HomeMy WebLinkAboutM101-HVACDetailsandSchedulePACKAGED ROOFTOP UNIT SCHEDULE
KEY: CENT.-CENTRIFUGAL; PROP.-PROPELLER; P.C.-FORWARD CURVE;
B.I.-BACKWARD WCLWED; A.F.-AIR FOIL
AIRFLOW SUPPLY FAN EVAPORATOR COIL COMPRESSOR CONDENSER FAN HEATING ELEC. DATA
TAG MODEL TONS QUANTITY (CFM) ESP BHP RPM AMBIENT EAT (F°) LAT (C) TOT SENS NO/TYPE EER STEPS N0. HP TYPE EAT LAT MBH MBH pFUE LBS. �OLTS NOTES
SUPPLY REiURN O.A. ON H20) (P) DB�WB DB�WB MBH MBH CAPACITY INPUT OUTPUT PHASE
RTII-5 LGC18052B 15 6000 4400 1600 1.0 --- --- 95 824/70.8 56.9/56.5 180 129.6 2/SCROLL -- 2 2 - GAS 35 99 260 208 80 EXIST 4fi0 1
3
NOTES:
1. UNIT EXISTING TO REMAIN. REBALANCE TO CFM IN�ICATED ON PLANS
AIR DEVICE SCNEDULE
NOTES :
I. SYMBOL KEY - q. VOLUME DAMPER-
FIRST LETTER: 5-SUPPLY R-RETURN E-EXH pq�TOR7 FURNISHED. OPPOSED BLADE OR
T- TRANSFER BUTTERFLY WHERE AVAILABLE. ADJUSTABLE
SECAND LETTER: D-DIFFUSER R-REGISTER pROM FACE.
G-GRILLE
2. PROVIDE OPTIONAL DIRECTIONAL BLOW FEATURE 5. BORDER ST7LE-
FOR OTNER THAN 4-WAY. A� SURFACE MOUNTED
"B" LAY-IN� PROVIDE WITH PLASTER FRAME FOR
3. FINISN- DRYWALL GEILING MOUNTING.
"A" WHITE. "C' LAY-IN PRAME FOR T-BAR CEILING.
"B" WNITE - 6.C. TO FlELD PAWT TO MATCN 6. PROVIDE BOOT FOR DUCT MOUNTING.
CEILING, WALL OR DUCTWORK WITH
ENAMEL FINISH.
S7MBOL MANUFAGTURER/ NOM. SRE MOUNTING MATERIAL FINISH DPR. BORDER
(I)(2) �ATA�a' FACE NECK �EIL- pTUER STEE ALUM. (3) (4) (5) NOTES
NUMBER ING
SD-I T?MS 24"x24" 8"m/10"0 • • A • C -
TITUS DUCT
��� 5301F5 20'x6" 18"x4" • • B A MOUNiED/FURNISH
W17H AIR SCOOP
TITUS DUCT
��2 5301F5 26'x6" 24'x4" • • B A MOUNiED/FURNISH
W17H AIR SCOOP
RG-I TITUS 24"xl2" 22"x10" • • A L -
350RL
ACGORD VENTILATION
EG-I BROOKLYN BLACK 11.125"x5" 10'k4" • • A • A DUCT MOUNTED
AMFRBLBK410
ARCHITELTURAL SUPPLIED W1iH
EG-2 GRILLE 11.125"x5' 10"x4" • • A • A TABLE BY DSW
EG-3 TITUS pq^x24" 8'd • • A • L -
350RL
MECI-IANICAL RESPONSIBILITY SCI-IEDULE
DSW
ITEM � CONTRALTOR DSW NOTES
z
F } J r J
N � � � �
w � F � F REUSE
� N � N N/A EXISTING
RCOF TOP UNIT
I4" ROOF CURB
DIFFUSERS AND GRILLES
LOW PRESSURE DUCTWORK
TNERMOSTAT
DUCT HEATER(5)
GAS UNIT HEATER(5)
ELECTRIC UNIT HEATER(5)
RETURN AIR FAN
TOILET EXHAUST PAN(5)
RCOF PENETRATION FOR
AIR BALANCE REPORT
AS-BUILT DR4WING5
•
•
•
•
• •
•
. .
