HomeMy WebLinkAboutM001 HVAC AbbreviationsSYMBOLS / ABBREVIATIONS
THERMOSTAT OT
MOTORIZEO DAMPER � �
SHEETMETALDUCTWIDTHBVDEPTH W��
LINEDSHEETMETALDUCTFREEAREAWIDTH _W�p _
BY DEPTH.
SQUARE SHEET METAL 90 PROVIDE WITH I / I
DOUBLETHICKNESSTURNINGVANES. LJ
RADIUS SHEET METAL 90, R=1.5'D �
��
MANUAL VOwME oAMPER LOCKING WITH SHAFT � �'
ROOF TOP UNIT � RiU
�
AIR COOLED CONDENSING UNIT aCCU
OR AIR COOLED HEAT PUMP � HP
VERTICAL FURNACE OR FC �
HORIZONTAL FURNACE OR FC WITH
SECONDARV DRAIN PAN � FC
F
HORIZONTAL AIR COOLED CONDENSING UNIT
� AC
ROOF EXHAUST FAN C��i
EXHAUST FAN � EF
ELECTRIC WALL HEATER � EWH
EXHAUSTGPoLLE � �
SUPPLVAIRDIFFUSER � �
RETURNAIRREGISTERORGRILLE � �
ROUND DIFFUSER O
LINEAR OR SLOT DIFFUSER O
DIFFUSER TAG x � MARK
XXX CFM
FIRE�AMPER � FD
COMeINATION FIREISMOKE DAMPER C� FD
SD
RADIANT FIRE DAMPER � RFD
AFF ABOVEFINISHEDFLOOR
ACCU AIRCOOLEDCONDENSINGUNIT
AWH ARCHITECTURALWALLHEATER
BDD BACK DRAFT DAMPER
BTUH BRITISH THERMAL UNIT PER HOUR
CFM CUBICFEETPERMINUTE
0 ROUNDDUCT
EC ELECTRICALCONTRACTOR
ECH ELECTRIC CEILING HEATER
EF EXHAUSTFAN
ESP EXTERNAL STATIC PRESSURE" W C.
EUH ELECTRIC UNIT HEATER
EWH ELECTRICWALLHEATER
F FURNACE
FC FAN COIL
FD RREDAMPER
FD/SD RREAN�SMOKE�AMPER
FPM FEETPERMINUTE
FSK FOIL SCRIM VAPOR BARRIER
GC GENERALCONTRACTOR
GUH GASUNITHEATER
HD HOOD
HP HEATPUMPORHORSEPOWER
IR WFRARED
MAN MANUAL
MaH i000sruH
MC MECHANICALCONTRACTOR
MCC MOTORCONTROLCENTER
MFR MANUFACTURER
OA OUTSIDEAIR
PC PLUMBINGCONTRACTOR
PSI POUNDS PER SpUARE INCH
PTAC PACKAGE�TERMINALAIRCONDITIONER
RA RETURNAIR
RTU ROOF TOP UNIT
SA SUPPLYAIR
TCC TEMPERATURECONTROLCONTRACTOR
RELEA5E0 FOR CONSTRIICTI�N �THERW�SE NOTEo
P
Su6ject �o compliance with all regula�ions
of S�a�e antl Local Codes
City of Carmel
�
�{�n„� i,.va�'
oarE: 03/19/20
MECHANICAL SPECIFICATIONS
GENERAL
1. PROJECTENCOIIRAGESCOMPETITIVEPRICWGAND
ALLOWS FOR SUBSTITUTIONS OF E�UAL EQUIPMENT
AND MATERIALS AGAINST THE BASIS OF DESIGN.
2. PRIORTOPROCUREMENTCONTRACTORSHALL
SUBMIT TO ARCHITECT FULL SUBMITTALS FOR ALL
ENERGV CONSUMING OR PRODUCING ITEMS AND
FOR ALL DUCT ACCESSORIES, W SULATION, VAV
BOXES, REGISTERS, GRILLES, DIFFUSERSAND
LOUVERS. SUBMITTALS SHALL BE DEL W EATED W ITH
TAGS INDICATED ON PRINTS, CONTRACTORS NAME,
PROJECT NAME. CLEARLY INDICATE ALL MODEL
NUMBERS AND ALL ACCESSORIES AND OPTIONS
BEING PROVIOED. SUBMISSIONS SHALL BE IN PDF
FORMAT. ALL EQUIPMENT AN� ITEMS SHALL BE PER
DESIGN BASIS OR APPROVED EpUAL ENGINEER
RESERVES THE RIGHT TO REJECT ANV SUBSTITUTE
ITEM.
