Loading...
HomeMy WebLinkAboutJ332 Backflow testBackflow Prevention Assembly Test and Maintenance Report Customer Information Assembly Information Name Ar chon - Citizens Utilities; Indianapolis Kroger #332 Contact Type RP Address Size 1.5 10679 N Michigan Manufacturer Wilkins Location Zionsville, IN 46077-Dock area by fire protection riser Model 975XL2 Serial# 1606984 Hazard Domestic Assembly Test Report Initial Test Final Test Tester Information Tester Name Repairs and Notes: Hazard ID 3876348 Test Date: BF18-6087 3241 N. Shadeland Ave 11/20/2018 Donald Cooper - Kroger Facility Engineering Tester License Expiration Certification # Test Kit Mfr & Mod # Company Serial # Midwest 845-50029 01181525 Kroger Facility Engineering Phone Indianapolis, IN 46250- 317-543-3588 Address Check Valve #1 Check Valve #2 Relief Valve 8.2 [x] [ ] Closed Tight Leaked N/A [x] [ ] Closed Tight Leaked 2.8 [x]Opened Did Not Open[ ] PASS The backflow prevention assembly detailed on this form has been tested and maintained as required by codes and regulations, is certified to be true & accurate, and is operating within acceptable parameters at time of testing. * Only Manufacturer's replacement parts have been used. **Test records must be kept for a minimum of three years Date Submitted: Residential Non-Residential[ ][x] 01/28/2019