HomeMy WebLinkAboutM0.1 Mech HVAC DetailsREGISTER, GRILLE & DIFFUSER SCHEDULE (GRD)��FMK
A1ARK SERVICE MANUFACTURER MODEL NECK SRE FRAME SIZE MAN NC FlNISH BORDER REMARKS
A SUPPLY PRICE SPD 8"0 24"x24" 25 BY ARCH IAYIN 1
R�R�
1. iHE MECHANICAL HVAC CONTRACTOR SHALL BE SOLELY RESPONSIBLE TO COORDINAiE AND VERIFY ALL CEILING iYPES WITH ARCHRECT AND
ARCHITECTURAL CEILING PIANS, DEfAILS, SCHEDULES, ETC., INCLUDING, BUT NOT LIMITED TO DIFFUSER/GRILLE COLORS, LENGTHS, TRIMS,
FINISHES, FRAMES, MOUNTING WNFIGURATIONS AND HARDWARE, ETC. PRIOR TO ANY ROUGH-INS AND PIACING FINAL PURCHASE ORDERS.
2. SEE FLOOR PLANS FOR CFM.
3. CONNECTING DUC7WORK SHALL BE SIZED TO MATCH NECK, UNLESS SHOWN OTHERWISE.
MECHANICAL HVAC NOTES
1. �RAWINGS INDICATE THE MINIMUM �ESIGN REOUIREMENTS. FE�ERAL, STATE, AND LOCAL
CODES SHALL BE FOLLOWED, COMPLY WITH THE IATEST E�ITIONS OF THE STATE
MECHANICAL CODE, NFPA, SMACNA, AN� ASHRAE STAN�AR�S. THE WNTRACTOR SHALL
INCWDE THE WST OF SATISFYING SUCH CODES AN� STAN�AR�S IN THE BI�.
2 GENERAL NOTES, SYMBOLS LIST AN� �EfAILS ARE APPLICABLE TO ALL �RAWINGS WITHIN
COMACT DOCUMENTS.
3. COOR�INATE WORK OF THIS SECTION WRH THAT OF OiHER SECTIONS.
4. SHEEf MEfAL FITfINGS SHOWN ARE TO BE PROVIDE�. NO SUBSTITUTES SHALL BE
ALLOWED WITHOUT PRIOR CONSENT FROIA ARCHITECT/ENGMEER.
5. RUN DUCTS AND PIPING CONCEALED, UNLE55 SPECIFlED OTHERWISE, AND 0.EAR OF
CEILING INSERTS. ALL DUCiWORK SHALL BE INSTALLED AS CLOSE AS P059BLE TO
WALL AND UNDERSIDE OF BEAMS AND JOISTS.
6. ALL WORK SHALL BE COORDINATED WITH ALL iRADES INVOLVED. OFFSEiS IN PIPING
AND DUCTS (INCLUDING DIVIDED DUCTS) AND TRANSITIONS AROUND OBSTRUCTIONS
SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER. ARRANGE OPERATIONS 50
AS NOT TO DEUY COMPLETION OF INSTALLATION OF ANY PARTS OF INTERREIATED
WORK 50 THAT CONSTRUCTION MAY PROCEED ON SCHEDULE.
7. DIFFUSER SIZES SHOWN ARE NECK SRES; REGISTER AND GRILLE SRE ARE NOMINAL.
SUPPLY DUCT TO �IFFUSERS/GRILLES SHALL EOUAL NECK SRE UNLESS SHOWN
OTHERWISE
8. INSUTATE ALL SUPPLY AIR �UCIWORK IN WNCFALED ANO REfURN AIR PLENUMS WITH
MINIMUM R-3.5 ALL SERVICE FIBER GLASS DUCT WRAP WITH FRN VAPOR REfAR01NG
FACING. DUCT WRAP IN REfURN AIR PLENUM SHALL COMPLY WITH ASTM E 84 (FUME
SPREAD - 25, SMOKE DEVELOPED - 50).
9. HVAC CONTRACTOR SHALL FlELD VERIFY ALL E%ISTING REMS SRES, AND MATERIALS
BEFORE FABRICATION OR PURCHASE OF ALL NEW ITEMS.
10. REPAIR FlREPROOFlNG ARER INSTALLATION OF HANGERS AND SUPPORTS.
11. ALL MATERWLS M CEILING SPACE SHALL BE PLENUM RATED PER OMC.
12. ALL ITEMS OF IABOR, MATERIAL, AND EOUIPMENT NOT SPECIFlCALLY MENTIONED HERBN
OR SHOWN ON PIAN, BUT MCIDENiAL T0, OR REQUIRED FOR THE COMPLETE
INSiALLAT10N AND PROPER OPERATION OF iHE WORK, SHALL BE FURNISHED AS IF
CALLED FOR IN DETAIL BY THE DRAWINGS.
