TA6LE I
M[NIMUM SPHCIFIED TIME RGQUIRGD FOR A I.0 psi
DROP FOR SIZE AND LENGTH OF PIPE INDICATED
(testing pressure after s[abiliza[ion no less [han 4.0 psi and m more [han 8.0 psi)
Pipc Minimum Length Cor Timc for
Diameter Time, Minimum Longer Specifieation Time for Length (L) Shown, mims
la min:s Time, tt Len [h, S
100 H I50 ft 2A0 ft 250 ff 300 ft 350 ft 400 ft 450 ft
4 3:46 597 0380 L 3:46 3:46 3:46 3:46 3:46 3:46 3:46 3:46
6 5:40 398 0.854 L 5:40 5:40 5:40 5:40 5:40 5:40 5:42 624
8 734 298 1.520 L 734 734 734 734 736 8:52 10:08 IL24
10 9:26 239 2374L 9:26 926 9:26 9:53 11:52 13:S1 15:49 17:48
12 I 120 199 3.418 L I 120 I120 I 124 14:15 17:05 19:58 22:47 2538
15 14:10 159 5342L 14:L0 L4:10 17:48 22:15 26:42 31:09 3536 40:04
18 17:00 133 7.692L 17:00 L9:13 2538 32:03 3827 44:52 51:16 57:4L
21 19:50 114 10.470L 19:50 26:10 34:54 43J7 5221 61:00 69:4R 78J1
24 22:40 99 13.674 L 22:47 34:11 45:34 56:58 6822 79:46 91:10 102:33
27 2530 88 17306 L 28:51 43:16 57:41 72:0'1 R632 100:57 I I5:57 129:48
30 2820 80 2L366L 3537 5325 71:13 89:02 106:50 12438 14226 160:15
33 31:10 72 25.852 L 43:05 64J8 86:10 107:43 129:16 150:43 17221 193:53
36 34:00 A6 30JGR L 51:17 76:55 102:34 12ft:12 153:50 17929 205:07 230:46
RELEASED FOR CONSTRl1CTI0N
Su6jec� �o compliance with all regula�ions
04 S�a�e antl Local Codes
City of Carmel
y\0.v��i �\p;,V`iiY?A�i
\
onrE: 09/19/19
SUMMAftV OF UITERAL INSTALUITION REqUIREMENTS
1. Only one building may mnnect to the sewer main per lateral unless offierwise approved by TriCo.
2. Foundationdrains,sumpdrains,downspoutsandotherstormwaterdrainsshallneverberonneo[edtothe
sanitary sewer. Site dewa[ering systems shall never be discharged m the sanitary sewer.
3. The euisting sewer line from the building to the septic tank may only be reused if it is located under a building
addition, patio, porch or paved driveway, and the line passes an air test that is observed by TriCo. Contact TriCo for
more information about air testing requirements. The property owner is responsible for testing wsts.
4. TriCo shall inspect all new laterals or laceral repairs In their entire[y. Final mnnection to ffie sanitary sewer must be
observed by Trim. The property owner or contractor must notify 7riCo prior to backfilling. Inspections must be
scheduled at least 24 hours in advanw. If an inspection fails and wbsequent inspections are required, or'rf the
mntracmr is not on site for the scheduled inspeRion, a$100 fee will be assessed and must be paid prior to
schetlulingthe reinspection.
5. Septic rystem rontents or effluent shall never be dischargetl to the sanitary sewer. Be advised that your munty
health department regulates septic systems. Upon connection ro sanitary sewer, a septic tank must typically be
abandoned, pumped clean, and filled completely with earthen material. Contact your counry heakh department for
more information on septic system and abandonment requirements, and to notify the department of any
abandonment.
