HomeMy WebLinkAboutDrainage Report 03-11-20 Firehouse Square Carmel, IN Drainage Report March 11, 2020 Woolpert Firehouse Square, Carmel, IN 2 March 11, 2020 Table of Contents Introduction .............................................................................................................. 3 Pre-Developed Analysis .......................................................................................... 3 Post-Developed Analysis ........................................................................................ 3 Storm Sewer ............................................................................................................. 4 Water Quality ........................................................................................................... 4 Conclusion ................................................................................................................. 4 Exhibits Exhibit 1 – Aerial Location Map Exhibit 2 – FEMA Firmette Exhibit 3 – Soils Map Exhibit 4 – Wetland Inventory Map Exhibit 5 – Storm Basin Map Appendices Appendix A – Storm Sewer Calculations Appendix B – Water Quality Calculations Woolpert Firehouse Square, Carmel, IN 3 March 11, 2020 Introduction This report outlines the storm water management system to serve the Firehouse Square development, located just north of the fire station on the Square in Carmel, Indiana. The development consists of a single condo building and several townhomes with an existing parking lot revision and associated infrastructure. Please see Exhibit 1 for the Aerial Location Map. Pre-Developed Analysis The approximate 2.60-acre site is located in Carmel, Indiana in Hamilton County. The proposed development site is located primarily on the north side of the existing fire station, which was previously a public parking lot. Currently an extension of Veterans Way is under construction along the east side of this lot. The project site also extends down the west side of the fire station, as well as along a portion of the existing parking lot on the east side of the proposed Veterans Way. In addition to the proposed Firehouse Square development, the existing parking lot to the east will be reconfigured as part of the overall project. The existing site overall is mostly pavement with some grass areas along the Monon Trail to the west. The proposed development is contained within a single watershed which ultimately drains to the southwest to Carmel Creek. As part of the Veterans Way project, the City of Carmel has recently installed new storm sewer infrastructure along the edges of the project site that consists of oversized storm sewer pipe to provide regional detention for the area. This system is replacing a previous underground detention system at the site that will be removed to allow for the Firehouse Square project to be developed. The new storm sewer will also provide detention for this project, so no additional stormwater detention is required according to the Carmel Engineering Department. The proposed site lies in Zone X according to FIRM map 18057C0209G from the FEMA database, eff. March 11, 2020. Please see the firm map attached in Exhibit 2. The U.S. Department of Agriculture, Soil Conservation Service identifies the watershed to contain two soil classifications. A copy of the Natural Resources Conservation Service (NRCS) can be seen in Exhibit 3. The National Wetland Inventory (NWI) indicates that there are no existing wetlands located at the project site. Please see the attached map in Exhibit 4. Post-Developed Analysis The proposed site consists of three different areas with different routes to the existing storm sewer infrastructure. The main area, shown on EX5-1, will collect stormwater into a new storm sewer system, including proposed rain gardens in the courtyard, and connect to the existing storm system. Woolpert Firehouse Square, Carmel, IN 4 March 11, 2020 The second drainage area is to the east of Veterans Way and currently consists of an existing parking lot, shown on EX5-2. Runoff from the reconfigured parking lot to the east will be captured with new storm sewer that also collect will stormwater from the townhomes along the east side of Veterans Way. This storm sewer will connect to the storm sewer within Veterans Way. The third drainage area is located along the west side of the fire station, shown on EX5-3. Runoff from this area currently sheet drains to an existing drainage ditch to the west, which is the JW Hawkins Legal Drain. The proposed drainage route directs runoff from the pavement to areas between the townhome buildings where it is captured by storm sewer inlets and outlet into the legal drain. The proposed site has been graded so that all runoff will be able to flow from basin to basin to get to the ultimate discharge point over land in the event of the existing storm sewer being blocked. The basins were designed to overtop in a 100-year rainfall event without impacting the buildings. Please see Exhibit 5 for flood routing arrows for each basin on site. Storm Sewer The proposed storm sewer network is designed to handle the proposed stormwater runoff from the parking lot expansion in accordance with the Carmel Stormwater Technical Standards Manual. The proposed 10-year hydraulic grade lines are contained within the pipes, and the 100- year hydraulic grade lines are contained within the