HomeMy WebLinkAboutE106.1-ElectricalSpecifications16010 ELEGTRIGAL GENERAL PROVISIONS
A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO
INSTALL NEW ELECTRICAL SYSTEM COMPLETE AS INDICATED CN DRAWINGS, AS
REQUIRED BY CODE AND AS SPEQFIED NEREM, IN SECTIONS 16010 THROUGH 16722
I. TEMPORARY SERVICE AS REQUIRED.
2 PRIMARY DISTRIBU710N BY ELECTRIC COMPANY_
3. SECONDARY SERVICE AND METERING FROM LANDLORD'S DISTRIBUTION
EQUIPf1ENT� INSTALLATION BY CONTRACTOR.
4. EMERGENCY AND EXIT LIGNTING SYSTEMS.
5. E�1PTY CONDUIT TELEPNONE SYSTEM AS SFIOWN ON TFIE DRAWINGS.
6. LIGFITING, NVAC AND POWER PANELS AND BRANCN GRCUIT WIRING.
7. WIRING DEVICES AND PLATES.
8. LIGNTING FIXTURES AND LAMPS, INSTALLATION AND WIRING.
9. LIGNTING CONTROLS.
10. CONNECTIONS TO EQUIPMENT FURN1541ED BY OTNERS.
B. WORK W411C4! SFJALL BE PERFORMED BY OTFIERS WCLUDES TFJE FOLLOWING-
L FlNAL CONNECTIONS OP MISCELLANEOUS EQUIPMENT BY TENANT.
2 TEMPERATURE CONTROL WIRING TNAT IS FURNISNED BY OTNERS PRE-WIRED IN
UNITS.
3. TELEPNONES AND FINAL CONNECTION OF WIRING T4lERETO.
4. WTERNAL WIRING OP EQUIP�1ENT FURN1541ED AND PRE-WIRED BY OTNERS.
5_ SECURITY SYSTEI'1 FURNISHED AND WSTALLED BY TENANT'S SECURITY
CONTRACTOR.
C. ELECTRICAL EQUIPMENT FURNISIJED BY OT41ER TRADES OR BY TENANT AND
SPEQFIED IN OR SNGWN ON CONTRACT DOCUMENTS SNALL 6E INSTALLEG AND
CONNECTED BY ELECTRICAL CONTRACTOR, EXCEPT AS OTNERWISE NOTED. PROVIDE
BRANCN QRCUIT CONNECTIONS TO ELECTRICALLY OPERATED EQUIPMENT FURNISNED
BY OTNERS AS SPEQFlED IN OR S410WN ON TNE CONTRACT DOCUMENTS. TEMPORARY
WIRING FOR OTFIER CONTRACTORS 54JALL BE INSTALLED BY T4JE ELEGTRIGAL
CONTRACTOR WNO SNALL BE ENTIRELY RESPONSIBLE TO TNE TENANT FCR TNE SAFE
AND SATISFACTORY OPERATION OF SAID TEMPORARY WIRING. CONTRACTOR
REQUIRING SUCN TEMPORARY WIRING S41ALL PAY FOR ALL DAMAGE TO PROPERTY
RESULTING FROM ITS USE COf1PLY WITFI LATEST REQUIREMENTS OF OCCUPATIONAL
SAPETY AND NEALTN ACT (OSNA). PROVIDE PERSONNEL WITN GROUND FAULT
PROTECTION ON ALL 7EMPORARY POWER AND LIGNTING QRCUITS 30 AMPERES OR
LESS. GROUND FAULT QRCUIT INTERRUPTERS ON CONSTRUCTION QRCUITS ARE NOT
REQUIRED WNERE GIRCUIT IS A PERMANENT GIRGUIT TO BE A PART OF TF1E
COMPLETED BUILDING. NOWEVER, CONTRACTOR SNALL PROVIDE APFRCVED CORD
SETS INCORPORATING GFCI PROTECTION FOR PERSONNEL SEE 2008 N.E.C. ALL FINISN
PAINTING IS TO 6E PERFORMED 6Y GENERAL CONTRACTOR, 410WEVER, TNIS
CONTRACTOR SHALL RESTORE TO ORIGINAL CONDITION ANY PAINTING DEPACED BY
FlIM APTER ORIGINAL PAINTING.
