HomeMy WebLinkAboutE0.1 Electrical SchedulesSYMBOL
LLU
�
W
Vll K
�
WIRING (OUTLET) DEVICE SYMBOL LEGEND
DESCRIPTION
DUPLE% RECEPTACLE - 125 VOLT, 20 AMPERE, 2 POLE, 3 WIRE, GROUNDWG ttPE MOUNTED
AT 18" AFF UNLE55 NOTED OTHERWISE
DOUBLE DUPLEX RECEPTACLE - 125 VOLT, 20 AMPERE, 2 POLE, 3 WIRE, GROUNDING ttPE
AIOUNTED AT 18" AFF UNLESS NOTED OTHERW6E
GFCI GROUND iYPE �UPLE% RECEPTACLE - 125 VOLT, 20 AMPERE, 2 POLE, 3 WIRE,
GROUNDING IYPE MOUNTED AT 18° AFF UNLE55 NOTED OTHERWISE
RECEPTACLE SYMBOL WITH AD�ITIONAL SUBSCRIPT DESIGNATES IYPE OR SPEQFlC
REQUIREMEN7S AS FOLLOWS:
"+48" RECEPTACLE MOUNTED AT HEIGHT INDICATED
JUNCiION BOX - SIZE PER N.E.C. ARTICLE 314 REOUIREMENTS
SYMBOL
�
LIGHTING CONTROLS SYMBOL LEGEND
oEscRiPrioN
LIGHT SWITCH. SINGLE POLE, 20 AA�PERE, 120/277 VOLT, 1HP.
�. LIGHi SWITCH. '%" INDICATES THE FOLLOWMG
"a" CONTROL OF INDICATED LUMINAIRES
'VD" WALLBOx PIR VAVANCY SENSOR WITH 0-10V DIMMING AND AIABIENT LIGHT
DETECTION SENSOR. LUTRON �MS-Z101-V-WH
'VS' WALLBOx DUAL TECHNOLOGY VACANCY SENSOR WIiH AMBIENT LIGHT DETECTION.
LUTRON MAESTRO �IAS-A102-V-WH
TELECOMMUNICATION OUTLET SYMBOL LEGEND
SYMBOL DESCRIPTION
V COMBINATION VOICE/DATA OUTLEf (4-11/16" x 2-1/8" DEEP JUNCTION BOX) COMPLEfE
WITH SINGLE GANG DRY WALL RMG (VERIFY DRYWALL THICKNESS) MOUNTED AT 18' AEF.
PROVIDE 3/4' CON�UIT WITH INSUUTING BUSHING AND PULLSTRING STUBBED UP 12" INTO
ACCESSIBLE CEILING SPACE.
LUMINAIRE SCHEDULE
IAMPS IAANUFACTURER
IYPE WATfAGE VOLTAGE OESCRIPTION AND CATALOG REMARKS
No. TYPE NUMBER
LED 2'x2' RECESSED LUMINAIRE WITH 4EEL HOUSING AND CENTER CLEAR ACRYLIC LITHONIA LIGHTING:
F2 B LED 35 UNV DIFFUSER. STANDARD 0-10V DIMMING DRIVER. �2VR2-40L-ADP-EZI-LP835
350�'K
SAME AS ttPE "F2B" E%CEPT WITH SELF CONTAINED EMERGENCY BATfERY PACK LITHONIA LIGHTING:
FZ B E - �E� 35 UNV {�2��-40L-ADP-EZI-LP835-EL14L
J500'K
LED RECESSED OPEN WALL WASH �OWNLIGHT WITH 4" SQUARE APERTURE, GOTHAM:
F4A _ LED p� UNV SELF-FLANGE� SEMI-SPECULAR, MATfE-DIFFUSE LOWER REFLECTOR, AND STANDAR� �EVO SOLW-35/10-4AR-L�-277
J500'K 0-1�V �IMMING �RIVER.
LED 30' ON�ER CABWEf WMINAIRE WITH EX�RU�ED AWMINUM HOOSING, SOLID MEfAL JUNO: NOTE 7
F6 _ LED �� �Zp FRONT, UV IMPACT RESISTANT ACRYLIC LENS, IMEGRATED OCCUPANCY SENSOR AN� �UPLED30-OC-WH
3000'K ROCKER SWITCH.