13. THE HVAC CONTRACTOR SHALL SECURE AND PAY FOR ALL PERIAITS AND INSPECTION$
REOUIRED FOR iHE PROSECUTION OF HVAC WORK. ALL PERMIT$ AND CERiIFlCATES OF
INSPECTION AND APPROVAL SIGNED BY THE CONTROLLING BUILDING DEPARTMENT SHALL
BECOME PROPERiY OF THE OWNER.
14. UNLE55 NOTED OiHERWISE, ALL HOLES OR DAMAGE CAUSED BY THE REMOVAL OF
E%ISTING WORK OR THE INSTALUTION OF NEW WORK SHALL BE PROPERLY PATCHED BY
THIS CONiRACTOR. HOLES SHALL BE NEATLY PAiCHED AND PAIMED WITH SUITABLE
MATERIAL i0 MATCH E%141NG SURFACES. HOLES THROUGH FLOORS OR FIRE WALLS
SHALL BE SEALED WITH THE APPROPRIAiE INTUMESCENi CAULK, PUTiY, SiRIP OR
SHEEi FIRE BARPoER PRODUCT.
15. ALL E%ISTING NR DISTRIBUTION DEVICES THAT ARE TO BE REUSED SHALL BE CLEANED
WITH MILD SOAP AND WATER SOLUTION AND THOROUGHLY DRIED.
16. ALL E%ISTMG TO REMAIN HVAC SYSTEAIS SHALL BE CLEANED PER CURRENi NATIONAL
AIR DUCT CLFANING ASSOCIATION GENERAL SPEQFICATIONS.
17. HVAC DRAWINGS ARE DIAGRAMMATIC, INDICATING GENERAL ARRANGEMENT, APPRO%IMATE
SRES, GENERAL LOCATIONS OF EQUIPMENT AND PIPING. VERIFY DIMENSIONS W FlELD;
ADJUST TO MANUFACTURER$ SHOP �RAWINGS. DO NOT SCALE �RAWINGS.
18. ALL DUC7WORK JOIMS AND SEAMS SHALL BE AIR-TIGHT PER SMACNA. POORLY MADE
JOINTS, SPLITS, VISIBLE HOLES AT CORNERS, EfC SHALL BE REWORKE� AND REPAIRED.
WHERE E%CESSIVE PULSATING OF �UCiWORK IS FOUND, ADDITIONAL STIFFENERS SHALL
BE ADDE�. ANY CRACKING IN THE SEALANT THAT IS APPARENT UPON INSPECTION
SHALL BE SUFFIGENT TO WARRANT REJECTION,
19. LOW PRESSURE DUC7WORK SHALL BE CONSTRUCTED PER SMACNA `HVAC DUCT
CONSTRUCTION STANDARDS"FOR 2 INCH STATIC PRESSURE, SEAL CLASS "B".
20. HANGERS AND SUPPORTS PROVIDE GALVANIZED STEEL ARAPS, ALL-THREAD ROD AND
HORIZONTAL ANGLE SUPPORTS SIZED PER SMACNA REQUIREMENTS.
2L INSTALL FLEkIBLE DUC7WORK FULLY EXTENDE�, FREE OF SAGS AND KWKS. MA%IMUM
LENGTH OF FLEXIBLE DUCiWORK SHALL BE 3'-�". FASTEN FLEXIBLE DUCiWORK TO
RIGI� �UC7WORN AN� �EVICES WITH SELFLOCKING 100 PERCENT NYLON, MJUSTABLE
�IAMEfER CIAMPS.
22. PROVIDE BAIANCMG DAMPERS FOR ALL AIR TERMINAL DEVICES (SUCH AS BUT NOT
LIMIiED T0, DIFFUSERS, REGISiERS, GRILLES, EfC.) AND BRANCH DUCiWORK RE�UIRED
FOR PROPER BALANCING OF SYSTEM. ALL BALANCING DAMPERS SHALL BE CONSTRUCTE�
IN ACCORDANCE WITH SMACNA "HVAC DUCT CONSTRUCTION SiANDAR�S".
FASTEN TO STRUCTURE
GALVANRED SHEEf METAL DUCT TO
SUPPLY AIR MNN
1" WI�E MINIMUM MEfAL STRAP
HANGER.
1" THICK FlBERGlASS INSUlATION
w/Fai� Fncwc pF REquiREo, sEE
SPECIFICATIONS)
VOLUME DAMPER
NSUTATE� FLEXIBLE CONNECTION.
(unxiuu� a rE�r) m vERncn�
ONLY.
MEfAL STRAP QAMPS (ttPICAL) 2
PwcEs iNNCR oucr x ou�cR
VAPOR BARRIER.
THERMAL INSOL1iING BLANKEf.
ECTING DUCT SIZE SHALL BE SAME OS
SER NECK UNLESS SHOWN OTHERWISE.
