HomeMy WebLinkAbout18-840.02 E501 ELECTRICAL SPECIFICATIONREAD ANO BE BOUND BY THE ARCHITECTURAL SPECIFICAilONS.
THESE SPECIRCAiIONS, ALL OTHER DOCUMENTS ATiACHED HEREiO, ALL ADDENDA
ISSUE� AN� THE ACCOMPANYING P�ANS ARE INiENDED i0 PROVIDE FOR THE
COMPLETE FURNISHMG AN� INSTALLING OF iHE ENiIRE ELECiRICAL SYSiEM.
THE WORK SHAl1 BE DONE IN ACCOR�ANCE WIiH BESi PRACTICE SO AS i0
CONTRIBIIiE ID EfFIQENCY OF OPERATION ANO 111NIAIUM MAIMENANCE ANO SHALL
BE INSTALLED WITH PROPER ACCESSIBILITY. THE AIATERIALS AN� EQIIIPMENi,
INCW�ING ALL NECESSAAY ACCESSORIES, SHALL BE PUT INTO PROPER ADJUSiMENT
50 iHAi THE COMPONENi PARTS FUNCTION iOGEiHER AS A WORKABLE SYSiEAI.
PROVI�E ALL EQOIPAIENT, MATERIALS AN� OPERATIONS AS INDICAiE� EITHER ON
THE DRAWINGS OR WNTAINE� HEREIN OR AS AIAY BE REASONABLY IMPLIED BY
EITHER TO ACCOMPLISH COMPLETE EIECTRICAL SYSTEMS.
�ESCRIPiION OF WORK:
PRINCIPAL ITEMS OF WORK INCLUDE, BUT ARE NECESSARILY LIYITED i0 THE
FOLLOWING:
SYSTEAI SEAVICE VOLTAGE SHALL BE 120/208 VOLT, 3 PHASE, 4 WIRE AND
277/680 VOLi, 3 PHASE, d WIRE.
FURNISH AND INSTALL ALL WIRING, STARTERS, DISCONNECT SWITCHES, ETC. FOR
ALL MECHANICAL EQUIPMENT, INCLUDINC CONTROLS AND REQUIRED INTERLOCKINC,
UNLESS SPECIFICALL7 STATED OTHERWISE.
FURNISH AND INSTALL ALL CONDUIT BACK BOXES, RECEPTACLES AND FACEPL4TE5.
PROVIDE ALL SUPPORTS REOUIRED FOR THE INSTALL4TION OF ELECTRICAL
EOUIPMENT.
FURNISH AND INSTALL ALL CROUNDING PER N.E.C. INCLODINC BRANCH CIRCUITING.
FURNISH AND INSTALL ALL INTERIOR LIGHTING FI%TURES, AU%ILIARIES, lAMPS
SWITCHES AND FACEPLITES.
FURNISH AND WSTALL ALL E%TERIOR LIGHTING FI%TURES, AUXILIARIES, UMPS,
PHOTOCELLS, CONTACTORS AND TIME SWITCHES.
FURNISH AND INSTALL LIGHTING MOTION SENSORS.
FURNISH AND INSTALL FLUSH BO%ES, COVER PL4TE5 AN� CONDUIT FOR
POWER/�ATA/TELEPHONE, COMMUNICATION CABLES BY OTHERS.
FURNISH ANP INSTALL ALL CONDWT, BACK BOXES, FACEPlATES, PULL STRING FOR
TELEPHONE/DATA SYSTEM, JACKS AND WIRING BY OTHERS.
�EFINITIONS:
'PROVIDE' - SHALL MEAN 'FURNISH AND INSTALL AND PLACE IN OPEAATION" OR
°FUkNISH LABOR AND MATEftIAL REQUIRE� FOR INSTALLATION OF AN� PLACE IN
OPERATION".
'CONDUIT" - INCLUDES IN ADDITION TO CONDUIT, AL50 FITfMGS, HANCERS AND
OiHER ACCESSORIES WHICH COMPRISE A SYSTEAI.
INSPECiION OF SITE:
THE ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SRE BEFORE HE SUBMITS HIS
BI�, TO FAMILIARIZE HIMSELF WITH ACTUAL JOB CONOITIONS.
GOVERNING AGENQES:
THE CONTRACiOR SHALL BE FULLY MFORMED OF ALL UWS, OROINANCES AND
CO�ES, AN� SHALL, IN THE PERFORMANCE OF iHE CONTRACT, COMPLY WITH ALL
APPLICABLE FEDERAL, SiATE AN� LOCAL REGUlATI0N5. ANY �EVIATION FROM THE
PL4N5 OR SPECIFlCAiIONS AN� ANY AD�ITIONAL WORK NECESSARY i0 MEET CODE
REOUIREMENTS SHALL BE MA�E BY THE CONTRACTOR WITHOUT E%iRA WST TO
THE OWNER.
