HomeMy WebLinkAboutE106.2-ElectricalSpecifications16115 TELEPNONE CANDUIT SYSTEM A. CONDUIT FOR TELEPFIONE WALL OUTLETS SNALL BE A MINIMU�1 OF 3/4" UNLESS NOTED OTNERWISE. B. TELEPNONE OUTLET BOXES SNALL BE SINGLE GANG. PLATES SNALL BE FURNISNED AND INSTALLED BY TNE TENANT. C. PURNISN AND INSTALL A 3/4" TNICK TELEPNONE BACKBOARD AT LOCATION SNOWN ON TNE CRAWINGS. TFIE PLYWOOG BACKBOARC SNALL BE SECURELY ATTACNED TO TNE BUILDING WALLS TO SUPPORT RELAY PANELS, TERMINAL BLOCKS AND OTFIER NARDWARE WEIGWNG APPROXIMATELY 10 POUNDS PER SQUARE FOOT. PRIME AND PAINT T41E BACKBOARD SIDES AND EDGES WIT41 TWO COATS OF W411TE FIRE RETARDANT PAINT. FINISN PAWT TNE BACKBOARD TO MATCN TNE ADJACENT WALL. D. CONDUIT SYSTEM SNALL BE CONTINUOUS FROM OUTLETS TO TELEPNONE BACKBOARD. MSTALL PULL STRING M EMPTY CONCUITS IF REQUIRED BY CODE. E. INSTALL tt6 GROUND WIRE FRCM TELEPNONE BACKBOARD TO SERVICE ENTRANCE GROUND PER TELEPNCNE COMPANY'S REQUIREMENTS. F. TNE TELEPFIONE SYSTEM SNALL CONSIST OF CONDUITS, OUTLETS, DEVICE COVERPLATES, PLYWOOD BACKBOARD, TERMINAL CABINETS, ETC, POR TELEPLIONE WIRING. GROUND TELEPNONE SERVICE TO COLD WATER LINE AS REQUIRED BY LOCAL TELEPNONE C0�1PANY. 16300 SERVIGE AND DISTRIBUTION A T41E CONTRACTOR SNALL FURNISN ALL LP$OR, f1ATERIALS AND EQUIPf1ENT NECESSARY TO WSTALL THE ELECTRICAL SERVICE FROM TNE LANDLORD'S DISTRIBUTION CENTER INCLUDING CA6LE5, CONDUIT, PULL WIRE, AND GROUND ROD AND SLEEVE. TNE ELECTRICAL CONTRACTOR SNALL COORDINATE INSTALLATION OF TNE MAIN DISTRIBUTION PANELBOARD WITN TNIS WORK. B. METERWG EQUIPMENT 5F1ALL BE FURNISIJED BY ELECTRIC GOMPANY AND INSTALLED AS INDICA7ED IN RISER ON T41E DRAWINGS_ ..- FURNISN AND INSTALL SERVICE ENTRANCE QRCUIT BREAKER DISTRIBUTION PANELBOARD AS SNOWN ON TNE DRAWINGS AND SPEQFIED NEREIN. NOMINAL VOLTAGE AND CURRENT RATINGS ARE INDICATED ON TNE DRAWINGS. PANELBOARD SNALL FIAVE A MINIMUM MTEGRATED EG�UIPMENT SNORT CIRCUIT CURRENT RATING OF 65,000 AMPS RMS SYMMETRICAL EXACT RATING SFJALL BE DETERMMED BY AVAILABLE FAUL7 CURRENT BY UTILITY_ PANELBOARD TO BE SQUARE D I-LINE_ EQUAL PRODUCT BY SIEMENS, GENERAL ELECTRIC OR CUTLER NAMMER �1AY BE PURNISNED AT TNE CONTRACTOR'S OPTION. D. DISGONNEGT SWITGFIES SFIALL BE FIFAVY-0UTY TYPE, UL LISTED. E ALL SWITCNES SNALL NAVE SWITCN BLADES WNICN ARE