GENERAL N07E5
I. 'ALL 20 AMP CIRCUITS UP TO 100' IN LENGTN SNALL UTILIZE #12 CONDUCTORS MINIMUM. ALL 20
AMP CIRCUITS FROM 100' TO 150' IN LENGTN SNALL UTILIZE tt10 CONDUCTORS MINIMUM. ALL 20
AMP QRCUITS 150' UP TO 250' IN LENGTN SHALL UTILIZE tt8 CONDUCTORS MINIMUM. ALL 20
AMP QRCUITS ABOVE 250' SNALL UTILIZE ttb CONDUCTORS MINIMUM. CALCULATED LENGTN IS
FROM OVERCURRENT PROTECTION DEVICE TO FARTNEST DEVICE IN ELECTRICAL RUN.
2"MS" REPRESENTS MOTION SENSOR, SEE SPEQFICATION IN LIGNTING FIXTURE SGNEDULE SNEET
E5.1. CONNECT TO FIXTURES PER MANUFACTURER'S RECOMMENDATIONS.
3. GONNECT ALL EMERGENCY LIGHTS AND EXIT SIGNS TO INDICATED CIRCUITS AHEAD OF ALL
SWITGNING. SEE CODED NOTES BELOW.
4. FINAL CONNECTIONS TO ALL LAY-IN FIXTURES AND RECESSED CAN FIXTURES IN LAY-IN
CEILINGS ARE TO BE MADE WITN GREENFIELD FLEXIBLE CONDUIT OR MC CABLE.
5. REFER TO ARCNITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF LIGNT FIXTURE
LAY-OUT. CONTRACTORS TO CORRELATE LOCATIONS OF LIGNTING, SPEAKERS, AIR DIFFUSERS,
GRILLES, AND TNE LIKE, WITN REFLECTED CEILING LAY-OUTS AS REQUIRED.
6. ALL DEVICES, EQUIPMENT, FIXTURES, AND THE LIKE, MUST BE GROUNDED BY USE OF A
PROPERLY SIZED GROUNDING GONDUGTOR. MECHANIGAL/ ELECTRIGAL BONDS OF THE METALLIC
RACEWAY SYSTEM SNALL AL50 BE MAINTAINED.
7. CIRCUITS MAY BE COMBINED IN A SINGLE CONDUIT PROVIDED WIRE IS PROPERLY DE-RATED
AND CONDUIT SIZED PER CODE. UNDER NO CIRCUMSTANCES SHALL MORE THAN (q) CURRENT
GARRYING CONDUCTORS BE RUN IN A SINGLE CONDUIT.
8. ALL CONDUITS SNALL CONTAIN A GROUND WIRE SIZED PER NEC TABLE #250.122. IN ADDITION,
WNERE AN ISOLATED, INSULATED GROUND IS REQUIRED A SEPARATE GREEN W/YELLOW
TRACER GROUND SNALL BE RUN FROM TNE PANEL ISOLATED GROUND BUS TO TNE ISOLATED
GROUND CONNECTION OF TNE DEVICE.IN NO CASE SNALL THE SYSTEM GROUND (WIRE AND
ASSOCIATED OUTLET BOXES, CONDUIT AND BUILDING STEEL) BE ALLOWED TO CONTACT TNE
ISOLATED GROUND (GREEN W/YELLOW TRACER WIRE AND DEVICE). WNERE CIRCUIT
CONDUCTORS ARE INCREASED IN SIZE FOR VOLTAGE DROP, TNE GROUND WIRE SIZE SNALL BE
INCREASED PROPORTIONATELY (ACGORDING TO CIRGULAR MIL AREA) FROM THE SIZE REQUIRED
BY N.E.C. TABLE #250.122.
q. ALL TRACK LIGNTING IS 120V, IPH AND ARE TO BE CIRCUITED TO PANEL P2 (480/277V
STORES ONLY. FOR 120/208V STORES CIRCUI7 TO PANEL LP).
/ \
CODED NOTES
1O SALES AREA EXIT AND EMERGENCY LIGNTING FIXTURES ARE TO BE WIRED TO LOCAL CIRCUIT
ANEAD OF ALL SWITCNING AND ENERGY MANAGEMENT SYSTEM. PROVIDE LOCK ON DEVICE AT
CIRCUIT BREAKER.
2O BACK OF NOUSE FIXTURES TO BE WIRED TO LOCAL CIRCUIT ANEAD OF ALL SWITCNING AND
ENERGY MANAGEMENT SYSTEM CONTROL.
O3 COORDINATE PLACEMENT OF MOTION SENSOR WITN OTNER EQUIPMENT IN LOCAL AREA. ENSURE
TNAT COVERAGE IS MAINTAINED FOR ACTIVATION OF MOTION SENSOR. CONTRACTOR TO SET
SENSOR TO SNUT OFF LIGNTS AT MAXIMUM TIME IF MOTION IS NOT DETECTED. MOTION SENSOR
TO BE MOUNTED TO A J-BOX
O ELECTRICAL CONTRAGTOR SHALL SUPPLY AND INSTALL SJ CABLE TO BE TIE WRAPPED TO
AIRCRAFT CABLE. USE FOR NF-I £ NF-lA FIXTURES. SJ CABLE SNALL BE WNITE. MC CABLE TO
BE USED IF RERUIRED BY LOCAL CODES.
5O ELECTRICAL CONTRACTOR TO SUPPLY AND INSTALL JUNCTION BOX MOUNTED TO CEILING AT
TRACK SUPPORT. SJ CABLE TO BE TIE WRAPPED TO AIRCRAFT CABLE LEADING TO TRACK.
O6 PROVIDE JUNCTION BOX AND DISCONNECT SWITCN FOR SNOP SIGN. CENTER JUNCTION BOX OVER
OPENING AND PROVIDE ACCE55 PANEL ON BACKSIDE OF WALL COORDINATE EXACT MOUNTING
NTG WITN SIGN VENDOR PRIOR TO ROUGN-IN. SEE ARCNITECTURAL ELEVATIONS FOR EXACT
LOCATION.
° 2 ' BIB�NOTES
NOTTOSCALE IA
Z W � N
� = O
O F N N
> � w �
� a o 0
w
N
�
O �
�, o m
� � W W M
a �aaa
3 ��
N��z
C/� o �;;�
cn Oa��
W (nUUU
�
Z �
�
h
W
�
�
V
�
�
r"GE q, !HQ ^+,
�y`Z'� �V�STFkr��i
�
LL
❑
r
m
0
w
Y
U
U
z
¢
❑
m
z
�
0
ENG JOB # 19-41-215
DRAWING NUMBER:
El.l
�
F
s
�
DATE: 03�20�20