ALL WORK SHALL BE E%ECUTED ANO INSPECTE� IN ACCOR�ANCE WITH iHE LAiEST
APPROVE� EDITION OF THE NATIONAL ELECTRIC CODE 2017, THE CODES OF O.S.H.A.
AND ALL LOCAL AUTHORITIES HAVING JURISDICiION.
PERMITS ANO FEES:
SECURE AN� PAY FOR ALL PERMITS, FEES, BONDS, INSPECTIONS AND TESTS
REQUIRED.
UTILITY COMPANY REOUIREMENTS
WORK SHALL BE �ONE IN ACCOR�ANCE WITH THE RULES OF LOCAL UTILITY
COMPANIES. THE CONiRACTOR SHALL CHECK WIiH EACH UTILITY SUPPLYING
SERVICE TO THIS PROJECT AN� SHALL �ETERMWE FROM THEM ALL EQUIPMENT AN�
CHARGES WHICH SHALL BE INCLUDE� IN HIS PRICE.
BARRIER FREE DESIGN:
THE CONTRACiOR SHALL REVIEW INSTALUTION REQUIREMENTS FOR CONFORMING TO
THE HAN�ICAPPE� BARRIER FREE REGULATIONS AN� AMERICAN �ISABILITY ACi. IN
PARiICUTAR, MOUNTING HEIGHTS OF OUTLEiS AND ACCESSIBILITY OF CONiROLS ETC.
SHALL BE COMPLIE� WITH.
HAN�LING OF MATEkIAL ANO EQUIPMENi�
THE CONTRACiOR SHALL RECEWE, PROPERLY HOUSE, TRANSPORT AN� INSTALL AT
PROPER LOCATIONS, EQUIPMENT AN� MATERIALS REQUIRE� FOR HIS CONTRACT.
RESPONSIBILITY FOR CAftE AND PROTECTION OF E�UIPMENT, MATERIAL AND WORK
PERFORMED AGAINST THEFT, INJURY OR DAMAGE FROM ALL CAUSES REMAINS WITH
THE CONTRACiOR UNTIL ACCEPTANCE OF THE PROJECT BY THE OWNER.
DAMAGE i0 OTHER WOkK:
THE ELECTRICAL CONTRACiOR WILL BE HELD RESPONSIBLE FOR �AMAGE TO WORK
CAUSED BY HIS WORK OR THROUGH THE NEGLECT OF HIS WORKMEN. ALL PATCHING
AN� REPAIRING OF DAAIAGE� WORK SHALL BE OONE BY THE GENERAL CONiRACTOR,
BUT THE COST OF SAME SHALL BE PAID BY THE CONTRACTOR RESPONSIBLE FOR
THE DAAIAGE.
WTTING CORING AND PATCXING
CUTTING, CORE DRILLING, INSERTS AN� CON�UIT OR CABLE AEEVES AN� PATCHING
REOUIRED IN THE GENERAL CONSTRUCTION FOR COMPLETION OF iHE WORK,
SPECIFlED HEREIN, SHALL BE NRNISHED AN� INSTALLED BY THE ELECTRICAL
CONTRACTOR. SEAL ALL OPENINGS THROUGH S WIiH 3M OR 5➢ FlRE RATE�
MATERIAL.
RELEA5E0 FOR CONSTRIICTI�N
Su6jec��o compliance with allregula�ions
of S�a�e antl Local Codes
City of Carmel
,
�{�n„� i�.vavua!
DATE: 03�Q�j�20
CONDUIT INSTALLATION:
ALL WORK SHAIL BE CONCEALED IN WALLS ANO ABOVE CEILMGS M FINISHED
AREAS, ONLESS OiHERWISE NOTED. EXPOSED CON�UIi WHERE REOIIIRE� SHALL
BE INSTALLED PERPENDICUTAR OR PARALLEL TO WALLS, CEILINGS AN� STRUCTURAL
MEMBERS AN� COOR�INATED WITH MECHANICAL OUCTS, PIPES, LIGHTING FIMTURES
AN� E�UIPMENT. IN GENERAL, ALL CON�UIiS SHALL BE RUN OVERHEA�.