FULLY VISIBLE IN TNE "OFF" POSITION WFIEN TFIE SWITCFI DOOR IS OPEN. SWITCFIES SFIALL FIAVE REMOVABLE ARC SUPPRESSORS WIJERE NECESSARY TO PERMIT EASY ACCE55 TO LME SIDE LUGS. LUGS SNALL BE FRON7 REMOVABLE AND UL LISTED FOR 75° C., ALUMINUM OR COPFER WIRES. E SWITCNES SNALL BE QUICK-MAKE, QUICK-6REAK. TNE OPERATING NANDLE SNALL BE AN INTEGRAL PART OF TNE BOX, NOT TNE COVER_ PROVISIONS FOR PADLOCKMG TNE SWITGFI IN TF1E 'bFF" POSITION WIT4J AT LEAST TIJREE LOCKS 541ALL BE PROVIDED- SWITCNES SNALL NAVE A DUAL COVER INTERLOCK TO PREVENT UNAUTIJORIZED OPENING OF TNE SWITCLI DOOR WIJEN TNE NANDLE IS IN TNE "ON" POSITION, AND TO PREVENT CLOSING OF TNE SWITCN MECNANISM WITN TNE DOOR OPEN. TNE NANDLE POSITION SNALL INDICATE WNETNER TNE SWITCLlIS "ON" OR uOFFu u. SWITCNES SNALL BE FURNISNED IN NEMA I GENERAL PURPOSE ENCLOSURE EXCEPT ALL SWITCNES LOCATED OUTDOORS SHALL BE NEMA 3R WEATHERPRCOF (WP)_ NEMA 3R ENCLOSURE SNALL BE MANUFACTURED FROM GALVANIZED STEEL. ENCLOSURES SNALL 41AVE A GRAY BAKED ENAMEL FINISN, ELECTRODEPOSITED, ON CLEANED, PNOSPNATIZED STEEL. N. SWITCNES SNALL BE RATED POR AC. FUSIBLE SWITCNES MUST ACCEPT CLA55 R FUSES AND NAVE PROVISIONS TO REJECT ALL FUSES EXCEPT CLA55 R. TNE UL LISTED SFIORT CIRCUIT RATING OF TFIE SWITCNES SFIALL BE 200,000 RMS SYMMETRICAL AMPERES W41EN CLA55 R PUSES ARE USED. I. IFS GEAR TO BE MANUFACTURED BY WESCO SYSTEMS. NO SU65TITUTIONS. REFER TO SNEET E52 FOR CONTACT INPORMATION_ J. NAMEPLATES SFIALL INDICATE FUNCTION GF EACFI DEVICE. NAMEPLATES SFIALL BE LAMINATED P4IENOLIC WITFI BLACK SURFACE AND WLIITE CORE. USE I/16" TIJICK MATERIAL FOR PLATES UP TO 2" X 4" FOR LARGER SIZES, USE I/8" TNICK MATERIAL. K. ALL FUSES S4lALL BE BUSSMANN� SIZES AS NOTED ON DRAWINGS. L ALL PUSES SNALL BE UL LISTED, CURRENT-LIMITING TYPE, MINIMUM 200,000 Af1P5 INTERRUPTWG CAPAGITY. M. FUSES I AMP AND A60VE SNALL BE BUSSMANN "LOW PEAK" RK-L 250 VOLT FUSES SNALL BE USED ON 208/120 VOLT SYSTE�15. 60G VOLT FUSES SNALL BE USED ON 480/277 VOLT SYSTE�15. N. CONTROL FUSES FOR �10TOR STARTERS, CONTACTORS, AND CONTROL PANEL TRANSFORMERS S4lALL BE BUSSMANN FNQ-R SIZED AT 500% RATED CURRENT. 