D. ALL WORK 541ALL 6E DONE IN ACCORDANCE WITVJ:
I. NATIONAL ELECTRICAL COCE.
2 CODES�. STATE, QTY AND COUNTY BUILDING CODES AND ORDINANCES_
3. NATIONAL BOARD OF FIRE UNDERWRITERS.
4- CERTAW CODES AND STANDARDS AS SET UP BY VARIOUS TEC4lNICAL SOCIETIES
SUCN AS UL, NEMA, NECA, IEEE, A5T�1, IES, IPCEA, AND ANSI.
5. TNIS WORK SNALL BE GOVERNED ALSO BY LOCAL MSPECTOR'S REQUIREMENTS.
6. FEDERAL OCCUPATIONAL SAFETY AND FIEALTFI ACT STANGARDS.
7_ AMERICANS WIT41 DISABILITIES ACT.
E ALL PER�11T5 REQUIRED BY LAWS, ORDINANCES AND BUILDING CODES 41AVING
JURISDICTION SNALL BE OBTAWED AT PROPER TIME BY AND AT TNE EXPENSE CF
TNIS CONTRACTOR.
F. ALL ELECTRICAL WORK SFIALL BE INSPE�TED BY TFIE GOVERNMENTAL AGENCY
4lAVING JURISDICTION, INCLUDWG LOCAL INSPECTION AUTFIORITIES.
G. UFON COMPLETION OF T4JE WORK, TIJIS CONTRACTOR 54lALL FURNI54! TO TFJE
ARCNITECT A CERTIFICATE OF INSPECTION AND APPROVAL FROM TNE ABGVE
DEPARTMENT BEFORE PINAL PAYMENT ON CONTRACT WILL BE ALLOWED.
IJ. TEST ALL WIRING AND CONNECTIONS FOR CONTINUITY AND GROUNDS BEFORE ANY
EGUIPMENT IS CONNECTED. WNEN DIRECTED BY ARCNITECT, DEMONSTRATE BY
PROPER VOLTAGE �1EGGER TEST OF INSULATION RESISTANCE OF ANY CONDUCTORS
AND REPLACE ALL CONDUCTORS WNICFJ FAIL SAID TESTS UNTIL ALL CONDUCTORS
ARE PREE FROM INSULATION PAULTS.
L ELECTRICAL LAYOUTS ARE SCHEMATIC. EXACT LOCATIONS ARE DETERMMED BY
EXACT LOGATION OF EOUIPMENT, ETG., AND MAY BE REVISED TO SUIT TNE
CONSTRUCTION CONDITIONS AND AID IN COORDINATION WITN WORK OF OT41ER
CONTRACTORS.
RELEA5E0 FOR CONSTRIICTI�N
Su6jec��o compliance with allregula�ions
of S�a�e antl Local Codes
City of Carmel
,
�{�n„� i,.va�i_
DATE: 03�20�20
1 ELECTRICAL DRAWINGS ARE WTENDEG TO INDICATE APPROXIMATE LGCATIONS OF SWITCNES,
RECEPTAQES, LIG4JTING FIXTURES AND OT4JER ITEMS OF VARIOUS ELECTRICAL SYSTEMS
OF PROJECT_ EXACT LOCATIONS AND ROUGN-IN DIMENSIONS FOR ALL WORK AND EQUIPMENT
SLIALL BE OBTAMED FROM ARGFIITEGT OR F115 REPRESENTATIVE AS WORK PROGRESSES.
54lOULD TNE ELECTRICAL CONTRACTOR FAIL TO PROPERLY OBTAIN SUCN LOCATIONS OR
DIMENSIONS, FIE SNALL CNANGE TNIS WORK AT NIS EXPENSE WNEN REQUESTED BY
ARC4lITECT. ARCIJITECT RESERVES T41E RIGLIT TC MAKE MINOR C4lANGES IN LOCATIGN OF
ELECTRICAL WORK OR EQUIPf1ENT PRIOR TO ROUGNING IN WITN NO ADDITIONAL COST TO
OWNER.