6. The follawing materials are acceptable for use in graviry sewer lateral installation ar repair:
PVC pipe: SDR 35 or SDR 26, ASTM D3034, 6" diameter
PVC pipe, preswre rated:SDR 21, ASTM D2241, 6" diameter
PVC restrained joint pipe for directional dnlling: Certatlo Greenline SDR 21, ASTM D2241, 6" diameter
All gasketed joints shall meet ASTM D321]
All fittings shall be SDR26 or better
�uc[ile iron mechanical joint fittings with proper hardware
5�6 26 gasketed repair sleeves or Indiana Seal shear guard
Femm and similar flexible couplings are only acreptable in certain circumstances and shall not be used wiMau[
prior appmval fmm TriCo
Cleanouts 6" threaded PVC caps
Bedding: Use qS croshed stone or fractured face aggregate
The following materials are accepta6le for use in low-pressure sewer lateral installation or repair
HDPE pipe for directional drilling: DR 11 IPS, 125" diameter, PE4710
Cannections shall be matle via electrofusion or using polypropylene or stainless steel compression fittings
Electrofusion high volume tapping tee, rated 200 psi, PE4710
125" IPS full port 1/4 tum fusible PE ball valve, ra[ed 200 psi
Threaded swing check valve, 316 stainless steel, ra[ed 20o psi
Cantact TriCo for acceptable pump sta[ion materials, equipment, pumps and other requirements
7. For gravity and low-pressure rystems, the line leaving the building shall not exceed 3' in length before a deanout
must be added and the line is transitioned to 6" diameter SDR 35 PVC pipe. Glued joints are not allowed after 3'. No
atlditional glued flttings are allowed 6etween the building and the transition/deanouL For all graviry lines, deanouts
shall not be spaced more than 300' apart between the building and the sewer main. See TriCo's standard drawings
for more information on deanout installation,
8. Bedding material shall be placed from at least 6 inches below to 12 inches above the pipe surface. The trench shall
be a minimum of 18" wide with at least 6" of dearance on boM sides of the pipe. Marerial shall be placed over the
pipe and tracer wire after inspectian. Saft, unstable ar unsuitable material found below and near ffie lateral,
induding any fill ar foundation backfill material, must be removed and replared with k8 stone. The mntraomr is
solely responsible for establishing stable pipe 6edding mnditions.
9. H10-AWG solitl copper tracer wire shall be laid on rop of and run ihe entire length of ihe lateral. All splicing of tracer
wire shall use 3M splice kit motlel DBR/V-6, King Innovation Drymnn Direct Bury Wg Aqua catalog #90220, or TriCo
approved equal.
30. Laterals shall be installed at least 20' from water wells unless PVC pressure grade pipe is used. Any proposed
installation requiring pressure pipe shall be reviewed by TriCo prior to installation. Where a transition is made
between SDR 35 pipe and pressure grade SDR 21 pipe, a ductile iron gasketed mechanical muplings must be used.
1L Laterals less than 5' deep shall be at least 24" from the propercy line. Laterals more than S deep shall be at least 36"
fmm the property line. Where the lateral run5 in dose pmximity to the pmperty line the pmperty romers must be
aocurately staked 6y a pmfessional land surveyor prior to inspectbn.
12. Laterals running parallel to a building or struc[ure shall be at least 36" trom the face of a crawl space or slab on grade
foundation and 60" trom [he face of a basement toundation wall.5pacing requirements also apply with respect to
the ancillary sbucture's foundation depth. Ancillary strucmres (e.g. window wells) and other utilities shall not be
placed over or near the lateral. TriCo may adjust requirements where future amess to the lateral may be obstructed
by other utilities. The mn[ractor should call to diswss further if he/she believes this muld be an issue.
13. All infrastructure connected to TriCo's sewer syscem may be resred, inspec[ed, or televised at TriCo's discretion, and
must remain accessible and properly maintained.
14. Call 811 or 1-500-382-5544 before you dig. For more information go to www.indiana811.org.
If you have any questions or if you want to request an exception to standards and specifcations, please mntact TriCo
during normal business hours at 317-844-9200 prior ro completing the work and scheduling an inspection. Go to
www.trico.eco ro view standard drawings and specifications.
Revised 3/19/2019
I I
u
u
u
H.
9.
10.
ll.
12.
I3.
14.
I5.
Backfill around all installcd or proposcd manholc s[ruc�ures, sidewniks, bikc pa[hs and/or all
paved areas shall be made with granular ma[erial (b-bortow)or No. 8 stone, up to 18-inches
below crosssection thickuess (which shall include "No. 53" s[one dep[h). Ifmocestringenl
backfill requiremeu[s are eel out per city, rown, county, or District specificatione thone
standarde shall be followed. Trench opening within 5-feet of ihe back of the curb of
paved roadways, shall be baekfi0ed with gcanulac material or No. ft stone in aewcdance with
Section 211 of the eurten[ INDOT standard spuifiwtions handbook.
