HomeMy WebLinkAboutE001 Electrical SpecsELECTRICAL ABBREVIATIONS
A
AFF
CO
CONTR
DN
DWG(S)
EC
EDC
EM
E�UIP
ETR
EWC
Ek
FLA
FS
GC
HP
MAX
MB
MC
MCA
MFR
MH
MIN
MLO
MOCP
MOD
MTD
NIC
NTS
OC
PC
PSI
RLA
RPM
V
UON
AMPS
ABOVE RNISHED ROOR
COMPANV
CONTRACTOR
DOWN
DRAWING(S)
ELECTRIC CONTRACTOR
ELECTRICAL DISTRIBUTION CENTER
EMERGENCV
EQUIPMENT
EXISTING TO REMAIN
ELECTRIC WATER COOLER
EMISTING
FULL LOAD AMPS
FLOW SWITCH
GENERALCONTRACTOR
HORSE POWER
MAXIMUM
MAIN BREAKER
MECHANICALCONTRACTOR
MIMIMUM CIRCUIT AMPS
MANUFACTURER
MOUNTING HEIGHT
MINIMUM
MAM WG ONLV
MAXIMUM OVER CURRENT PROTECTION
MOTOROPERATEDDAMPER
MOUNTED
NOT IN CONTRACT
NOT TO SCALE
ONCENTER
PLUMBING CONTRACTOR
POUNDSPERSQUAREINCH
RUNNING LOAD AMPS
REVOLUTIONS PER MINUTE
VOLTS
UNLESS OTHERWISE NOTED
PANELBOARD SCHEDULE
ABBREVIATIONS
L LIGHTING
R RECEPTAQE
PN POWERNONSEASONAL
PW POWER WINTER
MN MOTORNONSEASONAL
MNI MOTOR NONSEASONAL INTERMITTENT
MS MOTORSUMMER
MW MOTOR WINTER
KT KITCHEN
ELECTRICAL SYMBOLS
DISCONNECT �
EXIT SIGNAGE e
EXIT SIGNAGE WITH EMERGENCV HEADS �
EMERGENGV LIGHTING UNIT e�B
EMERGENCV EXIT EGRESS LIGHT e
SUSPENDED STRIP LIGHT �
SURFACE MOUNTED STRIP LIGHT �
RECESSED �OWN LIGHT �
MOTOR �
LIGHTFIXTURE-ONNIGHTLIGHTCIRWIT �
LAVINTROFFERFIXTURE �
FYI6y�ypU]y�]CVII�
SURFACE MOUNTED LAVIN �
LIGHTFlXTURE-UNDERCOUNTER 0
LI6HT FlXTURE - WALL SCONCE I� h
� � ��
LIGHT FlXTURE - PENDANT
LIGHTFIXTURE-TRACK �
LIGHTFIXTURE-RECESSEDDOWNLIGHT O
LIGHT FIXTURE - VANITV LIGHT �p
OURET-4 WAY �
OURET- DUPLEX �
OURET-6ROUNDFAULTINTERRUPT A
OURET-GROUNDFAULTINTERRUPTWEATHERPROOF QWP
OURET-DUPLEXWITHUSB �
OURET - 220 �
JUNCTION BOX O O
SPECIALEQUIPMENTCOORDINATEW/SUPPLIER O
FLOOR OUTLET WITH POWER, DATA AND PHONE � FLR
LOW VOLTAGE ONE LINE �
LOW VOLTAGE TWO LINE �
LOW VOLTAGE # LINES � p
ANALOG PHONE LINE �
WIRELESS ACCE55 POINT WAP
PUSHBUTTON
a
BUZZER �
PHOTO CELL -I( P IF
POWER POLE � pp
TIME CLOCK
SWITCH
SWITCH-3 WAV
SWITCH-4 WAV
SWITCH WITH DIMMER
SWITCH WITH OCCUPANCV SENSOR
CEILING MOUNTED OCCUPANCV SENSOR
PANEL DESIGATION � �-�r CIRCUIT BREAKER NUMBERS
� � �
x: xx,xx,xx
DOORALARM CONTROLPANEL DACP
HINGESIDEPLUNGERSWITCH DC
MAGNETIC LOCK WITH KEY PAD KP
MAGNETIC LOCK WITH CARD READER CR
ELECTRICAL SPECIFICATIONS
1. BID INSTRUCTIONS: CONTRACTORS SHALL PROVIDE BASE
BID IN STRICTACCORDANCE WITH DESIGN BA515
EQUIPMENT AN� MATERIALS. PROJECT �OES ENCOURAGE
COMPETITIVE PRIC WG AND ALLOWS FOR SUBSTITUTIONS
OF EQUAL EQUIPMENT AND MATERIALS AGAINST THE BASIS
OF DESIGN. SUBSTITUTE ITEMS WILL BE COMPARED
AGAINST DESIGN BA515 DURING SUBMITTAL PROCESS.