K. T41E ARCFJITECT OR TENANT RESERVES TFIE RIGNT TO DIRECT REMOVAL AND REPLACEMENT
OF ANY ITEM WNICN, IN NIS OPINION, SNALL NOT PRESENT AN ORDERLY OR REASONABLY
NEAT OR WORKMANLIKE APPEARANCE, PROVIDED TNAT SUCN ITEM CAN BE PROPERLY
INSTALLED IN SUCN ORDERLY WAY BY MET410D5 USUAL M SUC4! WORK, OR WNICN DOES
NOT COMPLY WITN CONTRACT DRAWINGS OR SPEQFICATIONS. SU�FI REMOVALS OR
REPLACEMENTS 541ALL BE DONE BY CONTRACTOR WNEN 50 DIRECTED IN WRITING BY
ARCNITECT OR TENANT AND AT CONTRACTOR'S EXPENSE.
L TNE CCNTRACTOR SNALL SUBMIT SNOP DRAWWGS FER TNE COCUMENTS PROVIDED BY TNE
TENANT
M. MANUPACTURER'S CATALOG CUTS MAY BE SUBMITTED FOR STANDARD CATALOG LIGN7ING
FIXTURES AND OTNER EQUIPMENT. CATALOG CUTS MAY BE �1ARKED UP TO I'1EET TNE
PROJECT SPEQFICATIONS. CUTS SNALL BE MARKED TO INDICATE MODEL NUMBER, SIZE,
TYPE� COLGR, RATING� ETC., OF TNE ITEM TO BE FURNISFIED.
N. DIG AND BACKFILL ALL TRENCNES AND FIOLES REQUIRED TO PLACE UNDERGROUND
ELECTRICAL WORK TRENCNES FOR BURIAL OF ELECTRICAL CONDUITS, DUCTS, OR
CONDUCTORS S41ALL BE A MINIMUM OF 30" DEEP BELOW FINISFIED GRACE� OR GEEPER, AS
5410WN ON DRAWINGS OR TO ACCOMMODATE FIELD CONDITIONS OR LOCAL CODES. TRENCN
BOTTOMS SNALL BE FLAT AND SMOOTN UNDISTURBED EARTN. WIDTN OF TRENCNES SNALL
BE AS REQUIRED TO ACC0�1�10DATE TNE CONDUCTORS, CONDUIT OR DUCT-BANK BUT IN NO
CASE LE55 TNAN 6" WIDE
0. PROVIDE INSTRUCTION TO TENANT'S OPERATING PERSONNEL AS NECESSARY, SNOWING
LOCATIONS AND PROPER OPERATION OF MAJOR ITEMS OF EQUIPMENT AND SYSTEM
COMPONENTS AND REFERRING TO TIJE OPERATING INSTRUCTION MANUAL DESCRBED BELOW
AS A 6UIDE.
P. COMPILE ELECTRONIC MANUAL OF OPERATING INSTRUCTIONS INCLUDING COPIES OF SNOP
DRAWINGS AND A LISTING OF EQUIPMENT SUPPLIERS_ MATERIAL 54lALL BE AS FOLLOWS�.
I_ TITLE PAGE, TITLE OF JOB, TENANT, ADDRESS, DATE OP SUBMISSION, CONTRACTOR,
AND ENGINEER.
2. INDEX.
3.LIST OF MAJOR EQUIPMENT USED IN PROJECT ACCOMPANIED BY CONTRACTOR PURC4IASE
ORDER NUMBERS AND SUPPLIERS' NAMES AND ADDRESSES.
ON CO 0 C4! SNO WIN OU 5 0 QUI M N I I N IN
4 E PY F EA P DRA G GR PED 6Y TYPE F E P E T, .E, LG T G
FIXTURES, PANELBOARDS, ETC.
5.SECTION FGR EACN SYSTEM, WCLUDING:
a_ BRIEF DESCRIPTION OF SYSTE�1 OPERATION WITN LOCATION OF �1AJOR COf1PONENTS.
b_ LIST OF ITEMS IN SYSTEM REQUIRWG PERIODIC SERVICE. REOUIRES SEPARATE
SECTION FOR EACIl OF ELECTRICAL DISTRIBUTION SYSTEM FROM TNE SERVICE
ENTRANCE TO EAC4! LIG4ITMG AND POWER PANEL AND OTNER 5Y57EM5 (LE CONTROL
SYSTEMS AND ANY OT41ER ELECTRICAL CONTR4CTOR SYSTEM LISTED IN T41ESE
SPECIFICATIONS.)