The Con[rac[or shall be responsible for veri(ying that all statc highways, city, and counTy
permits have been obtained by [he developer prior to staN ofconstruction.
Initial asbuilts shall be presented b the inspecting enginee� pnor ro final submittal ro the
District for rcvicw, othcrwisc Contractor shall bc rcquircd ro furnish ihc dcvcloper' s
Enginccr with a s'ct oCpcinle s'howing acWal scwcr locations and invcrts induding latcral
location, dcpth, and Icng[h. Such asbuilt prints must bc reccivcd by thc Enginccr bcforc
thc finel conirac[ paymcnt can bc anihorizcd. Asbuilts shall be submittcd per thc Dis[ricts
curren� standard which can be fowd at www.c�ewd.org.
The snnitnry sewer laterals and smbs termination shall be indicated on the eurface with a
detectuble metal post set immedia[ely above the s'aid termination point if full connection
is not immediately made.
All sanitary scwcr linc upon complction will bc rcq�irrd m pess a low pressurc eir tcst.
Said test shall be mnducted accortling to ASTM FI417-92, and shall be witnessed by a
Dis[eict employee or the Dis[ricts repcesenla[ive. The tes�ing shall be iu accordance with
Table 1 as follows wilh 0.5 psi being added for each fool of waler above [he sewer line
being tested. Sewer lines shall be subject to visual leak inspection at downsneam
manholce with all visual Icaks bcing ropaired and subject to tclevising requcsts by thc
District.
Pnor m finel deFlcetion tcst (mandrel tcst) all meinlines shall bc cicenrd and Ree of any
debris. DeFlection tes[s shall be perfonned on all flexible° pipe after the final backfill has
been in place a[ least 30 days. No pipe shall exceed a vertical deflution of 5% deflec[ion
tesl resulltl. ('The following are cons'idered noo-Flexible pipes: concrele pipe, ductile iron
pipq and cast iron pipe). The deflecnon test shall be perfarmed with a nino-point
mandrel. Proving rings shall be available at time of test otherwise no testing will be
allowed. All mandrel testing shall be witnessed by a District cmployee oc the Dislricts
represcntativc.
The ends of all la[eeals are [o be plugged water tight wi[h a gaske[ed cap capable of
wi[hs[andiug a low pressure aic leal wilhoul leakage. Lataals shall be subjecl lo visual
leak inspection at downstream manholes with all visual leaks being repaired
Bedding for flexible pipe and rigid pipe shall be No. B crushed srone from 6-inehes below
ro 12-inches above the pipe. Manholes sha0 be placed on no less than 6-inches of No. 8
crushcd srone brdding.
16. Watcr linq utiliTy, and Icgal drain crossings and separations shall bc in accordancc with
the more s[ringen[ of [he [wo: 327 IAC 3-6-9 or the Dis[ric[s s[andaed drawings.
17. The trench shall be upened sufficiently ahead uf pipe layiug ro ceveal obatruction, and
shall be properly protecteA and/orbarricaded when lefi unaitended.
18. No water shall be permitted to �ow into the sanitery sewec system during cons�metion.
CoNracror shall utilize a pump m keep the wa[er level below [he pipe. Pump discharge
shell be directed m a storm outlet in accordence wi[h statc and federal laws and
regulatio��s (3271AC 3-6-20). Auy pipe en[eeing existing sewers shall be plugged wi[h
screw type mechanical, braced plug until such time as all lesls on the sewers and all
punch list iteme are complete.
19. All sewec latecals installed shall be bedded the same as the main line sewec.
20. Forty-eight (4R) ho�rs notiw ehall be given ro the Distric� prior to the start of sewer
cons[ruction. Also, 48 hours noticc shall bc givcn prior to doing any testing on thc
sewer.
21. Manhole castings shall be stamped SANITARY SEWHR (Neenah Casting R-1772 or
East Jorden 1022ZIG5) and bc self-sealing type. Tde mstin�,J[onge slrn[[ be 34 inchec
and the clear operzing sGall be mirz. 20- 13/!6 incGes. Watertighl castings shall be bol4
down Eas� Jordan 1022ZIPT and also sfamped SANITARY SEWER.