• •
•
•
•
•
•
•
• •
•
• •
•
•
FAN SCI-IEDULE
KE7�. CENT.-GENTRIFU6AL; PROP.-PROPELLER; F.C.-FORWARD CURVE;
B.I.-BACKWARD INCLINED; A.F.-AIR FOIL
ELEGTRIGAL DATA
MFG TOTAL VOLTS AREA
TAG MODEL LOGATION GFM S.P. RPM HP ERVED NOTES
(IN H2O)
PHASE
EF-I LOREN COOK ROOF II00 03 1218 .167 120 NAIL BAR I, 2, 3, 4
120 AL� MOUNTED �
NOTES:
I. PROVIDE WITN D15CONNECT SWITCN, BACKDRAFT DAMPER AND BIRDSCREEN.
2 CONTROL WITN LOCAL LIGNTING QRCUIT CANTROLS.
3. PROVIDE HINGED BASE KIT AND ROOF CURB.
4. MAINTAIN 10'-0' FROM FAN TO AN7 OUTSIDE AIR INTAKE.
2. Space Ventilation An
ZoneNamelSpaceName
Zone 1
01 Nail Bar
02 Work/Storage
03 Waxing
04 Sales
VENTILATION SCHEDULE
(PER IMC TABLE 403.3)
Area Maximum Supply A
t. (R') Occupants (CFP
1 1326.0 35.0 3146
1 140.0 2.0 537
1 176.0 2.0 326
1 2588.0 43.'I 1989
OuttloorAir OuttloorAir OuttloorAir
(CFM/person) (CFMIft') (CFM)
20.00 0.12 859.1
5.00 0.12 26.8
20.00 0.12 61.1
7.50 0.12 634.1
1581.1
MAGNETIC
CONNECTION TO EG-I
AT PEDICURF �`•""
- 4" ROUND FLEXIBLE
DULT LONNELTION
(10 FT.)
E%HAUST GRILLE
(EG-I)
i1ADA DUCTWORK EXTENSION
Nrs
REFER TO ARGHITEQURAL PL4N5 FOR MORE INFORMATION.
ALL DULT LINER
TRANSVERSE EDGES TO
BE CLJATED W/ADHESNE IN
ACGORDANGE W/ SMACNA
STANDARDS, (ttP.)�
PROVIDE INTERNAL LINER
OR E%TERNAL WRAP
INSULATION AS
SPECIFIED
FASTEN W/ MIN. (3) SHT.
MTL SCREWS, SEAL W/
DUQ TAPE AND MASTIC
N TS
DUQ
FLANGED AND GASKETED .bINT
OR DUCT CONNECTION AND
REINFORCEMENT IN ACCORDANCE
W/ SMAGNA 2" W.G. CLA55 SE4L
NINJ-GASKETED TRANSVERSE
JOINTS IN ACCORDANGE W/SMGNA
CLA55 "C (TYP.)
�RMAINNDUGT-� � AIR
�W
DAMPER HANDLE TO �
BE INSTALLED
MA%IMUM OF 5'_0"
ABOVE CEILING
THERMAL INSULATING
BLANKEi WHERE
REQUIRED �
SUPPLY AIR �
DIFFUSER
TAPE DOWN IXTERNAL
MSULATION
CANICAL OR BELLMOUTH
SPIN-IN FITTING, SEAL
AIRTIGHT W/MASTIC
MANUAL BALANGING DAMPER
ROUND RIGID DUGT
I" WRAPPED MSULATION
VOLUME DAMPER
LCCATION WHERE
DAMPER WOULD BE
INAGGESSIBLE AT
TAKE-OFF, PROVIDE W/
3" IXTENDED SHAFT�
HANDLE AND GOLLAR.
�STRAP CLAMP (NP.)
RWND FLE%IBLE DUGT
�GONNEGTION, SAME SIZE
AS DIFFUSER NEGK SIZE
(MAX. 5 FT.)