0. PROVIDE 10% OF TOTAL PROJECT QUANTITY (BUT NOT LE55 TIJAN TNREE (3) FOR EACN TYPE AND RATING OF PUSES) TO TNE TENANT AS SPARE REPLACEMENT PUSES. P. TYPED LIST OF ALL SPARES SNALL BE PROVIDED TO TENANT. Q. PURNISN AND INSTALL CIRCUIT BREAKER TYPE POWER, NEATING ANC LIGNTING PANELBOARDS AS SNOWN ON TNE DRAWINGS. RELEA5E0 FOR CONSTRIICTI�N Su6jec��o compliance with allregula�ions of S�a�e antl Local Codes City of Carmel , �{�n„� i,.va�i_ DATE: 03�20�20 R. ALL PANELBOARDS SFIALL BE LISTED UNDER UL 67 AND SNALL FIAVE APPROPRIATE LABELING. 5. PANELBOARDS FOR USE IN ELECTRICAL DISTRIBUTION SYSTEM SNALL NAVE A MINIMUM MTEGRATED EQUIPf1ENT SNORT CIRCUIT CURRENT RATING OF 65,000 Af1P5 RMS SYMMETRIGAL EXAGT RATING 541ALL BE DETERMWED BY AVAIIABLE FAULT CURRENT FROf'I UTILITY_ ELECTRICAL CONTRACTOR S41ALL FURNIS41 PANELS BASED ON UTILITY COMPANY INFORMATION. T. FRONT ASSEMBLY SNALL INCLUDE A IJINGED DOOR WITLI A FLUSIJ MOUNTED CYLINDER LOCK TYPE SPRING LOADED LATCN. ALL LOCKS S4lALL BE KEYED ALIKE. DOOR SNALL INCLUDE A TYPED GRCUIT DIRECTORY CARD MCUNTED IN A FRAME WITN A QEAR PLASTIC PROTECTIVE COVER. U. EACN PANELBOARD SNALL NAVE A PULL CAPAQTY NEUTRAL SUBASSEMBLY. V- EACN PANELBOARD SNALL WCLUDE A GROUND BUS SUBASSEMBLY, SIMILAR IN CONSTRUCTION TO TNE NEUTRAL SUBASSE�1BLY, FACTORY �10UNTED AND BONDED TO T41E BOX. W. INTERIOR LABELING SNALL WCLUDE A CONNECTION DIAGRAM AND LABELS INDICATING PROPER TORQUE AND WIRE TYPES FOR MAIN INPUT CONNECTIONS AND BOTFI LME AND LOAD SIDE QRCUIT BREAKER GONNEGTIONS. X. GIRGUIT BREAKERS 541ALL BE QUIGK MAKE, QUICK BREAK, T4IERMAL MAGNETIG TRIP (ENCLOSURE COMPENSATED), MOLDED CASE TYPE, UL LISTED.15 AND 20 AMP SINGLE POLE BREAKERS SNALL CARRY TNE UL °SWD" MARKING. LME SIDE TERMINALS 54JALL BE BOLTED TO MAIN BUSBARS. 6REAKER RATINGS SFIALL BE PER DR,4WINGS_ Y- TERMINALS FOR CONNECTION OF TNE FEEDER TO TNE PANELBOARD MAINS OR MAIN 6REAKER SIJALL BE UL RECCGNIZED AS SUITABLE FOR TIJE TYPE OF CONDUCTORS SPEQRED. Z. NA�1EPLATES AS SCNEDULED ON DRAWINGS SNALL INDICATE FUNCTION OF EACN DEVICE. NAMEPLATES SNALL BE LAMINATED PNENOLIC WITN A BLACK SURFACE AND WWTE CORE. USE I/16° TNICK f�ATERIAL POR PLATES UP TO 2" X 4"_ FOR LARGER SIZES, USE I/8" T4JICK MATERIAL. AA. MANUPACTURER� SQUARE D TYPE NQOD FOR 208Y/120V APPLICATIONS, AND SQUARE D TYPE NF FOR 480Y/27N- EQUAL EQUIPMENT BY GENERAL ELECTRIC, CUTLER NAMMER, OR SIEMENS WILL BE ACCEFTED. AB. EACN PANELBOARD SNALL BE MSTALLED WITN TOP QRCUIT BREAKER AT 6'-0" ABGVE FLOOR, FLUSFI OR SURFACE MOUNTED. 