22. The minimum slope of [he sewer shall be:
Size of Pioe Minimum Conslructed Slooe
R-inch 0.40 %
10-inch 028 %
12-inch 022%
I S-inch 0.15 %
I S-inch 0.12 %
23. The Contracloc shall provide measurements of the slope of the sewe� foe each manhole
section as construclion progresses. Such measurements shall be certified by a Registered
Land Suwcyor or Enginccr and be availablc on-sitc for obsmation by thc DistricPs
Inspector. No more ihan lhree manhole seclions can be constmcted in advanre of such
measuremems.
24. In the event the Contractor docs not mect [he minimum slopes, thc sewer section and any
other affected sewer sections shall be reconstructed to meet such minimum slopea.
25. Latcrals are to be installed with a minimum 14 gaugc iracer wire Rom the wye to the
Icnninus. Upon laterel completion the contrectoc f'or ihe building or home will extend the
wire fmm Ihis teeminus to (he building cleauoul adjacent to the building.
u
u
u
�
2.
3.
4.
Y
6.
7.
u
TYPICAL SANITARY SEWER SPECIFICATIONS
TO BE USED FOR PRIVATE SEWER DEVELOPMENT
WITHIN
CLAY TOWNSHIP RF.GIONAL WASTF. DISTRICT
REVISED 3A/20U7
Slandard apecifications of Clay Township Regional Waste District (the District) and
Dcpartment of Transportation QNDOT) shall apply for all work and matcrials. Sanitary
sewerpipe shall be installed in accordance with Section 715 ofthe current INDOT standard
specifications handbook.
Sanitary sewer grevity pipe, unless pressure reled pipe required per IAC or direc[ional dnlled
pipe, shall be Polyviuyt Chloeide (PVC) in accorda�ce with ASTM D3034-89 with a
minimum wall thick�ess designation of SDR 35 nnd ins[alled pee ASTM D2321-89
specificatioa PVCpipcusedshallbegroovedbell,spigoCend,andgasketed. Thepipeshall
bc madc of PVC plastic having a ccll classification of I7A54B.
PVC sani�ary sewer graviry fi[[ings shall also conform [o the requirements of Ihe ASTM
D3034-R9 spccification. All fittings shall bc moldcd in onc picce with standard pipc
bells, gasketed elastomeric joinls, and spigol ends. Single piece molded PVC with
s[andaed pipe bells, gaskels, and spigot ends for back-ro-back tee wyes are acceptable.
Wall [hickness of all fittings s'hall have a minimum desiguation of SDR 26. Gaske�s' for
elastomericjoints shall be molded with a minimum cross-sectional arca of 020 squarc
inchcs and conform to ASTM F477 spccification.
All sanitary manholes shall be precast concrete manholes in accordance with ASTM C47R
and Section 720 of the wrrent INDOT standard specifieations hendbook. O-rings shell
confortn to C443. Double row ofKent Seal or equivalent shall also be applied to alljoinls
and between riser rings and cas[ings. Manhole s[ep s'pacing shall be no more [han 16-inches.
Manholes shall be air tested for leakage in accordance with ASTM CI244-02, Standard Test
Method for Concrete Sewer Manholes by the Negative Air Pressure (Vawum) Test.
A. Installation and opera[ion of vacuum cquipmcnt and indicating dcviccs must bc in
accordanec with manufacNrers' rccommendations and perfoimanec spccificationa
which have been provided by the manufacNrer and acrepted by [he District Engineer.
The vucuum e9uipment mmT be cupuble oftes(ing fhe emii�e mmrhole, iiiduding rhe
cae�ting and ne'er rings.
B. Wi�h �he vacuum testee set in place:
L Cortnec[ the vacuum pump b the outlet port with [he valve open.