3. CONTRACTOR SHALL BE RESPONSIBLE TO
COORDINATE ALL REQUIRED ELECTRICAL SUPPORT
NEEDED FROM THE ELECTRICAL CONTRACTOR.
ENSURE ALL SUBMITTALS FOR POWERED
COMPONENTS AND CONTROLS ARE PROVIDED AND
FULLV COOROINATED WITH ELECTRICAL
CONTRACTORS.
4. CONTRACTORSHALLBERESPONSIBLETOVISITTHE
SITE TO E%AMINE ALL CONOITIONS THAT MAV IN ANY
WAVAFFECTTHEEXECUTIONOFHISWOftK. HE
SHALL AL50 EXAM WE THE DRAWINGS AND
SPECIFICATIONS FOR OTHER BRANCHES OF WORK
MAKING REFERENCE TO THEM FOR DETAILS OF
EXISTING BUILDWG CONDITIONS. NO EXTRAS WILL
BE ALLOWED FOR FAILURE TO INCLUDE ALL
REDUIRED WORK IN THE BID. CONTRACTOR SHALL
GUARANTEE ALL LABOR AND MATERIALS ENTERING
INTO CONTRACT FOR A PERI00 OF ONE (1) YEAR
FROM OATE OF ACCEPTANCE.
5. THE�RAWINGSINTHISSECTIONARE
�IAGRAMMATIC AND ARE NOT INTENDED TO DEFINE
EXACT QUANTITIES, LOCATIONS OR CODIFIED
RE�UIREMENTS. DRAW WGS SHOW GENERAL
INTENT OF SVSTEMS. M.C. SHALL PROVI�E AND PAV
FORALL REQUIRED PERMITS.
6. PRIORTOWORKCOORDINATEALLOPENINGSAND
INSTALLATIONS OF DUCT, PIPING, EOUIPMENT,
CONTROLS, DIFFUSERS AND GRILLES W ITH G.C. AND
OTHER TRADES. PROVIDE INSTALLATIONS WITH
PROPERMANUFACTURERSRECOMMENDED
CLEARANCES.
]. ALL WORK SHALL BE IN FULL ACCORDANCE WITH
2014 INDIANA MECHANICAL CODE (2012
INTERNATIONAL MECHANICAL CODE), INDIANA
ENERGV CODE (ASHRAE 90.L200]) PERTINENT
STATE, COUNTV, CITV CODES AND OR�INANCES AND
INDIANA AMENDMENTS.
E�UIPMENT
1. INSTALLALL WUIPMENT W FULLACCORDANCE
WITH MANUFACTURERS RECOMMENDATIONS AN�
CLEARANCE REOUIREMENTS. PROVIOEALL
REQUIRED MOUNTING OR HOUSEKEEPWG PADS.
G.C. SHALL PROVIDE LEVEL GRADE FOR EXTERIOR
MOUNTED EQUIPMENT. M.C. SHALL PROVIDE ALL
HOISTING AND RIGGING NEEDED TO SET ALL HVAC
EpUIPMENT.
2. ALL E�UIPMENT SHALL BE INSTALLED AS NEE�ED
TO PREVENT OBJECTIONABLE NOISE ANDIOR
VIBRATION. M.Q SHALL PROVIDE VIBRATION PADS,
SPRINGISOLATORS,ATTENUATORSAND
ACCESSORIES AS NEEDED.
DUCTWORK
L CONCEALED ROUND DUCTWORK SHALL BE
CONSTRUCTED PER SMACNA LOW PRESSURE
STANOARD51" PRESSURE CLASS, 5' MAXIMUM JOINT
LENGTHS, SEAL CLASS B LONGITUDINAL SEAM SNAP
LOCK PIPE AND ADJUSTABLE FlTTINGS.