castings. StormCAD was utilized to size the proposed storm sewer. Calculations are provided in Appendix A. Water Quality Per the “Carmel Stormwater Technical Standards Manual Chapter 700”, Best Management Practices (BMP’s) must be capable of removing 80% TSS from the stormwater in order to meet water quality standards. To meet this standard, rain gardens and flow through BMPs have been designed to appropriately treat the runoff routed through the storm system. Water quality calculations are provided in Appendix B. Conclusion The proposed storm sewer system and rain gardens have been designed to be in accordance with Carmel Stormwater Technical Standards Manual and the site has been designed to convey runoff through the site to the existing regional storm sewer system and the JW Hawkins legal drain. Therefore, no adverse impacts are anticipated as a result of the proposed development. Firehou se Sq uare Legend 400 ft N➤➤N © 2020 Google © 2020 Google © 2020 Google USGS The National Map: Orthoimagery. Data refreshed April, 2019. National Flood Hazard Layer FIRMette 0 500 1,000 1,500 2,000250Feet Ü86°8'2.31"W 39°58'15.95"N 86°7'24.85"W 39°57'48.38"N SEE FIS REPORT FOR DETAILED LEGEND AND INDEX MAP FOR FIRM PANEL LAYOUT SPECIAL FLOODHAZARD AR EAS Without Base Flood Elevation (BFE)Zone A, V, A99With BFE or Depth Zone AE, AO, AH, VE, AR Regulator y Floodway 0.2% Annual Chance Flood Hazard, Areasof 1% annual chance flood with averagedepth less than one foot or with drainageareas of less than one square mile Zone X Future Conditions 1% AnnualChance Flood Hazard Zone XArea with Reduced Flood Risk due toLevee. See Notes.Zone X Area with Flood Risk due to Levee Zone D NO SCREE N Area of Minimal Flood Hazard Zone X Area of Undetermined Flood Hazard Zone D Channel, Culver t, or Storm SewerLevee, Dike, or Floodwall Cross Sections with 1% Annual Chance17.5 Water Surface ElevationCoastal Transect Coastal Transect BaselineProfile BaselineHydrographic Feature Base Flood Elevation Line (BFE) Effective LOMRs Limit of StudyJurisdiction Boundar y Digital Data Available No Digital Data Available Unmapped This map complies with FEMA's standards for the use of digital flood maps if it is not void as described below. The basemap shown complies with FEMA's basemap accuracy standards The flood hazard information is derived directly from theauthoritative NFHL web ser vices provided by FEMA. This mapwas exported on 3/11/2020 at 11:36:52 AM and does notreflect changes or amendments subsequent to this date andtime. The NFHL and effective information may change orbecome superseded by new data over time. This map image is void if the one or more of the following mapelements do not appear: basemap imagery, flood zone labels,legend, scale bar, map creation date, community identifiers,FIRM panel number, and FIRM effective date. Map images forunmapped and unmodernized areas cannot be used forregulatory purposes. Legend OTHER AREAS OFFLOOD HAZARD OTHER AREAS GENERALSTRUCTURES OTHERFEATURES MAP PANELS 8 1:6,000 B 20.2 The pin displayed on the map is an approximate point selected by the user and does not represent an authoritative proper ty location. Soil Map—Hamilton County, Indiana (Firehouse Square) Natural Resources Conservation Service Web Soil Survey National Cooperative Soil Survey 3/11/2020 Page 1 of 344243504424380442441044244404424470442450044245304424560442459044246204424350442438044244104424440442447044245004424530442456044245904424620574320574350574380574410574440574470574500 574320 574350 574380 574410 574440 574470 574500 574530 39° 58' 6'' N 86° 7' 47'' W39° 58' 6'' N86° 7' 38'' W39° 57' 57'' N 86° 7' 47'' W39° 57' 57'' N 86° 7' 38'' WN Map projection: Web Mercator Corner coordinates: WGS84 Edge tics: UTM Zone 16N WGS84 0 50 100 200 300 Feet 0 20 40 80 120 Meters Map Scale: 1:1,400 if printed on A portrait (8.5" x 11") sheet. Soil Map may not be valid at this scale. MAP LEGEND MAP INFORMATION Area of Interest (AOI) Area of Interest (AOI) Soils Soil Map Unit Polygons Soil Map Unit Lines Soil Map Unit Points Special Point Features Blowout Borrow Pit Clay Spot Closed Depression Gravel Pit Gravelly Spot Landfill Lava Flow Marsh or swamp Mine or Quarry Miscellaneous Water Perennial Water Rock Outcrop Saline Spot Sandy Spot Severely Eroded Spot Sinkhole Slide or Slip Sodic Spot Spoil Area Stony Spot Very Stony Spot Wet Spot Other Special Line Features Water Features Streams and Canals Transportation Rails Interstate Highways US Routes Major Roads Local Roads Background Aerial Photography The soil surveys that comprise your AOI were mapped at 1:15,800. Warning: Soil Map may not be valid at this scale. Enlargement of maps beyond the scale of mapping can cause misunderstanding of the detail of mapping and accuracy of soil line placement. The maps do not show the small areas of contrasting soils that could have been shown at a more detailed scale. Please rely on the bar scale on each map sheet for map measurements. Source of Map: Natural Resources Conservation Service Web Soil Survey URL: Coordinate System: Web Mercator (EPSG:3857) Maps from the Web Soil Survey are based on the Web Mercator projection, which preserves direction and shape but distorts distance and area. A projection that preserves area, such as the Albers equal-area conic projection, should be used if more accurate calculations of distance or area are required. This