ENGINEER RESERVES THE RIGHT TO REJECT
SlIBSTITUTIONS FOUND NOT TO BE EQUAL TO ITEMS
LISTED IN DESIGN BASIS..
2. PRIOR TO PROCUREMENT CONTRACTOR SHALL SUBMIT TO
ARCHITECT FULL SUBMITTALS FOR ALL ENERGY
CONSUMING OR PRODUCING ITEMS AND FOR ALL SW ITCH
GEAR, LOAD CENTERS AND PANEL BOARDS. SUBMITTALS
SHALL BE DELINEATED WITH TAGS IN�ICATED ON PRINTS,
CONTRACTORS NAME AND PROJECT NAME 0.EARLV
INDICATE ALL MODEL NUMBERS AND ALL ACCESSORIES
ANO OPTIONS BEWG PROVIDED. SUBMISSIONS SHALL BE IN
PDF FORMAT. ALL E�UIPMENT ANo ITEMS SHALL BE PER
DESIGN BASIS OR APPROVED EQUAL ENGMEER RESERVES
THE RIGHTTO REJECT ANV SUBSTITUTE ITEM FOUND NOT
EQUAL TO THE SPECIFIED ITEM AS DESIGNED.
3. CONTRACTORSHALLFURNISHATEMPORARVSERVICEFOR
THE USE OF ALL TRADES DURWG CONSTRUCTION AS
RE�UIREDBVTHEGENERALCONTRACTOR. REMOVEALL
TEMPORARV EQUIPMENT AS PERMANENT SERVICES
BECOME AVAILABLE.
4. THEDRAWINGSINTHISSECTIONAREDIAGRAMMATICAND
ARE NOT INTEN�ED TO �EFlNE EXACT �UANTITIES,
LOCATIONSORCOOIFlEDREOUIREMENTS. DRAWINGS
SHOW GENERAL INTENT OF SVSTEMS. MODIRCATIONS IN
ELECTRICAL SVSTEM ROUTING AND LOCATIONS AS
RE�UIRED TO MEET THE INTENT, SHALL BE PERFORMED
W ITHOUT ADDITIONAL COST TO OW NER. SECURE AND PAV
FOR ALL REQUIRED PERMITS.
5. THE ELECTRICAL CONTRACTOR IS TO PROVIDE ALL
REpUIRED LABOR, MATERIALS, EpUIPMENT, AND
CONTRACTOR'S SERVICESNECESSARVTOCOMPLETETHE
INSTALLATION OF SVSTEMS RE�UIRED M FULL
CONFORMITY WITH APPLICABLE CODES AND ORDINANCES.
THE FINISHED JOB SHALL BE FUNCTIONAL AND COMPLETE
W EVERV �ETAIL INC W DING ANV ANO ALL SUCH ITEMS FOR
A COMPLETE SVSTEM. CONTRACTOR SHALL GUARANTEE
ALL LA90R AN� MATERIALS ENTERING INTO CONTRACT
FOR A PERIOD OF ONE (i ) VEAR FROM �ATE OF
ACCEPTANCE.
6. ALL WORK SHALL IN BE IN FULL ACCORDANCE WITH 2O09
INDIANA ELECTRICAL CODE (2008 NFPA ]0), 2�101NDIANA
ENERGV COOE (ASHRAE 90.7-200�), PERTMENT STATE,
COUNTY. CO�ES AND ORDINANCE AND INDIANA
AMENOMENTS. COORDINATE WORK WITH OTHERTRADES.