NELSOI�
Nelm Architedure, Inc.
a licensed affliate
30 West Monroe Street - Suite 200
Chicago, IL 6060&2409
Phone: (312�263-6605
(312) 216L340
OWNER'S PROJECT MANAGER
]ones Lang LaSalle
Leslie Soto
590 W. Madison St, Suit eIL4-590-04-55
Chicago, IL 60661
T:31L90A2139 E:lesliesoto@am.jll.com
MEPENGINEER
[ntegrated Engineering Consultants, Inc (IEC)
Tlm Vining
9700 Rockside Road, Suite 290
Cleveland, OH 44125
T: 216.901.67ll E: tim.vining@iec-inc.cc
GENERALCONTRACTOR
Mid America Contracting, Inc.
Tyler Crawford
107 N. Main Street, Suite 3A
Columbia, IL 62236
T: 618.589.2770 E: tic@midamericacontracting.com
ARCHITECT OF RECORD
Nelm Architecture, Inc.
Vincent Paul Duet
M. LIC NO: AR11500046
Exp: 12/31/2021
T: 215.825.6620 E: vduetC�nelsonww.mm
ConsWtant
MERRILL�
A BANK OF AMERICA COMPANY
Client
INW-044 BofA Indianapolis MLWM
Pantry Refresh, Sth Floor
510 96th Street
Indianapolis, IN 46240
PmjeQ TiHe & Fddress:
MECHANICAL HVAC SCHEDULES,
LEGENDS AND NOTES
SheetTiHe:
= PE118005]5
[�l •
' STATEOF �%g
`-Po'..!NoinN?.� �`�i�
'. F NG`
� " SsioNn�E r
��c� j,�����,,���
THICKNESS & REINFORCING SCHEDULE -* LOW PRESSURE DUCTWORK
cR�arEsr oucT srEc� oucTs us.
�IMENSION STAN�ARD GAUGE
17' OR LESS 26
13" THRU 18" 24
19" THRu 30" 24
31' THRU 4Y ZZ
43' THRU 54' ��
duM oucrs e & �oNciTuoiNn�
S GAUGE SEAM
24(OD20') PITf58URGH OR
ACME LOCK
22(0.025') PITfSBURGH OR
ACME LOCK
22(0.025') PfRSBURGH OR
ACME LOCK
20(0.032') PfRSBURGH OR
ACME LOCK
ANGLES TO BE THE
SAME SRE AS REQl11RE�
REINFORCING ANGLES
ANGLE SLIP
ANGLES TO BE THE
SAME SRE AS REQUIRED
REMFORCMG ANGLES
CAULK OR GASKET
COMPANION ANGLES
ANGLES TO BE THE
SAME SRE AS REQUIRED
REMFORCMG ANGLES
ANGLE REINFORCED POCKEf LOCK
���
ACME LOCK
HEMME� '�' SLIP
��
STAN�ING SEAM
7RANSVERSE JOINT 7RANSVERSE JOINT
SMALLEST �IMENSION GRFATEST DIMENSION
DRIVE SLIP OR POCKEf PUIN "S" SLIP OR POCNEf
LOCK OR BAR SLIP LOCK OR BAR SLIP
DRNE SLIP OR POCKET p�qlN "S" SLIP OR POCKET
LOCK OR BAR SLIP LOCK OR BAR SLIP
HEMMED "5" SLIP OR BAR HEMMED "5" SLIP OR BAR
SLIP OR DRNE SLIP OR 1" SLIP OR 1" POCKEf LOCK
POCKEf LOCK
DRNE SLIP 18" OR LE55 �E SLIP OR REIN- FORCEI
BAR SLIP REIN- FORCED BAR SIJP OR POCKEf LOCN
3AR $LIP OR POCKET LOCK
1 1/4" BAR SLIP, OR RE- 1 1/4' BAR SLIP, OR RE-
MFORCED BAR SLIP, OR 1 MFORCED BAR SLIP, OR 1
1/2" POCKEf LOCK 1/2" POCKEf LOCK
� G
DRNE SLIP
�
REINFORCED BAR SLIP
�
ALTERNATE BAR SLIP
NOTE:
L LOW PRESSURE DOCiWORK SHALL BE �UCiWORK IN WHICH THE PRESSURE DOES NOT EXCEE� 2" WATER GAUGE.