product is generated from the USDA-NRCS certified data as of the version date(s) listed below. Soil Survey Area: Hamilton County, Indiana Survey Area Data: Version 20, Sep 16, 2019 Soil map units are labeled (as space allows) for map scales 1:50,000 or larger. Date(s) aerial images were photographed: Aug 1, 2018—Sep 30, 2018 The orthophoto or other base map on which the soil lines were compiled and digitized probably differs from the background imagery displayed on these maps. As a result, some minor shifting of map unit boundaries may be evident. Soil Map—Hamilton County, Indiana (Firehouse Square) Natural Resources Conservation Service Web Soil Survey National Cooperative Soil Survey 3/11/2020 Page 2 of 3 Map Unit Legend Map Unit Symbol Map Unit Name Acres in AOI Percent of AOI UbaA Urban land-Brookston complex, 0 to 2 percent slopes 5.4 94.7% UcfA Urban land-Crosby silt loam complex, fine-loamy subsoil, 0 to 2 percent slopes 0.3 4.8% UkbB2 Urban land-Miami silt loam complex, 2 to 6 percent slopes, eroded 0.0 0.4% Totals for Area of Interest 5.7 100.0% Soil Map—Hamilton County, Indiana Firehouse Square Natural Resources Conservation Service Web Soil Survey National Cooperative Soil Survey 3/11/2020 Page 3 of 3 Firehouse Square U.S. Fish and Wildlife Service, National Standards and Support Team,wetlands_team@fws.gov Wetlands Estuarine and Marine Deepwater Estuarine and Marine Wetland Freshwater Emergent Wetland Freshwater Forested/Shrub Wetland Freshwater Pond Lake Other Riverine March 11, 2020 0 0.045 0.090.0225 mi 0 0.075 0.150.0375 km 1:2,864 This page was produced by the NWI mapperNational Wetlands Inventory (NWI) This map is for general reference only. The US Fish and Wildlife Service is not responsible for the accuracy or currentness of the base data shown on this map. All wetlands related data should be used in accordance with the layer metadata found on the Wetlands Mapper web site. UP UPUP MONON GREEN BLVD.VETERANS WAY1.0 0.22 ACRES TC = 5 MIN. C = 0.82 1.1 0.23 ACRES TC = 5 MIN. C = 0.76 1.2 0.23 ACRES TC = 5 MIN. C = 0.82 1.3 0.14 ACRES TC = 5 MIN. C = 0.80 1.4 0.21 ACRES TC = 5 MIN. C = 0.81 2.1 0.05 ACRES TC = 5 MIN. C = 0.58 2.2 0.05 ACRES TC = 5 MIN. C = 0.58 D4 0.46 ACRES TC = 5 MIN. C = 0.71 CY (Court Yard) 0.10 ACRES TC = 5 MIN. C = 0.45 2.0 0.03 ACRES TC = 5 MIN. C = 0.63 2.3 0.03 ACRES TC = 5 MIN. C = 0.63 EX 6 0.16 ACRES TC = 5 MIN. C = 0.65 EX 7 0.22 ACRES TC = 5 MIN. C = 0.76 D3 0.07 ACRES TC = 5 MIN. C = 0.30 EX 3 0.09 ACRES TC = 5 MIN. C = 0.69 EX 4 0.22 ACRES TC = 5 MIN. C = 0.64 EX 2 0.07 ACRES TC = 5 MIN. C = 0.74 EX 1 0.14 ACRES TC = 5 MIN. C = 0.65 EX 5 0.11 ACRES TC = 5 MIN. C = 0.71 D1 0.22 ACRES TC = 5 MIN. C = 0.40 D2 0.10 ACRES TC = 5 MIN. C = 0.33 CKD.DR.DES.DATEPROJECT No:REVISIONDATENo.FIREHOUSE SQUARETOWNHOMESVETERANS WAY & MONON GREEN BOULEVARDCARMEL, INDIANA 46032333 North Alabama StreetSuite 200Indianapolis, IN 46204317.299.7500FAX: 317.291.5805APP R O V A L PEN DI N G - NOT F O R CON S T R U C TI O N R Know what'sbelow.Callbefore you dig. R R EX5-1 DRAINAGE BASIN MAPFOR CONTINUATION SEE SHEET C402 FOR CONTINUATION SEE SHEET C401 MONON GREEN BLVD.RANGELINE ROADVETERANS WAYEX 6 0.16 ACRES TC = 5 MIN. C = 0.65 EX 7 0.22 ACRES TC = 5 MIN. C = 0.76 4.0 0.15 ACRES TC = 5 MIN. C = 0.75 3.3 0.14 ACRES TC = 5 MIN. C = 0.79 3.6 0.21 ACRES TC = 5 MIN. C = 0.75 3.5 0.38 ACRES TC = 5 MIN. C = 0.76 3.4 0.29 ACRES TC = 5 MIN. C = 0.76 EX 8 0.14 ACRES TC = 5 MIN. C = 0.78 CKD.DR.DES.DATEPROJECT No:REVISIONDATENo.FIREHOUSE SQUARETOWNHOMESVETERANS WAY & MONON GREEN BOULEVARDCARMEL, INDIANA 46032333 North Alabama StreetSuite 200Indianapolis, IN 46204317.299.7500FAX: 317.291.5805APP R O V A L PEN DI N G - NOT F O R CON S T R U C TI O N R Know what'sbelow.Callbefore you dig. R R EX5-2 STORM BASIN MAPFOR CONTINUATION SEE SHEET C400 VETERANS WAYGRADLE DRIVE C = 0.30 5.1 0.17 ACRES TC = 5 MIN. C = 0.72 6.1 0.16 ACRES TC = 5 MIN. C = 0.76 D5 0.20 ACRES TC = 5 MIN. C = 0.68 CKD.DR.DES.DATEPROJECT No:REVISIONDATENo.FIREHOUSE SQUARETOWNHOMESVETERANS WAY & MONON GREEN BOULEVARDCARMEL, INDIANA 46032333 North Alabama StreetSuite 200Indianapolis, IN 46204317.299.7500FAX: 317.291.5805APP R O V A L PEN DI N G - NOT F O R CON S T R U C TI O N R Know what'sbelow.Callbefore you dig. R R EX5-3 STORM BASIN MAPFOR CONTINUATION SEE SHEET C400 FOR CONTINUATION SEE SHEET C401 Prepared by Jacob Cramer 3/11/2020Page 1Firehouse SquareSTR #: 1 STR #: 1.1 STR #: 1.2 STR #: 1.3Cover Type C Value Area (ac.) Cover Type C Value Area (ac.) Cover Type C Value Area (ac.) Cover Type C Value Area (ac.)grass 0.21 0.01 grass 0.21 0.01 grass 0.21 0.04 grass 0.21 0.01Pavement 0.820.03Pavement 0.820.04Pavement 0.820.05Pavement 0.820.04Concrete 0.850.04Concrete 0.850.05Concrete 0.850.04Concrete 0.850.01Roof 0.85 0.14 Roof 0.85 0.13 Roof 0.85 0.10 Roof 0.85 0.08Total Area = 0.22 Total Area = 0.23 Total Area = 0.23 Total Area = 0.14Weighted C Value = 0.82 Weighted C Value = 0.82 Weighted C Value = 0.73 Weighted C Value = 0.80STR #: 1.4 STR #: 2 STR #: 2.1 STR #: 2.2Cover Type C Value Area (ac.) Cover Type C Value Area (ac.) Cover Type C Value Area (ac.) Cover Type C Value Area (ac.)grass 0.21 0.01 grass 0.21 0.01 grass 0.21 0.02 grass 0.21 0.02Pavement 0.820.04Pavement 0.820.01Pavement 0.820.02Pavement 0.820.02Concrete 0.850.02Concrete 0.85 Concrete 0.85 Concrete 0.85Roof 0.85 0.14 Roof 0.85 0.01 Roof 0.85 0.01 