FIRE DAMPER WHERE
� REQUIRED
FINISFIED CEILING
TEE 8AR OR
MOUNTING FRAME
i�DIFFUSER MOUNTING DETAIL
N TS
FAN MOTOR �
ALUMINUM HOUSIN6
FAN �
BIRDSCREEN �
FAN CURB CAP�
DISGONNEGT SWITGH
BY UNIT MFR.
PIGTAIL CORD
EXTERNAL AWMINUM
WIRE POST BY UNIT
MFR.
IXHAUST FAN TO BE
HINGED MOUNTED.
MINIMUM 12" HIGH
RCOF CURB.
RCOF OPENING BY
CANTRAGTOR. VERIFY
ALL REQ'D DIMENSIONS
FOR ROOF OPENINGS
PRIOR TO ANY ROOF
CUTTING.
�
RCOF BLOCKING 6
INSULATION.
BACKDRAFT DAMPER
FLEXIBLE CANNECTION
IXHAUST DUGT. SEE
PLANS FOR SIZE AND
GONTINUATION.
Nrs
NOTE:
MAINTAIN A MINIMUM OF 10'_0° SEPARATION BETWEEN
ALL EXNAUST AND INTAKE LOCATIONS
FIELD VERIFY ALL CONDITIONS
DESIGN DRAWINGS ARE SCNEMATIC. THIS CONTR4CTOR SHALL VISIT THE SITE PRIOR TO BIDDING OR
AWARD OF CANTRACT TO INSPEQ E%ISTING FlELD CONDITIONS. THIS CONTRACT SHALL WCWDE ALL
LABOR AND MATERIALS NECESSARY FOR FlELD MODIFICATIONS DUE TO IXISTING CONDITIONS.
THE CANTRAQOR SHALL CONTACT THE ARCHITEQ, ENGMEER OR OWNER PRIOR TO BIDDING FOR
INTERPRETATIONS AND CLARIFICATIONS OF THE DESIGN AND MCLUDE IN HIS BID ALL COSTS TO MEET
THE DESIGN INTENT. CLARIFICATIONS MADE BY THE ARCHITECT, ENGINEER OR OWNER AFTER BIDDING
WILL BE FINAL AND SHALL BE IMPLEMENTED AT CONTR4CTOR5 COST.
BIDDING CONTRQCTORS SHALL HAVE A WORKING KNOWLEDGE OF LCCAL CODES AND ORDINANCES AND
SHALL MCLUDE IN THEIR BIDS THE COSTS FOR ALL WORK INSTALLED IN STRIQ ACCORDANCE WITH
GOVERNING CODES, THE PLANS AND SPEQFICATIONS NOT WITHSTANDING. THE CONTR4QOR SHALL
ALERT ARCHITEQ, ENGMEER OR OWNER OF ANY APPARENT DISCREPANQES BETWEEN GOVERNING CODES
AND DESIGN INTENT.
RELEA5E0 FOR CONSTRIICTI�N
A"OUIGK" REFERENCE. ALL ITEMS LISTED HERE ARE SPEGIFIED AND
Su6jec��ocompliancewithallregula�ions F THE GONTRAGTOR ENCAUNTERS ITEMS THAT ARE GONTRADIGTOR7
ofS�a�eantlLocalCodes ESPONSIBILITY TO INFORM TENANTS LONSTRUGTION MANAGER 50
City of Carmel FOR THE GONTR4GTOR.
r
�{�n„� i,.va��
DATE: 03�20�20
Z W � N
� � o
� F N N
> � w �
W W � N
� a o 0
W
N
�
O �
w p m
� � W W M
Vo c
3 ���� `c
w NwwZ u
�� W ��w o
V)OJJK �
� W (% U U (¢j .
r
Z �
� �
h
W
�
W
�A
�
AU
�
U
� �
;',y`2��G��S �Fr�O�O~i,
i
U
}
m
0
w
Y
U
U
3
m
z
�
0
_
�
ENG JOB # 19-41-215 s
DRAWING NUMBER:
H4.1 �
s