DRAWINGS:
THE DESIGN DRAWINGS SHOW THE GENERAL ARRANGEMENi AND E%TENi OF iHE
WORK. THE DRAWINGS ARE DIAGRAMMATIC AND MAY NOT BE ORAWN TO SCALE IN
CERTAIN AREAS FOR PURPOSES OF CIARIiY AN� LEGIBILITY. IT IS INiENDED THAT
ALL APPARATUS BE LOCATED SYMMETRICAL WITH ARCHIiECiURAL ELEMENTS ANO BE
INSiALLE� TO AV01� OBSTRUCTIONS AN� PRESERVE HEADROOM. THE CONTRACiOR
SHALL REVIEW iHE PUNS OF OTHER iRADES WITH HIS OWN WORN TO AV01�
CONFLICTS AN� IMERFERENCES; HE SHALL MAKE USE OF ALL SOURCES OF DATA,
INCLO�ING SHOP �RAWINGS AND DRAWINGS OF EQUIPMENi Fl1RNI5HED BY OTHERS.
SHOP DRAWINGS:
COMPLETE SHOP DRAWINGS FOA ALL ELECTRICAL WORK SHALL BE SOBMITTED i0
THE ENGINEER FOR REVIEW BEFORE FABRICATION OF THE WORK. SEVEN (7)
COPIES OF SHOP �RAWINGS SHALL BE SUBMITfE� ON ALL ITEMS OF ELECTkICAL
EQUIPMENT, LIGHT FlXTURES, FACTORY GENERATED MOTION SENSOR LAYOUi,
SPECIALTIES, ETC.
RECOkO OkAWINGS:
CONTRACTOR SHALL PREPARE AND MAINTAIN ACCURATE RECOR� ORAWINGS OF ALL
UN�ERGROUNO AN� CONCEALED WORK AN� SHALL SUBMIi THESE DRAWINGS TO
OWNER UPON FINAL ACCEPTANCE OF iHE WORK OR UPON OWNER'S REQUEST.
COORDINATION WITH OTHER TRADES:
COORDINAiE WORK WITH OTHER TRADES TO AVOID INTERFERENCES AND PRESENT A
NEAT APPEARANCE. INTERFERENCES AS A RESULT FROM POOR COOR�INATION WILL
NOT BE CONSIDERED AS E%TRA WORK.
INTERFERENCES:
ALL MINOR DEVIATIONS REQUIRED �UE TO INTERFERENCES WITH THE WORK OF
OTHERS SHALL BE MADE BY ELECTRICAL CONTRACTOR AT NO ADDITIONAL WST.
VERIFY LOCATIONS OF EXISTING SYSTEMS AND BUILDINC STRUCTURAL SYSTEMS IN
THE PROJECT AREA FOR CONNECTIONS TO SAME AND TO AVOID POSSIBLE
INTERFERENCES.
SUPPORTS:
PROVIDE ALL SUPPORTS, FRAMING, ETC., FOR THE PROPER MSTALLITION OF
CONDUIT, TRANSFORMERS, ELECTRICAL EDUIPMENT, IIGHTING FIXTURES, ETC.
EQUIPMENT CONNECTIONS AND LOCATIONS
CONNECTIONS ID ELECTRICAL EQUIPNENT: MOTORS, LIGHTMG FIXTURES, PACKAGE
PANELS ETC. SHALL BE MADE IN ACCOR�ANCE WIiH SHOP �RAWINGS AND
ROUGH�IN MEASUREMENTS FURNISHE� BY THE MANUFACTURERS OF THE PARTICUL4R
EOUIPMENT FURNISHE�. AN7 AND ALL ADDITIONAL CONNECTIONS NOT SHOWN ON
THE PL4NS, BUT CALLE� FOR BY THE E�UIPMENT MANUFACTURER'S SHOP �RAWINGS
OR RE�UIRED FOR iHE SUCCESSFUL OPERATION OF iHE PARTICULAR EQUIPMENT
FURNISHED, SHALL BE INSTALLED BY THE CONTAACiOR AS PART OF HIS CONTRACT
WITH NO ADDIiIONAL CHARGE.
PAINTING:
ALL FACTORY FINISHED EQUIPAIENT SHALL BE CLEANED Ai COMPLETION OF JOB.
EQUIPMENT SHOWING RUST OR AIARS SHALL BE GNEN ONE COAi OF ENAIIEL PAINT.
COLOR AS SELECiED BY iHE OWNER OR SHALL MAiCH ORIGINAL FINISH.
ACCESS TO EOUIPAIENT:
ALL CONTROL DEVICES, EQUIPMENT, ETC., SHALL BE SO LOCATED SO AS i0
PROVI�E FOR EASY ACCESS OF OPERATION, REPAIRS AND MAINTENANCE. PROVIDE
ACCE55 DOORS AS REQUIRED.