Roof 0.85 0.01Total Area = 0.21 Total Area = 0.03 Total Area = 0.05 Total Area = 0.05Weighted C Value = 0.81 Weighted C Value = 0.63 Weighted C Value = 0.58 Weighted C Value = 0.58STR #: 2.3 STR #: CY STR #: 3.3 STR #: 3.4Cover Type C Value Area (ac.) Cover Type C Value Area (ac.) Cover Type C Value Area (ac.) Cover Type C Value Area (ac.)grass 0.21 0.01 grass 0.21 0.06 grass 0.21 0.01 grass 0.21 0.03Pavement 0.820.01Pavement 0.820.04Pavement 0.820.06Pavement 0.820.25Concrete 0.85 Concrete 0.850.00Concrete 0.850.01Concrete 0.850.01Roof 0.85 0.01 Roof 0.85 Roof 0.85 0.06 Roof 0.85Total Area = 0.03 Total Area = 0.1 Total Area = 0.14 Total Area = 0.29Weighted C Value = 0.63 Weighted C Value = 0.45 Weighted C Value = 0.79 Weighted C Value = 0.76STR #: 3.5 STR #: 3.6 STR #: 4 STR #: 5.1Cover Type C Value Area (ac.) Cover Type C Value Area (ac.) Cover Type C Value Area (ac.) Cover Type C Value Area (ac.)grass 0.21 0.04 grass 0.21 0.03 grass 0.21 0.02 grass 0.21 0.03Pavement 0.820.25Pavement 0.820.09Pavement 0.820.06Pavement 0.820.07Concrete 0.850.09Concrete 0.850.01Concrete 0.850.01Concrete 0.850.02Roof 0.85 0.00 Roof 0.85 0.08 Roof 0.85 0.06 Roof 0.85 0.05Total Area = 0.38 Total Area = 0.21 Total Area = 0.15 Total Area = 0.17Weighted C Value = 0.76 Weighted C Value = 0.75 Weighted C Value = 0.75 Weighted C Value = 0.72 Prepared by Jacob Cramer 3/11/2020Page 2STR #: 6.1 STR #: D1 STR #: D2 STR #: D3Cover Type C Value Area (ac.) Cover Type C Value Area (ac.) Cover Type C Value Area (ac.) Cover Type C Value Area (ac.)grass 0.21 0.02 grass 0.21 0.15 grass 0.21 0.08 grass 0.21 0.06Pavement 0.820.07Pavement 0.820.07Pavement 0.820.02Pavement 0.820.01Concrete 0.850.02Concrete 0.85 Concrete 0.85 Concrete 0.85Roof 0.85 0.05 Roof 0.85 Roof 0.85 Roof 0.85Total Area = 0.16 Total Area = 0.22 Total Area = 0.10 Total Area = 0.07Weighted C Value = 0.76 Weighted C Value = 0.40 Weighted C Value = 0.33 Weighted C Value = 0.30STR #: D4 STR #: D5 STR #: EX 1 STR #: EX 2Cover Type C Value Area (ac.) Cover Type C Value Area (ac.) Cover Type C Value Area (ac.) Cover Type C Value Area (ac.)grass 0.21 0.09 grass 0.21 0.05 grass 0.21 0.04 grass 0.21 0.01Pavement 0.820.19Pavement 0.820.10Pavement 0.820.08Pavement 0.820.05Concrete 0.850.09Concrete 0.850.02Concrete 0.850.02Concrete 0.850.01Roof 0.85 0.09 Roof 0.85 0.03 Roof 0.85 Roof 0.85Total Area = 0.46 Total Area = 0.2 Total Area = 0.14 Total Area = 0.07Weighted C Value = 0.71 Weighted C Value = 0.68 Weighted C Value = 0.65 Weighted C Value = 0.74STR #: EX 3 STR #: EX 4 STR #: EX 5 STR #: EX 6Cover Type C Value Area (ac.) Cover Type C Value Area (ac.) Cover Type C Value Area (ac.) Cover Type C Value Area (ac.)grass 0.21 0.02 grass 0.21 0.03 grass 0.21 0.02 grass 0.21 0.04Pavement 0.820.06Pavement 0.820.06Pavement 0.820.08Pavement 0.820.08Concrete 0.850.01Concrete 0.850.01Concrete 0.850.01Concrete 0.850.02Roof 0.85 Roof 0.85 Roof 0.85 Roof 0.85Total Area = 0.09 Total Area = 0.1 Total Area = 0.11 Total Area = 0.14Weighted C Value = 0.69 Weighted C Value = 0.64 Weighted C Value = 0.71 Weighted C Value = 0.65STR #: EX 7 STR #: EX 8 STR #: STR #:Cover Type C Value Area (ac.) Cover Type C Value Area (ac.) Cover Type C Value Area (ac.) Cover Type C Value Area (ac.)grass 0.21 0.04 grass 0.21 0.01 grass 0.21 0.00 grass 0.21 0.00Pavement 0.820.13Pavement 0.820.13Pavement 0.820.00Pavement 0.820.00Concrete 0.850.02Concrete 0.850.00Concrete 0.850.00Concrete 0.850.00Roof 0.85 Roof 0.85 Roof 0.85 Roof 0.85Total Area = 0.19 Total Area = 0.14 Total Area = 0 Total Area = 0Weighted C Value = 0.69 Weighted C Value = 0.78 Weighted C Value = #DIV/0! Weighted C Value = #DIV/0! Scenario: Base CO-34CO-35CO-37CO-44CO-45CO-47CO-48CO-49CO-50CO-51Page 1 of 127 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA +1-203-755-1666 3/11/2020 Bentley CivilStorm V8i (SELECTseries 3) [08.11.03.77] Bentley Systems, Inc. Haestad Methods Solution CenterFirehouse.stsw FlexTable: Catch Basin TableCurrent Time: 0.000 hoursHydraulic Grade Line (In)(ft)Flow (Captured)(cfs)Inflow (Wet) CollectionElevation (Invert)(ft)Elevation (Rim)(ft)LabelID831.580.97<Collection: 0 items>831.09835.023.6136831.571.78<Collection: 0 items>830.82835.163.5139831.161.36<Collection: 0 items>830.28835.423.4141831.080.68<Collection: 0 items>830.07835.013.3143828.400.76<Collection: 0 items>828.00831.705.1151828.390.75<Collection: 0 items>828.00831.496.1154829.600.00<Collection: 0 items>829.60834.211.4157829.480.69<Collection: 0 items>829.10833.421.3158829.221.04<Collection: 0 items>828.65833.051.2160828.431.11<Collection: 0 items>827.61833.001.0162828.270.18<Collection: 0 items>828.10833.002.2166828.080.18<Collection: 0 items>827.80833.002.1167827.890.39<Collection: 0 items>827.50833.002.0169828.140.12<Collection: 0 items>828.00833.002.3173831.110.69<Collection: 0 items>830.55835.054.0175828.791.16<Collection: 0 items>828.11833.001.1177Page 1 of 127 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA +1-203-755-16663/11/2020Bentley CivilStorm V8i (SELECTseries 3)[08.11.03.77]Bentley Systems, Inc. Haestad Methods Solution CenterFirehouse.stsw FlexTable: Catchment TableCurrent Time: 0.000 hoursFlow (Total Out)(cfs)Runoff MethodArea (User Defined)(acres)Time of Concentration(hours)Rational COutflow ElementLabelID0.97Rational Method0.2100.0830.7503.63.61801.78Rational Method0.3800.0830.7603.53.51811.36Rational Method0.2900.0830.7603.43.41820.69Rational