2. Draw a vawum oCteu QO) inches of Hg. (5 psi) and close the valve.
C. Aceepted s�andards for Icakage will be establishcA from thc clapsed timc for a
ncgativc pressurc changc Gom tcn QO) inchcs to ninc (9) inchcs of mcreury. Thc
maximum allowablc Icakagc ratc for a four (4) fw[ diamctcr manholc must bc in
accordancc with �hc following:
Minimum Elapsed Time for a:
Manhole Depth Press'uce Change u( I Inch Hg
10 feet or less 60 seconds
>IO Ceet bW q5 feet 75 seronds
>IS fee[but Q5 feet 90 seconds
Formanholes five (5) feet in diameter, add an additional Rfreen (IS) seconds and for
manholas aix (6) feet iu diameteq add an additioual [hirty (30) secouda to the time
requi�ements for fou� (4) foot diameter manholes. For all manholes deeper than
Iwcnty-fivc (25) fcct, Ihc Enginccr will dctcrtninc [hc applicablc minimum clapscd
time.
D. If the manhole fails the icst, necessery repairs muet be made. The vacu�m �es[ and
repairs m�st be repea[ed ontil thc manhole passes the test.
P. If manhole joiut sealanle are pulled oul du�ing lhe vacuum les�, the manhole must be
disassembled and the joint sealants replaced.
F. Menholes will be subjecl to visual inspution with all viwal leaks being repaired.
Butyl rubber coa[ing wi[h plastic wrap shall be applicd around cach manholejoin[ from 3-
inchesabaveto3-inchesbeloweachjoint Theappropriateprimershallbeappliedpriorro
applying the mbber coating. Inside joinls to be filled with precoal plug material. Entire
exrerior surface of sanitary sewer manholes shall be sprayed with a bituminous coating and
all exterior gap exposure o( dscr nngs shall be back plasicred or groumd with nonshnnk
grout.
The menhole chimneys, including all riser rings shall 6e sealed using Flex rib in[emal
chimncy scal manuFacNred by Cretex, NPC, or a Disiric[ approved eqoal. The flex rib
internal chimney seal shall extend fmm a minimum of 3-inches below the top ofthe cone
sec[ion l0 3-inches over Ihe manhole cas'ling t}ame o[ per manufacturers installalion
procedures iCdirected otherwise. Intemal Chimney Seal shall be inslalled atter manhole
vacuum tu�sting and prior ro final ecccptancc. Watcr tcst may bc donc, per manufacturoror
Disteicts ruommendatioq to pmvide assucance that inremal chimney seal is water tight.
The casting elevations are se[ by plaq however, [he castings am �o be adjusted in the ficld by
the District's representative sho�ld a discrepancy occur bctwcen plan grade and existing
gcade. New manhole ring(s) and covcr shall bc installcd to establish gradc. Maximum
heighl of adjus'ting �ings s'hall be 72-inch un exisling s'Imclure ad7uslment and 10.inch
maximum on ncw conStruclion.
u
�
J
ZP Investments,
LLC Office
North Illinois St
Carmel, IN 46032
Owner
ZP Investments, LLC
11460 N Mendian Street
Carmel,IN 46032
317-705-5050
Architect/ Landscape Architect
RATIO ......... ......... ......... .........
101 South PennsyNania Street
Indianapolis, Indiana 46204
317-633-4040
Structural Engineer
CE Solutions..... ......... ......... .........
10 ShoShone Dr.
Carmel, IN 46032
317324-6024
Mechanical / Electrical Engineer
Heapy Engineering ......... ......... .........
3850 Priority Way 5. Dr #204
Indianapolis, IN 46240
317-571-8795
Civil Engineer
Civil and Environmental Consultants, Inc.
530 E Ohio Street G
Indianapolis, IN 46204
317-655-7777
�� KEY PLAN
SEAL � DATE O6/21/19
LL J�,``�N C„����pi
z ,` Q':'v�'s�eRNL :
p . P:pE Fo .��
w : Q: No
¢ � * • PN0300058 •7 *
Q , STATEOF :
i 0•'� d T
z
c� %9oT';'�'OfAN?.'��c',
Ul I� Fy� NG ,�
z,���qnnn� ���,,
«� (�onmCHw,i 0G�21�<
SHEETISSUE
ISSUE�FORCONSTRUCTION Ofi'P1119
PROJECT NO. 02000.000
SHEET TITLE
SAN ITARY
SPECIFICATIONS
SHEETNUMBER
C806