2 EXPOSEDROUNDDUCTWORK(ORWHERESPIRALIS
INDICATED ON THE PLANS) SHALL BE LINDAB OR
EpUAL GALVANIZED STEEL CONFORMING TO ASTM
STANOARDS A653 AND A924 GASKETED SPIRAL
DUCTING WITH NO SEALER EDPM RUBBER GASKET
SHALL BE U.L CLASSIFlED RATING OF RAME
SPREAD 0 AND SMOKE DEVELOPED 5 IN
ACCORDANCE WITH ASTM STANDARD E84-91A
SMACNA LEAKAGE CLASS 3. FITTINGS SHALL BE
MANUFACTURED USING ONE OR MORE OF THE
FOLLOWING CONSTRUCTION METHODS:
OVERLAPPE� E�GES STITCH WELDED ALONG THE
ENTIRE LENGTH OF THE FITTWG, STANO WG SEAM
GORE LOCKED AN� INTERNALLV SEALED, BUTTON
PUNCHED AND INTERNALLY SEALED. ELBOWS 3-INCH
THROUGH 12-INCH DIAMETER WILL BE DIE STAMPED
AND CONTINUOUSLV STITCH WELDEO.
2 PROVIDE SHEET METAL 90 FOR ALL TURNS GREATER
THAN 45 DEGREES. DO NOT USE REXIBLE �UCT
FOR CHANGES IN DIRECTION GREATER THAN 45
oecRees.
3. PROVIDEMANl1ALBALANCINGDAMPERSFORALL
SUPPLV AIR RUNS. ROUN� DAMPERS SHALL BE
SECURED ON BOTH SIDES OF �UCT AND SHALL
CONTAIN LOCKING HANDLE SPIRAL DUCTS SHALL
USE SPIRAL STVLE �AMPERS WITH FULL WIDTH
SHAFTS AND NVLON BEARINGS AT EACH END.
RECTANGULAR DUCTS SHALL USE MULTI OR SINGLE
BLADE WELDED FRAMED DAMPERS WITH JACK
SHAFTS AND LOCKING HANDLE INSTALL NYLON
RIBBON ON ALL DAMPER HANDLES LOCATED IN
INSULATED DUCTING. �O NOT INSTALL DAMPERS IN
NON ACCESSIBLE LOCATIONS. PROVIDE INTEGRAL
oAMPERS WITH �IFFUSER IN NECK IF NO
ACCESSIBLE LOCATION IS POSSIBLE ALL SUPPLV
AIR RUNS SHALL HAVE MEANS OF BALANCE. RETURN
AND EXHAUST AIR RUNS SHALL CONTAIN DAMPERS
WHERE SHOWN ON PLANS.
4. INSULATED REXIBLE DUCTING SHALL NOT EXCEED
25 FEET. ALL FLEX SHALL BE LISTED FLEXIBLE DUCT,
FLEXIBLE CONNECTORS ARE NOT ACCEPTABLE.
FLE%IBLE DUCT EQUAL TO FLEXIBLE DUCT CLASS 1
AIR DUCT, DOUBLE LAMINATED POLVESTER FILM ON
STEEL WIRE REINFORCING, INSULATED WITH SCRIM
REINFORCED METALIZED POLVESTER OIITER FIRE
RETARDANT JACKET. R-42 FOR CONDITIONED
SPACES AND R-6A FOR ANV SPACES OUTSIDE
BUILDING THERMAL ENVELOPE. FLEX DUCTS SHALL
NOT BE RUN THROUGH WALLS OR FLOORS. PROVIDE
HARD OUCTED SLEEVES AS NEEDED.