16500 LIGrF�ITING A. INSTALL LIGNTING PIXTURES AS SNCWN ON TNE DRAWINGS. B_ ALL PIXTURES TO BE LISTED AND LABELED BY UNDERWRITERS LABORATORIES AND ALL BALLASTS TO BE CERTIFIED BY CB17 AND ETL. C. LAMPS SNALL BE MANUFACTURED BY PNILIPS. ALL LAMP TYPES SNALL BE BY TNE SAME MANUFACTURER. D. FIXTURES ARE TO BE PROVIDED COMPLETE WITN BALLASTS, SCCKET, LAMPS, END AND TRIP PLATES AND ALL �10UNTING ACCESSORIES REQUIRED FOR A COMPLETE FixTURe iNSTA��nTioN. E. USE ELECTRONIC BALLASTS AND T-8 LAMPS, UNLE55 NOTED OTNERWISE FURNISN SPECIAL LOW TEMPERATURE BALLASTS FOR EXTERIOR MOUNTED FIXTURES. F. BALLASTS SNALL BE BY ADVANCE. EQUAL PRODUCT BY GENER4L ELECTRIC OR UNNERSAL MAY BE PURNISNED AT TNE OWNER'S OPTION. G. UNLE55 OTNERWISE NOTED, ALL LENSES ON FLUORESCENT FIXTURES ARE TO BE ACRYLIC AND A MINIMUM OF OJ25 IN. TNICK. N. USE STEEL WIRE NANGERS FASTENEG TO TNE BUILDING STRUCTURE TO SUPPORT RECESSED FIXTURES AT EACFI CORNER (FOUR CGRNER SUSPENDED). FIXTURES TO FIT TIGNT AGAINST CONSTRUCTION TO ELIMINATE LIGNT LEAKS. I. WALL-MOUNTED FIXTURES SNALL BE MOUNTED PLUMB WITFJ BUILDING LINES AND MSTALLED WITN PROPER BOX AND COVER NARDWARE- 1 SURPACEMOUNTED FIXTURES SNALL COVER MOUNTING 41ARDWARE USE A CANOPY TIJAT IS NO LONGER TNAN TNE LENGTLI AND WIDTN OF TL1E FlXTURE AND AT A NEIGNT TNAT IS NO NIGNER TNAN REQUIRED TO MOUNT RXTURE ABSOWTELY VERTICAL CANOPY FINIS4! SNALL MATCH PIXTURE PINISN. K. STE�1-MOUNTED FIXTURES SNALL BE MOUNTED TO BE ABSOLUTELY VERTICAL AND NORIZONTAL.INSTALL AND SUPPORT AS SNOWN ON DRAWINGS. L FIXTURES SNALL BE AS SNOWN ON TNE DRAWINGS. ALL LIGNTING FIXTURES SNALL BE INSTALLED COf1PLETE WITFI NEW LAMPS� OF TFIE PROPER TYPE� WATTAGE� AND VOLTAGE RATING. BALLAST SNALL BE LIIGN PACTOR, CBM AND ETL LABELED, WITN INTERNAL FUSE LINK. 16722 FIRE ALARM SPEGIFIGATIONS A A MICROPROCESSOR CONTROLLED FIRE DETECTION SYSTEM SNALL BE MSTALLED IN ACCORDANCE WITN TNE SPEQFICATIONS AND DRAWWGS, AND AS REQUIRED BY TNE LOCAL AUTNORITY. B. GENERAL SYSTEM DESCRIPTION= TNE SUPERVISED, CODED, CLOSED-QRCUIT TYPE SYSTEM SNALL BE SO ARRANGED TNAT PULLING A MANUAL PULL STATION OR OPERATION OF ONE OP TNE AUT0�1ATIC DETECTING DEVICES WILL REGISTER AN ALARM AT TNE FIRE ALARM CONTROL PANEL TNIS WILL