AIR TERMINAL UNIT SCHEDULE
ELERRIC HFATING DATA
TAG INLEf SIZE QN) MAX CFM HFATIN6 ffM MIN CFM MAX APD (M WG) KW AMPS VOLTS PHASE MANUFAQURER MODEL REMARKS
TB-1-0O1 10 390 390 130 0.45 3.5 4.2 480 3 TRANE VCEF 2
TB-1-002 10 390 195 130 0.95 3 3.6 9H0 3 TRANE VCEF 2
TB-1-003 10 390 195 130 0.45 3 3.6 480 3 TRANE VCEF 1
TB-1-004 10 39� 195 130 0.95 3.5 92 9H0 3 TRANE VCEF 2
TB-1-010 6 560 305 185 0.45 3.5 42 480 3 TRANE VCEF 3,4
TB-1-011 8 ]W 385 230 0.95 9.5 5.9 9H0 3 TRANE VCEF 3,4
TB-1-012 B 495 275 165 0.45 3 3.6 980 3 TRANE VCEF 3,4
TB-t-013 6 560 305 l85 0.45 3.5 4.2 4H0 3 TRANE VCEF 3,4
REMARKS:
L EXIS7ING AIR TERMINAL UNIT TO REMAIN,
2. RELOCATED EXISRNG AIR TERMINAL UNIT.
3, FURNISH WITH FAQORY MOUNTED AND WIRED DISCONNECf.
4, HEATiNG STEPS TO BE 1.
FAN POWERED AIR TERMINAL UNIT SCHEDULE
HEATIN6 DATA iNLET STATIC ELEC�RICAL DATA
TAG LOCAIION INLEfSQE MA%CFM MMCFM EATDB IATDB NOOFSTEPS FANCFM PRESSURE KW MCA MOP VOLTS PHASE MANUFACTURER NqDEL REMARKS
FPB-1-0-11 990-HALL 8 H00 265 55 101.10 1 265 �JS" 6.5 11.8 15 9H0 3 TRANE VPEF 3,9,5
FPB-1-401 426-FXAM 8 600 180 55 1 3 ].5 15 980 3 TRANE VPEF 1
FPB-1-902 440-HALL 8 500 150 55 l 3 7.5 l5 480 3 TRANE VPEF 1
FPB-1-403 4�1- RECEPIION 8 500 150 55 1 3 ].5 15 980 3 TRANE VPEF 2
FPB-1-409 901- RECEpRON 8 500 150 55 1 3 7.5 15 480 3 TRANE VPEF 2
FP8-1-406 923-HALL 8 600 180 SS 1 3 ].5 15 980 3 TRANE VPEF 1
REMARKS:
1. EXISTING FAN POWERED AIR TERMINAL UNCf TO REMAIN.
2. RELOUTED EXISTIN6 FAN POWERED AIR TERMINAL UNIL
3. PRONDE SINGLE POINT CONNECTION W1TH 277 VOLT SINGLE PHASE FAN MOTOR.
4. INCUDE SHEEf MEfAL INNER LINER.
5. FURMSH WITH FAQORY MOUNTED AND WIRED DISCONNECT.
NOTES:
1. WHERE DIFFUSER/GRILLE IS INSTALLED M U+YiN CEILING, PROVIDE lAY IN CEILING BORDER N7TH A 24X290R 24X12 PHNELAS REQUIRED TO MATCH SRE SCHEDULED.
2. WHERE GRILLE OR OIFFUSER I$ INSrALLE0IN A HARD CEILING OR GYP. BOARO WALL PROVIOE ORYWALL BOROER.
3. ROUND DUQ RUNOUT SRES TO DIFFUSERS SHALL MATCH ROUND NECK SIZE, UN1E550THERN75E NOTED.
LINEAR SLOT DIFFUSER SCHEDULE
REMARKS:
L FURNISH WLfH N/0 1" SLOTS AND UNMSULATED PLENUM. PLENUM SHALL BE INSULATED M THE FIELD.
2.AD]USfABLE BL4DE5.
3. NDJUS� OUTSIDE SLOT THROW TO WASH WINDOW. ADJUST INSIDE SLOT THROW TOWARD ROOM.
NOTES:
1. 0.20" WC STATIC PRESSURE DROP MAXIMUM.
2. PROVIDE CENTER NOTCH FOR T-BAR GRIDINSTALLATION,LO6ITUDINAL AND TRANSVERSE NOTCH AS REQURIED FOR SPECIFICINSfALLATION.
201 N. Delaware Street, Suite B
Indianapolis, IN 46204
317.951.9192 T � 317.951.9194 F
www.arcdesign.us
This drawing and i�s conten�s are �he pmperty
of arc�ESIGN P C., antl shall no[ be
reproduced in whole or in part by any means,
mechanical orelectmnic, wi�hout express
wn��en permission of arcDESIGN.
-�.-
I OF-US tM;INEEIi Vt-. hr.
.
I..L
O
�
U
J
0
WC
G
Z
O
�
Z
W
�
Q
No.
1200650 ; •
Z
r�n
V
m
�
J
W
LL
Q
U
O�
ti
O
M
Z
Z
W N
W M
� O
H �
� �
Z 0 Z
Q � Q
�N LL1J 0
L.1_ r Z
w�-
� � W
z g
o �
N Q
� U
M
�
100% CONSTRUCTION
DOCUMENTS
0 REVISIONS:
DATE:
MARCH 12, 2020
arcDESIGN PROJECT NUMBER:
19164
DRAWN BV:
AKE
DRAW ING TITLE:
MECHANICAL
SCHEDULES
DRAWING NUMBER:
M701