SAIAE AS NPE 'F' E%CEPT WITHOUT OCCUPANCY SENSOR OR ROCKER SWITCH. JUNO: NOiE 7
F6A - LED �� �Zp �UPLED30-NS-WH
300�'K
SAME AS ttPE 'F' EXCEPT WITHOUT OCCUPANCY SENSOR OR ROCKER SWITCH AND 22" JUNO: NOTE 7
F/�8 - �gp g �Zp W LENGTH. {�UPLE�22-NS-WH
�� J000'K
1. THE ELECTRICAL CONTRACTOR SHALL BE SOLELY RESPONSIBLE TO COORDINATE AND VERIFY WITH THE ARCHITECT AND ALL ARCHRECTURAL DRAWINGS SUCH AS FLOOR PLANS, CEILING PLANS, SCHE�ULES, ELEVATIONS, SECTIONS, DEfAILS,
EfG ALL CEILING ttPES CONFIGURATIONS AND SPECIFICATIONS LUMINAIRE COLORS AND FINISHES LENGTHS TRIMS MOUNTINGS MOUNTING SYSTEMS HARDWARE LUMINAIRE CONFIGURATIONS SttLES SHAPES HEIGHT OF SUSPENDED AND
� � �
WALL MOUNTED LUMINAIRES, EfC. PRIOR TO SHOP DRAWING SUBMITfALS, ANY ROUGH-INS, AND PLACING FINAL PURCHASE ORDERS. .
2. VERIFY FINAL LUMINAIRE LOCATIONS WITH OTHER CEILING MOUNTE� EQUIPMENT SUCH AS DIFFUSERS, FIRE AIARM �EVICES, SPEAKERS, EfG WITH ARCHITECTURAL RCP (REFLECTED CEILING PLANS).
3. VERIFY EXACT HEIGHT AND LOCATIONS OF ALL WALL MOUNTED AND PENDANT/CABLE MOUNTED LUMINAIRES WITH ARCHRECTURAL ELEVATIONS PRIOR TO ANY ROUGH-IN.
4. LUMINAIRES SHALL NOT BE SUPPORTED FROM SUSPENDED CEILING SUPPORTS UNLESS A�DITIONAL CEILING FRAMING AND SUPPORTS ARE ADDED BY THE CEILING CONTRACTOR ACCOR�ING TO MANUFACTURER'S RECOMMEN�ATIONS LLL.
LISTINGS, AND ANY APPLICABLE STATE OR LOCAL CODES.
5. CONNECTIONS TO RECESSED LUMINAIRES SHALL BE MADE WITH MINIMUM 1/2° FLEXIBLE MEfAL CONDUIT (FMC) FROM FI%TURE TO OUTLEf BO%. LENGTH OF FMC SHALL NOT EkCEED 6'.
6. AT THE CONCLUSION OF THE WORK, EACH LUMINAIRE MUST BE CLEANED PER MANUFACTURER'S INSTRUCTIONS, EQUIPPED WITH THE PROPER ttPE, NUMBER OF LAMPS, INCLUDING KELVIN TEMPERATURE AND WATfAGE, AND ALL IN GOOD
OPERATING CON�ITION.
7. ELECTRICAL CONTRACTOR TO CONFIRM SIZE TO PROVIDE FULL LENGTH OF UNDER CABINEf. FIRST FI%TURE SHALL BE ttPE 'F6' REST SHALL BE ttPE 'F6A', 'F6B' AND 'F6C
LIGHTING SYMBOL LEGEND
SYMBOL
F2B
�
a
�NL
F4A
U
F6A
��
DESCRIPTION
RECESSED MOUNTED 2'x2' LUMINNRE. °F2B" INDICATES NPE; "a" INDICAiES SWITCH CONTROL.
REFER i0 LUTAINAIRE SCHEDULE FOR ADDIiIONAL MFORMATION.
LUMINAIRE WITH SELF CONTAINED EMERGENCY LIGHTING BATTERY PACK.
"NL"- DENOTES LUAIINAIRE TO BE WIRED AS A NIGHT LIGHT.