Q. ELECTRICAL CONTRACTOR SNALL GUARANTEE 4115 WORKMAN5411P AND MATERIAL, EXCEFT
FOR TENANT-SUPPLIED MATERIAL, FOR A PERIOD OF ONE YEAR FROM DATE OF
SUBSTANTIAL COMPLETION AND LEAVE NIS WORK IN PERFECT ORDER AT COf1PLETION.
R. SNOULD DEFECTS DEVELOP WITNIN GUARANTEE PERIOD, TNIS CONTRACTOR SNALL, UPON
NOTICE CF SAME, REMEDY CEFECTS AND NAVE DAMAGES TO OTNER WORK OR FURNISNINGS
CAUSED BY DEFECTS OR WORK OR CORRECTING SAf1E REPAIRED AND/OR REPLACED AT
NIS EXPENSE TO CONDITION BEFORE SUC41 DAMAGE.
5. WITNIN 60 DAYS AFTER TF1E DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF TIJE
ACTUAL INSTALLATION SNALL BE PROVIDED TO T41E TENANT_ RECORD DRAWINGS S41ALL
INCLUDE AS A MINIMUM TNE LOCATION AND RATING OF EACN PIECE OF EQUIPMENT,
GENERAL CONPIGURATION OF WIRE AND CONDUITS INCLUDING SIZES AND ROUTING, ETC.
16100 ELECTRICAL BASIC MATERIALS AND METHODS
A. ELECTRICAL CONDUCTORS SFIALL BE ENCLOSED IN CONTINUOUS GROUNDED RACEWAY
SYSTEM EXCEPT AS OT4IERWISE NOTED_
B_ RACEWAY AND ENCLOSURE SIZES SNALL BE AS SNOWN ON DR4WING5 OR, IF NOT SFIOWN,
541ALL BE SIZED TO COMPLY WIT41 N.E.C. PILL REQUIREMENTS POR CONDUCTORS ENCLOSED.
G. RAGEWAYS AND ENGLOSURES SFIALL BE ADEQUATELY SUPPORTED FROM BUILDING
STRUCTURE WITN AFPROVED SUPPORT RODS AND/OR CLAf1P5.
D_ ALL CONDUIT S4lALL BE RIGID 4lEAVYWALL GALVANIZED STEEL OR TNIN WALL EMT WNERE
PERMITTED BY CODE OR AS NEREINAFTER SPEQPIED. PVC SCLIEDULE 80 CONDUIT MAY BE
USED UNDER FLOOR SLAB. MINIMUM CONDUIT SIZE SNALL BE 3/4"
E. ALL CONDUIT FITTINGS SNALL BE GALVANIZED MALLEABLE IRON OR STEEL �ONNECTORS
AND COUPLINGS SLlALL BE TLlREADED OR CUPPED SET SCREW TYPE, CONCRETE TIGNT.
CONDUIT BODIES SNALL BE MALLEABLE IRON, TNREADED FOR NEAVYWALL CONDUIT AND
CUPPED SET SCREW TYPE FOR EMT, WITN CADf11Uf1 FINISFI AND CADMIU�1 PLATED SFIEET
STEEL GOVERS. SYNTNETIC RUBBER GASKETS SFIALL BE USED UNDER BODY GOVERS
EXPOSED TO WEATNER. EMT CONNECTORS SNALL BE INSULATEC TNRCAT TYPE.
E EMT T411N WALL �ONDUIT �1AY BE USED INSIDE NOLLOW PARTITIONS, AND ABOVE
SUSPENDED CBLINGS AND EXPOSED A60VE 8'-0" ABOVE FINISNED FLOOR OR ABOVE
PANELBOARDS_ EMT CONDUIT MAY NOT BE USED BURIED IN EARTN OR FILL, IN OR
UNDER CONCRETE FLOOR OR IN POURED CONCRETE CONSTRUCTION. PVC CONDUIT USED
UNDER FLOOR SLABS 54lALL NAVE RIGID GALVANIZED 57EEL ELLS AND METALLIC
CONDUIT ABOVE FLOOR SLAB. CONDUITS INSTALLED IN GROUND FLOOR CONCRETE
FLOOR SLABS SNALL BE COVERED TOP AND BOTTOM WIT41 A MINIMUM OF 2" OF
CONCRETE.