ELECTRICAL CONTRACTOR SHALL BEAR ALL COSTS
RESULTING FROM ANV NON COMPLIANCE WITH CODE
RE�UIREMENTS.
]. MATERIALS AND EQUIPMENT SHALL BE NEW UNLESS
IN�ICATEDOTHERWISE. MATERIALSHALLBEARU.L.LABEL
WHERE SUCH STANDARDS HAVE BEEN ESTABLISHED AND
LISTED BV U.L. MATERIALS AND EpUIPMENT SHALL
CONFORM WITH THE LATEST ISSUES OF APPLICABLE
TECHNICALSTANDAROS.
8. THEELECTRICALCONTRACTORISTOPROVIDEA
COMPLETE SVSTEM OF LIGHTING, RECEPTACLES, AND
POWERASRE�UIRED. VERIFVALLVOLTAGESANDPHASE
RE�UIREMENTS WITH MECHANICAL CONTRACTOR'S
EQUIPMENT PRIOR TO PERFORMING ANV WORK.
9. ELECTRICALCONTRACTORSHALLVISITTHESITEAND
VERIFV ALL EMISTING CONDITIONS BEFORE SUBMITTING A
BID. NO EXTRAS WILL BE ENTERTAINED FOR
CONTRACTORS FAILURE TO IDENTIFV EXISTING
CONOITIONS ANO A�JUST AS REpUIRE� TO MEET �ESIGN
INTENT.
10. ALL CONDUIT COl1PLINGS AND CONNECTIONS SHALL BE
COMPRESSION TVPE AND MADE TO ENSURE POSITIVE
GROUNDINGCONTINUITV. MAKECONNECTIONSTO
EpUIPMENT SUBJECT TO VIBRATION W ITH 18 INCHES OF
FLEXIBLE WATERTIGHT CONDUIT WITH WATERTIGHT
FITTINGS. PROVIDEFORSUPPORTANDSECURINGOFALL
CON�UITANDEQUIPMENT. CONNECTIONSTOLIGHTING
FIXTURES SHALL BE MADE WITH SIX (6) FEET OF FLEXIBLE
CONOUIT FROM A BOX WITHIN TWO (2) FEET OF THE
FIXTURE. SPLICEALL WIRES ONLV IN ACCESSIBLE BOXES.
ALL FIXTURE WHIPS TO BE FLE%IBLE METAL CONDUIT V2"
MINIMUM SIZE WITH COMPRESSION CONNECTORS WITH
INSULATEDTHROATS. WHIPSSHALLNOTEXCEED6'.
FIXTURE WHIPS TO BE SUPPORTED FROM BUILDING
STRUCTURE.
WIRWG AND RACEWAVS
1. ALLLIGHTINGANDBRANCHCIRCUITWIRINGSHALLBE
SOLID COPPER MINIMUM SIZE #12 AWG. 6�OV INSULATION,
]5 DEG. C., TVPE THW OR TH W N, NOT LESS THAN N12 AWG.
ALL WIRE SERVING AS FEEDS TO DISTRIBUTION PANEL
BOARDS OR INTEGRAL HORSEPOWER MOTORS SHALL BE
EITHER STRANDED COPPER CONDUCTOR OR ASTM B800
ALUMINUM AA-800� SERIES. THESE SHALL BE SIZED NOT
LESS THAN #10 AWG FOR COPPER AND NOT LESS THAN M8
AWG FOR AWMINUM. EACH WITH MINIMIIM 600V THW OR
THWN INSULATION, 15 DEG. C. ALL FEEDER SHALL BE
SRED IN ACCOR�ANCE WITH NEC 310.15.
2 EXPOSED WIRING SHALL BE W EMT RACEWAV. EXTERIOR
WIRING SHALL BE IN CONOl11T. CONCEALED WIRING SHALL
BE IN EMT OR METAL CLAD CABLE WHERE ALLOWED BV
CODE.
3. ALL LOW VOLTAGE WIRING IN PLENUM RATED CEILINGS OR
EXPOSED IN ROOMS SHALL BE PLENUM RATED CABLE.
