1. GENERAL PROVISIONS
A. THE PROVISIONS OF iHE INSTRUCTIONS TO BIDDERS, GENERAL CONDIilONS,
SUPPLEMENTARY WNDITIONS, ALTERNATES, ADDENDA'S', ANO DIVISION 1 ARE
A PART OF THIS SPEQFICATION. WNTRACTORS AN� SUBCONTRACTORS SHALL
EXAMINE SAME AS WELL AS OTHER DIVISIONS OF THE SPEQFICATIONS WHICH
nFrECT woRK uNocR Tws oivisioN.
B. THIS CONTRACTOR SHALL PROVI�E ALL IABOR, EQUIPMENT, SUPPLIES,
SERVICES, AND SHALL PERFORM ALL WORK COMPLEfE AND IN S�RICT
ACCOR�ANCE WITH THIS SPECIFICATION AND APPLICABLE �RAWINGS. ANY
�EVIATIONS SHALL BE CLFARLY DEFINED AND ITEMRED IN ACCORDANCE WITH
SECTION 10.F OF THIS SPECIFICATION.
C. THIS CONTRACTOR IS INSTRUCTE� TO READ CARENLLY THE SPECIFICATIONS
FOR ALL PAR7S OF THE WORK, WHICH INCW�E THE ARCHITECTURAL,
ELECTRICAL, MECHANICAL, PWMBING, FIRE PROTECTION, CIVIL, STRUCTURAL
AND ALL OTHER �RAWINGS AS WELL AS THE SPECIFlCATIONS FOR ALL THE
�IVISIONS THAT ARE PART OF THE CONTRACT DOCUMENTS.
�. ALL ITEMS OF UBOR, MATERIAL, AND EQUIPMENT NOT SPECIFICALLY
MENTIONE� HEREIN OR SHOWN ON PLAN, BUT INCIDENTAL T0, OR REQUIRE�
FOR THE COMPLEfE INSTALUTION ANO PROPER OPERATION OF THE WORK,
SHALL BE FURNISHE� AS IF CALLED FOR IN �EfAIL BY THE SPECIFlCATIONS
OR DRAWINGS.
E. AS USED IN THIS SPECIFICATION, "PROVI�E" MEANS "FURNISH AND INSTALC'.
"FURNISH' MEANS "TO PURCHASE AND �ELNER TO THE PRQIECT SITE
COMPLEfE WITH EVERY NECESSARY APPURTENANCE AN� SUPPORT; AN�
"INSTALC MEANS "TO UNLOAD AT THE �ELNERY POINT AT THE SITE AN�
PERFORM EVERY OPERATION NECESSARY FOR PROPER INSTALLATION PER
CO�ES AND MANUFACTURERS REQUIREMENTS, TO ESTABLISH SECURE
MOUNTING AN� CORRECT OPERATION AT THE PROPER LOCATION IN THE
PROJECT'
2 PERMITS, CO�ES, INSPECTIONS AND TES7S
A. THE HVAC CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AN�
INSPECTIONS REQUIRED FOR THE PROSECUTION OF HVAC WORK. ALL
PERMITS AN� CERTIFICATES OF INSPECTION AN� APPROVAL SIGNE� BY THE
CONTROLLING BUILDING DEPARTMENT SHALL BECOME PROPERiY OF THE
OWNER
B. �RAWINGS INDICATE THE MINIMUM �ESIGN REQUIREMENTS. NATIONAL, STATE,
AND LOCAL CODES SHALL BE FOLLOWE�, COMPLY WITH THE IATEST E�ITIONS
OF THE STATE MECHANICAL CO�E, NFPA, SMACNA, AND ASHRAE STAN�ARDS.
THE WNTRACTOR SHALL INCLU�E THE COST OF SATISFYING SUCH CO�ES
AND STANDAR�S IN THE BID.
C. FOLLOWING COMPLEfION OF THE HVAC WORK, FURNISH TO THE OWNER, IN
�UPLICATE, CERTIFICATES OF INSPECTION AN� APPROVAL BY REGUTATORY
AGENCIES HAVING JURISDICTION.
(1) �EMONSTRATE TO THE OWNER'S SATISFACTION THE PROPER OPERATION
OF EACH OF 7HE SYSTEMS COMPRISING THIS COMRACT BEFORE FlNAL
PAYMENT.
(2) IIAMEDIATELY CORRECT ANY WORK FOUND AT VARIANCE WITH THESE
SPEQFlCATIONS, THE NATIONAL, STATE, AND LOCAL WDES, AND
REQUIREMENTS OF GOVERNING REGUU+TORY AGENCIES.
(3) TEST PIPING FOR LEAKS: REPAIR LEAKS IN COPPER TUBING BY
SWEATING OUT JOINT; THOROUGHLY CLEANING BOTH TUBE AND FITfING,
AND RESOLDERING. CORRECT LEAKS IN SCREWED JOINT BY REPLACING
THREAD OR FITfING OR BOTH.