G. CONDUIT SNALL .iENERALLY BE CONCEALED WNERE POSSIBLE. NO CONDUIT SNALL BE
RUN M SLAB, EXCEPT AS REQUIRED FOR FLOOR-MOUNTED DEVICES.
N. EXPOSED CONDUIT WILL BE PERMITTED W ELECTRIC ROOMS, AND SIMILAR UNFINISNED
SPACES, OVERFIEAD IN AREAS WIT410UT CEILINGS AND ELSEWFIERE AT T4lE DISCRETION
OF TF1E ARCIJITECT OR TENANT.
I. DURING ROUGNING-IN, CAP ALL CONDUITS WNIGN MAY BECOME FOULED WITN FOREIGN
MATERIAL.
I. FLEXIBLE CONDUIT SNALL BE USED FOR "MAKEUP" CONNECTIONS TO VIBRATMG
EQUIP�1ENT, MOTORS, AND AS OTNERWISE NECESSARY OR PERMITTED BY CODE.
LIGNTING FIXTURES MAY BE SUPPLIED WITN SNORT LENGTNS (MAX. 6'-0") OF
FLEXIBLE CONDUIT. GROUNDING SFIALL BE GREEN GROUNDING CONDUCTOR AS
SPEQRED IN "GROUNDING"
2 PLIXIBLE CONDUIT SNALL BE UL APPROVED V2" MINIMUM TRADE SIZE.
3.LIQUID-71G41T FLEXIBLE CONDUIT AND LIQUID-71GNT FI7TING5 SNALL BE USED IN
AREAS EXPOSED TO TNE WEATLlER OR EXCESSIVE MOISTURE.
1 NO MORE THAN POUR (4) q0-DEGREE BENDS WILL BE ALLOWED IN ANY ONE CONDUIT
RUN. WFIERE MORE BENDS ARE NECESSARY IN ANY SINGLE RUN, A PULL BOX SIJALL
BE INSTALLED. PULL BOXES SNALL AL50 BE MSTALLED IN LONG RUNS AT A MAXIMUM
SEPARATION OF 100'-0". ALL CONDUIT EXCEPT M CONCRETE SLAB OR EARTN SNALL BE
ROUTED PARALLEL OR PERPENDICULAR TO TNE LWES OF TNE BUILDING, AND NO
OUT-0E-PWf�B OR DIAGONAL LMES WILL BE ACCEPTABLE.
K. OUTLETS SFIALL BE PROVIDED FOR DEVICES, LIGNTING FIXTURES, f10TOR5 AND
EQUIPMENT CONNECTIONS, SYSTEMS EQUIPMENT CONNECTIONS, SPEQAL OUTLETS AND
AS OTFIERWISE REC�UIRED-
L CONDUCTORS SFIALL BE COPPER. UNLESS NOTED OTFIERWISE ON TFIE DRAWINGS, TFIE
MINIMUM GOPPER WIRE SIZES POR WET AND DRY AREAS AS DEPWED BY TIJE N.EG.
SNALL BE AS FGLLGWS:
20 AMP CKT BKR OR FUSE _#12 AWv, TNNN/TNWN
30 AMP CKT BKR OR PUSE = tt10 AWG, TN41N/TNWN
40 AMP CKT BKR OR FUSE = tt8 AWG, TNNN/TNWN
50 AMP CKT BKR OR FUSE _#8 AWG, TF141N/TNWN
100 AMP CKT BKR OR FUSE _�3 AWG, TNNN/TFJWN
125 AMP CKT BKR OR FUSE = ttl AWG, TNNN/TNWN
200 AMP CKT BKR OR FUSE = tt3/0 AWG, TNNN/T41WN
CONDUCTORS USED FOR EMERGENCY LIGNTING CIRCUITS 541ALL
BE tt10 AWG, MINIMUM, AND SNALL BE RUN IN SEPARATE
CONDUIT USED FOR NO OTNER PURPOSE.
