT DO NOT REQUIRE THE PLACEMENT
OF GROUND LADDERS OVER OPENINGS SUCH AS
WINDOWS OR DOORS, AND LOCATED AT STRONG
POINTS OF BUILDING CONSTRUCTION WHERE THE
ACCESS POINT DOES NOT CONFLICT WITH
OVERHEAD OBSTRUCTIONS SUCH AS TREES,
WIRES OR SIGNS.
10.PV ARRAY COMBINER/JUNCTION BOX
PROVIDES TRANSITION FROM ARRAY WIRING TO
CONDUIT WIRING
GENERAL NOTES
SCOPE OF WORK
GENERAL SYSTEM INFORMATION:
SYSTEM SIZE:
5440W DC, 3800W AC
MODULES:
(17)HANWHA Q.PEAK DUO BLK-G5 320W
INVERTER:
(1)SOLAREDGE TECHNOLOGIES SE3800H-US
(240V)
SCALE:1"=30'-0"
(N) AC DISCONNECT (EXTERIOR)
DRIVE WAY
CONDUIT RUN
3' FIRE SETBACK
PROPERTY LINE
FENCE
FENCE
185'-8"
185'-8"
109'-2"
71'-3"
12'-10"
13'-2"
77'-8"
(E) UTILITY METER(EXTERIOR)
03/04/20
Nick Mishler
AERIAL VIEW
ADDRESS:9860 CHAMBRAY DR,
INDIANAPOLIS, IN 46280
39°55'54.7"N 86°07'13.2"W
APN:291-407-303-027-000-018
DESIGNER/CHECKED BY:
CUSTOMER INFORMATION
SS/BH
NAME: KEVIN ROBERTSON
DATE:2/26/20
SCALE:AS NOTED REV:A
AHJ:IN- CITY OF INDIANAPOLIS
UTILITY:DUKE ENERGY
PRN NUMBER: GRN-008006
MOUNTING DETAIL
M-1SCALE:1/8"=1'-0"
ARRAY MP-01
SITE INFORMATION - WIND SPEED: 115 MPH AND SNOW LOAD: 20 PSF
SR.
NO AZIMUTH PITCH NO. OF
MODULES
ARRAY AREA
(SQ. FT.)ROOF TYPE ATTACHMENT ROOF
EXPOSURE FRAME TYPE FRAME
SIZE
FRAME
SPACING
MAX RAIL
SPAN
OVER
HANG
MP-01 270° 18° 17 308.4 COMPOSITION
SHINGLE FLASH FOOT 2 ATTIC PRE FABRICATED TRUSSES 2 X8 2'-0" 4'-0" 2'-0"
NOTE:
PENETRATIONS ARE STAGGERED
ALUMINIUM RAILS
2X8 PRE FABRICATED TRUSSES@
2'-0"SPACING
4'
INSTALLATION NOTES
1.STRUCTURAL ROOF MEMBER LOCATIONS ARE
ESTIMATED AND SHOULD BE LOCATED AND VERIFIED
BY THE CONTRACTOR WHEN LAG BOLT PENETRATION
OR MECHANICAL ATTACHMENT TO THE STRUCTURE IS
REQUIRED.
2.ROOFTOP PENETRATIONS FOR SOLAR RACKING
WILL BE COMPLETED AND SEALED WITH APPROVED
SEALANT PER CODE BY A LICENSED CONTRACTOR.
3.LAGS MUST HAVE A MINIMUM 2.5" THREAD
EMBEDMENT INTO THE STRUCTURAL MEMBER. 4.ALL
PV RACKING ATTACHMENTS SHALL BE STAGGERED BY
ROW BETWEEN THE ROOF FRAMING MEMBERS AS
NECESSARY.
5.ROOF MOUNTED STANDARD RAIL REQUIRES ONE
THERMAL EXPANSION GAP FOR EVERY RUN OF RAIL
GREATER THAN 40'.
6.ALL CONDUCTORS AND CONDUITS ON THE ROOF
SHALL BE MINIMUM 1-1/2" ABOVE THE ROOF
SURFACE (INCLUDING CABLES UNDERNEATH
MODULES AND RACKING).
7.THE PV INSTALLATION SHALL NOT OBSTRUCT ANY
PLUMBING, MECHANICAL OR BUILDING ROOF VENTS.