4. ALL CABLE SHALL BE NEW WIRE OF RECENT
MANUFACTURE AND IN ACCORDANCE WITH THE LATEST
STANDARDS OF IPCEA AND NEMA AS A MINIMUM.
5. ALL DEVICES AND E�UIPMENT SHALL BE SOLIDLV
ELECTRICAL SPECIFICATIONS
GROUNDED IN ACCORDANCE WITH NEC REQUIREMENTS.
6. ALL SOLID CONDUCTOR WIRES MAV BE TERMINATEO
UNDER SCREW HEA�S. STRAN�ED WIRES MAY BE
TERMINATED BV USING PUSH-IN CLAMP TYPE
CONNECTORS FURNISHED WITH DEVICES OR TERMINATED
WITHCOMPRESSIONTVPETERMINALLUGS. SETSCREW
TVPE TERMINATIONS ARE NOT PERMITTED.
]. NO MOTORS ARE TO BE SUPPLIED UNOER THIS CONTRACT
UNLESS ITEMS REQUIRING A MOTOR ARE FURNISHED BV
THISCONTRACTOR. THECONTRACTORSHALLFURNISH
ALL STARTERS FOR ALL MOTORS REQUIRWG A STARTER.
THE CONTRACTOR SHALL CONNECT ALL POWER
EQUIPMENT IF & WHERE SHOWN ON PLANS 11NLES5
OTHER-WISE SPECIFIED 8 ASSURE OWNER THE MOTORS
ARE IN GOOD RUNNING ORDER.
8. EG SHALL PROVIDE ALL COMPONENTS NEEDED TO MEET
MEANS OF DISCONNECT PER N.EG FOR ALL HARO WIRED
EQUIPMENT.
PANELS AND �ISCONNECTS
1. PANELBOARDS SHALL BE A DEAD-LOCK SAFETY TVPE,
SURFACE OR RECESSED MOUNTED AS SHOWN, EQUIPPED
WITH THERMAL-MAGNETIC MOLDED CASE CIRCUIT
BREAKERS W ITH FR4ME AND TRIP RATINGS AS REQUIRED.
TERMINALS FOR FEEDER CONDUCTORS TO THE
PANELBOARD MAINS AND NEUTRAL SHALL BE U.L LISTED
AS SUITABLE FOR THE TVPE OF CON�UCTOR SPEQFIED.
TERMINALS FOR BRANCH CIRCUIT WIRING. BOTH BREAKER
AND NEUTRAL, SHALL BE U.L LISTED AND CONNECTORS
SHALL BE OF THE FULL COMPRESSION TVPE.THE
PANELBOARD BUS ASSEMBLV SHALL BE ENCLOSED IN A
STEEL CAB WET. THE SRE OF THE WIRING GUTTERS AND
GAUGE OF STEEL SHALL BE IN ACCORDANCE WITH NEMA
STANDARD PUBLICATION N0. PB4971 AND U L.
STAN�ARDS NO. 6] FOR PANELBOARDS. CABINET SHALL
BE FABRICATED FROM GALVANIZED STEEL OR E�UIVALENT
RUST-RESISTANT STEEL FRONTS SHALL INCLUDE DOORS
AND HAVE FW SH, BRUSHED STAWLE55 STEEL, CVLINDER
TUMBLER-TVPE LOCKS W ITH CATCHES AND SPRING
LOADED DOOR PULLS. THE FLUSH LOCK SHALL NOT
PROTRUOEBEVONDTHEFRONTDOOR.ALLPANELBOARD
LOCKS SHALL BE KEVED ALIKE. FRONTS SHALL HAVE
ADJUSTABLE INDICATING TRIP CLAMPS WHICH SHALL BE
CONCEALED WHEN THE DOORS ARE CLOSED. DOORS
SHALL BE MOUNTED BV COMPLETELV CONCEALED STEEL
HINGES. FRONTS SHALL NOT BE REMOVABLE WITH DOOR
IN THE LOCATED POSITION. A CIRCUIT OIRECTORV FRAME
AND TVPE WRITTEN CARD W ITH A CLEAR PLASTIC
COVERING SHALL BE PROVIDED ON THE MSIDE OF THE
DOOR. THE DIRECTORV CARD SHALL PROVIDE A SPACE AT
LEAST il4" HIGH X 3" LONG OR EQUIVALENT FOR EACH
QRCUIT. FRONTS SHALL BE OF CODE GAUGE, FULL
FINISHED STEEL WITH RUST-INHIBITWG PRIMER FACTORV
FINISHED ENAMEL PAINT.