(4) PROVIOE SERNCES OF A CERTIFIEO A.A.B.C. OR N.E.E.B. TEST AGENCY.
CONOUCT ALL TESTS IN ACCORDANCE WITH ASSOCIATE� AIR BAIANCE
COUNCIL STANDAR�S. IEST AN� A�JUST AIR HAN�LING SYSTEM TO
WITHIN 59 OF �ESIGN REQUIREMENTS.
3. VISIT TO THE SIiE
A. THE CONTRACTOR SHALL NSIT THE SITE OF THE WORK AN� BECOME FAMWAR
WITH ALL CON�ITIONS AFFECTING THE WORK. THE SUBMISSION OF A
PROPOSAL SHALL PRESUPPOSE KNOWLE�GE OF ALL SUCH CON�ITIONS AN�
NO AD�ITIONAL COMPENSAiION SHALL BE ALLOWE� WHERE EX�RA LABOR OR
MATERIALS ARE REQUIRE� BECAUSE OF IGNORANCE OF THESE WNDIiIONS..
4.PROTECTION
A. THE HVAC CONTRACTOR SHALL PROVIDE ALL NECESSARY PROTECiION FROM
�IRT AN� WATER DURING WNSTRUCTION NECESSITATEO BY HVAC WORK.
PROTECTION MEfHO�S ARE SUBJECT TO APPROVAL BY THE ARCHITECT.
S.EQUIPMENT AND MAiERIALS
A. ALL EQUIPMENT AN� MATERIALS SHALL BE NEW AND SHALL CONFORM TO
UNDERWRRERS' LABORATORIES STANDARDS, WHERE APPLICABLE WHERE
SPEQFlCATIONS DESCRIBE, OR PlANS SHOW, MATERIALS OR EOUIPIAENT OF
HIGHER QUALIN THAN REQUIRED BY CODE AND LOCAL RULMG, THE
DRAWINGS AND SPEQFlCATIONS SHALL GOVERN THE �UALIiY OF THE
IAATERIAL OR E�UIPMENT. 11$_F�EOUIPMENT fLR IAATERIALS A�_PROHIBRED
UNLESS NOTED OTHERWISE.
B. NEW OR ENISTING TO REIAAW EQUIPMENT SHALL NOT BE OPERATED DURING
CONSTRUCTION. HVAC CONTRACTOR SHALL COORDINATE WITH OTHER TRADES
AND PROVIDE TEMPORARY SPACE CONDITIONING IN ORDER TO IAAINTAIN
TEMPERATURES AND HUTAIDIN LEVELS AS RE�UIRED FOR GENERAL
CONSTRUCTION.
C. THE CONTRACTOR $HALL SUBMIT PROOF, IF REOUESiED BY THE OWNER,
THAT THE IAATERIALS, APPLIANCES, E�UIPA�ENT OR DEVICES FURMSHED AND
INSTALLED UNDER THIS CONTRACT MEEi THE REQUIREA�ENTS OF THE
UNDERWRITERS' U+BORATORIES, INC. IN REGARDS TO FIRE AND CASUALtt
HAZAR�S. THE IABEL OF OR LISTING BY THE UNOERWRITERS� LABORATORIES,
INC. WILL BE ACCEPTED AS WNFORMING TO THIS REQUIREMENT. W LIEU OF
THE LABEL OR LISTING, THE WNTRACTOR MAY SUBMIT INDEPENDENT PROOF
SATISFACTORY TO THE ARCHITECT THAT THE MATERIAL, APPLIANCES OR
�EVICES CONFORM TO THE PUBLISHE� STAN�AR�S, INCWDING MEfHO�S OF
TEST FOR THE UNDERWRIiERS' LABORATORIES INCORPORATED. UN�ERWRITERS
UBORATORIES, INC. ANO ITS PUBLICATIONS WILL BE REFERRED TO
HEREINAfTER BY THE ABBREVIATION 11L WITH OR WITHOUT AD�ITIONAL
IDENTIfYING SYMBOLS.
6.GUARANTEE
A. THE HVAC CONTRACTOR SHALL GUARANTEE FOR A PERIOD OF ONE YEAR
THAT ALL WORK AN� EQUIPMENT WILL REMAW FREE FROIA ALL DEFECTS IN
WORKMANSHIP AND IAATERIALS, AN� THAT IT WILL COMPLY WITH ALL THE
SPECIFlC REOl11REMEMS OF THE SPECIFlCATIONS AND OiHER WNTRACT
�OCOMENTS GOVERNING THE WORK.
B. ALL WORK FOUND BY THE ENGMEER TO BE �EFECTIVE WILL BE REPLACE�
WITH NEW WORK MEEfING ALL THE REOUIREMEMS OF THE CONTRACT. THE
HVAC CONTRACTOR WILL BEAR ALL COSTS OF Sl1PPLYING SUCH NEW, AN�
INSTALLING AN� FlNISHING SAME, AN� WILL fSSUME ALL COSTS FOR
REPUCING OTHER WORN �AMAGED BY THE REMOVAL AN� REPLACEMENT OF
ANY OF THE WORK. iHE HVAC CONTRACTOR WILL BEAR ALL WSTS FOR
fREIGHT, �RAYAGE AND �EMURRAGE, AN� ALL IABOR IN CONNECTION
THEREINITH.