ROOF ACCESS PATHWAYS AND SETBACKS: IFC
605.11.3.2.1 RESIDENTIAL BUILDINGS WITH
HIP ROOF LAYOUTS. PANELS/MODULES INSTALLED
ON RESIDENTIAL BUILDINGS WITH HIP ROOF
LAYOUTS SHALL BE LOCATED IN A MANNER THAT
PROVIDES A 3-FOOT-WIDE (914 MM) CLEAR ACCESS
PATHWAY FROM THE EAVE TO THE RIDGE ON EACH
ROOF SLOPE WHERE PANELS/MODULES ARE
LOCATED. THE ACCESS PATHWAY SHALL BE LOCATED
AT A STRUCTURALLY STRONG LOCATION ON THE
BUILDING CAPABLE OF SUPPORTING THE LIVE LOAD
OF FIRE FIGHTERS ACCESSING THE ROOF.
IFC 605.11.3.2.2RESIDENTIAL BUILDINGS WITH
A SINGLE RIDGE. PANELS/MODULES INSTALLED ON
RESIDENTIAL BUILDINGS WITH A SINGLE RIDGE
SHALL BE LOCATED IN A MANNER THAT PROVIDES
TWO, 3-FOOT-WIDE (914 MM) ACCESS PATHWAYS
FROM THE EAVE TO THE RIDGE ON EACH ROOF SLOPE
WHERE PANELS/MODULES ARE LOCATED.
IFC 605.11.3.2.3 RESIDENTIAL BUILDINGS WITH
ROOF HIPS AND VALLEYS. PANELS/MODULES
INSTALLED ON RESIDENTIAL BUILDINGS WITH ROOF
HIPS AND VALLEYS SHALL BE LOCATED NO CLOSER
THAN 18 INCHES (457 MM) TO A HIP OR A VALLEY
WHERE PANELS/MODULES ARE TO BE PLACED ON
BOTH SIDES OF A HIP OR VALLEY. WHERE PANELS
ARE TO BE LOCATED ON ONLY ONE SIDE OF A HIP OR
VALLEY THAT IS OF EQUAL LENGTH, THE PANELS
SHALL BE PERMITTED TO BE PLACED DIRECTLY
ADJACENT TO THE HIP OR VALLEY.
IFC 605.11.3.2.4 RESIDENTIAL BUILDING SMOKE
VENTILATION. PANELS/MODULES INSTALLED ON
RESIDENTIAL BUILDINGS SHALL BE LOCATED NO
HIGHER THAN 3 FEET (914 MM) BELOW THE RIDGE IN
ORDER TO ALLOW FOR FIRE DEPARTMENT SMOKE
VENTILATION OPERATIONS.
03/04/20
Nick Mishler
MODULE
END CLAMPMID CLAMPMODULE
MODULES DATA
HANWHA Q.PEAK DUO BLK-G5 320W
MODULE DIMS 66.3"x39.4"x1.26"
LAG SCREWS 5/16"x3.5":2.5"MIN
EMBEDMENT
ADDRESS:9860 CHAMBRAY DR,
INDIANAPOLIS, IN 46280
39°55'54.7"N 86°07'13.2"W
APN:291-407-303-027-000-018
DESIGNER/CHECKED BY:
CUSTOMER INFORMATION
SS/BH
NAME: KEVIN ROBERTSON
DATE:2/26/20
SCALE:AS NOTED REV:A
AHJ:IN- CITY OF INDIANAPOLIS
UTILITY:DUKE ENERGY
PRN NUMBER: GRN-008006
STRUCTURAL DETAIL
M-2
MID-CLAMP AND END-CLAMP ANATOMY
ATTACHMENT DETAIL-FLASH FOOT 2
FLASH FOOT 2SOLAR MODULE
STAINLESS STEEL 5/16" HANGER
BOLT 2.5" EMBEDMENT
PILOT HOLE REQUIRED
RAIL
FLASHING
6" MAX
SCALE:NTS
GROUNDING LUG
MID CLAMP
ASSEMBLY
MODULE
FRAME
RAIL
MODULE TO MODULE & MODULE TO RAIL
GROUNDING MID-CLAMP
SCALE: NTS
GROUNDING DETAILS
IRONRIDGE RAIL
IRONRIDGE INTERNAL SPLICE
SELF-DRILLING SCREW
SCALE: NTS
RAIL TO RAIL
T-BOLT
DEAD LOAD CALCULATIONS
BOM QUANTITY LBS/UNIT TOTAL WEIGHT
(LBS)
MODULES 17 41.2 700.40
MID-CLAMP 24 0.050 1.20
END-CLAMP 20 0.050 1.00
RAIL LENGTH 189 0.680 128.52
SPLICE BAR 8 0.630 5.04