M. TNE FOLLOWING COLOR CODE SNALL BE USED-
208/120 VOLT 480/277 VOLT
P41ASE A BLACK BROWN
PNASE B RED PURPLE
P41ASE C BLUE YELLOW
NEUTRAL WNITE GRAY
GROUND GREEN GREEN
ISOLATED GROUND GREEN WITL1 YELLOW TRACER
N. GIRCUIT BREAKER/FUSE AND WIRE SIZE COMBINATIONS NOT SIJOWN ABOVE SFIALL BE
APPROVED BY TNE ENGWEER PRICR TO INSTALLATION.
G. FURNISN AND INSTALL WIRING GEVICES, INCLUDING SWITCNES, RECEPTACLES AND
POWER RECEPTAQES, TELEPNONE OUTLET BOXES, COVERPLATES AND BLANK OUTLET
PLATES AS SNOWN OR DESCRBED ON CRAWMGS. WIRING DEVICES SNALL BE NUBBELL
OR EQUNALENT PREMIU�1 SPEQFICATION GRADE AS f1ANUFACTURED BY BRYANT,
EAGLE, SLATER, PASS 4 SEYMOUR, OR LEVITON_ COLOR OF RECEPTAQES, SWITC4lES
AND COVERPLATES SNALL BE COORDINATED AS FOLLOWS-
P�inereR sa�es aRea (wueRe e; isriNG), accessorzies nRea (wueRe �isriNG),
OFFICE, RESTROOMS, JANITORS CLOSET, LOUNGE, UNDERSIDE OF MANICURE TABLES,
CORRIDOR AND RECEIVING AREA RECEPTAQES AND COVER PLATES SNALL BE WNITE
IN COLOR.
RECEPTACLES AND COVER PLATES ON UNDERSIDE OF PEDICURE BENCN SNALL BE
BLACK IN COLOR.
E RECESSED OUTLET BOXES SNALL BE STAMPED STEEL SUITABLE FOR TNE DEVICE
INSTALLED.
Q. SURFACE 170UNTED OUTLET BOXES SLIALL BE CAST IRON SUITABLE POR TNE DEVICE
MSTALLED.
R. DUPLEX RECEPTACLES SNALL BE A MINIMUM OF 20 AMPERE RATMG.
5_ COVERPLATES FOR SURPACE MOUNTED BOXES S4lALL BE STAMPED STEEL SUITABLE
FOR TNE PARTICULAR BOX AND DEVICE CONPIGURATION.
PERIMETER SALES AREA (WNERE EXISTING)� ACCESSORIES AREA (WNERE EXISTING)�
OFFICE, RESTROOMS, JANITORS CLOSET, LOUNGE, CORRIDOR AND RECEIVIN� AREA.
SURFACE MOUNTED BOXES AND COVER PLATES SNALL BE WNITE IN COLOR. SURFACE
MOUNTED BOXES AND COVER PLATES AT ALL COLUMNS SNALL BE BLACK IN COLOR.
T. WIRING DEVICES UNLE55 OTNERWISE PROPERLY AUTLIORIZED, SNALL BE SAME
MANUFACTURERS ONLY; NO ADDITIONAL MANUFACTURERS SNALL BE PERMITTED
UNLESS SPEQFICALLY AUTNORIZED BY TFIE TENANT.
U. LOW VOLTAGE CONTROL DEVI�ES 541ALL BE AS NOTED ON DRAWINGS OR AS REQUIREG.
V. BOND ALL STRUCTURAL STEEL TO EARTN, GROUND RODS OR PLATES, OR WATER
SYSTEM.
W. BOND ALL ROOF �10UNTED EQUIPf�ENT TO N.E.C. (20G8) ACCEPTABLE GROUNDS ONLY.
X_ ANY ACCE55 PANELS REQUIRED, NOT SPEQFlED OR SNOWN ON DRAWWGS AS FURNISNED
BY GENERAL CONTRACTOR 5F1ALL BE FURN154JED BY ELECTRICAL CONTRACTOR WITF1
DESIGN TO BE APPROVED BY ARCNITECT BffORE ELECTRICAL CONTRACTOR STARTS
MSTALLATION.