TESiING:
ALL WORK SHALL BE iESTED AND ACCEPTED IN THE PRESENCE OF iHE ARCHITECT
OR ENGINEER, IF NOT IN WORKMG ORDER OR COAIPLIANCE, THE CONTRACiOR SHALL
PROMPiLY CORRECi SAAIE AND AIAKE G00� TO CONFORM TO SPECIFICATIONS.
EACH RECEPiACLE SHALL BE CHECKED FOR POWRITY, OPENS, GROUNDS, EiC.,
USING AN APPROVED RECEPiACLE TESiER, HUBBELL .y5200 OR EQUAL.
PERFORM ALL TESTS REDUIRED BY STATE, CITY, COONTY AND/OR OTHER AGENCIES
HAVING JIIRISDICTION.
ARER ALL ELECiRICAL WORK HAS BEEN COAIPLETED, THE CONTRACiOR SHALL
�EMONSiRATE TO THE ARCHITECT OR ENGINEER THAT iHE ENTIRE INSTALLAiION IS
IN WORKING OR�ER. ANY �EFECTIVE WORK OR EQUIPMENT, OR ANY WORK THAT IS
NOT IN COMPLIANCE WITH iHE SPECIFICATIONS, SHALL BE PROMPiLY CORRECiE� BY
THE CONTRACiOR.
QEANING AND FINISHMG
AFiER ALL TESiS HAVE BEEN MADE, THE CONiRACTOR SHALL MAKE A THROUGH
INSPECTION OF iHE PROJECT AN� ARRANGE TO HAVE WORK INVOLVE� iHOROUGHLY
0.EANE�, ALL RUBBISH REMOVE� ANO LEAVE ALL WORK IN A SATISFACTORY
CON�ITION TO THE ARCHITECT OR ENGINEER.
DEMOLITION:
ELECTRICAL DEAIOLITION WORK SHALL INCLUDE: REMOVMG AND/OR RELOCAiING OF
EXISTING PANELS, LIGHTING FI%TURES, RECEPTACLES, WIRE, CON�UIT, BO%E5, ETC.,
AS INDICATED ON THE DRAWINGS.
REMOVE ALL CONDUIT, WIRE, HANGERS, ClAMPS, ETC., THAT IS NOT BEING
RE-USED UNLESS CONCEALED ABOVE CEILINGS OR IN WALLS, WHICH MAY BE
ABANDONED AND LEFT IN PL4CE.
REMOVE ALL WIRE IN EXISTING CONCEALED ABANDONED CONDUITS. E%ISTINC
CONCEALE� CON�OITS QF APPLICABLE) MAY BE RE-USE� FOR NEW WIRING.
RENOVE WIRE FROM CONDUITS ENTERING THE FLOOR. CAP CONDUIT FLUSH WITH
OR FILL WITH CONCREiE.
ALL E%ISTING PANELS, LIGHTING FI%TURES, WIRMG DEVICES, TELEPHONE OUTLETS,
ETC., SHALL REMAIN IN THEIR EXISTMG LOCATIONS, UNLE55 OTHERWISE NOiED.
RENOVE E%ISiING WIRING DEVICES, PULL ALL WIRES OUT AND INSTALL A BIANK
STAINlESS STEEL COVER PL4TE OVER THE EXISTING OUTLET. A1AKE CIRCUIT 'SAFE".
REVISE PANEL DIRECTORIES AS REQUIRE� i0 REFLECT ALL REVISIONS TO E%ISiING
PANELS.
ALL AIAiERIALS THAT ARE TO BE REMOVED; PANELS, LIGHTING FI%TURES, WIRMG
DEVICES, CON�UIT, WIRE, ETC., SHALL BECOME THE PROPERTY OF iHE CONTRACTOR
UNLESS OTHERWISE NOTED ON THE DRAWINGS AN� REMOVE� FROA1 THE SITE AND
LEGALLY DISPOSED OF.
NAMEPLATES:
PROVI�E NAMEPLAiES ON EACH INOIVIOUAL MOTOR SiARiERS, PANELS, SAFEiY
SWITCHES, ETC., INOICATMG DEVICES CONiROLLEO. NAMEPLATES SHAIL BE WHIiE
LAMINATED PLASTIC WITH BLACK SCRIBED LETTERS SEWRELY FASTENED i0 �EVICE
WITH SCREWS.