Method0.1500.0830.7504.04.01840.68Rational Method0.1400.0830.7903.33.31850.18Rational Method0.0500.0830.5802.22.31860.12Rational Method0.0300.0830.6302.02.01870.12Rational Method0.0300.0830.6302.32.31880.18Rational Method0.0500.0830.5802.12.11890.00Rational Method0.2100.0830.0001.41.41900.69Rational Method0.1400.0830.8001.31.31911.04Rational Method0.2300.0830.7301.21.21921.16Rational Method0.2300.0830.8201.11.11931.11Rational Method0.2200.0830.8201.01.01940.76Rational Method0.1700.0830.7205.15.11950.75Rational Method0.1600.0830.7606.16.11960.28Rational Method0.1000.0830.4502.0CY197Page 1 of 127 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA +1-203-755-16663/11/2020Bentley CivilStorm V8i (SELECTseries 3)[08.11.03.77]Bentley Systems, Inc. Haestad Methods Solution CenterFirehouse.stsw FlexTable: Conduit TableCurrent Time: 0.000 hoursNumber of BarrelsHydraulic Grade Line (Out)(ft)Hydraulic Grade Line (In)(ft)Flow / Capacity (Design)(%)Capacity (Full Flow)(cfs)Flow(cfs)Length (Unified)(ft)Velocity(ft/s)Manning's nDiameter(in)Slope (Calculated)(ft/ft)Invert (Stop)(ft)Stop NodeInvert (Start)(ft)Start NodeLabelID1831.57831.5838.62.510.974.03.000.01312.00.005831.073.5831.093.6CO-331401831.20831.5767.54.082.7572.83.570.01315.00.004830.533.4830.823.5CO-341421831.08831.1661.36.644.0727.53.950.01318.00.004830.173.3830.283.4CO-351441830.67831.0880.16.735.3975.54.230.01318.00.004829.763.1830.073.3CO-361461830.44830.6781.36.575.3448.64.140.01318.00.004829.473.0829.663.1CO-371481830.23830.44129.54.105.3119.73.010.01318.00.002829.34O-7829.373.0CO-381501828.30828.4033.42.260.7614.92.590.01312.00.004827.945.0828.005.1CO-391531828.30828.3932.32.320.7514.12.630.01312.00.004827.946.0828.006.1CO-401561829.48829.600.02.240.00100.90.000.01312.00.004829.201.3829.601.4CO-411591829.25829.4830.52.270.6949.52.530.01312.00.004828.901.2829.101.3CO-421611828.27828.4359.06.563.8623.13.860.01318.00.004827.52O-10827.611.0CO-441651828.08828.276.62.710.1834.61.950.01312.00.006827.902.1828.102.2CO-451681827.89828.0817.52.030.3561.81.940.01312.00.003827.602.0827.802.1CO-461701827.30827.8920.24.200.8536.04.180.01312.00.014827.00O-11827.502.0CO-471721827.89828.143.13.790.1235.32.180.01312.00.011827.602.0828.002.3CO-481741831.08831.1130.72.260.6994.52.530.01312.00.004830.173.3830.554.0CO-491761828.88829.2242.24.051.7173.83.160.01315.00.004828.361.1828.651.2CO-501781828.43828.7942.56.652.8399.73.610.01318.00.004827.711.0828.111.1CO-51179Page 1 of 127 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA +1-203-755-16663/11/2020Bentley CivilStorm V8i (SELECTseries 3)[08.11.03.77]Bentley Systems, Inc. Haestad Methods Solution CenterFirehouse.stsw FlexTable: Manhole TableCurrent Time: 0.000 hoursFlow (Total Out)(cfs)Hydraulic Grade Line (In)(ft)Inflow (Wet) CollectionElevation (Invert)(ft)Elevation (Rim)(ft)Set Rim to Ground Elevation?Elevation (Ground)(ft)LabelID5.34830.67<Collection: 0 items>829.66835.31True835.313.11455.31830.44<Collection: 0 items>829.37835.30True835.303.0147Page 1 of 127 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA +1-203-755-16663/11/2020Bentley CivilStorm V8i (SELECTseries 3)[08.11.03.77]Bentley Systems, Inc. Haestad Methods Solution CenterFirehouse.stsw FlexTable: Outfall TableCurrent Time: 0.000 hoursFlow (Total Out)(cfs)Hydraulic Grade(ft)Elevation (Invert)(ft)Set Rim to Ground Elevation?Elevation (Ground)(ft)LabelID5.29830.23829.34True833.00O-71490.75828.30827.94True827.945.01520.75828.30827.94True827.946.01553.85828.27827.52True831.90O-101640.84827.30827.00True835.00O-11171Page 1 of 127 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA +1-203-755-16663/11/2020Bentley CivilStorm V8i (SELECTseries 3)[08.11.03.77]Bentley Systems, Inc. Haestad Methods Solution CenterFirehouse.stsw FlexTable: Catch Basin TableCurrent Time: 0.000 hoursHydraulic Grade Line (In)(ft)Flow (Captured)(cfs)Inflow (Wet) CollectionElevation (Invert)(ft)Elevation (Rim)(ft)LabelID831.851.45<Collection: 0 items>831.09835.023.6136831.852.65<Collection: 0 items>830.82835.163.5139831.552.03<Collection: 0 items>830.28835.423.4141831.481.02<Collection: 0 items>830.07835.013.3143828.491.13<Collection: 0 items>828.00831.705.1151828.491.12<Collection: 0 items>828.00831.496.1154829.600.00<Collection: 0 items>829.60834.211.4157829.571.03<Collection: 0 items>829.10833.421.3158829.371.54<Collection: 0 items>828.65833.051.2160828.651.66<Collection: 0 items>827.61833.001.0162828.310.27<Collection: 0 items>828.10833.002.2166828.150.27<Collection: 0 items>827.80833.002.1167827.980.59<Collection: 0 items>827.50833.002.0169828.170.17<Collection: 0 items>828.00833.002.3173831.561.03<Collection: 0 items>830.55835.054.0175828.981.73<Collection: 0 items>828.11833.001.1177Page 1 of 127 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA +1-203-755-16663/11/2020Bentley CivilStorm V8i (SELECTseries 3)[08.11.03.77]Bentley Systems, Inc. Haestad Methods Solution CenterFirehouse.stsw FlexTable: Catchment TableCurrent Time: 0.000 hoursFlow (Total Out)(cfs)Runoff MethodArea (User Defined)(acres)Time of Concentration(hours)Rational COutflow ElementLabelID1.45Rational Method0.2100.0830.7503.63.61802.65Rational Method0.3800.0830.7603.53.51812.03Rational Method0.2900.0830.7603.43.41821.03Rational Method0.1500.0830.7504.04.01841.02Rational Method0.1400.0830.7903.33.31850.27Rational Method0.0500.0830.5802.22.31860.17Rational