Y. FURN1541 AND INSTALL A COMPLETE GROUNDING SYSTEM IN COMPLIANCE WITN ALL
RE'�UIREMENTS OF TNE NATIONAL ELECTRICAL CODE.
Z. A SEPARATE EQUIPMENT GROUNDING CONDUCTOR, 171NIMUM SIZE PER NEC TABLE 250.122,
SNALL BE MSTALLED IN ALL FEEDERS, BRANCN CIRCUITS AND CONTROL CIRCUITS.
CONDUCTOR INSULATION SNALL BE GREEN.
AA. CONDUIT SYSTEM SNALL BE ELECTRICALLY CONTINUOUS. ALL ENQOSURES AND
NON-CURRENT CARRYING f1ETAL5 TO BE GROUNDED. ALL LOCK NUTS MUST CUT
TLIROUG4J ENAMELED OR PAINTED SURFACES ON ENCLOSURES. WIJERE ENCLOSURES AND
NON-CURRENT CARRYING METALS ARE ISOLATED FROM TNE CONDUIT SYSTEM, USE
BONDWG JUMPERS WITN APPROVED CLAMPS.
AB. ALL RECEPTAQES SFJALL BE BONDED TO A GROUND CONDUCTOR USING A#12 AWG
MINIMUM BONDING JUMPER BETWEEN RECEPTACLE TER171NAL AND GROUND CONDUCTCR.
METAL-TO-�1ETAL CONTACT BETWEEN TNE DEVICE YOKE AND TNE OUTLET BOX IS NOT
ACCEPTABLE FOR EITNER SURFACE MOUNTED BOXES OR FLUSFI TYPE BOXES.
AC. LIGNTING FIXTURES SNALL BE GROUNDED BY TNE USE OF A PIGTAIL FASTENED ON BARE
ME1AL TNAT IS PREE OF PAWT.
AD. REFER TO ALL PROJECT DRAWWGS AND FlT ALL WORK ACCORDINGLY. THE REL4TION OF
WIRING AND CONNECTIONS ARE NOT INTENDED TO BE SCALED POR EXACT LOCATIONS.
AE. ALL APPARATUS, MATERIALS AND EQUIPMENT 54lALL 6E NEW AND SNALL BEAR TNE
UNGERWRITERS LABORATORIES' SEAL.
AE TNE COMPLETE MSTALLATION S4lALL BE FREE FROM GROUNDS, SNORT QRCUITS AND
OPEN CIRCUITS.
AG. TNE SYSTEM OF DISTRIBUTION FOR POWER AND LIGNTING SNALL BE ARRANGED AS
INDICATED ON TNE DRAWINGS.
A4l. FURNI54! AND MSTALL ALL POWER WIRING TO MOTORS, NEATERS, AND MECNANICAL
EQUIP�1ENT AS INDICATED ON TNE DRAWINGS. WIRING WTO MOTOR OR EQUIP�1ENT
TERMINALS SNALL BE COMPLETE WITN CCNNECTIONS TNROUGN ASSOQATED MOTOR
STARTERS AND DISCONNECT SWITCNES.
AI. OUTLETS SNALL BE PROVIDED M TNE WIRING SYSTEf1 WNEREVER REQUIRED FOR
PULLING OF WIRES, MAKWG CONNECTIONS, MAKING TRANSITIONS FROM ONE WIRING
SYSTEM TO ANOT4IER, AND FOR MOUNTWG WIRING DEVICES OR LIGNTING FIXTURES.
A1 ALL EXPOSED NON-CURRENT CARRYING METALLIC PARTS OF ELECTRICAL EQUIPMENT�
DEVICES, FIXTURES AND TNE CONDUIT SYSTEMS SLIALL BE GROUNDED.