RECESSED WALL WASH WIAINAIRE. "F4A" INDICATES WMINNRE 1VPE. REFER ID WMINAIRE
SCHEDULE FOR A��ITIONAL MFORMATION.
UN�ERCABINEf WMINAIRE. "F6A" IN�ICATES WMINAIRE iYPE. REFER ID WMINAIRE SCHEDULE
FOR ADOITIONAL INFORMATION.
CIRCUITING AND RACEWAY LEGEND
SYMBOL DESCRIPTION
_ HP2�� HOME RUN TO PANEL "HP2", CIRCUIT �7 VIA A 20A/1P CIRCUIT BREAKER WITH
2�12AWG, �12(G), 3/4"CONDUIT UNLESS NOTED OTHERWISE.
�3�8AWG, j�10(G), ��� HOME RUN TO PANEL "LPi", CIRCUITS w'S 8,10,12 VIA A 40A/3P CIRCUIT BREAKER
LP7�8,10,12 CONDUCTOR SIZE/QUANiItt AS INDICAiED.
40/3
POWER DISTRIBUTION EQUIPMENT SYMBOL LEGEND
SYMBOL DESCRIPTION
� 480Y/277 WLT, 30, 4 WIRE BRANCH CIRCUIT PANELBOAR�
� 2�BY/120 VOLT, 30, 4 WIRE BRANCH CIRCUIT PANELBOARD
FIRE ALARM SYMBOL LEGEND
� VISUAL (SiROBE) ONLY SIGNALING DEVICE
DEMOLITION ANNOTATION LEGEND
"g° DENOTES ExISTMG DEVICE/EQUIPMENT TO BE REIAWED IN ITS ENTIREIY INCLUDMG JUNCTION
BOXES, CONDUITS AND CIRWITRY, ETC. COMPLETE, BACK TO SOURCE OR NERT ACTNE DEVICE
BEMG MAINTAMED ON CIRCUIT.
"XR" DENOTES EXISTING DEVICE/EOUIPAIENT TO BE RELOCATED IN IT$ ENTIREIY. MAINTAIN ALL
BRANCH CIRWIT WIRING, CONDUIT, EiC. FOR RELOCATION TO NEW LOCATION ('%N") AS
INOICAiED ON "NEW WORK' DRAWINGS.
°%N" DENOTES NEW LOCATION OF EXISTMG RELOCATED ("NR') DEVICE/EQUIPMENT. REWORK ALL
BRANCH CIRCUIT WIRING, CONDUIT, ETC. i0 NEW LOCAiION A$ REQUIRED.
"%M" DENOTES EXISiING DEVICE/E�UIPA�ENT TO BE MAINTAMED.
TYPICAL DEVICE MOUNTING
FIRE AIARA� AUDIBLE/VISUAL AND
VISUAL ONLY SIGNALING DEVICES
RECEPTACLES BEHIND
0 REFRIGERAi0R5 AND
VENDING MACHMES
WALL TELEPHONES
FlRE AlAR1A MANUAL PULL STATION
LIGHTING CONTROLS CONFIRM MOUNTING HEIGHT
� (
� � WIiH LOCAL CODE RE�UIREMEMSJ
�
VOLUME CONTROLS
DEVICES ABOVE COUNTERiOP
�
AND/OR BACKSPLASH
� ? � � � RECEWACLES IN MECH/ELEC
� � � �
�
IAVATORIESO ADJACENT TO � � �
� �� RECEPTACLES BEHIND
� � �OIAESTIC WASHERS
AND DRYERS
�GENERAL PURPOSE � �
RECEPTACLES
M � � �'� R�ECE TACLES SERVING �
DISHWASHER AND
_ GARBAGE �ISPOSAL
NOTES:
1. ALL MOUNTING HEIGHiS SHALL BE MEASURED FR01A FlNISHED FLOOR TO THE CEMERLWE OF DEVICE
E%CEPT FIRE AURM STROBE LIGHi.
2. NO WIRING DEVICE OUTLEf BO%ES SHALL BE MOUNTED BACK TO BACK.
3. ALL MOUNTING DEVICES SHALL BE INSTALLED AT MOUNTING HEIGHTS AS INDICATE� ON THIS DEiAIL
UNLE55 OTHERWISE NOTED.