CAUSE IMMEDIATE AND CONTINUOUS OPERATION OF ALL TFIE BUILDING ALARM SIGNALS TO SOUND TNE GENERAL AIARM SIGNAL UNTIL T4JE ALARM IJAS BEEN ACKNOWLEDGED AT T4JE CONTROL PANEL C_ BASIC PERPORMANCE: L ALARM� TROUBLE AND SUPERVISORY SIGNALS FROM ALL REPORTING DEVICES SNALL BE ENCODED ONTO AN NFPA STYLE 4(CLA55 B) SIGNALING LME CIRCUIT. D E. F G N. 1 J. a L. �1. �I 0. P Q. 2_ INITIATION DEVICE CIRCUITS SNALL BE WIRED CLASS 8(NPPA STYLE B)- 3_ INDICA7WG APPLIANCE CIRCUITS 54lALL BE WIRED STYLE Y(CLA55 B)- SUBMIT COORDINATED SNOP DRAWINGS TO TNE ARCNITECT FOR APPROVAL. ALL REFERENCES TO MANUFACTURER'S MODEL NUMBERS AND OTNER PERTINENT WFORf1ATI0N NEREIN IS INTENDED TO ESTABLISFI MINIf1UM STANDARDS OF PERPORMANCE, PUNGTION AND QUALITY. TNE SYSTEM MUST NAVE PROPER LISTING ANC/OR APPROVAL FROM T41E FOLLOWING NATIONALLY RECOGNIZED AGENCIES: L UL, UNDERWRITERS LA$ORATORIES, WC_ Z NFPA 70-2005, NA710NAL ELECTRICAL CODE (NEC)_ 3_ NFPA 72-2007, NATIONAL PIRE ALARM CODE- MODULAR LP$ELING�� T4lE FIRE ALARM CONTROL PANEL SNALL f1EET TNE MODULAR LISTWG REQUIREMENTS OF UNDERWRITERS LABORATORIES, INC. TO FACILITATE SYSTEM C4lANGES AND EXPANSIONS, AND TO ENSURE T4lA7 ALL SUBASSEMBLIES NAVE TNE PROPER LISTING, EACN SUBASSE�18LY OF TFIE FACP SFIALL CARRY TNE APPROPRIATE UL MODULAR LA6EL T4J15 WCLUDES ALL PRINTED QRCUIT BCARD ASSEMBLIES, POWER SUPPLIES, AND ENCLCSURE PARTS. ALL EQUIPMENT COMPCNENTS SNALL BE NEW, AND TNE MANUFACTURER'S CURRENT f10DEL T41E MATERIALS, APPLIANCES, EQUIPMENT AND DEVICES SNALL BE TESTED AND LISTED BY A NATIONALLY RECOGNIZED APPROVALS AGENCY POR USE AS PART OF A PROTECTED PREMISES PROTECTIVE SIGNALMG (FIRE ALARM) SYSTEM. TNE AUTNORIZED REPRESENTATNE OF TFIE MANUFACTURER SNALL BE RESPONSBLE FOR TIJE SATISFACTORY INSTALLATION OF TIJE COMPLETE SYSTEM. ALL EQUIPMENT AND COMPONENTS SNALL BE INSTALLED IN STRICT COMPLIANCE WITN MANUFACTURER'S RECOMMENDATIONS. CONSULT TNE MANUFACTURER'S INSTALLATION MANUALS FOR ALL WIRING DIAGRAMS, SC4IEMATICS, P4IYSICAL EQUIPMENT SIZES, ETC., BEFORE BEGINNING SYSTEM INSTALLATION. ALL EQUIPMENT SFJALL BE ATTACLIED TO WALLS AND CEILING/FLOOR ASSEMBLIES AND SNALL BE NELD FIRMLY IN PLACE. ALL WIRING SNALL BE INSTALLED M CONDUIT OR RACEWAY, IF REQUIRED BY CODE. CONDUIT PILL 541ALL NOT EXCEED 40 PERCENT OF INTERIOR CRO55-SECTIONAL