FLASH FOOT 2 55 1.88 103.40
TOTAL WEIGHT OF THE SYSTEM (LBS) 939.56
TOTAL ARRAY AREA ON THE ROOF (SQ. FT.) 308.39
WEIGHT PER SQ. FT.(LBS) 3.05
WEIGHT PER PENETRATION (LBS) 17.08
2 X8 TRUSSES
@2'-0"SPACING
COMPOSITION SHINGLE ROOF
MODULE
5/16" X 3.5" LAG SCREW
1 BOLT PER PENETRATION
LOAD BEARING WALL
SCALE:NTS
ROOF FRAMING DETAILS
03/04/20
Nick Mishler
(N)SOLAREDGE TECHNOLOGIES
SE3800H-US (240V), 3800W
INVERTER
INVERTER-1
DC DISCO
DC
AC
LOAD RATED DC DISCONNECT & AFCI
(N)JUNCTION
BOX OR EQUI.
3 3 2 1
PV MODULES
G
(N)HANWHA Q.PEAK DUO BLK-G5 320W,
320W MODULES
17 MODULES WIRED
IN (1) SERIES OF 17 MODULES
SOLAREDGE POWER
OPTIMIZERS
(N)60A AC
DISCONNECT
(E)200A END FED
MAIN PANEL
UTILITY
GRID
(E)200A MAINBREAKERPV BREAKER AT THE
OPPOSITE END OF
BUSBAR
(E) GROUND
ELECTRODE
20A 2P
PV BREAKER
EXISTING 120/240V 1PH 60HZ
METER#:DUKE ENERGY
318 546 523M
SIEMENS LN222RA OR
EQUIV. PV SYSTEM AC
DISCONNECT SWITCH
NON FUSED, 60A, 1PH,
120/240V 2P,NEMA 3R
SINGLE LINE DIAGRAM: DC SYSTEM SIZE - 5440W, AC SYSTEM SIZE - 3800W
ADDRESS:9860 CHAMBRAY DR,
INDIANAPOLIS, IN 46280
39°55'54.7"N 86°07'13.2"W
APN:291-407-303-027-000-018
DESIGNER/CHECKED BY:
CUSTOMER INFORMATION
SS/BH
NAME: KEVIN ROBERTSON
DATE:2/26/20
SCALE:AS NOTED REV:A
AHJ:IN- CITY OF INDIANAPOLIS
UTILITY:DUKE ENERGY
PRN NUMBER: GRN-008006
SINGLE LINE DIAGRAM
E-1
SYSTEM CHARACTERISTICS
DC SYSTEM SIZE 5440W
INVERTER STRING VOLTAGE:Vmp 380V
MAX INVERTER SYSTEM VOLTAGE: Voc 480V
MAX SHORT CIRCUIT CURRENT 15A
OPERATING CURRENT 14.32A
INVERTER-1 SPECIFICATIONS
MODEL SOLAREDGE TECHNOLOGIES
SE3800H-US (240V)
POWER RATING 3800W
MAX OUTPUT CURRENT 16A
CEC WEIGHTED EFFICIENCY 98%
MAX INPUT CURRENT 10.5A
MAX DC VOLTAGE 480V
MODULE SPECIFICATION
MODEL HANWHA Q.PEAK DUO
BLK-G5 320W
MODULE POWER @ STC 320W
OPEN CIRCUIT VOLTAGE:Voc 40.56V
MAX POWER VOLTAGE:Vmp 33.8V
SHORT CIRCUIT VOLTAGE:Isc 9.94A
MAX POWER CURRENT:Imp 9.47A
ELECTRICAL CALCULATIONS
DC WIRE SIZING CALCULATIONS BASED OF FOLLOWING EQUATIONS>>
·REQUIRED CONDUCTOR AMPACITY: 125% PER 690.8(A)(1) X Isc(A) X #OF
PARALLEL STRINGS = MAX CURRENT PER 690.8(A)(1) X 125% PER
690.8(B)(2)(a)=MAX CURRENT PER 690.8(B)(2)(a)
· CORRECTED AMPACITY CALCULATIONS:AMPACITY X TEMPERATURE DERATE
FACTOR X CONDUIT FILL DERATE = DERATED CONDUCTOR AMPACITY
·DERATED CONDUCTOR AMPACITY CHECK: MAX CURRENT PER 690.8(B)(2)(2) <
DERATED CONDUCTOR AMPACITY
AC WIRE SIZING CALCULATIONS BASED OF FOLLOWING EQUATIONS >>
·REQUIRED CONDUCTOR AMPACITY: INVERTER OUTPUT CURRENT X #OF
INVERTERSXMAX CURRENT PER 690.8(A)(3)X125% PER 690.8(B)(2)(A)