5. ftECTANGULARDUCTNORKSHALLBE
CONSTRUCTED IN ACCORDANCE WITH SMACNA LOW
PRESSURE DUCT STANDARDS, +/- 1.0" W.G FROM
ASTM A 653/A 653M G90 COATED GALVAMZEO
SHEET STEEL SEAMS SHALL BE PITTSBURGH
CONSTRUCTION, NO BUTTON PUNCH OR SNAP LOCK
SEAMS ARE ACCEPTABLE SEAL ALL TRANSVERSE
AND LONGITUDINAL SEAMS WITH WATER BASED
OUCT SEALER, SEAL CLASS 6. GAUGE AND JOINT
CLASSIFICATIONS ACCEPTABLE ARE AS FOLLOW S,
ALL SECTION LENGTHS ARE 4B" MAXIMUM, REFER TO
SMACNA RIGIDITY TABLES FOR GAUGES ON LONGER
SECTIONS IF REQUIRED:
<iP' 26GAUGE,FLATSANDDRIVE
12"-2a" 24 GAUGE FLAT S AND DRIVE
25'34" 22GAU6E,STANDINGSANDRAT
DRIVE
34"-40" 22GAUGE,STANDINGSANDSTANDING
DRIVE
�40" REFER TO SMACNA FOR STANDARDS.
6. DUCT HANGERS: COMPLV WITH SMACNA'S "HVAC
DUCTCONSTRUCTIONSTANDARDS-METALAND
REXIBLE;' CHAPTER 5, "HANGERS AND SUPPORTS"
FLEXIBLE DUCTING SHALL BE SUPPORTED USING
MINIMUM 2" WIDE NVLON STRAP. ALL INTERVALS ARE
PERSMACNA
DUCT ACCESSORIES
1. COORDINATEWITHARCHITECTURALDRAWINGSAND
PROVIDE FIRE AND FIRE AND SMOKE �AMPERS AT
FIRE RATEDASSEMBLV PENETRATIONS IN
ACCORDANCE WITH THE INTERNATIONAL BUILDING
CODE AND WHERE SHOWN ON PLANS.
2. PROVIDERASHINGMATERIALSANDORSLEEVESAS
REpUIRED FOR ALL DUCT PENETRATIONS OF NON
RATED ELEMENTS.EXPOSED PENETRATIONS SHALL
BE FLASHED WITH SHEET METAL TIGHT TO WALLS.
3. PROVIDE TAKE OFFS. PEAL AND STICK STVLE
ATTACHED TO RECTANGULAR DUCTING WITH SHEET
METAL SCRE WS FOR ALL ROUND SUPPLV AIR TAKE
OFFS AN� SADDLES.
DUCTINSULATION
1. ALL DUCT WSULATION MATERIALS SHALL HAVE A
FLAME SPREAD RATING OF 25 OR LE55 (ON THE
FLAME SPREAD TEST SCALE) ANO SMOKE
DEVELOPMENT OF 50 OR LESS (ON THE SMOKE TEST
SCALE) OR AS oEFlNED BV NFPA 255 STANDARD
METHOD OF TESTING OF SURFACE BURNING
CHARACTERISTICS OF BUILDING MATERIAL$ LOCAL
CODES ANO LOCAL AUTHORITIES HAVING
JURISDICTION. DUCT WRAP SHALL BE RBERGLASS
MATERIAL PER ASTM C-411,ASTM C-1104,ASTM C665,
ASTM C-1338, ASTM E84, U V23, NFPA 90A,CAN/ULC
5102-1188,ASTM C1290, ASTM C553, ASTM C1136.
2. INSULATION:INSTALLALLINSULATIONIN STRICT
ACCOROANCE WITH MANUFACTURERS
INSTRUCTIONS IN A TIGHT ANo NEAT MANOft. NO
SAGGING, FRAVE� ORTORN INSULATION WILL BE
EXCEPTED. UNLE55 OTHERW ISE NOTEO ON PLANS
DUCTWORK SHALL BE INSULATED AS FOLLOW S:
XX- 1412" FIBERGLASS DUCT WRAP WITH
FSK FAqN6, ]5 N/FT3 MINIMUM APPLIED
R-3.S INSTALLED IN STRICT
ACCORDANCE WITH MANUFACTURERS
REQUIREMENTS.
XX NONEREQUIREDUNLESSNOTEDON
PLANS.
XX INUNCONDITIONEDORATTICSPACES
OUTSIDE THE BUILDMG INSULATION
ENVELOPEYMINIMUM R-6ASAPPLIED
FSK DUCT WRAP.