Method0.0300.0830.6302.02.01870.17Rational Method0.0300.0830.6302.32.31880.27Rational Method0.0500.0830.5802.12.11890.00Rational Method0.2100.0830.0001.41.41901.03Rational Method0.1400.0830.8001.31.31911.54Rational Method0.2300.0830.7301.21.21921.73Rational Method0.2300.0830.8201.11.11931.66Rational Method0.2200.0830.8201.01.01941.13Rational Method0.1700.0830.7205.15.11951.12Rational Method0.1600.0830.7606.16.11960.41Rational Method0.1000.0830.4502.0CY197Page 1 of 127 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA +1-203-755-16663/11/2020Bentley CivilStorm V8i (SELECTseries 3)[08.11.03.77]Bentley Systems, Inc. Haestad Methods Solution CenterFirehouse.stsw FlexTable: Conduit TableCurrent Time: 0.000 hoursNumber of BarrelsHydraulic Grade Line (Out)(ft)Hydraulic Grade Line (In)(ft)Flow / Capacity (Design)(%)Capacity (Full Flow)(cfs)Flow(cfs)Length (Unified)(ft)Velocity(ft/s)Manning's nDiameter(in)Slope (Calculated)(ft/ft)Invert (Stop)(ft)Stop NodeInvert (Start)(ft)Start NodeLabelID1831.85831.8557.62.511.454.03.310.01312.00.005831.073.5831.093.6CO-331401831.55831.85100.64.084.1072.83.790.01315.00.004830.533.4830.823.5CO-341421831.48831.5591.46.646.0727.54.260.01318.00.004830.173.3830.283.4CO-351441831.02831.48117.36.737.9075.54.470.01318.00.004829.763.1830.073.3CO-361461830.70831.02119.16.577.8348.64.430.01318.00.004829.473.0829.663.1CO-371481830.43830.70189.74.107.7819.74.410.01318.00.002829.34O-7829.373.0CO-381501828.39828.4949.82.261.1314.92.870.01312.00.004827.945.0828.005.1CO-391531828.39828.4948.22.321.1214.12.930.01312.00.004827.946.0828.006.1CO-401561829.57829.600.02.240.00100.90.000.01312.00.004829.201.3829.601.4CO-411591829.37829.5745.52.271.0349.52.820.01312.00.004828.901.2829.101.3CO-421611828.45828.6588.26.565.7823.14.190.01318.00.004827.52O-10827.611.0CO-441651828.15828.319.82.710.2734.62.190.01312.00.006827.902.1828.102.2CO-451681827.98828.1526.12.030.5361.82.170.01312.00.003827.602.0827.802.1CO-461701827.38827.9830.24.201.2736.04.680.01312.00.014827.00O-11827.502.0CO-471721827.98828.174.63.790.1735.32.450.01312.00.011827.602.0828.002.3CO-481741831.48831.5645.82.261.0394.51.320.01312.00.004830.173.3830.554.0CO-491761829.00829.3763.04.052.5573.83.490.01315.00.004828.361.1828.651.2CO-501781828.65828.9863.56.654.2399.73.990.01318.00.004827.711.0828.111.1CO-51179Page 1 of 127 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA +1-203-755-16663/11/2020Bentley CivilStorm V8i (SELECTseries 3)[08.11.03.77]Bentley Systems, Inc. Haestad Methods Solution CenterFirehouse.stsw FlexTable: Manhole TableCurrent Time: 0.000 hoursFlow (Total Out)(cfs)Hydraulic Grade Line (In)(ft)Inflow (Wet) CollectionElevation (Invert)(ft)Elevation (Rim)(ft)Set Rim to Ground Elevation?Elevation (Ground)(ft)LabelID7.83831.02<Collection: 0 items>829.66835.31True835.313.11457.78830.70<Collection: 0 items>829.37835.30True835.303.0147Page 1 of 127 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA +1-203-755-16663/11/2020Bentley CivilStorm V8i (SELECTseries 3)[08.11.03.77]Bentley Systems, Inc. Haestad Methods Solution CenterFirehouse.stsw FlexTable: Outfall TableCurrent Time: 0.000 hoursFlow (Total Out)(cfs)Hydraulic Grade(ft)Elevation (Invert)(ft)Set Rim to Ground Elevation?Elevation (Ground)(ft)LabelID7.77830.43829.34True833.00O-71491.12828.39827.94True827.945.01521.12828.39827.94True827.946.01555.76828.45827.52True831.90O-101641.26827.38827.00True835.00O-11171Page 1 of 127 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA +1-203-755-16663/11/2020Bentley CivilStorm V8i (SELECTseries 3)[08.11.03.77]Bentley Systems, Inc. Haestad Methods Solution CenterFirehouse.stsw WQv=P*Rv*A/12Rv=0.05+0.009*IArea 2.0Area 2.1Area 2.2Area 2.3Area CYArea 61 Inch of RainfallP111111Runoff CoefficientRv0.02970.0270.0270.02970.0180Area in AcresA0.030.050.050.030.1Impervious Cover (percent)I6660606640Water Quality Volume in Acre-ftWQv7.43E-050.0001130.0001137.43E-050.00015Water Quality Volume in cubic-ft3.234334.90054.90053.234336.534WQV provided Cubic-ft96969696Part of 2.0 Table of Contents i Table of Contents ********************** MASTER SUMMARY ********************** Watershed....... Master Network Summary ............. 1.01 ********************** TC CALCULATIONS ********************* EAST WQ......... Tc Calcs ........................... 2.01 WEST WQ......... Tc Calcs ........................... 2.03 ********************** CN CALCULATIONS ********************* EAST WQ......... Runoff CN-Area ..................... 3.01 WEST WQ......... Runoff CN-Area ..................... 3.02 S/N: Bentley PondPack (10.00.027.00) 3:37 PM 3/11/2020 Bentley Systems, Inc. File.... G:\DE\Clients\Onyx+East\80219 Firehouse Square\4.0 Disciplines\Civil\Eng\Storm Design\Proposed WQ.ppw Name.... Watershed Type.... Master Network Summary Page 1.01 MASTER DESIGN STORM SUMMARY Network Storm Collection: City of Carmel Total Depth Rainfall Return Event in Type RNF ID ------------ ------ ---------------- ---------------- 2 1.0000 Synthetic Curve TypeII 24hr MASTER NETWORK SUMMARY SCS Unit Hydrograph Method (*Node=Outfall; +Node=Diversion;) (Trun= HYG Truncation: Blank=None; L=Left; R=Rt; LR=Left&Rt) Max Return HYG Vol Qpeak Qpeak Max WSEL Pond Storage Node ID Type Event ac-ft Trun hrs cfs ft ac-ft ----------------- ---- ------ ---------- -- --------- -------- -------- ------------ EAST WQ AREA 2 .087 11.9000 1.45 *OUT 1 JCT 2 .087 11.9000 1.45 *OUT 2 JCT 2 .087 11.9000 1.45 