AREA W4lERE TNREE OR MORE CABLES ARE CONTAINED WITNIN A SIN:,LE CONDUIT. CABLE MUST BE SEPARATED FROM ANY OPEN CONDUCTORS OF POWER OR CLA55 I CIRCUITS, AND SNALL NOT BE PLACED IN ANY CONDUIT, JUNCTION BOX, OR RACEWAY CONTAINING TFIESE CONDUCTORS EXCEPT AS ALLOWED BY LOCAL CODE. WIRING SNALL BE IN ACCORDANCE WITN LOCAL, STATE AND NATIONAL CODES (E.G., NEC ARTICLE 760) AND AS RECOMI7ENDED BY TNE MANUPACTURER OF TNE FIRE ALARM SYSTEM. NUMBER AND SIZE OF CONDUCTORS 54lALL BE AS REC0�1MENDED BY TNE FlRE ALARM SYSTE�1 �1ANUFACTURER, BUT NOT LESS TNAN #IS AWG (I.02 MM) FOR INITIATING DEVICE CIRCUITS AND SIGNALING LWE CIRCUITS, AND ul2 AWG (1.63 MM) FOR INDICATIN� APPLIANCE CIRCUITS. ALL WIRE AND CABLE 541ALL BE LISTED AND/OR APPROVED BY A RECOGNIZED TESTING AGENCY FOR USE WITN A PROTECTIVE SIGNALING SYSTEM_ TNE FIRE ALARf1 CONTRGL PANEL SNALL BE CONNECTED TO A SEPARATE DEDICATED BRANCN CIRCUIT, MAXIMUM 20 AMPERES. PIRE ALARM CONTROL PANEL FRIMARY POWER WIRING SNALL BE ttl2 AWG. TNE CONTROL PANEL CABWET SNALL BE GROUNDED SECURELY TO TFIE BUILDING GROUNDING SYSTEf�. PIRE ALARM CONTROL PANEL SNALL BE BOSCN RADIONICS 7024 OR FIRELITE MSq200 AND SNALL BE SURFACE MOUNTED W41ERE INDICATED ON PLAN. PROVIDE A REMOTE ANNUNQATOR PANEL FOR RECESS MOUNTMG AT TNE LOCATION SNOWN ON TIJE PLAN. I. UNLE55 PROIJIBITED BY TFIE LOCAL AFlJ, FIRE ALARM SNALL INGLUDE, IN LIEU OF (2) POTS NARDWIRED CONNECTIONS, A NFPA 72 AND UL APPROVED CELLULAR ALARM COMf1UNICATOR FOR 3G OR 4G CELLULAR SIGNAL WITN BATTERY BACK UP AND COMFATIBLE WIT41 T41E ALARM SYSTEM COMMUNICATION PROTOCOL AND ALARM FORMAT REQUIRED BY ALARM SYSTEM AND RECENING CENTRAL STATION. PRODUCT SNALL BE TELEGUARD TG-7F5 LTE-V, www.teleguardcom. STROBE LIGNTS: L SNALL OPERATE ON 24 VDC, NOMINAL Z SNALL MEET TNE REQUIREMENTS OP TNE ADA AS DERNED IN UL STANDARD Iq71, AND SNALL f1EET T41E POLLOWING CRITERIA= a. UNLE55 OTNERWISE SPEQFlED ON TNE DRAWINGS, TNE MTENSITY SNALL BE A MINIMUM OF 75 CANDELA. b. ALL STROBES IN ANY GIVEN AREA 54lALL BE SYNC4lRONIZED WIT41 OTNER STROBES W TNAT AREA. a TNE APPLIANCE SNALL BE PLACED 80 IN. ABOVE TNE NIGNEST FLOOR LEVEL WITFIIN TNE SPACE, OR 6ELOW TNE CBLING, W411CNEVER MEETS CODE. R- AUDIBLENISUAL COMBINATION DEVICE�� I_ SNALL f1EET TNE APPLICABLE REQUIREf1ENTS OF SECTION 16722-Q LISTED ABOVE FOR VISIBILITY. 