GUARANTEE:
ALL MAiERIAL AN� WORKYANSHIP SHALL BE GIIARANTEED FOR A PERIOD OF ONE
YEAR FROY THE DATE OF ACCEPTANCE, AND iHE CONiRACTOR SHALL MAKE G00�
ANY OEFECTS WITHIN iHAi PERIOD AT NO ADDITIONAL WST i0 THE OWNER.
AIOUNTING HEIGXTS:
LIGHTING SWITCHES 4'-0" TO CENTERLINE
RECEPiACLES 1'-6' i0 BOTfOM
TELEPHONE/�ATA 1'-6" TO BOTiOM
WALL TELEPHONE 4'-0" TO CENTERLINE
RECEPiACLE PANELS fi'-6" i0 TOP
MOTOR STARTERS/�ISWNNECT 5'-fi" TO i0P
ALL MOUNiMG HEIGHTS TO BE VERIFIED PRIOR TO SiARTING WORK.
CERTIFICATE OF APPROVAL:
WHEN THE JOB IS COMPLETED, THE CONTRACTOR SHALL PAOVIDE THE
ARCHITECT�ENGINEER WITH CERTIFlCATE OF APPROVAL FROM THE LOCAL ELECTRICAL
INSPECTION AOTHORITY. iHE CONTRACTOR SHALL GIVE THE OWNER A WRITiEN
GUARANTEE iHAi HE WILL AIAKE GOOD, Ai HIS OWN E%PENSE, ANY DEFECTS IN
MATERIAL$ OR WORKAIANSHIP WHICH MA7 �EVELOP WRHIN ONE (1� YEAR FROA1 THE
DATE OF FINAL ACCEPTANCE.
ELECikICAL - BASIC MAiERIALS
AIATEkIALS:
MATERIALS SHALL BE NEW AN� BEAR THE U.L. LABEL OR LISTING, WHEREVER
STANOAROS HAVE BEEN ESiABLISHE�.
ALL EQUIPMENT OF THE SAME OR SIMIIAR SYSTEMS SHALL BE OF THE SAME
MANUFACTURER.
CONDUIT:
CONDUIT SHALL BE MC, iHINWALL (EMi) R.G.S. OR PVC. CONDUIT MSiALLE� IN OR
UN�ER SHALL BE 3/4" MINIMIIM, R.G.S. OR PVG CONOUIT INSTALLE� IN
FINISHED AREAS SHALL BE CONCEALED.
FLEXIBLE AIETAL CONDUIi WITH GROUND WIRE SHALL BE USED FOR FINAL
CONNECTION TO LICHTING FIXTURES, TRANSFORMERS, MOTORS, ETC., 1/2" MINIMUM.
MC CABLE MAY BE USED IN PARTITION WALL OR ABOVE ACCESSIBLE CEILINGS.
NO PVC CONDUIT WILL BE ALLOWE� IN BUIL�MG. ALL CONDUIiS TURNING UP
FROM UN�ERGROUNO SHALL BE STEEL ELLS.
EXPANSION:
PROVI�E EXPANSION RTTINGS IN ALL CONDUIi RUNS THAT CROSS BUIL�ING
EXPANSION JOINTS.
CONOUIi SLEEVES:
PROVIDE CON�UIT SLEEVES WHERE CON�WTS PASS iHRU FLOORS, WALLS, ETG AS
REOUIRED.
ALL V01�5 BETWEEN SLEEVES OR HOLES ANO CONOUITS PASSING THRU SHALL BE
FIRESiOPPE�. 3M, STI SPECSEAL 100 FIRE SiOP SEAL4NT OR EQUAL.
FIRE STOPPING:
SEAL ALL OPENING WHERE NONMETALLIC SHEATHED CABLES, TELEPHONE AND
CON�UITS PASS THRII JOISiS, WALLS, S ETC. TO PREVENT PASSAGE OF FIRE,
SYOKE, iOXIC GASSES ANO WATER.
SEALANi SHALL BE LATE% BASED HIGH SOLIDS FIRE STOP COMPOUN�. SEALANi
SHALL A�HERE WELL i0 ALL SUftfACES AN� MAY BE APPLIE� USING A STANDARD
CAULK GUN OR PUiTY KNIFE.
SEAUNi SHALL BE SPECIFIED iECHNOLOGIES MC. (STI) �LC700.
WIRING:
FEE�ERS SHALL BE TYPE "THW" OR "XHNW". BRANCH CIRCUIi WIRING SHALL BE
TYPE �THWN�THHN", �12 MINIMUM.
ALL WIRE SHALL BE COPPER, HAVE 600 VOLi INSULAiION, /8 WIRE AND LARGER
SHALL BE SiRAN�ED.