WEST WQ AREA 2 .087 11.9000 1.45 S/N: Bentley PondPack (10.00.027.00) 3:37 PM 3/11/2020 Bentley Systems, Inc. File.... G:\DE\Clients\Onyx+East\80219 Firehouse Square\4.0 Disciplines\Civil\Eng\Storm Design\Proposed WQ.ppw Name.... EAST WQ Type.... Tc Calcs Page 2.01 :::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::: TIME OF CONCENTRATION CALCULATOR :::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::: ------------------------------------------------------------------------ Segment #1: Tc: User Defined Segment #1 Time: .0830 hrs ------------------------------------------------------------------------ ========================= Total Tc: .0830 hrs Calculated Tc < Min.Tc: Use Minimum Tc... Use Tc = .0833 hrs ========================= S/N: Bentley PondPack (10.00.027.00) 3:37 PM 3/11/2020 Bentley Systems, Inc. File.... G:\DE\Clients\Onyx+East\80219 Firehouse Square\4.0 Disciplines\Civil\Eng\Storm Design\Proposed WQ.ppw Name.... EAST WQ Type.... Tc Calcs Page 2.02 ------------------------------------------------------------------------ Tc Equations used... ------------------------------------------------------------------------ ==== User Defined ====================================================== Tc = Value entered by user Where: Tc = Time of concentration S/N: Bentley PondPack (10.00.027.00) 3:37 PM 3/11/2020 Bentley Systems, Inc. File.... G:\DE\Clients\Onyx+East\80219 Firehouse Square\4.0 Disciplines\Civil\Eng\Storm Design\Proposed WQ.ppw Name.... WEST WQ Type.... Tc Calcs Page 2.03 :::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::: TIME OF CONCENTRATION CALCULATOR :::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::: ------------------------------------------------------------------------ Segment #1: Tc: User Defined Segment #1 Time: .0830 hrs ------------------------------------------------------------------------ ========================= Total Tc: .0830 hrs Calculated Tc < Min.Tc: Use Minimum Tc... Use Tc = .0833 hrs ========================= S/N: Bentley PondPack (10.00.027.00) 3:37 PM 3/11/2020 Bentley Systems, Inc. File.... G:\DE\Clients\Onyx+East\80219 Firehouse Square\4.0 Disciplines\Civil\Eng\Storm Design\Proposed WQ.ppw Name.... WEST WQ Type.... Tc Calcs Page 2.04 ------------------------------------------------------------------------ Tc Equations used... ------------------------------------------------------------------------ ==== User Defined ====================================================== Tc = Value entered by user Where: Tc = Time of concentration S/N: Bentley PondPack (10.00.027.00) 3:37 PM 3/11/2020 Bentley Systems, Inc. File.... G:\DE\Clients\Onyx+East\80219 Firehouse Square\4.0 Disciplines\Civil\Eng\Storm Design\Proposed WQ.ppw Name.... EAST WQ Type.... Runoff CN-Area Page 3.01 RUNOFF CURVE NUMBER DATA :::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::: -------------------------------------------------------------------------- Impervious Area Adjustment Adjusted Soil/Surface Description CN acres %C %UC CN -------------------------------- ---- --------- ----- ----- ------ Water Quality East 99 1.170 99.00 COMPOSITE AREA & WEIGHTED CN ---> 1.170 99.00 (99) ::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::: S/N: Bentley PondPack (10.00.027.00) 3:37 PM 3/11/2020 Bentley Systems, Inc. File.... G:\DE\Clients\Onyx+East\80219 Firehouse Square\4.0 Disciplines\Civil\Eng\Storm Design\Proposed WQ.ppw Name.... WEST WQ Type.... Runoff CN-Area Page 3.02 RUNOFF CURVE NUMBER DATA :::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::: -------------------------------------------------------------------------- Impervious Area Adjustment Adjusted Soil/Surface Description CN acres %C %UC CN -------------------------------- ---- --------- ----- ----- ------ Water Quality West 99 1.170 99.00 COMPOSITE AREA & WEIGHTED CN ---> 1.170 99.00 (99) ::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::: S/N: Bentley PondPack (10.00.027.00) 3:37 PM 3/11/2020 Bentley Systems, Inc. Index of Starting Page Numbers for ID Names Appendix A A-1 ----- E ----- EAST WQ... 2.01, 3.01 ----- W ----- Watershed... 1.01 WEST WQ... 2.03, 3.02 S/N: Bentley PondPack (10.00.027.00) 3:37 PM 3/11/2020 Bentley Systems, Inc. Project Information Project Name Firehouse Square Option #A Country UNITED_STATES State Indiana City Carmel Contact Information First Name Jacob Last Name Cramer Company Woolpert Phone #317-223-2234 Email jacob.cramer@woolpert.com Design Criteria Site Designation East Basin Sizing Method Treatment Flow Rate Screening Required?Yes Treatment Flow Rate 1.45 Peak Flow (cfs)5.29 Groundwater Depth (ft)10 - 15 Pipe Invert Depth (ft)0 - 5 Bedrock Depth (ft)>15 Multiple Inlets?No Grate Inlet Required?Yes Pipe Size (in)18.00 Required Particle Size Distribution? No 90° between two inlets? N/A Treatment Selection Treatment Unit CDS System Model CDS-5-C Target Removal 80%Particle Size Distribution (PSD) NJDEP Hydrodynamic Separation Product Calculator Firehouse Square East Basin CDS CDS-5-C CDS ESTIMATED NET ANNUAL SOLIDS LOAD REDUCTION BASED ON THE RATIONAL RAINFALL METHOD Rainfall Intensity¹ (in/hr) % Rainfall Volume¹ Cumulative Rainfall Volume Rainfall Volume Treated Total Flowrate (cfs) Treated Flowrate (cfs) Operating Rate (%) Removal Efficiency (%) Incremental Removal (%) Removal Efficiency Adjustment² = Predicted % Annual Rainfall Treated = Predicted Net Annual Load Removal Efficiency = 1 - 2 - Reduction due to use of 60-minute data for a site that has a time of concentration less than 30-minutes. Hydrodynamic Separation Product Calculator Firehouse Square East Basin CDS CDS-5-C 2. The contractor shall fill all voids associated with lifting provisions provided by the manufacturer. These voids shall be filled with non-shrinking grout providing a finished surface consistent with adjacent surfaces. The contractor shall trim all protruding lifting provisions flush with the adjacent concrete surface in a manner, which leaves no sharp points or edges. 