HomeMy WebLinkAboutP600REMARKSZURN NO.
100
200
400
500
600
300
P.D.I. CERTIFIED
P.D.I. CERTIFIED
P.D.I. CERTIFIED
P.D.I. CERTIFIED
P.D.I. CERTIFIED
P.D.I. CERTIFIED
WADE NO.
W-5
W-10
5005
5010
J.R. SMITH NO.
W-50
W-75
W-100
5030
5040
5050
5020 W-20
F.U. RATING
1 - 11
12 - 32
MARK
1"
WHA-A
WHA-B
I.P.S.
3/4"
61 - 113
114 - 154
155 - 330
1"
1"
WHA-D
WHA-E
1"WHA-F
WHA-C 1"33 - 60
Water Hammer Arrestor Schedule (WHA)
NOTE: Locate water hammer arrestor in an accessible location, above finished ceiling.
NOTE:
This contractor to provide for testing and
certification per state requirements.
Pipe discharge to
floor drain
Air gap drain funnel
From water
supply source
Line size
shut-off (typ)
To system
2NWODKPI(KZVWTG5EJGFWNG
Mark
No.
Description
HW CW W V
Pipe Connections (in)Model Numbers
WATER CLOSET - 1.28 GPF, Vitreous china, wall mtd., elongated
bowl, siphon jet. Battery operated, automatic, top spud, flush valve.
Open front seat less cover. Chrome plated brass supply. Carrier.
+ 18" A.F.F. to top of seat to suit ADA. Flush actuator to be on wide
side of stall. Map score: 800 grams or better.
WC-1H -1 3 2
CHURCH #295C
CARRIER: PC to select carrier on the basis of field
conditions at each location
KOHLER #K-4323-0
ZURN #ZEMS6152AV-HET-HW6
MOP SINK - Floor mounted, 24" X 24", cast polymer. Provide hose
with hanger, mop hook, p-trap, ss strainer, ss wall guards. Service
faucet with vacuum breaker. Seal at wall.
MS-1 34 34 3 2
FLORESTONE #MSR-2424
SPEAKMAN #SC-5814
FLORESTONE #MR-370, MR-372, MR-373, MR-375
MURDOCK #M-OBR4-GRD-FRA3
DRINKING FOUNTAIN - Tandum, two-level stainless steel round
bowls, recessed bottle filler, barrier free, push buttons, freeze
resistant valve system. Provide p-trap, supplies and stops. Mount
per ADA requirements at +3412" A.F.F. to bubbler.
DF-1H -12 112 114
FLOOR DRAIN - Ductile iron body, nickel bronze round flat strainer.
Deep seal p-trap with trap seal.FD-A ---2 SIOUX CHIEF #832
SURE SEAL #SS2009V
WILKINS #375XLREDUCED PRESSURE ZONE BACKFLOW PREVENTER - Make
and model as approved by the Ind. Dept. of Health.RPZ-A 2---
EXTERIOR CLEAN OUT - (Paved areas) Ductile iron body, round
scoriated nickel bronze reinforced cover, brass plug. (Unpaved
areas) PVC body, round scoriated nickel bronze cover, brass plug.
CO-A SIOUX CHIEF #851-N
SIOUX CHIEF #834-NRBH (PAVED AREAS)--SIZE
LINE -
BRADFORD WHITE #LE120L3-3WATER HEATER - Electric, shelf mounted, 19 gal. storage, 2.5 kW,
120V., 1Ø, energy saver. Overflow pan. Thermal expansion tank.
Set outlet temperature to 140°F.
WH-A --34 34 WATER-TITE #HP 2022
AMTROL #ST-5
34 34MV-A
MIXING VALVE - ASSE 1017. Thermostatically controlled,
temperature and pressure compensated. Provide with unions,
check stops, shut off valve & thermometer. Set outlet temperature
to 110°F.
--LAWLER #84008-61-15
Notes
Provide one (1) power converter to serve all
automatic plumbing valves.
Power to faucet to be from power converter supplied
with water closet flush valve.KOHLER #K2006-0
LAVATORY - Vitreous china, wall hung. Faucet: 1.5 GPM, single
hole, lever handle, flat plate strainer. Accessories: Cast brass trap
w/ co., loose key stops, chrome plated supplies, offset tailpiece,
protective pipe and valve coverings, floor mounted carrier with
concealed arm support. Mount @34" to rim, to suit ADA.
L-1H 12 12 112 114 ZURN #Z1231-EZ
TRUEBRO #103 E-Z
ZURN #Z6913-XL-CP4-MV
WOODFORD #B67
FREEZE PROOF HOSE BIB - Wall mounted, cast bronze valve,
chrome plated face plate, automatic draining, stainless steel stem,
integral backflow protection, locking box.
FPHB -34 --
HOSE BIBB - Chrome plated, brass valve, loose key, integral
vacuum breaker.HB-A OR --12 WOODFORD #24-12
12
Extend drain to
nearest code
approved
discharge point.
34"CW
Wall bracket, if not provided
by mfgr., shall be constructed
of angle iron suitable for
support of unit.
Thermometer
ASME T&P
relief valve
Mixing valve
(MV-B)
34"HW
Thermal expansion
tank similar and equal
to Amtrol #ST-5.
Support as necessary.
CW main
NOTE:
Details shown here are typical only and may not be complete. Contractor shall provide all
material and labor necessary for the configuration, piping and accessories required to
operate this system in the manner intended with complete safety.
Overflow pan
Vertical pipe drop out of bottom of
horizontal pipe
Vertical pipe rise out of top of horizontal
pipe
Freeze proof hose bibb (FPHB)
Floor drain (FD)
Shutoff valve in pipe
90° Elbow down (drop in pipe)
90° Elbow up (rise in pipe)
Clean out in floorCO
Sanitary below grade or slab (W)
Vent piping (V)
2NWODKPI5[ODQNUCPF#DDTGXKCVKQPU
Cold water piping (CW)
Hot water piping (HW)PROF
E
SS
IONA L E N G NIEERSA M U E L L.HU
R
TINDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ERGNIBMULP·LACITCELE·LACINAHCEM R2410 Executive Drive - Suite 100
Indianapolis, Indiana 46241
317.636.3941
YYY6'%Ä/'2EQO
THEENGINEERING
C O L L A B OR
A
T
I