· CORRECTED AMPACITY CALCULATIONS:AMPACITY X TEMPERATURE DERATE
FACTOR X CONDUIT FILL DERATE = DERATED CONDUCTOR AMPACITY
·DERATED CONDUCTOR AMPACITY CHECK: MAX CURRENT PER 690.8(B)(2)(2) <
DERATED CONDUCTOR AMPACITY
OPTIMIZER CHARACTERISTICS
MODEL P340
MIN INPUT VOLTAGE 8 VDC
MAX INPUT VOLTAGE 48 VDC
MAX INPUT CURRENT 11 ADC
MAX OUTPUT CURRENT 15 ADC
NOTES:
1.CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT
RESISTANT PER NEC 310.0(D).
2.CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE
IN WET LOCATIONS PER NEC 310.8(C).
3.MAXIMUM DC/AC VOLTAGE DROP SHALL BE NO MORE THAN 2%.
4.ALL CONDUCTORS SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED.
5.BREAKER/FUSE SIZES CONFORMS TO NEC 240.6 CODE SECTION.
6.AC GROUNDING ELECTRODE CONDUCTOR SIZED PER NEC 250.66.
7.AMBIENT TEMPERATURE CORRECTION FACTOR IS BASED ON NEC 690.31(C).
8.AMBIENT TEMPERATURE ADJUSTMENT FACTOR IS BASED ON NEC
310.15(B)(2)(C).
9.MAX. SYSTEM VOLTAGE CORRECTION IS PER NEC 690.7.
10.CONDUCTORS ARE SIZED PER WIRE AMPACITY TABLE NEC 310.16.
NOTE:
MAIN PANEL RATING:200A, MAIN BREAKER RATING:200A
120% RULE: (200AX1.2)-200A=40A =>ALLOWABLE BACKFEED IS 40A
OCPD CALCULATIONS:
INVERTER OVERCURRENT PROTECTION= INVERTER O/P I X CONTINUOUS LOAD(1.25)
=16x1.25=20.00A=>PV BREAKER = 20A
ALLOWABLE BACKFEED 40A =>20A PV BREAKER
THE DESIGNED INTERCONNECTION MEETS THE 705.12(D)(2) REQUIREMENTS.
CONDUIT SCHEDULE
TAG ID CONDUIT SIZE CONDUCTOR NEUTRAL GROUND
1 NONE (4) 10AWG PV WIRE NONE (1) 10AWG BARE COPPER
2 3/4"IMC (4) 10AWG THHN/THWN-2 NONE (1) 10AWG THHN/THWN-2
3 3/4"IMC
(2) 10AWG THHN/THWN-2 (1) 10AWG THHN/THWN-2 (1) 10AWG THHN/THWN-2
WIRE SIZE DETERMINED PER INVERTER
DC WIRE CALCULATIONS:- MATERIAL:COPPER & TEMPERATURE RATING:90°C
TAG ID REQUIRED CONDUCTOR AMPACITY CORRECTED AMPACITY CALCULATION DERATED CONDUCTOR AMPACITY CHECK
1 1 X 15 X 1 = 15 X 1.25 = 18.75A 40 X 0.58 X 1 = 23.20A 18.75A < 23.20A
2 1 X 15 X 1 = 15 X 1.25 = 18.75A 40 X 0.71 X 0.8 = 22.72A 18.75A < 22.72A
AC WIRE CALCULATIONS:- MATERIAL:COPPER & TEMPERATURE RATING:90°C
TAG ID REQUIRED CONDUCTOR AMPACITY CORRECTED AMPACITY CALCULATION DERATED CONDUCTOR AMPACITY CHECK
3 16 X 1 = 16 X 1.25 = 20.00A 40 X 0.87 X 1 = 34.80A 20.00A < 34.80A
03/04/20
Nick Mishler
UMACINV MSPWARNING PLACARD
ADDRESS:9860 CHAMBRAY DR,
INDIANAPOLIS, IN 46280
39°55'54.7"N 86°07'13.2"W
APN:291-407-303-027-000-018
DESIGNER/CHECKED BY:
CUSTOMER INFORMATION
SS/BH
NAME: KEVIN ROBERTSON
DATE:2/26/20
SCALE:AS NOTED REV:A
AHJ:IN- CITY OF INDIANAPOLIS
UTILITY:DUKE ENERGY
PRN NUMBER: GRN-008006
WARNING PLACARDS
PL-1
!