ALL WIRE INSULATION i0 BE COLOR CODEO.
PROVI�E SEPARATE NEUTRAL ANO GROUNO WIRE FOR EACH RECEPiACLE CIRWIT
FOR COMPUTER EOUIPMENT.
CON�UIT STUBS:
ALL FLUSH PANELS TO HAVE TWO (2) 1"C STUBBED TO CEILMG SPACE FOR
FUTURE.
DISCONNECT SWITCXES:
DISCONNECT SWIiCHES SHALL BE 250 VOLT OR 600 VOLT HEAVY DUTY, FUSED OR
NON-NSED AS INDICAiE�, IN A NEMA I ENCLOSURE. �ISCONNECT SWITCHES
INSiALLE� OUTOOORS SHALL BE IN A NEMA 3R ENCLOSURE. SQUARE � 3110
SERIES OR AS NOTED.
AIOTOR SiARTERS:
SINGLE PHASE MOTOR STARTERS SHALL HAVE MANUAL TOGGLE SWIiCH WIiH
THERMAL OVERLOADS, FLUSH MOUNiE� WITH PILOT LIGHT, SQUARE D, CLASS 2510,
CUTLER HAMMER, G.E., OR SIEMENS I.T.E.
SINGLE PHASE MOiOR STARTERS WITH AUTO-0FF-HANO SPDT SELECTOR SWITCH,
SHALL BE FLUSH MOUNiE� WITH PILOT LIGHi. SQUARE � CL45S 2510-FF71P
CUTLER HAMMER, GE. OR SIEMENS I.T.E.
THREE PHASE MOTOft STARiERS SHALL BE MAGNETIC iYPE, WITH NSE� CONTROL
TRANSFORMER WITH 3 OVERLOADS, HAN�-OFF AUTO SWITCH, AU%ILIARY CONiACTS
AND PILOi LIGHi AS REQUIREO, SOUARE �, CLASS 8536, CUTLER HAMMER, GE., OR
SIEMENS I.T.E.
COMBINATION THREE PHASE MOTOR STARTERS SHALL BE THE SAME AS ABOVE
EXCEPT WITH FUSED OISCONNECT AN� CLASS R FUSES.
FUSES:
fi�1 AMPERE AN� LARGER SHALL BE PROTECTED BY CURREM LIMIiING BUSSMANN
HI-CAP TIME DEIAY FUSES KRP-C, 250 VOLT OR 680 VOLi.
0 TO 600 AAIPERE SHALL BE PROiECiED BY CURREM LIMIiING BUSSMANN
LOW-PEAK DUAL ELEMENT FUSES LPN/LPS, 250 VOLT OR d80 VOLTS.
MOTOR CIRCUITS SHALL BE PROTECTEO BY BUSSMANN LOW-PEAK DUAL-ELEMENT
FUSES LPN/LPS, 250 VOLT OR 680 VOLTS.
CIRCUIT BREAKER PANELS SHALL BE PROTECTED AY BUSSMANN LOW-PEAK
DUAL-ELEMENT FUSES LPN/LPS, 250 VOLT OR 480 VOLiS.
GROUNDING:
PROVI�E SEPARATE GROUND WIRE FOR ALL MOTORS, RECEPTACLES AND FEEDERS.
CABINETS, MOTOR FRAAIES, SiARiERS, CONDUR SYSTEAIS, PANELS, ETC., SHALL BE
GROUNDEP IN ACCORDANCE WITH iHE LAiEST N.E.C. AND LOCAL CODES AS
ADOPTED BY THE AUiHORIiY HAVMG JURISDICTION.
$WITCHES:
SWITCHES SHALL BE 20A., 120/277V., I POLE, 3 AND 4 WAY AS INDICATED,
HUBBELL �1221 SERIES OR EQOAL COLOR i0 BE WHRE OR AS SELECTE� BY
ARCHITECT.
�IMMER SWITCHES:
LOW VOLiACE �IMMER SWIiCHES SNALL INTERFACE WITH OCCUPANCY SENSORS AND
POWER PACKS. �IMMER SWITCHES SHALL BE RATE� 0-10V�C UNLESS OTHERWISE
NOTE�, SOLID SiATE, U.L LISTE�. PROVIDE EXTERNAL DIMME� POWER PACK RELAY
AS REOUIRE� PER MANUFACTURER. VERIFY MANUFACTURER DE-RATING
REOUIREMENiS IF GANGE� WIiH OTHER �IAIAIER SWIiCHES.