4. FOR ALL ELEVATIONS (WHERE APPLICABLE), CASEWORK �EfAILS, FIRE WALLS, SMOKE WALLS, LOCATION
OF COUNTERTOP RECEPTACLES, LIGHTING FIXTURE SWITCHES, TELEPHONE OUTLEfS, EQUIPMENT
ROUGH-INS, HEA�WALLS, EfC., SEE ARCHITECTURAL �RAWINGS. WHERE NO ARCHITECTURAL ELEVATIONS
OR DEfAILS OCCUR, THE ELECTRICAL CONTRACTOR SHALL USE PRACTICAL MFANS AN� MEfHODS AS
WELL AS HIS FIEL� KNOWLEOGE ID LOCATE �EVICES IN THE BEST SUITE� AND MOST PRACTICAL
LOCATIONS FOR THE �EVICE.
�Inregrared
1�En�'meerinp
Consvdtants,l�c.
9700 ROCNSIDE RD. SUITE 290
CLEVELAND.OX 44125
PHONE:716901�6711
FA%:216-901-6712
GENERAL ELECTRICAL NOTES
1. ALL 'BUIL�ING STAN�AR�S" ANO/OR "BUILDING SPECIFICATIONS" SHALL BE CONSI�ERED AN INiEGRAL PART OF
THESE OOCUMENTS AN� THE CONTRACTOR SHALL BE RESPONSIBLE TO OBTAIN A COPY OF THESE DOCUMENTS
AN� COMPLY WITH ALL REQUIREMENTS, STAN�AROS, AND SPEQFICATIONS CONTAINED WITHIN.
2 THESE DRAWINGS ARE GENERALLY �IAGRAMMATIC AND ARE IMENDE� TO CONVEY THE SCOPE OF WORK AN�
INDICATE GENERAL ARRANGEMENT OF LIGHTING FIX�URES, DEVICES, CONTROLS, ELECTRICAL FIXTURES, MOTORS,
PANELBOARDS, EOUIPMEM, EfC. THE LOCATIONS OF ALL ITEMS SHOWN ON THESE �RAWINGS OR CALLEO FOR IN
THE SPECIFICATIONS THAT ARE NOT OEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE. THE EXACT LOCATIONS
NECESSARY TO SECURE THE BEST CON�ITIONS AND RESULTS MOST BE �EfERMINE� AT THE PROJECT. ALL
LOCATIONS OF WORK EXPOSEO TO VIEW ARE SUBJECT TO APPROVAL OF THE ARCHRECT PRIOR TO ROUGH-WS.
3. THE ELECTRICAL WNTRACTOR SHALL VERIFY EXISTING CON�ITIONS TO WSIIRE iHAT ALL NEW WORK WILL FIT IMO
THE EXISTING STRUCTURE AN� CON�ITIONS IN THE MANNER INTEN�E� AN� AS SHOWN ON THE �RAWINGS. THE
CONTRACTOR SHALL NOTIFY THE ARCHRECT/OWNER$ REPRESENiATNE PRIOR TO ANY ROUGH-INS. FABRICATIONS,
OR PERFORIAMG ANY WORK IN THE AREA INVOLVING DIFFERENCES. NOTIFlCATION SHALL BE IN THE FORM OF A
RFl, INCLUDMG A DRAWING OR SKEiCH INDICATING FlELD IAEASUREMENTS AND NOTES RELATED TO THE AREA.
4. ANY DISCREPANCIES BEiWEEN DRAWINGS AND SPECIFlCATION$ SHALL BE PROMPTLY BROUGHT TO THE ATTENTION
OF THE ENGMEER FOR CIARIFlCATION �URING THE BIODING PERIOD. NO ALLOWANCE SHALL SUBSEOUEMLY BE
MADE TO THE CONTRACTOR 8Y REASON OF MS FAILURE TO HAVE BROUGHT SAID DISCREPANCIES TO THE
ATfENT10N OF iHE ENGMEER DURING THE BIDDING PERIOD OR OF ANY ERROR ON THE CONTRACTOR'S PART.
5. ALL EOUIPMENT SHALL BE INSTALLED IN A NEAT, PROFESSIONAL AND WORKMANLME MANNER, RECTILWEAR TO
RNISHES AND BUILDING SiRUCTURE.