!
!
!
!
A
V
15
480
380RATED MAXIMUM POWER-
POINT VOLTAGE(Vmp)
MAXIMUM SYSTEM
VOLTAGE(Voc)
MAXIMUM CIRCUIT
CURRENT(Isc)
RATED MAXIMUM POWER-
POINT CURRENT(Imp)
INVERTER 1
WARNING
CAUTION: SOLAR CIRCUIT
CAUTION: SOLAR ELECTRIC
SYSTEM CONNECTED
LABEL LOCATION
POINT OF INTERCONNECTION
(PER CODE: NEC 705.12(D)(7)
[ Not Required if Panel board is rated not less than sum of ampere
ratings of all overcurrent devices supplying it]
ELECTRIC SHOCK HAZARD
THE DC CONDUCTORS OF THIS PHOTOVOLTAIC
SYSTEM ARE UNGROUNDED AND MAY BE
ENERGIZED
LABEL LOCATION
DC DISCONNECT,INVERTER
[PER CODE: NEC 690.35(F)]
[To be used when inverter is ungrounded]
WARNING
INVERTER OUTPUT
CONNECTION
DO NOT RELOCATE THIS
OVER-CURRENT DEVICE
WARNING:PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION
CONDUIT, COMBINER BOX
[PER CODE: NEC690.31(G)(3)(4) & NEC
690.13(G)(4)]
WARNING-Electric Shock Hazard
No User Serviceable Parts inside
Contact authorized service provide
for assistance
LABEL LOCATION
INVERTER, JUNCTION BOXES(ROOF),
AC DISCONNECT
[PER CODE: NEC 690.13.G.3 & NEC 690.13.G.4]
LABEL LOCATION
DISCONNECT, POINT OF INTERCONNECTION
[PER CODE: NEC690.13(B)]
LABEL LOCATION
AC DISCONNECT , POINT OF INTERCONNECTION
[PER CODE: NEC 690.54]
LABEL LOCATION
MARKINGS PLACED ON ALL INTERIOR AND EXTERIOR DC CONDUIT,
RACEWAYS, ENCLOSURES AND CABLE ASSEMBLES AT LEAST EVERY
10 FT, AT TURNS AND ABOVE/BELOW PENETRATIONS AND ALL
COMBINER/JUNCTION BOXES.
(PER CODE: IFC605.11.1.4)
LABEL LOCATION
POINT OF INTERCONNECTION
[PER CODE: NEC705.12(D)(4)]
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION
LABEL LOCATION
AC DISCONNECT,POINT OF INTERCONNECTION
[PER CODE: NEC 690.17(E)]
DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR
MODULES ARE EXPOSED TO SUNLIGHT
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION
WARNING
LABEL LOCATION
AC DISCONNECT,POINT OF INTERCONNECTION
[PER CODE: NEC 690.17(E)]
LABEL LOCATION
WEATHER RESISTANT MATERIAL, DURABLE ADHESDIVE,
UL969 AS STANDARD TO WEATHER RATING (UL LISTING
OF MARKINGS NOT REQUIRED), MIN 3 8" LETTER HEIGHT
ARIAL OR SIMILAR FONT NON-BOLD,PLACED WITHIN
THE MAIN SERVICE DISCONNECT,PLACED ON THE
OUTSIDE OF THE COVER WHEN DISCONNECT IS
OPERATED WITH THE SERVICE PANEL CLOSED.