AK. CONDUCTORS SNALL BE 600 VOLT TNERMOPLASTIC INSULATED COPPER OF 987,
CONDUCTIVITY. ALL CCNDUCTORS SNALL BE INSTALLED IN CONDUIT. TNE NUMBER OF
CONDUCTORS INSTALLED IN ANY CONDUIT SFIALL NOT BE GREATER TFIAN TNE NU�1BER
FOR WNICN TNE CONDUIT IS APPROVED, WITN TNE NUM6ER OF CONDUCTORS BEING
SNOWN A MINIMUM AND ADDITIONAL CONDUCTORS 54lALL BE INSTALLED IP NEEDED� AND
TIJE CONDUIT SIZE INCREASED IP REOUIRED. CONDUCTORS 5F1ALL BE A MINIMUM OF ul2
AND SNALL BE "T4lNN" TYPE BRANCN QRCUIT CONDUCTORS INSIDE LIG4ITMG FIXTURES
SLIALL BE A MINIMUM OF #12 AND 541ALL BE "T4141N" TYPE. ALUMINUM WIRING IS NOT
ACCEPTABLE.
AL. DEVIGES AND COVERPLATES 5F1ALL BE SPEQFICATION �RADE WITN A MINIMUM RATING
OF 20 AMPS_ COLOR OF DEVICES AND COVERPLATES - SEE SPEQPICATIONS 16000 ITEMS
0 AND 5. DEVICES AND COVERPLATES TO BE MANUPACTURED BY NUBBELL, LEVITON OR
EAGLE.
AM.ELECTRICAL CONTRACTOR 5F1ALL PROVIDE ELEGTRIG SERVIGE AND MAKE CONNEGTIONS
TO TF1E IJVAC EQUIPMENT, SIGNS AND GRILLE MOTORS (IF APPLICABLE) AS 54JOWN ON
TNE DRAWINGS.
AN_ DEDICATED QRCUIT OUTLETS AT CASH WR4P AREAS SNALL BE CLEARLY AND
C0�1PLETELY MARKED FOR UNMISTAKABLE IDENTIFlCATION BY TFIE TENANT'S EMPLOYEES.
A0. ALL TE�1PORARY WIRING SNALL BE REI'10VED WNEN WORK IS COMPLETED.
AP. ALL WIRING MUST BE IN CONDUIT. NO CONDUIT SNALL BE RUN TNROUGN NVAC DUCTS.
NO ROMEX, BX, ETC., IS PERMITTED. FLEXIBLE CONDUIT SNALL BE USED ONLY FOR
suoRr FiNa� coNNecrioNs (5'_0" oR �ess) To uGUTiNG FixTURes aN� eQuiPneNr.
FLEXIBLE CONDUIT SNALL NOT BE RUN IN DEMISING WALL.
AQ. QRCUIT BRFAKERS 54lALL BE QUICK MAKE, QUICK BREAK, T4IERMAL MAGNETIC TRIP
(ENCLOSURE COMPENSATED), MOLDED CASE TYPE, UL LISTED.15 AND 20 AMP SINGLE
POLE BREAKERS SFIALL CARRY TNE UL "SWD" MARKING. LINE SIDE TERMINALS SNALL
6E BOLTED TO MAIN 6USBARS. BREAKER RATWGS SNALL BE PER DRAWINGS. QRCUIT
BREAKERS USED TO PROTECT 41VAC LOADS SNALL BE NACR R4TED.
AR. EXPOSED CONDUIT SFIALL BE INSTALLED IN STRAIG4IT LMES, PARALLEL OR IN RIGNT
ANGLES TO TFJE BUILDING STRUCTURE DO NOT LOOF EXCE55 FLEXIBLE CONDUIT IN
CEILING SPACE OR WALL CAVITY-
A5. T410f'IAS ff BETTS °SUPER STRUT":
10' 12 GA. STEEL NALF SLOT CNANNEL WITN PRE-GALVANIZED FINISN.
T d B CATALOG tt1200NS 10_
Norros�A�E I E
Z W � N
� � o
O F N N
u' � -
�
W W � N
� a o 0
w
N
�
O �
W � mN
� � W W M
c
N
U
U
0
a ��
a
a
�
rn a
3
N
�
�
a
�
z -
�
� _
� O W H H J 0
w
V) OJJK �
� W � U V U .
r
Z �
U �
h
w
�
�
�
�
U
�
U
ar^
VI
�
�
W
1�-�
W
,,..G�A Mo-+,
y`Z'� �V�STFi�E��i
�
0
r
0
Y
U
x
U
z
¢
❑
m
3
�
0
o����� ��oy��,N�k���4 �
ENG JOB # 19-41-215 0
s
DRAWING NUMBER:
E6.1 