AIOTION SENSORS:
CEILMG MOUNTE� NOTION SENSORS AND SWITCH PACKS (POWER PACKS) ARE iHE
RESPONSIBILITY OF iHE ELECiRICAL CONiRACTOR i0 REVIEW MANUFACiURER'S
INSTALLATION INSTRUCilONS PRIOR i0 ROUGH-IN.
CONTRACTOR SHALL PROVIDE MANUFACTURERS FACTORY GENERATED DEVICE LIYOUT
AS PART OF SHOP ORAWINC SUBMITTALS. (SENSOR SWITCH, GREENGATE, WATT
STOPPER, LUTRON OR LEVITON).
ELECTRICAL CONTRACiOR SHALL VERIFY AN� COOR�INATE MOTION SENSOR
LOCATIONS WITH LIGHiING LIYOUT, MECHANICAL EQUIPMENT LIYOUT, ETC PRIOR i0
ROUCH-IN INCLU�INC NRNIiURE LAY-OUL ELECiRICAL CONTRACTOR IS
RESPONSIBLE FOR FlEL� VEkIFICATION OF iHE NUMBER OF SWITCH PACKS NEE�E�.
ONE SWITCH PACK PER CIRCUIT. MAXIMUM OF FIVE SENSORS PER SWITCH PACK.
MULTIPLE CIRCUITS MAY BE CONTROLLE� BY ON SENSOR BY USING A�DITIONAL
SWITCH PACNS. MAXIMUM OF TEN SWITCH PACNS PER SENSOR.
ELECTRICAL CONTRACiOR SHALL FOLLOW MANUFACTURER'S RECOMMENDAiION OF
FINAL DEVICE LOCATIONS, COVERACE, FREQUENCY, DUANTITY AND VERIFY CIRCUITS
WITH RESPECT TO SWITCH PACK NEEDED IN THE FIEID PER MANUFACTURER OF
CHOICE.
TO PREVENT FALSE ACTIVATION, CEILMG MOUNTED SENSORS SHALL BE MOUNTED
AWAY FROM THE PATH OF SiRONG AIR TURBULENCE, A MINIMUM OF FOUR FEET
FOR STANDARD SENSITIVITY AND SIR FEET FOR MA%IMUM SENSITIVItt.
ELECTRICAL CONTRACiOR SHALL FlEL� A�JUST EACH AREAS MOiION SENSOR'S TIME
DEL4Y FROM IS SECONDS i0 30 MINUTES PER OWNER�S DIRECTION. PRIOR TO
INSiALLATION OF MOiION SENSORS, ELECTRICAL WNTRACiOR SHALL MEET WITH
OWNER TO �ETERMME EACH AREAS TIME �ELAY SETTING.
RECEPTA0.E5:
RECEPiACLES SHALL BE SPEQRCATION GRA�E �l1PLEX, GROUN�ING TYPE 20A.,
125V., WHIiE FINISH, HUBBELL #5362-W OR EQUAL SPECIAL PURPOSE
RECEPiACLES 3�A., 4�A., S�A., 2P. OR 3P., ETC., SHALL BE SPECIFICATION GftADE,
HUBBELL, COOPER WIRING �EVICES, PA55 & SEYMOUR, OR LEVITON.
G.F.I. RECEPTACLES SHALL BE SPECIFlCATION GRA�E �UPLEX GROUN�ING TYPE,
20A., 125V, HUBBELL �Gf53fi2-WA, COOPER WIRING �EVICES, PASS & SEYMOUR
Ok LEVITON.
WEATHERPROOF GFl RECEPiACLES SHALL BE OUTDOOk RATE� ANO HAVE
WHILE-IN-USE POLYCARBONATE WEATHERPROOF COVER . iHE ENCLOSURE SHALL
HAVE CORO PORTS CAPABLE OF ALLOWING AN ELECTRICAL COR� TO PASS THROUGH
WHEN COVER IS CLOSE�, TAYMAC �20310 OR EQUAL.
WALL PL4TES:
WALL PL4TES FOR SWIiCHES, RECEPTACLES ANO TELEPHONE OUiLETS SHALL BE
HIGH-IMPACT SA100TH NYLON Ok SUPER STAINLESS STEEL, ANSI 302, HUBBELL P1
SERIES OR �97��0 SERIES OR EQUAL.
SPECIAL PLATES AS NECESSARY.
WEATHERPROOF RECEPTACLES SHALL HAVE CASi GASKET COVERPL4TE HUBBELL
d!5206W0 OR EQUAL.
OUTLETS:
OIIiLET BOXES FOR WNCEALEO WORK SHALL BE PRESSED STEEL BO%ES,
GALVANIZED, yl2 GAUGE. CEILMG BOXES SHALL BE d" ROUND OR OCTAGONAL.