7. CUTfING, PATCHING, FIRESTOPPING AN� PAINTING
A. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR WTfING ALL HOLES
REOUIRED FOR INSTALUTION OF HVAC WORK HOLES SHALL BE COT IN A
NEAT IAANNER SATISFACTORY TO THE ARCHITECT.
B. COMRACTOR SHALL EMPLOY AN BUILOMG OWNER APPROVED ROOFING
COMRACTOR FOR ALL ROOF PENEfRATIONS. ROOF SHALL BE REPAIRED SO
AS NOT TO V01� ROOF WARRANIY.
_.,.,._,... ..___.. __.,_....,,_� .,. �.-�-- �R DAMAGE CAUSED BY THE
RELEA5E0 FOR CONSTRIICTI�N ATioN oF NEw woeK sHnu eE
HOLES SHALL BE NEATLY
Su6jec��ocompliancewithallregula�ions �TERIAL TO MATCH EX6TING
of S�a�e antl Local Codes WALLS SHALL BE SEALE� WITH
um, sTeiP oa sHe�r FiRe
City of Carmel
r
�un��\i lo•rvalM��_
DATE: Qrj�Q�j�2O
�. fIRESTOP SYSTEM (REQUIRE� FIRESTOPPING MATERIALS) SHALL BE
�EiERMWE� BY THE WALL OR FLOOR/CEILING ASSEMBLY AN� PENEfRATION
IYPE AND SHALL BE UL LISTED AN� TESTE� IN ACLbR�ANCE WITH ASTM
E814, FlRE RATING OF THE FlRESTOP SYSTEM SHALL BE EQUIVALENT TO THE
ASSEMBd WHICH IS PENEiRATE�.
E ACCEPTABLE FlRE BARRIER PRO�UCTS'. HILTI 'FS-ONE"NELSON FLAMESEAC'OR
APPROVED EOUAL AS A�ANOFACTURE� BY 3M.
8. CLEANING AND PAINTING
A. CLEAN NEW PIPING AFfER WORK IS COMPLEfE TO REMOVE PIPE DOPE.
LOOSE MILL SCALE, AN� OTHER EX�RANEOOS MATERIALS.
B. TOUCH OP AN� REPAIR ANY �AMAGEO FACTORY RNISHES ON WUIPMENT AN�
MATERIALS FURNISHE�. OTHER PAINTING WILL BE �ONE UN�ER THE PAINTING
oivisioN oF THe sPeciFicnTioNs.
C. ALL EXISTING AIR �ISTRIBUTION �EVICES THAT ARE TO BE REUSE� SHALL BE
CLEANED WITH MIL� SOAP AN� WATER SOWTION AN� THOROUGHLY �RIE�.
�. ALL EXISTING TO REMAIN HVAC SYSTEMS SHALL BE CLEANE� PER CURREM
NATIONAL NR �UCT CLEANING ASSOCIATION GENERAL SPEQFlCATIONS.
9. COOR�INATION AND WNDOCT OF WORN
A. HVAC DRAWWGS ARE DIAGRAMMATIC, INOICATING GENERAL ARRANGEMENT,
APPROHIMATE SIZES, GENERAL LOCATIONS OF EQUIPMENT AN� PIPING.
VERIFY DIMENSIONS W FlELD; ADJUST TO MANUFACTURER'S SHOP DRAWINGS.
DO NOT SCALE DRAWINGS.
B, ALL REQUESTS FOR MFORIAATION SUPPLEIAENTAL TO THE CONSTRUCTION
DOWMENTS SHALL BE SUBA�ITfED IN WRITING TO THE ARCHIiECT FOR
DISTRIBUTION TO THE APPROPRIATE PARtt(S).
C. DRAWINGS AND SPECIFICATIONS ARE TO BE CONSIDERED AS SUPPLEMENTING
EACH OTHER. WORK SPEGFIED BUT NOT SHOWN, OR SHOWN BUT NOT
SPECIFIED, SHALL BE PERFORMED OR FURNISHED AS THOUGH MENTIONED IN
BOTH SPECIFICATIONS AND DRAWINGS.
D. ANY DISCREPANCIES BEIWEEN THE DRAWINGS AND SPECIFICATIONS SHALL BE
BROUGHT TO THE ATfENTION OF THE ARCHITECT AND ENGINEER.
E. ARCHITECTURAL AND STRUCTURAL DRAWINGS SUPERSEDE HVAC DRAWINGS.
DEfERMINE THAT WORK OF THIS DNISION CAN BE ACCOMMODATED WITHIN
SPACES PROVIDED. NOTIFY ARCHITECT OF ANY INTERFERENCE BEFORE
STARTING INSiALLATION.