XX- IN RETURN AIR PLENUMS OR
CONDITIONED SPACES WHERE NOT
CONCEALED BV DRVWALL CEILING OR
BULKHEAD CONSTRUCTION WITHIN THE
BUIL�ING WSULATION LME NONE
REDUIRED.
LINERS: PLENUMS, REGISTER BOXES, ANO RTU
DROPS SHALL BE MINIMUM 1" THICK
1412 # DENSITY PER CU. FT., HAVING
MAT FACED OR MONOLITHIC
CONSTRUCTION W ITH SKIN SMOOTH
MICROBIAL SURFACE TO WITHSTAND
VELOCITIES TO 4000 FPM. INSULATION
SHALL RT SNUGLY AGAINST THE
INTERIOR DUCT SURFACES, AND BE
FASTENED TO THE DUCT W ITH A 50 %
HEAW COAT OF RECOMMEN�ED
ADHESNE ANO METAL FASTENERS
WHICH DO NOT PIERCE THE �UCT,
SPACEDATI2"CENTERS.ALLEXPOSED
EDGES OF THE INSULATION SHALL BE
COATED WITH MANUFACTl1RE�
RECOMMEN�E� ADHESNE SIZES ON
PLANS INDICATE FREE AREA.
EXTERIOR INSULATEWITHCONTINUOUSMINIMUM
R-6 POLVISOCVANURATE FOAM
SHEATHING C W ERED WATER TIGHT IN
VENTURE CLAD 151�CW CLADDWG.
18. RRE STOPPING.
a. FIRE STOPPING SYSTEMS SHALL BE IN FULL
COMPLIANCE W ITH SECTIONS ]13 OF THE IBC AND
SECTION 607 OF THE IMC.
b. CONTRACTORSHALLMAKEREFERENCETO
ARCHITECTURAL PLANS AND PROVIDE ALL
REpUIRED FIRE STOPPING.
a CONTRACTORSHALLPROVIDEFIILLSUBMITTAL
INDICATING METHODS OF CONSTRUCTION AND UL
LISTING OF EACH SVSTEM.
d. DUCTS AND AIR TRANSFER OPENINGS.
PENETRATIONS OF FIRE-RESISTANCE-RATE�
WALLS BV DUCTS THAT ARE NOT PROTECTED W ITH
DAMPERS SHALL COMPLV WITH SECTIONS ]132
THROUGH ]1333 OF THE IBC. PENETRATIONS OF
HORIZONTAL ASSEMBLIES NOT PROTECTED W ITH A
SHAFT AS PERMITTED BV EXCEPTION 4 OF
SECTION ]082, AND NOT R W UIRED TO BE
PROTECTED WITH FlRE DAMPERS BV OTHER
SECTIONS OF THE IBC CODE, SHALL COMPLV WITH
SECTIONS ]13 4 THROUGH ]13 4 2 2 OF THE IBC.
DUCTS AND AIR TRANSFER OPENINGS THAT ARE
PROTECTED W ITH DAMPERS SHALL COMPLY WITH
SECTION ]i6.
e. FIRE DAMPERS, SMOKE DAMPERS, COMBINATION
FIRE/SMOKE DAMPERS AND CEILING RAOIATION
DAMPERS LOCATED WITHIN AIR OISTRIBUTION AND
SMOKECONTROLSVSTEMSSHALLBEINSTALLED
IN ACCORDANCE W ITH THE REpUIREMENTS OF
SECTION 60] OF THE IMC. AND THE
MANUFACTURER'S INSTALLATION INSTRUCTIONS
AND LISTING.
f. ACCESS DOORS SHALL BE PERMITTED IN CEILINGS
OF FIRE-RESISTANCE-R4TED FLOOR/CEILING AND
ROOF/CEILING ASSEMBLIES PROVIDE� SUCH
DOORS ARE TESTED IN ACCORDANCE WITH ASTM E
119 OR UL 263 AS HORIZONTAL ASSEMBLIES AND
LABELEDBVANAPPftOVEDAGENCYFORSUCH
PURPOSE. ALL ACCE55 DOORS SHALL BE
PROVI�ED BV TRADE MAKING PENETRATIONS.