WALL OUTLEi BO%ES SHALL BE 4" SOUARE BY I-1/2" DEEP, SINGLE GANG PoR
WIRING DEVICES.
TIME SWITCHES:
TIME SWITCHES SHALL BE 7-OAY, ELECiRONIC, d CIRCUIT, RATED 20A PER POLE,
INTERMATIC Ei70615CR, PARAGON OR TORK.
UGHiING FI%TURES:
(REFER TO LIGHTING FI%TURE SCHE�ULE)
ALL FIXTURES SHALL BE U.L. LISTED.
ALL FIXTURES INSiALLEO OUTSIDE SHALL HAVE DAMP LOCATION LABEL.
LED:
LUAIINAIRE SHALL MAINiAIN 70% LUMEN OUiPUi (UO) FOR A MINIMUII OF 50,000
HOURS.
DRIVER SHALL HAVE A RATED LIFE OF 50,000 HOURS, MINIMUM.
LUMEN OUTPUT SHALL NOT DEPRECIATE MORE THAN 20% AFTER 10,000 HOURS OF
USE.
DRIVER AND LEDS SHALL BE FURNISHED FROM A SINGLE MANUFACTURER TO ENSURE
COMPATIBILITY.
WIRING CONNECTIONS i0 LED DRNERS SHALL UTILIZE POIARIZED QUICK-
DISCONNECTS FOR FlELD MAINTENANCE.
THE LED LUMINAIRE SHALL CARRY A LIMITED 5-YEAR WARRANTY MINIMUM FOR LED
LIGHT ENGINE(S)�BOARD ARRAY, AND �RIVER(5).
❑GHTING
PHOTOCONTROL
PHOiOCONTROL SHALL BE RAiED 2�00 WATTS Ai 120 VOLT ANO 3fi�� WATTS Ai
277 VOLi. INiERMAiIC S!N6121N ANO gK1123C, OR TORK.
NCO iROL
PROVI�E Al1 CONiACTORS, TIYE SWITCHES AND PHOiOCELL FOR A COMPLETE
OOiSI�E LIGHTMG SY4EY.
PHOTOCELL TURNS LIGHTING 'ON", TIME CLOCK TURNS LIGHTING 'OFF".
TELEPHONE/�ATA (CON�UIT ONLYI:
TYPICAL OUTLET SHALL BE A DOUBLE GANG BO% WITH SINGLE GANG FACEPL4TE
AN� 1" MINIMUM CON�UIT TERMINATING ABOVE AN ACCESSIBLE CEILINC (L4Y-IN)
AND/OR JOIST SPACE WHERE NO CEILING IS PRESENT.
PROVIDE ALL CONOUIiS, FITTINGS, NYLON BUSHINGS, PIILL WIRE, BACK BO%ES,
ETC.
PROVIDE BLANN COVER PL4TES ON UN-IISE� BOXES.
OWNER WILL PROVIDE ALL CABLING, EQUIPMENT AN� JACKS.
COVERING M/E/P DESIGN
' ���QO �T �R �O�c�
No.
' � 10000214 ;
Jp STATE OF ' •
Q'
�����,��, ,`SS/OON6LENG\��F.
ivivis
nm
mm
a�
`mn
rn�
�v
� =
`o
a
�'' �o
c
¢'�
.......��'. ov
spON
na
TDGArchitects.com
Automotive
O
�
N
�
N �
L� Z a
C)W�' 0
0 � m C�
W 0C (..% LLl � O
Z C �; > � 00
� W � ���
L
�
O a � � Q �
N N
1.6 = CO O � �
d � � � � _
Q�"'�' a��
� � JW �, YCn�
a�ZQo c �� o
Z
'o
v a� �n
O
W o
� �— w
�—
d =�vU dc�m
�
Rsvleian Scheduls
Date DeecrlpHon
03-13-19 Review
10-03-19 Bids
11-11-19 Permits
EAM Engineers, Inc.
EleclricelaiM MechenialGonsNting Englneare
400 S. OI4 Wootlma�d SUVs 1 W, Bimiingham, MI 480�B
PM1one248S4A16]0 Faz24&528.1642
wrnr.eem�er�qlnaersnom � eam@eam�eqqlneerscvm
]ab Na.: 423—IB041
� . , � � .
1- .
Z e
Ov
J � B;
Q s«
U Q g`
—�/ U -
I..1� � a y
� U U �a
3 J a//� ��
p` W V J �a
Proiect Number
18-840.02
Drawing Number
E 501