E DEfERMME SIZES, LOCATIONS FOR CHASES AND OPENINGS NECESSARY FOR
MSTALlATION OF HVAC WORK, COOPERATE WITH OTHER TRADES IN PROVIDING
SLEEVES, INSERTS AND HANGERS.
G. COORDINATE THIS WORK WITH ALL TRADES. ARRANGE OPERATIONS 50 AS
NOT TO DELAY COMPLEfION OF INSTALLATION OF ANY PARTS OF
INTERRELATED WORK 50 THAT CONSTRUCTION MAY PROCEED ON SCHEDULE.
H. COOPERATE WITH ALL TRADES IN PREPARING INTERFERENCE DRAWINGS FOR
AREAS WHERE THERE IS POSSIBLE CONFLICT BEfWEEN TRADES. E%ACT
LOCATION OF PIPES, DUCTS AND EQUIPMENT SHALL BE BASED ON FIELD
MEASUREMENT WITH FINAL ARRANGEMENT DEfERMWED BY INTRA-TRADE
AGREEMENTS SUBJECT TO ARCHRECT'S APPROVAL.
I. ARCHITECT RESERVES THE RIGHT TO MAKE REASONABLE CHANGES IN
IN�ICAiE� LOCATIONS WITHOUT EXiRA COST TO iHE OWNER.
J. ALL WORK SHALL BE INSTALLED IN NEAT AN� WORKMANLIKE MANNER BY
FIRST-ClASS MECHANICS. THE COMRACTOR SHALL PROVIDE A�EOUATE AN�
COMPEfEM SUPERVISION OF THE JOB AS REQIIIRE�.
K. �UC7WORN, PIPING AN� EQUIPMENT SHALL BE ARRANGE� SUBSTANTIALLY AS
IN�ICAiE�. ANY CHANGE RESULTING IN A SAVINGS IN UBOR OR MATERIAL
SHALL BE MA�E ONLY IN ACWR�ANCE WITH A CONTRACT CHANGE OR�ER.
�EVIATIONS SHALL BE MA�E ONLY WHERE NECESSARY TO AV01�
INTERFERENCES AN� ONLY AFTER �RAWINGS SHOWING THE PROPOSE�
�EVIATIONS HAVE BEEN SUBMITfED TO AN� APPROVE� BY THE ARCHITECT.
L COOR�INATE ALL SHUTDOWNS OF ANY HVAC SYSTEM IN A�VANCE WIiH THE
OWNER.
AS-BUILT �RAWINGS
A. AS WORK PROGRESSES, RECOR� ON A SEf OF "AS-BUILP PRINTS ANY
�EVIATIONS FROM �ESIGN DRAWINGS. DELNER THIS SEf TO THE OWNER
BEFORE SUBMITfING REQUEST FOR FlNAL PAYMEM. 7HE 'AS-BUILT" PRINTS
SHALL BE AN ACCl1RATE �EPICTION OF THE PROJECT AS COMPLEfED.
WSl1lATI0N
A. PROVIDE ALL INSUlATION MATERIAL$ QNSUlATION, JACNETS, FlTiING COVERS,
ADHESIVES, CEMENiS, MASTICS, SEALERS AND FIWSHES) WITH A
FIAME-SPREAD INDE% OF 25 OR LE55 AND SMOKE DEVELOPED INDEX OF 50
OR LESS. AS TESTED UN�ER PROCE�URE ASTM E-84 (NFPA 255)
B. ALL INSUlATION SHALL BE INSTALLED OVER CLFAN, DRY SURFACES.
INSUlATION MUST BE ORY AN� M GOOD WNDITION. WEf OR DAMAGE�
INSUlATION IS NOT ACCEPTABLE. NO INSUlATION SHALL BE APPLIE� PRIOR
TO PRESSURE TEST COMPLEfION OF THE RESPECTIVE SYSTEM.
C. ALL INSUlATION SHALL BE CONTINUOUS QNCWDING VAPOR BARRIER)
THROUGH WALL AND CEILING OPENMGS AND SLEEVES. OVERIAP AT SEAMS
PER MANUFACTURER'S RECOMMENDATIONS.
D. ALL MSULATION PRODUCTS SHALL BE APPLIED IN ACCORDANCE WITH
MANUFACTURER'S WRITfEN RECOMMENDATION. THE WORKMANSHIP SHALL BE
FIRST CLASS AND ALL JOINTS SHALL BE MADE TIGHT.
E. INSULATE ALL CONCEALED SUPPLY AIR DUCiWORK WITH 2" THICK
OWENS-CORNING FIBERGUSS DUCT WRAP WITH FOIL FACED ALL-SERVICE
JACKEf.
F. REPAIR EXISTING INSUUTION WHERE REMOVED FOR NEW CONNECTIONS OR
MSUUTION DAMAGED DURING CONSTRUCTION. INSUlATION SHALL BE THE
SAME AS SPEGFIED FOR NEW SERVICE.