CHECK TEST ANo $TART UP REQUIREMENTS
1. ALLHVACEQUIPMENTINSTALLATIONSSHALLBE
VERIFIED AND STARTED UP PER MANUFACTURERS
RECOMMENDATIONS. VERIFV ALL MOOES OF
OPERATION. CONFIGURE ALL CONTROLS AN�
PROGRAM OCCUPANCIES PER OWNER PROVIDED
SCHEDULES.
2. PROVIDEAIRBALANCEBYCONTRACTOR.
CONTRACTOR SHALL BALANCE SUPPLV, RETURN,
OUTSIDE, RELIEF AND EXHAUST AIR SVSTEMS IN
ACCORDANCE W ITH CURRENT SMACNA, NEEB OR
AABC STANDARDS TO DESIGN VAW ES AND PROVIDE
WRITTEN REPORT TO ARCHITECT. MECHANICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVIDWG ALL DEVICES �RNES, SHEAVES, MOTOR
CHANGES AND RE WORK AS REQUIRED TO MEET
OESIGN REpUIREMENTS.
3. TEMPERATURE CONTROL WORK SHALL BE THE
RESPONSIBILITV OF THE HVAC CONTRACTOR.
PROVIDE ALL COMPONENTS INCLUDING T/S, T/S
W IRE (PLENUM RATED IN RA PLENUMS), SW ITCHES,
ACTUATORS ETG AS REpUIRED FOR A COMPLETE
SVSTEM. PRIOR TO ROUGH-IN COORDINATE FINAL
LOCATION FOR ALL CONTROLS WITH OWNERS
REPRESENTATNE.
4. CLOSE OUT: PROVIDE MANUFACTURERS OPERATION
AND MAINTENANCE MANUALS, AIR BALANCE REPORT
AND AS BWLT �RAWINGS. PROVIDE (1 � TRAINING
SESSION TO OW NER SELECTED PERSONNEL AS
REQUESTEO AND PROVIDE WARRANTY
INFORMATION FORALL MANUFACTURERS
WARRANTED EOUIPMENT.
DIFFUSERS, REGISTERS AND GRILLES
TAG DESCRIPTION MFR MODEL MAT'L CFM MOUNTNG INTEGRAL NOTES:
STVLE DAMPER
5-� 12"X12" LAV-IN �IFFUSER-6" NECK PRICE SCD STL 100 LAV-IN NO 1 2
5-2 24"X24" LAV-IN �IFFUSER-6" NECK PRICE SCD STL 100 LAV-IN NO 1 2
S-3 24"X24" LAV-IN �IFFUSER-8" NECK PRICE SCD STL 130-220 LAV-IN NO 1 2
S-4 10X4 DOUBLE DEFECTION REGISTER PRICE 52� ST 0-054 LAV-IN VES 1 2
Ei 6X6DOUBLEDEFECTIONREGISTER PRICE 52� STL �-]5 SURFACE VES �O2
R-1 24X12FlXEDBLADEGRILLE PRICE 53� STL 0-00�0 LAV-IN NO �O2
� COLOR'. WHITE
� REFER TO FLOOR PLAN FOR EXACT CFM.
LOUVERS, INTAKES, RELIEFS
MIN FREE
GREENHECK TVPEFANAND FftEE PSI AREA
MWEL# LOCATION�SERVICE DESCRIPTION SRE CFM AREA OROP VEL NOTES
(FT2) (IN WG.) FPM/MA
ESD-035 GARAGE 4"INTAKELOWER 32W.xi6H. 1,100 1.6 0.08 989
ENERGY RECOVERY SCHEDULE
PERFORMANCE OATA ELECTRICAL DATA
GREENHECK TVPEAN� SUMR WNTR SUPPLV EXHAUST
TAG MODEL# DESCRIPTION CFM EFF EFF ESP ESP HP VOLTS/PHIHZ MCA MOCP
ERV4 ERV-2045L STATICPLATEHEATANDHUMIpITV 11�0 ]9.1% 81.8% 0.5 15 (1)3/4,(1)1 208/3/60 8.8 15
VENTILATION AIR CALCULATIONS
TOTAL OCCUPANTS CALCULATED CFM/PERSON PEOPLE CFM AREA CFM AREA CFM TOTAL CFM E%HAUST RATE
AREA TVPE NET PER 1000 FT OCCUPANTS REQUIRMENT REQUIRE� RpUIRMENT REQUIRED REpUIREO CFM X 0.6
AREA CFM/FT2
1781 25 30 20 600 0.12 143 143 �12
TOTAL 1187 743 772
1"Xi"Xi/B" STEEL ANGLE �
SCREW TO LOWER SLEEVE 6"
O.C. N 1 � SCREWS AND
ANCHOREDTO MASONRV
WALL iP' O.C. WITH 1/6"