2. AUDIBLE SIGNAL SNALL BE 15DB ABOVE AMBIENT SOUND LEVEL. 5. f1ANUAL STATIONS: I. ADDRESSABLE MANUAL STATIONS SNALL BE PROVIDED TO CONNECT TO TLIE FIRE ALARM CONTROL PANEL SIGNALING LINE CIRCUIT (SLC) LOOPS. 2. TIJE MANUAL STATIONS SLIALL USE A KEY OPERATED TEST-RESET LOCK, ANG SNALL BE DESIGNED 50 ?NAT AFTER ACTUAL EMERGENCY OPERA710N, 7NEY CANNOT BE RESTORED TO NORMAL USE EXCEPT BY TNE USE OF A KEY. 3. ALL OPERATED STATIONS SNALL NAVE A POSITIVE, VISUAL INDICATION OP OPERATION TNAT CANNOT BE RESET WITNOUT TNE USE OF A KEY. A_ MANUAL STA710N5 SNALL BE SUITABLE FOR SEMIPW54I MOUNTING AS S4lOWN ON TNE PLANS, AND 541ALL BE INSTALLED NOT LESS TFIAN 42 INCNES, AND NOT MORE TNAN 48 WCNES ABOVE TNE FINISFJEG FLOOR TO TNE CENTERLME OF TNE DEVICE. T. WTELLIGENT P410TOELECTRIC SMOKE DETECTOR: I_ TNE DETECTORS SNALL USE T41E P410TOELECTRIC (LIG41T-SCATTERMG) PRINCIPAL TO MEASURE SMOKE DENSITY AND SNALL, ON COMMAND PROM TLlE CONTROL PANEL, SEND DATA TO TNE PANEL REPRESENTING TNE ANALOG LEVEL OF Sf10KE DENSITY. EACFI DETECTOR SFIALL CONTAIN A REMOTE LED OUTPUT. A VISUAL INDICATION OF AN ALARM SNALL BE PROVIDED BY DUAL LATG-IING LIGNT EMITTING DIODES (LEDs), ON TNE DETECTOR, WNIG-I MAY BE SEEN FROM GROUND LEVEL OVER 360 DEGREES. TNESE LEDs SNALL PERIODICALLY FLASN TO INDICATE TIJAT TNE DETECTOR IS IN COMMUNICATION WIT41 T41E CON?ROL PANEL- 2. TNE DETECTORS SNALL BE CEILING-MOUNTED AND GETECTOR SNALL BE PROVIDED ON A TWIST-LOCK BASE. ALL FIELD WIRE CONNECTIONS SNALL BE MADE TO TNE BASE TNROUGN TNE USE OF CLAMFING PLATE AND SCREW. 3. IT SNALL BE POSSIBLE TO PERFORM A CALIBRATED SEN5171VITY AND PERFORf1ANCE TEST ON TFIE DETECTOR WITFIOUT TFIE NEED FOR TNE GENERATION OF SMCKE. TFIE TEST METFJOD SNALL TEST ALL CETECTOR QRCUITS. 4. TNE DETECTOR SNALL NOT GO INTO ALARM WNEN EXPOSED TO AIR VELOQTIES CF UP TO 1500 FEET PER MINUTE (FPM). 5_ TNE DETECTOR SCREEN AND COVER ASSEMBLY SNALL BE EASILY REMOVABLE FOR RELD CLEANING OP TNE DETECTOR CNAMBER. 