G. ALL INSULATION USED AS PLENUM WRAP COVERING FOR COMBUSTIBLE
MATERIALS IN A PLENUM SPACE SHALL BE }M PLENUM PROTECTION SYSTEM
(PP-10�-P), ONE IAYER OF 3M FIRE BARRIER �l1CT WRAP SA, IN
ACCORDANCE WITH UL910 & I1L1887.
H. PROVIOE INTERNAL ACOUSTIC LINING AS FOLLOWS:
(1) INTERNALLY LME THE FIRST TEN FEET OF DUCiWORK DOWNSTREAIA OF
AIR HANDLMG UNITS, VAV TERA�INALS, AND ELSEWHERE INDICATED ON
PLANS.
(2) OMIi LINING IN THE FIRST 2'-0" DOWNSTREAM OF AN ELECTRIC HEATING
COIL AND PROVIDE ExTERNAL INSUlAT10N IN PLACE.
(J) FIBROUS GUSS, COMPLYING WITH THERMAL INSULATION MANUFACTURERS
ASSOCIATION (TIMA) AHC-101.
(4) ASTA� C 7071, iYPE II, WITH COAiED SURFACE EXPOSED i0 AIRSiREAM
TO PREVENT EROSION OF GLA55 FIBERS 1"THICK. 1-1/2 LB. DENSItt.
COATING MATERIAL SHALL BE ANTI-MICROBIAL AND COMPLY WITH NFPA
90A AND 90B.
(5) K-FACTOR EQUAL TO 028 OR BEfTER, AT MEAN TEMPERATURE OF 75
�EG. F.
(6) FIAME SPREAD INDE% SHALL BE 25 OR LE55 AND SMOKE DEVELOPED
INDEX SHALL BE 50 OR LESS, AS TESTED IN ACCORDANCE WITH ASTM C
411.
(7) DUCT LINING ADHESNE SHALL COMPLY WITH ASTM C 916 SPECIFICATIONS
FOR AOHESNES FOR "DUCT THERMAL INSUlATIOMI OUCT LINING
FASTENERS ALL COMPLY WITH SMACNA DUCT CONSTRUCTION STANDARDS,
ARTICLE 5211
(8) ALTERNATE DOCT LINMG MATERIAL - ARMACELL AP ARIAAFLEX SA BLACK
DUCi LMER, 3/4" THICK, MICROBAN ANTI-MICROBIAL PROiECTION.
10.
11.
12. MEiAL DUCiWORK
A. HVAC CONTRACiOR SHALI VERIFY ALL E%ISiING CONDITIONS PRIOR TO
FABRICAiION OF DUCiWORK. ANY CONFLICTS OR IMERFERENCES SHALL BE
BROUGHT TO THE ATfENiION OF THE ENGINEER.
B. GALVANIZED DUCTWORK SHALL BE FABRICATED OF N0.1 PRIME GALVANIZED
SHEEf METAL OF LOCK FORMING QUALIiY.
G SEALING MAiERIALS SHALL BE SUITABLE FOR; USE wITH AIR DISTRIBUTION
DUCIWORK. ACCEPiABLE 1AANUFACiURERS ARE MONOCO INDUSiRIES, 3M, OR
UNRED SHEET MEiAL.
D. PROVIDE ALL DUCiWORK AS INDICAiED ON THE DRAWINGS, MAKING ALL
NECESSARY OFFSEfS (WHEfHER OR NOT SPEQFICALLY INDICTED) AS
REOUIRED TO MEEf THE VARIOUS BUILDING WN�ITIONS DUC7WORK
INSTALlATION SHALL NOT CONFLICT WITH EQUIPMENT OR PIPING.
E. EXPOSE� �UCIWORK SHALL NEATLY INSTALLED, PRIMED, AN� PAINTED.
EXPOSED ROUN� DUCPNORK SHALL BE SPIRAL COORDINATE WITH
ARCHITECTURAL PIANS FOR COLOR SELECTION.
F. ALL OUCT DIMENSIONS LISTED ON PLANS ARE E%TERIOR ANO INCWDE ANY
ALLOWANCE FOR INTERNAL ACOUSTIC LINING.
G. ALL CHANGES IN CROSS SECTION SHALL BE MADE WITHOUT REDUCING THE
�ESIGN ARFA OF THE DUCT OR RAISING THE PRESSURE �ROP PER 1�� FEEf
OF DUCT SHOWN ON OOCUMENTS.
H. NO PIPE OR OTHER OBSTRUCTIONS SHALL PASS THROUGH AIR DUCTS,
UNLESS SPECIFICALLY SHOWN ON PIANS.
I. CAP ALL OPEN ENDS TO �UC7WORK DURING WNS7RUCTION TO PREVENT
ENTRANCE OF DUST, �EBRIS, MOISTURE EfC.