6. ALL COMPONENTS SHOWN ON THE RISER�ONE-LINE DIAGRAMS, BUT NOT ON THE PIAN OR VICE VERSA, SHALL BE
INCWDE� AS IF SHOWN ON BOTH.
7. REFER TO ARCHITECTURAL ELEVAiIONS TO �ERNE EXACT LOCATIONS OF ALL RECEPTACLES, OUTLEfS/JACKS,
SWITCHES, WALL AND PENDANT/CABLE MOUNTED LUMINAIRES, ETG LUMINAIRES AND CEILING MOUNTED EOUIPIAENT
SHALL BE COORDINATED WITH THE ARCHRECTURAL RCP (REFLECTED CEILING PLANS).
8. ALL CIRCUITING SHALL BE RUN CONCEALE� UNLE55 SPEGFlED OTHERWISE.
9. ALL RACEYVAYS RUNNING THROUGH BUILDING EXPANSION JOINTS SHALL BE EQUIPPED WITH APPROPRIATE
EXPANSION FITfINGS.
1�. CON�UIT HOME RUNS SHOWN ON THE DRAWING WITH MORE THAN (3) CURRENT CARRYING WNDUCTORS ARE
SHOWN �WGRAA�ATICALLY. THIS CONTRACTOR SHALL NOT INSTALL MORE THAN (3) CURRENT CARRYING CONDUCTORS
IN A RACEwAY UNLESS NATIONAL ELECiRIC CODE (REC), ARTICLE 310.15 DERAiING FACTORS ARE APPLIED.
n. ALL LIGHTING AND GENERAL POWER BRANCH CIRCUITS SHALL INCLU�E A SEPARATE NEUTRAL CONDUCTOR, UNLESS
SPEqFICALLY INDICATED OTHERWISE.
12. THE ELECTRICAL CONTRACTOR SHALL REFER i0 THE ELECTRICAL SPEQFICAilONS FOR ACCEPTABLE CONDUIT
IYPES/LOCATIONS. ALL CONDUIT SIZES ON THE �RAWINGS ARE BASED ON THE CURRENT AOOPTE� EDITION OF THE
N.EG WNDUIT FlLL TABLES FOR ELECiRICAL MEfALLIC TUBING (E.M.T). WN�UIT SRES SHALL BE REVISE� TO
THE SIZE REQOIRE�, REIATNE TO THE ACTUAL CONDUIT NPE TO BE WSTALLE�.
13. IT IS NOT IMEN�ED THAT THE PVilJS INOICATE ALL OBSTRUCTIONS, NECESSARY BENDS, OFFSEfS, AN� POLL
BOXES. IT SHALL BE iHE RESPONSIBILIIV OF THE CONTRACTOR TO INSTALL HIS WORK TO CONFORM TO N.EC.
REQUIREA�ENTS THE STRUCTURE MAINTAIN HEADROOM AN� KEEP OPENINGS AN� PASSAGEWAYS CLEAR. REFER TO
THE ARCHITECTURAL �RAWINGS FOR ALL �IMENSIONS AS REOl11RE�.
14. IT IS NOT WTEN�E� THAT THE PLANS INOICATE ALL WN�l11T ROUTES, PULL BORES, JUNCTION BOXES, EfC.
CONTRACTOR SHALL BE RESPONSIBLE FOR �EfERMINING ACTUAL CONOUIT ROUTING QUANTItt AN� LOCATION OF
POLL BOXES WITHIN ACCESSIBLE LOCATIONS.
15. PROVI�E SCREW-COVER PULL BOXES IN CON�UR RUNS AS REOUIRED TO LIMIT THE NUMBER OF BENDS TO NO
MORE iHAN FOUR (4) 90' OR 360 DEGREES iOTAL. SIZE PULL BORES IN ACCORDANCE WITH NEC, ARTI0.E
31428. DOWMENT ON RECORD DRAWINGS, SIZE AND LOCATION OF PULL BOXES USED W FEEDER CON�UIT
RUNS.
16. WHERE MULTIPLE DEVICES OF THE SAME ttPE/SttLE ARE SHOWN NE%T TO EACH OTHER, GANG TOGEfHER IN A
SINGLE COVER PIATE.