2. LOAD CENTERS SHALL BE UL LISTED AND MANUFACTURED
IN ACCOR�ANCE WITH THE LATEST NEMA STANDARDS.
CABINETS SHALL USE HINGED STVLE DOORS. MOUNT AT
6'-6" TO TOP OF CAB W ET.
3. CIRCUITBREAKERSSHALLBEQUICK-MAKE,QUICK-BREAK,
THERMAL-MAGNETIC. TRIP INDICATING AND HAVE COMMON
TRIP ON ALL MULTI-POLE BREAKERS. BRANCH CIRCUIT
BREAKERS FEEDING CONVENIENCE OUTLETS SHALL HAVE
SENSITNE INSTANTANEOUS TRIP SETTINGS OF NOT MORE
THAN 10 TIMES THE TRIP RATWG OF BREAKER TO PREVENT
REPEATED ARQNG SHORTS RESULTING FROM FRAVED
APPLIANCE CORDS. CONNECTION TO BUS SHALL BE BOLT
ON.
4. CONTRACTORTOOBTAINMAXIMUMFAULTCURRENT
AVAILABLE FROM THE UTILITV. CALCULATE THE FAULT
CURRENTAVAILABLEATTHEPANELS. ALL
PANELS/BREAKERSISWITCHES ARE TO BE BRACED TO
EXCEE� MA%IMUM AVAILABLE FAULT CURRENT AND
CIRWIT BREAKERS ARE TO BE CAPABLE OF INTERRUPTING
FAULT CURRENT. MANUFACTURER SHALL PROVIDE ALL
REQUIRED FAULT CURRENT ANO ARGFLASH LABELING PER
110.16 AND 11 Q24.
5. MAXIMUMLOADINGOF20AMPCIRCUITSSHALLNOT
EXCEE� 1]50 WATTS. VOLTAGE DROP OF BRANCH
CIRWITS SHALL NOT EXCEE� 3% AN� FEEDER qRCUITS
SHALL NOT EXCEED 2%. SEAL ALL PENETRATIONS
THROUGH WALLS, CEILINGS AND FLOORS AIRAN� WATER
TIGHT. FIRE STOP WHERE REQWRED.
6. CONTRACTOR SHALL PROVIDE ENGRAVED BAKELITE
NAMEPLATES FOR ALL ELECTRICAL PANELS AS REQUIRED
BV NEC 408A(B) AND SHALL LABEL ALL DISCONNECTS,
TRANSFORMERS AND MOTORS OVER 1 HP. FURNISH
TVPEWRITTEN PANEL DIRECTORIES TO IDENTIFV ALL
ELECTRICAL CIRCUITS BOTH NEW AND EXISTING.
]. DISCONNECT SWITCHES SHALL BE GENERAL DUTV, NEMA
TVPE 1 FOR INDOOR SERVICE AND NEMA TVPE 3R FOR
OUT�OOR SERVICE, SUITABLE FOR PA�LOCKING, NUMBER
OF POLES, RATINGS, FUSES QF REQUIRED) SHALL BE AS
INDICATED ON THE DRAWINGS.
DEVICES
1. VERIFVEXACTLOCATION,COLORANOHEIGHTSOFALL
OUTLETS, RECEPTACLEQ LIGHT Fl%TURES AND EQUIPMENT
WITH OWNER'S REPRESENTATIVE PRIOR TO START OF
WORK FURNISH GENERAL SERVICE DUPLEX'S, 15 AMP
SWITCHES, 1520 AMP GFlCS, HEAVV DUTV DISCONNECTS,
HVACSSUSWITCHES,PANELBOARDS,LOADCENTERS,
DISTRIBl1TION PANELS ETC. AS REQUIRED.