REMFORCING (ALL DUCTS 18' THRU 54' SHALL BE CROSSBROKEN)
NONE REQUIRED
IF iRANSVERSE JOINTS ARE LOCAiED 4'-0" OR LESS ON CEMER NO
REINFORCING IF ON 8'-0" CENTERS REINFORCE WITH 1"R1°%1/8"
IF TRANSVERSE JOINTS ARE LOCAiED 4'-0" OR LESS ON CEMER NO
REINFORCING IF ON 8'-0" CENTERS REINFORCE WITH 1"R1°%1/8"
IF iRANSVERSE JOINTS ARE LOCAiED 4'-0" OR LESS ON CEMER NO
REINFORCING IF ON 8'-0" CENTERS REINFORCE WITH 1"X1°X1/8"
�
POCKEi LOCN
�
PITTSBURGH LOCK
�
AB R SLIP
PIAIN '�LIP
ANGLES TO BE THE
SAME SRE AS REQUIRED
REINFORCING ANGLES
ANGLE REWFORCE�
DUCT CONSTRUCTION MINIMUM SHEET METAL THICKNESSES
RECTANGUL4R DUCTS
MA%IMUM SRE 4EEL ALUAIINUM
QNCHES) (MINIMUM THICKNESS, NOMINALJ (MINIMUM THICKNESS, NOMINAL)
THROUGH 12 0.022 INCH (26 GAGE, GALV.) 0.020 INCH (N0. 24 B&S GAGE)
13 THROUGH 3� OD28 INCH (24 GAGE, GAW.) a.ozs iNCH (No. zz e&s cncE)
31 THROUGH 54 0.034 INCH (22 GAGE, GALV.) 0.032 INCH (N0. 20 B&S GAGE)
55 THROUGH 84 0.040 MCH (20 GAGE, GALVJ 0.040 MCH (N0. 18 B&S CAGE)
ovEe aa o.osz iNcn (ia cncE, cn�v.) o.osi mcn (No. is e&s cnce)
ROUND DUCTS
SPIRAL SEAM DUCT LONGIiUDINAL SEAM DUCT FITTINGS
MA%IMUM SIZE STEEL STEEL STEEL
QNCHESJ (IAINIMUM THICKNESS, NOMINAL) (MINIIAUTA THICNNESS, NOMINAL) (MINIMUM THICKNESS, NOMINAL)
iHROUGH 12 0.019 INCH (28 GAGE, GALV.) OD22 INCH (26 GAGE, GALV.) �A22 INCH (26 GAGE, GALV.)
13 THROUGH 18 0.022 INCH (2fi GAGE, GALV.) 0.028 INCH (24 GAGE, GALV.) 0.028 INCH (24 GAGE, GALV.)
19 THROUGH 28 0.028 INCH (24 GAGE, GALV.) 0.�34 INCH (22 GAGE, GALV.) �.034 INCH (22 GAGE, GALV.)
29 THROUGH 36 0.034 MCH (22 GAGE, GALV.) 0.040 INCH (20 GAGE, GALV.) 0.040 INCH (20 GAGE, GALV.)
3� rHeoucH ss o.oao iNCH (za cace, cn�v.) o.osz mcH (ia cncE, cn�v.) o.osz mcH (ia cncE, cuv.)
RELEA5E0 FOR CONSTRIICTI�N
Su6jec��o compliance with allregula�ions
of S�a�e antl Local Codes
City of Carmel
r
�un��\i lo•rvalM��_
DATE: 03�27�20
MECHANICAL HVAC SYMBOL LEGEND
�
�
�
�
�
-x-x- x
�
xx CFMK
%M
�Inre��arcd
1�Engineenn�
Consvltan2s,lnc.
9700 ROCNSIDE RD. SUITE 790
CLEVELAND,OX 44125
PHONE:1169014711
FAX:216901�6712
SUPPLY OR OUT�OOR AIR �UCT UP
SUPPLY OR OUTDOOR AIR DOWN
REfURN, OR RELIEF AIR DUCT UP
REfURN, OR RELIEF AIR DUCT DOWN
BAUNCING (VOWME) �AMPER
EXISTING ITEM TO BE REMOVED
NEW DUC7WORK
EXISTING �UCiWORK/EQUIPMENT TO REMAIN
7HERMOSTAT
DIFFOSER OR GRILLE DESIGNATION
NOTE: ALL REIAS LISTED IN THI$ LEGEND MAY OR MAY NOT BE ON TMS PROJECT.
Seal:
Pmj. No: 19A�OSD].�00 Designco ERO;MBM
�rawn By: ]PH Revicwctl By. HHH
Pmjcct Managcr. MJL qppmved By: HHH
MO-1
ALL�IMENSIONSAN� LON�ITIONS M114 BE p1ELKED AND VEFIFIE�
ON SRE 6Y THE CONTRPQOF AND SUB-CONTRAQOPS PNIOR TO
FCRFORMING TI IC WOPK. TI IC PROJCR MANAGCR SI IALL 9C NOTIFlC� IN
W WTIN6 OF ANY �ISCREPANC[ES PFIOR TO PROCcE�ING WRH THE WORK.
;� rvEisory waR�ow�oE, uc zozo Au nrcrvTs nESEavEo
CEILING DIFFUSER DETAIL
SCALE:NONE