17. ALL FWSH MOUMED PANELBOARDS SHALL HAVE THREE (3), 3/4" CONDUITS STUBBE� ABOVE ACCESSABLE
CEILINGS FOR FUTURE CIRCUITS.
1fl FIEL� VERIFY THE EXACT LOCAiION OF MECHANICAL HVAC AND PWMBING EQUIPMENT THAT REQUIRE ELECTRICAL
CONNECTIONS WITH RESPECTIVE CONTRACTORS.
19. ALL CIRCUITS INDICATED ORIGINAiING M EXISTING PANELBOARDS ARE BASE� ON INFORMATION OBTAIN PRIOR TO
ANY DEIAOLITION WORK. IF A CIRCUIT NUMBER(S) INDICATED TO BE RE-USED REMAWS "IN-USP' AFfER ALL
DEMOLITION WORK IS C0IAPLETED, iERMINATE HOMERUN ON A SPARE(5) qRCUIT BREAKER IN SAME PANEL OR
PROVIDE A NEW CIRCUIT BREAKER(S) TO MATCH E%ISTING IYPE AN� HOMERUN TO AVAILABLE SPACE(S) IN SAME
PANEL
20. ALL CONDUR SIZES IN�ICAiE� ARE BASE� ON ELECTRIC MEfALLIC TUBING (EMT). THE ELECTRICAL CONTRACTOR
SHALL BE RESPONSIBLE FOR PROPERLY SIZING ALL OTHER WNDOITS NPES USED PER NEC RWUIREMENTS.
NELSOI�
Nelm Architedure, Inc.
a licensed affliate
30 West Monroe Street - Suite 200
Chicago, IL 6060&2409
Phone: (312)263-6605
(312) 2I8-0340
OWNER'S PROJECT MANAGER
]ones Lang LaSalle
Leslie Soto
540 W. Madison St, Sui[ eIL9-540-09-55
Chicago, IL 60661
T:312.909.2139 E:lesliesoto@am.jlLmm
MEPENGINEER
Integrated Engineering ConsWtants,Inc (IEC)
Tim Vlning
9700 Rockside Road, Suite 290
Cleveland, OH 44125
T. 216.901.67ll E: tim.vining@ieC-inCcc
GENERALCONTRACTOR
Mid America Contracting, Inc.
Tyler Crawford
107 N. Main Street, Suite 3A
Columbia, IL 62236
T: 618.589.2770 E: tic@midamericacontracting.com
ARCHITECT OF RECORD
Nelm Architecture, Inc.
Vincent Paul Duet
IN. LIC NO: AR11500046
Exp:12/31/2021
T. 215.825.6620 E: vduet@nelsonww.com
ConsWtant'.
MERRILL�
A BANK OF AM ERICA COMPANY
Cllent.
INW-044 BofA Indianapolis MLWM
Pantry Refresh, Sth Floor
510 96th Street
Indianapolis, IN 46240
Project TiHe & Nddress:
ELECTRICAL SCHEDULES, LEGENDS
AND NOTES
SheetTiHe�.
= PE118005]5
i�l •
- STAiE OF ; Q-
=Po''.�NoIAN?.' 2�N
�'. FSSroNA�e���
��.c �-•�/���,,,�%/'�
RELEA5E0 FOR CONSTRIICTI�N
Su6jec��o compliance with allregula�ions
of S�a�e antl Local Codes
City of Carmel
r
�un��\i lo•rvalM��_
DATE: 03�27�20
Seal:
Pmj. No'. 19.00052]J.000 Dcsigncr. ERO;MBM
�rawn By: T6V Reviewed By: HHH
Pmjcct Managcr. M]L qppmved By: HHH
EO-1
ALL �IMENSIONS AN� LONDITIONS MOA BE CHECKED AND VERIRED
ON SITE BY THE CONTPPQON PND SU6-CONTRAQORS PRIOF TO
PCFFORMING TIIC W02K. TI IC FROJCQ MBNAGCR SI IALL 8C NOTIFlC� IN
WRITING �F ANY �ISCREPANCIES PRIOR TO PROCEE�ING WITH THE W�RK.
m me�sory won�owroe, uczozo nu aisnTs aeseaveo