2. CONVENIENCE RECEPTACLES SHALLBE MOUNTE�18"
ABOVE RNISHEO ROOR (AFF.)TO BOTTOM UNLESS
NOTED OTHERWBE, SWITCHES AND PUSHBUTTONS SHALL
BE 42" A.F.F. TO BOTTOM UNLESS SPECIFIED OTHERWISE
ON THE DRAWINGS.
3. PRIOR TO ROUGH-IN E.G SHALL VERIFV FINAL LOCATIONS
AND COLORS OFALL DEVICES WITH OWNER.
ELECTRICAL SPECIFICATIONS
4. WSTALLALLDEVICESPARALLELANDPERPENDICULARTO
ADJACENT WALL AND CEILINQ RUSH WITH SURROUNDING
SURFACES AND FREE FROM ALL OBSTRUCTIONS.
REWORKING OF EQUIPMENT INSTALLED IMPROPERLV
SHALL BE AT THE CONTRACTOR'S E%PENSE.
5. SWITCHES, BOXES, ETC., SHALL BE NEMATVPE 1
CONSTRUCTION FOR IN�OOR APPLICATIONS AND NEMA
TVPE 3R CONSTRUCTION FOR OUTDOOR APPLICATIONS.
6. SWITCHES SHALL MEET NEMA STANDARDS, COLOR SHALL
BE BV ARCHITECT. SWITCHES SHALL BE EQUAL TO
HUBBELL COMMERCIAL SPECIFlCATION GRADE 20115
AMPERES, SINGLE POLE, 125/2]]V. MULTI-POLE OR
SPECIAL SWITCHING SHALL BE AS NOTED ON THE
DRAW WGS.
Z RECEPTACLES SHALL BE 125 VOLT, 15/20 AMPERES,
DUPLEX,GROUNDEDHUBBELLCOMMERCIAL
SPECIRCATION GRADE SPECIAL RECEPTACLES SHALL BE
AS NOTED ON THE DRAWINGS.
8. MATCHING COVER PLATES SHALL BE PROVIDED FOR ALL
RECEPTACLES AND SWITCHES.
I�[Hi11N[Hi131�1:�3�Y
1. CONTRACTORSHALLBERESPONSIBLEFORVERIFVING
FIXTURES- MODEL Nl1MBER5, QUANTITV AN� DISTANCE
BETWEEN LIGHTING FlXTURE PER FLOOR PLANS.
2. PRIOR TO ROUGH-M E.C. SHALL VERIFV FlXTURE
QUANTITV. MODELS, STVLE, TRIM, LENS, ETG WITH OWNER
FOR ALL FIXTURES.
3. PROVIDELIGHTINGFI%TlIRESCOMPLETEWITH,BUTNOT
NECESSARILV LIMITED T0. HOUSINGS LAMPS LAMP
HOLDERS, RERECTORS, BALLASTS. STARTERS AND
WIRING.
4. INSTALL LIGHTING FIXTURES AT LOCATIONS AND HEIGHTS
AS INDICATED, IN ACCORDANCE WITH FIXTURE
MANUFACTURER'S WRITTEN INSTRUCTIONS, APPLICABLE
REQUIREMENTS OF NEQ NECA'S "STANDARD OF
W STALLATION", NEMA STANDARDS, AND W ITH RECOGNRED
INDUSTRV PRACTICES TO ENSURE THAT LIGHTING
FI%TURES FULFlLL REQUIREMENTS.
5. COORDINATEWITHOTHERELECTRICALWORKAS
APPROPRIATE TO PROPERLV INTERFACE INSTALLATION OF
INTERIOR LIGHTING FIXTURES WITH OTHER WORK.
6. E.C. TO FASTEN FI%Tl1RE5 SECURELV DIRECTLV TO
BUILDINGSTRUCTURALSVSTEM. LIGHTTROFFERSSHALL
BE SUPPORTED AT EACH CORNER OF FIXTURE BV WIRES
OF SAME GAUGE AS HANGER WIRE FOR CEILING GRID.
ATTACH EARTHOUAKE CLIPS TO GRID AS RECOMMENDED
BV LIGHT MANUFACTURER. USE SCREWS IF REpUIRED BV
MANUFACTURER. ATTACH THE WIRE TO THE STRUCTURE
ABOVE LIGHTS SHALL NOT BE SUPPORTED IN ANYWAV BV
LAV-IN CEILING.