J. INSTALL �UCiWORK RUN ABOVE CEILING AS HIGH AS POSSIBLE 50 AS TO
MAINTAIN DESIGN CEILING HEIGHTS. E%POSE� �UC7WORK SHALL BE
INSTALLED TO PROVI�E MAXIMUM HFA�ROOM OR AT HEIGHT SPECIFIE� ON
PlANS.
K. �UC7WORK SHALL NOT BE HUNG FROM EQUIPMENT, PIPING, CON�UIT, ROOF
�ECKING OR OTHER �UC7WORK.
L ALL �UCiWORK JOINTS AND SEAMS SHALL BE AIR-TIGHT PER SMACNA TABLE
1.1. POORLY MA�E JOINTS, SPLITS, VISIBLE HOLES AT CORNERS, EfC SHALL
BE REWORKED AND REPAIRE�. WHERE E%CESSIVE PULSATING OF DUC7WORK
IS FOUND, AD�ITIONAL STIFFENERS SHALL BE A��ED. ANY CRACKING IN THE
SEALANT THAT IS APPARENT UPON INSPECTION SHALL BE SUFFlCIENT TO
WARRANT REJECTION.
M.IF THE INTERIOR OF SHEEf MEfAL IS EXPOSED TO VIEW THROUGH AIR
�ISTRIBUTION �EVICES IN FINISHE� AREAS OF THE BUIL�ING, IT SHALL BE
COATE� WITH PRIMER ANO A FIAT BIACK FINISH COAT.
N. ALL DUC7WORK SHALL BE SUPPORTED PER SMACNA REQUIREMENTS.
0. RECTANGUTAR �UCiWORK FITfINGS.
(1) BRANCH CONNECTIONS SHALL BE 45 �EGREES EMRY. STRAIGHT TAPS
ARE NOT PERMITiED.
(2) CHANGES IN DIRECTION SHALL BE MADE WITH FULL RADIUS ELBOWS
WITH RADIUS EQUAL TO 1-1/2 TIMES THE HORIZONTAL WIDTH OF THE
DUCT OR WITH SQUARE ELBOWS WITH TURNING VANES. TURNING VANES
SHALL BE DOUBLE THICKNESS ttPE WNARUCTED OF THE SAME
MATERIAL AS THE SURROUNDING �UCiWORK, PER SMACNA
REOUIREMENTS.
P. ROUND DUC7WORK FITfINGS:
(1) BRANCH WNNEC710NS SHALL BE MADE WOH 45 �EGREE ENTRY TEES.
(2) CHANGE IN DIRECTION SHALL BE MADE WITH FULL RADIUS ELBOWS WITH
RADIUS EQUAL i0 1-1/2 iIMES THE DIAIAETER OF THE DUCT.
Q. LOw PRESSURE DUCTWORK SHALL BE CONSiRUCTED PER SMACNA "HVAC
DUCT CONSTRUCTION SiANDARDS'FOR 2 INCH SiATIC PRESSURE, SEAL CLASS
B..
R. HANGERS AND SUPPORTS
(1) PROVI�E GALVANIZED STEEL STRAPS, ALL-THREA� R0� AN� HORIZONTAL
ANGLE SUPPORTS SIZE� PER SMACNA REQUIREMENTS.
(2) �UCT ATfACHMEMS SHALL BE MADE USING SHEH MEfAL SCREWS
COMPATIBLE WITH OUCT MATERIALS.
(J) BUILDING ATTACHMENTS SHALL BE WNCRETE INSERTS OR STRUCTURAL
STEEL FASTENERS APPROPRIATE FOR THE BUILDING MATERIALS. DO NOT
USE POWER ACTIVATE CONCREiE FASiENERS. 'C ttPE MALLEABLE IRON
BEAM CUA�PS ARE ACCEPTABLE ONLY IF USED WITH CARBON 4EEL
RETAMER STRAP.
REXIBLE DUCTWORK
A, TESTED AND CIASSIFlED BY UNDERWRRERS UBORATOPoES ING AS CLA55 I
AIR DUCT AND IABELED IN ACCORDANCE WITH U.L. 181, STANDARD FOR AIR
DUCiS', THE FUTAE SPREAD RATING SHALL BE 25 OR LE55 AND THE SIAOKE
DEVELOPED RATING SHALL BE 50 OR LE55.
B. LMER SHALL BE CONSiRUCTED OF ALUTAINUM FOIL, FIBERGUSS AND
ALUMINRED POLYESTER, MECHANICALLY LOCKED WITHOUT ADHESIVES, HELI%
SHALL BE GALVANIZED STEEL, FORMED AND MECHANICALLY LOCKED i0
FABRIC,
C. WHERE DUCTWORK IS TO BE INSULAiED, REXIBLE DUCiWORK LMER SHALL
BE COVERED BY A FACTORY WRAPPED, 1-1/2"THICK, 3/4POUND DENSItt
FIBERGLASS INSULATION BLANKEf WITH A FIRE REfARDANT REINFORCED
ALUMINUM OUTER JACKEf.