3. The contractor shall removal all loose material and pooling water from the SWTD prior to the transfer of operational responsibility to the Owner. TABLE 1 Storm Water Treatment Device Hydraulic and Storage Capacities         CDS Model   Treatment Capacity (cfs)/(L/s) Minimum Sump Storage Capacity (yd3)/(m3) Minimum Oil Storage Capacity (gal)/(L) CDS2015-G 0.7 (19.8) 0.5 (0.4) 70 (265) CDS2015-4 0.7 (19.8) 0.5 (1.4) 70 (265) CDS2015 0.7(19.8) 1.3 (1.0) 92 (348) CDS2020 1.1 (31.2) 1.3 (1.0) 131 (496) CDS2025 1.6 (45.3) 1.3 (1.0) 143 (541) CDS3020 2.0 (56.6) 2.1 (1.6) 146 (552) CDS3030 3.0 (85.0) 2.1 (1.6) 205 (776) CDS3035 3.8 (106.2) 2.1 (1.6) 234 (885) CDS4030 4.5 (127.4) 5.6 (4.3) 407 (1540) CDS4040 6.0 (169.9) 5.6 (4.3) 492 (1862) CDS4045 7.5 (212.4) 5.6 (4.3) 534 (2012)       CDS2020-D 1.1 (31.2) 1.3 (1.0) 131 (495) CDS3020-D 2.0 (56.6) 2.1 (1.6) 146 (552) CDS3030-D 3.0 (85.0) 2.1 (1.6) 205 (776) CDS3035-D 3.8 (106.2) 2.1 (1.6) 234 (885) CDS4030-D 4.5 (127.4) 4.3 (3.3) 328 (1241) CDS4040-D 6.0 (169.9) 4.3 (3.3) 396 (1499) CDS4045-D 7.5 (212.4) 4.3 (3.3) 430 (1627) CDS5640-D 9.0 (254.9) 5.6 (4.3) 490 (1854) CDS5653-D 14.0 (396.5) 5.6 (4.3) 599 (2267) CDS5668-D 19.0 (538.1) 5.6 (4.3) 733 (2774) CDS5678-D 25.0 (708.0) 5.6 (4.3) 814 (3081)       CDS3030-DV 3.0 (85.0) 2.1 (1.6) 205 (776) CDS5042-DV 9.0 (254.9) 1.9 (1.5) 294 (1112) CDS5050-DV 11.0 (311.5) 1.9 (1.5) 367 (1389) CDS7070-DV 26.0 (736.3) 3.3 (2.5) 914 (3459) CDS10060-DV 30.0 (849.6) 5.0 (3.8) 792 (2997) CDS10080-DV 50.0 (1416.0) 5.0 (3.8) 1057 (4000) CDS100100-DV 64.0 (1812.5) 5.0 (3.8) 1320 (4996) END OF SECTION PLAN VIEW B-B N.T.S. CENTER OF CDS STRUCTURE, SCREEN AND SUMP OPENING PVC HYDRAULIC SHEAR PLATE 2'-7" [787](2'-0" [610])1'-9" [533](5'-3" [1600])ELEVATION A-A N.T.S. FIBERGLASS SEPARATION CYLINDER AND INLET SOLIDS STORAGE SUMP SEPARATION SCREEN INLET PIPE (MULTIPLE INLET PIPES MAY BE ACCOMMODATED) OUTLET PIPE (4'-0" [1219])FLOW OIL BAFFLE SKIRT A 60" [1524] I.D. MANHOLE STRUCTURE VARIES+/-135°MAX.+/-65° MAX. FLOW FIBERGLASS SEPARATION CYLINDER AND INLET TOP SLAB ACCESS (SEE FRAME AND COVER DETAIL) CONTRACTOR TO GROUT TO FINISHED GRADE GRADE RINGS/RISERS A BB PERMANENT POOL ELEV. FRAME AND COVER (DIAMETER VARIES) N.T.S. FOR M AINTENANCE C A L L 1 .8 0 0 .3 3 8.1122 www.ContechES.com T MClean w a t e r s t a r t s her e ® 800-338-1122 513-645-7000 513-645-7993 FAX 9025 Centre Pointe Dr., Suite 400, West Chester, OH 45069 CDS-5-C (CDS2520) ONLINE CDS STANDARD DETAIL I:\STORMWATER\COMMOPS\22 CDS\40 STANDARD DRAWINGS\NJDEP SIZING\CDS-C (ONLINE)\DWG\DWG WITHOUT FLOWS\CDS-5-C DTL.DWG 2/12/2018 10:31 AMwww.ContechES.com THIS PRODUCT MAY BE PROTECTED BY ONE OR MORE OF THE FOLLOWING U.S. PATENTS: 5,788,848; 6,641,720; 6,511,595; 6,581,783; RELATED FOREIGN PATENTS, OR OTHER PATENTS PENDING. STRUCTURE ID WATER QUALITY FLOW RATE (CFS OR L/s) PEAK FLOW RATE (CFS OR L/s) RETURN PERIOD OF PEAK FLOW (YRS) SCREEN APERTURE (2400 OR 4700) PIPE DATA:I.E.MATERIAL DIAMETER INLET PIPE 1 INLET PIPE 2 OUTLET PIPE SITE SPECIFIC DATA REQUIREMENTS WIDTH HEIGHTANTI-FLOTATION BALLAST NOTES/SPECIAL REQUIREMENTS: RIM ELEVATION * PER ENGINEER OF RECORD * * * * *** *** *** * ** CDS-5-C (CDS2520) DESIGN NOTES THE STANDARD CDS-5-C (CDS2520) CONFIGURATION IS SHOWN. GENERAL NOTES 1.CONTECH TO PROVIDE ALL MATERIALS UNLESS NOTED OTHERWISE. 2.DIMENSIONS MARKED WITH ( ) ARE REFERENCE DIMENSIONS. ACTUAL DIMENSIONS MAY VARY. 3.FOR FABRICATION DRAWINGS WITH DETAILED STRUCTURE DIMENSIONS AND WEIGHTS, PLEASE CONTACT YOUR CONTECH ENGINEERED SOLUTIONS LLC REPRESENTATIVE. www.ContechES.com 4.CDS WATER QUALITY STRUCTURE SHALL BE IN ACCORDANCE WITH ALL DESIGN DATA AND INFORMATION CONTAINED IN THIS DRAWING. 5.STRUCTURE SHALL MEET AASHTO HS20 LOAD RATING, ASSUMING GROUNDWATER ELEVATION AT, OR BELOW, THE OUTLET PIPE INVERT ELEVATION. ENGINEER OF RECORD TO CONFIRM ACTUAL GROUNDWATER ELEVATION. CASTINGS SHALL MEET HS20 (AASHTO M 306) AND BE CAST WITH THE CONTECH LOGO. 6.IF REQUIRED, PVC HYDRAULIC SHEAR PLATE IS PLACED ON SHELF AT BOTTOM OF SCREEN CYLINDER. REMOVE AND REPLACE AS NECESSARY DURING MAINTENANCE CLEANING. INSTALLATION NOTES A. ANY SUB-BASE, BACKFILL DEPTH, AND/OR ANTI-FLOTATION PROVISIONS ARE SITE-SPECIFIC DESIGN CONSIDERATIONS AND SHALL BE SPECIFIED BY ENGINEER OF RECORD. B. CONTRACTOR TO PROVIDE EQUIPMENT WITH SUFFICIENT LIFTING AND REACH CAPACITY TO LIFT AND SET THE CDS MANHOLE STRUCTURE (LIFTING CLUTCHES PROVIDED). C. CONTRACTOR TO ADD JOINT SEALANT BETWEEN ALL STRUCTURE SECTIONS, AND ASSEMBLE STRUCTURE. D. CONTRACTOR TO PROVIDE, INSTALL, AND GROUT PIPES. MATCH PIPE INVERTS WITH ELEVATIONS SHOWN. E. CONTRACTOR TO TAKE APPROPRIATE MEASURES TO ASSURE UNIT IS WATER TIGHT, HOLDING WATER TO FLOWLINE INVERT MINIMUM. IT IS SUGGESTED THAT ALL JOINTS BELOW PIPE INVERTS ARE GROUTED.