MASONRV ANCHORS. TYPICAL
TOP, BOTTOM AND SIDES �
LOWER SLEEVE
20 GA.
INTERIOR
CAULK INTERIOR ANO
- EXTERIOR PERIMETER
WEATHERTIGHT WITH
URETHANE CAULKING.
LOUVER COLOR TO BE
APPROVEDBY
ARCHITECT
EXTERIOR
SECURE REXIBLE OUCT TO
SUPPLY DIFFUSER ELBOW
FITTING WITH DRAWBANDS.
SHEET METAL ELBOW
SEAL ALL RIBS AND
CONNECTION TO
DIFFUSER NECK
SUPPLY �IFFUSER
ACT CEILING
A MASONRY PENETRATIONS
SCALE: NONE
45 DEG.
O
RECTANGULAR LL
DUCT �
BRANCH � ¢
OCL CONNECTION
TAKEOFF.HAMMER
LOCKED OR FLANGED ANO
FULLV SEALED
ROUNOSHEETMETAL
�UCTTODIFFUSER V.D.
� LL
¢
45 DEG. HIGH EFFlqENCV �
TAKE OFFCOMPLETELV �
SEALED �
�30° MAX
�
�
OFFSET. PROVIDE MINIMUM 2"
STRAIGHT SECTION AT EACH
END. MAX 30 DEG.
LAY-IN DIFFUSER DETAIL
BNO SCALE
�0 M� �
ECCENTRIC TRANSITION MAX,
30 DEG.
v
NOTE:
IN GENERAL, ELBOWS TO HAVE
FULL TURNING RADIUS (R=A).
WHERE "R" IS EpUAL TO OR
GREATERTHAN"A" MINIMUM
RA�IUS (RJ=4 WCHES.
� 0
CONCENTRIC
TRANSITION MAX, 45
DEG. DNERGING AND
60 DEG. CONVERGING
��
�� im
1Y
NOTE:
DOUBLE THICKNESS
TURNING VANES TO BE USED
WHERE NORMAL RADIUS
ELBOW IS IMPRACTICAL
& WHERE ELBOW IS WITHIN 5
FT OF A
BRANCHTAKE-OFF.
DUCT CONSTRUCTION DETAILS
CSCALE NONE
REX DUCT MAXIMUM LENGTH
SHALL NOT EXCEED T-0"
�
Z
K Q
W
W
Z
�
Z
W
� �
W
a ` o
U d �
0 �
� � >N N
Q W > �
� C� �N N(O C
�'.. ��� r �
�� C c0 W N C
� c � � p � �
w o a�zu���
OU
L -
o a U � � � �
O W a OMM'O
i'J� W QaIL W
W
N
�
�
�
�
V/
N
W
V
� �
��
V/
�
NO. �€
10200395 � �--�
s.<.EOF �u�E_--'--' / 1
2�
i
�a
I
�/ �
w > C� �
oH
��
m`S�ONA�.E?O.. 7� %� i� j �
°�mu noo��
/
11/27/2019
n
O
O�
U
W
0
�
d
G
�
� ^
� Q �
0 Z �
W Z
� O W
ti
w
� � �
(h
C`7
O
� �
Q �
OQ
� z
Q
J � �
Z Z WC
} � C
Q (7 �
U �U
�
Z
� �
Z ¢
O U
~ LL
Q -
jU
W w
�a
m �
Q �
�
�m
�
}
�
M001