(PWER CODE: NEC690.15 ,690.13(B))
WARNING
DUAL POWER SOURCE SECOND
SOURCE IS PHOTOVOLTAIC
SYSTEM
SOLAR DISCONNECT
V
A
14.32
WARNING
LABEL LOCATION
DC DISCONNECT[PER CODE: NEC690.14(C)(2)]
RATED AC OPERATING CURRENT
AC NOMINAL OPERATING VOLTAGE
16.00
240
AMPS AC
VAC
PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH
!
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS LOCATED
AS SHOWN
!WARNING:
SOLAR
PHOTOVOLTAIC
ARRAYS ON ROOF
ALL PLACARDS SHALL BE OF WEATHER PROOF CONSTRUCTION, BACKGROUND ON ALL PLACARDS SHALL BE
RED WITH WHITE LETTERING U.O.N.
PLACARD SHALL BE MOUNTED DIRECTLY ON THE EXISTING UTILITY ELECTRICAL SERVICE.
FASTENERS APPROVED BY THE LOCAL JURISDICTION
(E) UTILITY (EXTERIOR)
(N) PV INVERTER (EXTERIOR)
(N) AC DISCONNECT(EXTERIOR)
(E) MAIN SERVICE PANEL (INTERIOR)
03/04/20
Nick Mishler
SPEC SHEET
ADDRESS:9860 CHAMBRAY DR,
INDIANAPOLIS, IN 46280
39°55'54.7"N 86°07'13.2"W
APN:291-407-303-027-000-018
DESIGNER/CHECKED BY:
CUSTOMER INFORMATION
SS/BH
NAME: KEVIN ROBERTSON
DATE:2/26/20
SCALE:AS NOTED REV:A
AHJ:IN- CITY OF INDIANAPOLIS
UTILITY:DUKE ENERGY
PRN NUMBER: GRN-008006
MODULE SPEC SHEET
SS-1
03/04/20
Nick Mishler
SPEC SHEET
ADDRESS:9860 CHAMBRAY DR,
INDIANAPOLIS, IN 46280
39°55'54.7"N 86°07'13.2"W
APN:291-407-303-027-000-018
DESIGNER/CHECKED BY:
CUSTOMER INFORMATION
SS/BH
NAME: KEVIN ROBERTSON
DATE:2/26/20
SCALE:AS NOTED REV:A
AHJ:IN- CITY OF INDIANAPOLIS
UTILITY:DUKE ENERGY
PRN NUMBER: GRN-008006
INVERTER SPEC SHEET
SS-2
03/04/20
Nick Mishler
SPEC SHEET
ADDRESS:9860 CHAMBRAY DR,
INDIANAPOLIS, IN 46280
39°55'54.7"N 86°07'13.2"W
APN:291-407-303-027-000-018
DESIGNER/CHECKED BY:
CUSTOMER INFORMATION
SS/BH
NAME: KEVIN ROBERTSON
DATE:2/26/20
SCALE:AS NOTED REV:A
AHJ:IN- CITY OF INDIANAPOLIS
UTILITY:DUKE ENERGY
PRN NUMBER: GRN-008006
OPTIMIZER SPEC SHEET
SS-3
03/04/20
Nick Mishler
SPEC SHEET
ADDRESS:9860 CHAMBRAY DR,
INDIANAPOLIS, IN 46280
39°55'54.7"N 86°07'13.2"W
APN:291-407-303-027-000-018
DESIGNER/CHECKED BY:
CUSTOMER INFORMATION
SS/BH
NAME: KEVIN ROBERTSON
DATE:2/26/20
SCALE:AS NOTED REV:A
AHJ:IN- CITY OF INDIANAPOLIS
UTILITY:DUKE ENERGY
PRN NUMBER: GRN-008006
MOUNT SPEC SHEET
SS-4
03/04/20
Nick Mishler
SPEC SHEET
ADDRESS:9860 CHAMBRAY DR,
INDIANAPOLIS, IN 46280
39°55'54.7"N 86°07'13.2"W
APN:291-407-303-027-000-018
DESIGNER/CHECKED BY:
CUSTOMER INFORMATION
SS/BH
NAME: KEVIN ROBERTSON
DATE:2/26/20
SCALE:AS NOTED REV:A
AHJ:IN- CITY OF INDIANAPOLIS
UTILITY:DUKE ENERGY
PRN NUMBER: GRN-008006
RAIL SPEC SHEET
SS-5
03/04/20
Nick Mishler