]. FIXTURE LOCATIONS SHALL BE AT APPROXIMATE
LOCATIONS AS SHOWN ON THE DRAWINGS FREE FROM ALL
OBSTRUCTIONS. CLEAN ALL uGHTWG E�UIPMENTAFTER
LIGHTING INSTALLATION AND GENERAL CONSTRUCTION IS
COMPLETE REPAIRANV RXTURES DAMAGEO DURING
CONSTRIICTIONS.
8. PROVIDENECESSARVMOUNTINGFRAMES,SUPPORTSAND
RELATED ITEMS REQUIRED TO PROPERLV MSTALL
RXTURES. SUPPORT FlXTURES INDEPENDENTLV OF PIPING
ANDDUCTWORK. MAKEMODIFICATIONSTOTHE
STRUCTURE AS REOUIRED TO INSTALL FIXTURES. ANV
MODIFICATIONS TO THE STRUCTURE SHALL NOT IMPAIR
THE STRUCTURAL INTEGRITY OF THE BUILDING.
LOW VOLTAGE
1. ALL LOW VOLTAGE CABLE WHERE CONCEALED IN
CONSTRUCTION OR IN E%POSED OPEN AREAS SHALL BE
FREE RUN. CONTRACTOR SHALL INSTALL 3l4" CONDUIT
(MINIMUM) FROM EACH LOW VOLTA6E ROUGH-IN LOCATION
TO ACCESSIBLE CEILING SPACE, LOW VOLTAGE WIRE
TRAV OR HANGERS AND THEN TO MDF, HEAD-IN, PBX
PIINCH DOWN, CONTROLLER ETC.
2. EA. SHALL COORDINATE WITH LOCAL PHONE AND CABLE
PROVIDER AS CHOSEN BV OWNER AND PROVIDE
RACEWAVS FOR BRINGING IN SERVICES AS REQUIRED.
3. ALL LOW VOLTAGE CABLE SHALL BE PLENUM RATEO IN
PLENUMS.
4. ALL DATA CABLE SHALL BE CAT 6 UNLESS OTHER WISE
NOTED. TERMINATE, LABEL AND TEST ALL W IRING.
5. ALL N CABLE SHALL BE HIGH DEFINITION COAX RG6 0R AS
REQ W RED BV PROVIDER, VERIFV PRIOR TO ROUGH IN.
CLOSE OUT
1. PROVIDEMANUFACTURERSOPERATIONAN�
MAINTENANCE MANUALS AND PROVIDE AS BUILT
DRAW WGS. PROVIDE (1) TR4INING SESSION TO OWNER
SELECTED PERSONNELAS REpUESTED AND PROVIOE
WARRANTV INFORMATION FOR ALL MANUFACTURERS
WARRANTE� EQUIPMENT.
c�
Z
� 4
W
W
Z
U
Z
W
� �
W p
Q ` U
U m �
C � �
� .� @
> N
Q W > �
°6 C � N ln (D �
� � N n N
� � � t0 W ln C
�' C �-N' � (O ln m
�U a�z�n�
Un n >
C � � 1p
OW �OMM'O
c�� m�¢ai�ui
W
N
�
O
�
�
Vl
N
W
�
� �
��
VJ
�
�No. ,:
10200395 WE
s.a.E o. =�u€ ////
�
moi wa
C� s� �/
o� '/ //
�`S�ONA�-��c
1 �/`>i�� �/ C
�no�mmninninn��nNo••
11/27/2019
n
O
U
U
�
�
d
P
�
n
� Q �
0 Z �
W Z
� O W
H
� � �
J
Q
Z
i
Q
U
M
M
O
� �
Q �
� ¢
� Z
iQ
Q 0
'�n Z
V
ZWC
� <
M �
N Q
�U
RELEA5E0 FOR CONSTRIICTI�N
Su6jec� �o compliance with all regula�ions
of S�a�e antl Local Codes
City of Carmel
,
��n„� �,.va�!
oarE: 03/19/20
ELECTRICAL
ABBREVIATIONS,
SYMBOLS,&
SPECIFICATIONS
E001