6. TNE UNIT SNALL BE A FIRELITE SD355 SMOKE DETECTOR INSTALLED IN A FIRELITE 8350LP 6ASE OR E`�UAL COMPATIBLE WITN TNE BOSCN RADIONICS SYSTEM. U. INTELLIGENT DUCT SMOKE DETECTORS�. I. TNE S17CKE DETECTOR NOUSING SNALL ACCOMMODATE EITNER AN INTELLIGENT IONIZATION DETECTOR OR AN MTELLIGENT PNOTOELECTRIC DETECTOR, TNAT PROVIDES CONTINUOUS ANALOG MONITORING AND ALARM VERIFICATION FROM rNE PaNE� 2_ W41EN SUPPIQENT SMOKE IS SENSED, AN ALARf� SIGNAL IS INITIATED AT TNE FACP, AND APPROPRIATE ACTION TAKEN TO CNANGE OVER AIR FIANDLING SYSTEMS TO NELP PREVENT TNE RAPID DISTRIBUTION OF TOXIC SMOKE AND FIRE GASES TNROUGNOUT TNE AREAS SERVED BY T41E DUCT SYSTEM. 3. TNE UNIT SIJALL BE A FIRELITE SD355 SMOKE DETECTOR INSTALLED IN A FIRELIGNT D355PL INTELLIGENT NON-RELAY PNOTOELECTRIC LOW FLOW SMOKE DETECTOR NOUSING OR EQUAL C0�1PATIBLE WITN T41E BOSCN RADIONICS SYSTEM. V. INTELLIGENT TNERMAL DETECTORS I. TIJERMAL DETECTORS SNALL BE INTELLIGENT ADDRESSABLE DEVICES RATED AT 135 DEGREES FA4JRENFIEIT (58 DEGREES CELSIUS) AND 4JAVE A RATE-0E-RISE ELEMENT RATED AT I5 DEGREES F(9.4 DEGREES C) PER f11NUTE. IT SNALL CONNECT VIA TWO WIRES TO TNE FIRE ALARM CONTROL PANEL SIGNALING LME GIRGUIT. 2. TNE UNIT SNALL BE A FIRELITE N355R(A) TNERMAL DETECTOR INSTALLED IN A FIRELITE 8350LP BASE OR EQUAL COMFATIBLE WITN TNE BOSCN RADIONICS SYSTEM. W. AT TNE FINAL INSPECTION, A FACTORY TRAINED REPRESENTATIVE OF TNE �1ANUFACTURER OP TFIE MAJOR EQUIPf1ENT SNALL DE�10NSTRATE TNAT T41E SYSTE�1 FUNCTIONS PROPERLY W EVERY RESPECT. X. TNE CONTRACTOR AND/OR TNE SYSTEMS MANUPACTURER'S REPRESENTATIVES SNALL PROVIDE A TYPEWRITTEN "SEQUENCE OF OPERATION" TO TNE TENANT. Y_ BEFORE PINAL APPROVAL OP TNE FIRE ALARM SYSTEM IS REQUESTED, PROVIDE TNE OWNER/TENANT(DSW), IN WRITING, A STATE�1ENT T41AT ALL REQUIREMENTS OF T41E CITY BUILDING INSPECTION AND FIRE DEPARTMENTS LIAVE BEEN MET IN TIJE INSTALLATION OP TNE FIRE ALARM SYSTEM_ Z SUBMIT TO TNE TENANT, UPON COMPLETION OF TNE SYSTEM INSTALLATION� A CONTRACTOR'S FIRE ALAR�I SYSTEM CERTIPICATION AND DESCRIPTION FORM AS OUTLMED BY NFPA 72-2007, AND AN APPROVED INSPECTION FORM FOR T41E FIRE ALARM PORTION OF TNE SYSTEM. AA. TNIS FIRE ALARM SYSTEM SNALL INTERFACE WITN TNE LANCLORD'S FIRE ALARM SYSTEM AS REQUIRED. COORDINATE WIT41 L4NDLORD. No11os�A�E I E Z W � N � � o O F N N m � _ K W W � N � a o 0 iL N � O � W � mN � � W W M Vo c 3 �aa� � � � u w NwwZ ' �� W ��w o V) OJJK � � �UUU - � w (n � Z � C� � h w � z � U � U ar^ VI � � W a W ,,..G�A Mo-+, y`Z'� �V�STFi�E��i � 0 r 0 Y U x U z ¢ ❑ m 3 � 0 � ENG JOB # 19-41-215 0 s DRAWING NUMBER: E6.2 