D. MSTALL FLE%IBLE DUCiWORK FULLY EkTENDED, FREE OF SAGS AND KINKS.
MAXIMUM LENGTH OF FLEXIBLE �UC7WORK SHALL BE 3'-P'. FASTEN
FLEXIBLE �UC7WORN TO RIGID �UCiWORK ANO OEVICES WIiH SELF-LOCKING
100 PERCEM NYLON, A�JUSTABLE OIAMEfER CUMPS.
BAIANCING �AMPERS
A. PROVIOE BAUNCING DAMPERS FOR ALL AIR TERMINAL DEVICES (SUCH AS
BUT NOT LIMITED T0, DIFFUSERS, REGISTERS, GRILLES, ETC.) AND BRANCH
DUCIWORK RE�UIRED FOR PROPER BAIANQNG OF SYSTEM.
B. ROUND DAMPERS SHALL BE SINGLE BLADE ttPE CONSiRUCTION, MINIMUM 18
GAUGE GALVANIZED STEEL. PIVOT ROD SHAFf SHALL BE CONTINUOUS.
C. RECTANGUTAR DAMPERS SHALL BE SINGLE BU�E OR MULTIPLE (OPPOSE�
BLADEJ NPE CONSTRUCTION. MAXIMUM BIA�E WI�TH IS 8 INCHES.
D. ALL BALANCING �AMPERS SHALL BE CONSTRUCTED IN ACCORDANCE WITH
SMACNA "HVAC DUCT CONSTRUCTION STANDAR�S"
E FORNISH ALL BALANCING OAMPERS WITH YOONG REGULATOR COMPANY
VALCALOX REGUUTORS WITH HANDLE PERMANENTLY ATfACHED. �AIAPER
HAN�LE POSITION SHALL BE SECURELY LOCKE� IN PIACE BY TIGHTENING OF
A LOCK NIIC WHERE Dl1CiWORK IS EXTERNALLY INSUTATE�, REGULATOR
BASE HEIGHT SHALL ACCOMMO�ATE INSULATION THICKNESS.
F. PROVI�E ALL MANl1AL BALANCING �AIAPERS WHERE INDICATED ON THE
�RAWINGS AN� WHERE NECESSARY TO PROPERLY �ISTRIBUTE AN� BAIANCE
THE AIR.
13.
14.
15. REGISiERS, GRILLES AND DIFFUSERS
A. PROVIDE REGISTERS, GRILLS AN� DIFFUSERS WHERE SHOWN ON iHE
DRAWINGS, OF SIZE ttPE, AND MATERIAL AS INDICATED AND AS REQUIRED
FOR A COMPLEiE INSTALLATION.
B. BORDER lYPES SHALL BE COMPATIBLE WITH THE CEILINGS WHERE iHE
GRILLES AND DIFFUSERS ARE TO BE INSTALLED.
C. ALL GRILLES AND DIFFUSERS SHALL BE FINISHED WITH A FACTORY APPLIED
OFF-WHITE FIN6H UNLE55 NOiED OTHERWISE.
D. REFER TO ARCHITECiURAL REFLECiED CEILING PLANS FOR E%ACT LOCATION
OF GRILLES AND DIFFUSERS.
i6. TESTING, ADJUSiING AND BALANCING
A. THIS CONTRACiOR SHALL SECURE SERVICES OF AN INDEPENDENT A4BC OR
NEEB CERiIFIED TAB COMPANY. iA8 COMPANY SHALL BAUNCE ALL
COMPONENTS TO NO MORE THAN 5% ABOVE AND 5% BELOW DESIGN
REOUIREMENiS. BALANCED POSITIONS ON DAMPERS, VALVES, EiC. SHALL BE
PERMANENTLY MARKED.
B. THE FOLLOWING DEVICES AND EOUIPMENT SHALL BE MEASURED AND
�OCUMENTEO IN THE BALANCE REPORT: AIR DISTRIBUPON (GRILLES,
�IFFUSERS, REGISTERS).
17. PROJECT COMPLEfION
A. UPON COMPLEfION OF PROJECT THIS CONTRACTOR SHALL PROVI�E NEW
FlLTERS WITHIN ALL E%ISTING AN� FAN POWERE� EQUIPMENT.
B. ALL EXISTING AN� NEW FAN POWERE� EOUIPMENT SHALL HAVE THEIR
EX7ERIOR CLEANED WITH A IAIL� SOAP AN� WATER SOW710N ANO
THOROUGHLY �RIED.
C. PROVIOE 3 COPIES OF FlNAL TEST AN� BAIANCE REPORT TO
OWNER/ARCHRECT.
18. WATER SOURCE HEAi PUTAP UNITS
A. DESCRIPTION: PACKAGED WATER-SOURCE HEAT PUMP WITH TEMPERATURE CONTROLS;
FACTORY ASSEMBLED, TESTEQ AND RATED ACCORDING TO ARI-I50-iJ256-1, ETL
LISiED.
B. CABWEi AND CHA5515: PAINTED STEEL CASING WITH THE FOLLOWING FEATURES:
1. ACCE55 PANEL FOR ACCE55 AND MAINTENANCE OF INTERNAL COMPONENTS.
2. KNOCKOUTS FOR ELECTRICAL CONNECTIONS. NO KNOCKOUTS FOR PIPING. WATER
CONNECilONS ARE FLUSH MOUNT WITHOUi REOUIRING BACKUP WRENCH.
3. HORIZONiAL FUT TOP WITH GRILLE AND HINGED CONTROL COVER
4. CABINEf INSUlATION: FOIL FACED, MINIMUM ',� INCH THICK, COMPLYING WITH UL
181.
5. CONDENSATE DRAINAGE: (PVC) PLASTIC DRAIN PAN PITCHED AS REQUIRED IN
ASHRAE fi2 WITH CONDENSATE �RAIN PIPMG PROJECTMG THROUGH UNR CABWEf.
fi. SOUN� ATTENOATION PACKAGE:
a. MINIA�UM 0.598-INCH-THICN COMPRESSOR ENCLOSURE AN� FRONT
PANEL IAINIMOM 0.0977-INCH-THICK FOAM GASKEf AROUND THE
COMPRESSOR AND PERIMEfER OF END PANEL.
b. SOUN� ATTENUATING BIANKEf OVER COMPRESSOR.
C. FAN: DIRECT DRNEN, CENTRIFUGAL, WITH IAULTI-SPEED MOTOR RE9LIEMLY MOONTED
M FAN MLEf.
1. MOTOR: MULTI-SPEED, PERMANENTLY WBRICATED, ECIA MOTOR OR AS SCHEDOLED.
D. WATER CIRCUIT:
1. REFRIGERANT-TO-WATER HEAT EXCHANGERS 25 'F TO 12PF OPERATING
TEA�PERATURE RANGE.
a. INSULATED, EX�EN�ED RANGE COA%IAL HEAT E%CHANGERS WITH COPPER
WATER TUBE WITH ENHANCED HEAT-TRANSFER SURFACES INSIDE A
STEEL SHELL; BOTH SHELL AND TUBE LEAK TESTEO TO 45� P9G ON
REFRIGERANT SIDE AND 40� PSIG ON WATER SIDE FACTORY-MOUNT
HEAT EXCHANGER IN UNIT ON RESILIENT RUBBER VIBRATION ISOIATORS.
E REFRIGERANT-TO-AIR-COILS: COPPER TOBES WITH AWMINUTA FWS, LEAK TESTE� TO
450 PSIG.
F. REFRIGERANT CIRCUIT COMPONENTS:
1. SEALED REFRIGERANT CIRWIT: CHARGE WITH R-410A REFRIGERANT (R-22 IS NOT
ACCEPTABLE).
2 FlLTER-0RYER: FACTORY WSTALLE� TO CLEAN AND �EHYDRATE THE REFRIGERANT
CIRCUIT.
3. CHARGING WNNECTIONS: SERVICE FITTINGS ON SUCTION AND LIQUI� FOR CHARGING
AND TESTING.
4. REVERSING VALVE: PILOT-OPERATEO SLI�ING-iYPE VALVE �ESIGNEO TO BE
FAIL-SAFE IN HFATING POSITION WITH REPIACEABLE MAGNEfIC COIL.
5. COMPRESSOR: DUAL CAPAQ7Y SCROLL COMPRESSOR INSTALLE� ON VIBRATION
ISOLATORS AN� HOUSED IN AN ACOUSTICALLY TREATE� ENCLOSURE WITH
FACTORY-INSTALLED SAFEfIES AS FOLLOWS:
a. DUAL CAPAGN-HEAT PUMP �UiY.
b. AMIRECYCLE TIMER.
c. HIGH-PRESSURE CUTOUT.
d LOW-PRESSURE CUTOUT OR LOSS OF CHARGE SWITCH.
e. INTERNAL THERMAL-OVERLOA� PROTECTION.
L FREEZESTAT TO STOP COMPRESSOR IF WATER-LOOP TEMPERATURE IN
REFRIGERANT-TO-WATER HEAT EXCHANGER FALLS BELOW 25 �EG F.
g. CON�ENSATE OVERFLOW SWITCH TO STOP COMPRESSOR WITH HIGH
CON�ENSATE LEVEL IN CON�ENSATE DRAIN PAN.
6. REFRIGERANT PIPING MATERIALS: ASTM B 743 COPPER TUBE WITH
WROUGHT-COPPER FlTfINGS AND BRAZE� JOINTS.
7. PIPE INSUUTION: REFRIGERANT MINIIAUTA 3/8-MCH-THICK, FLE%IBLE EUSTOMERIC
INSUlATION ON PIPING E%POSED TO AIRFLOW THROUGH THE UNIT. MAXIMUM
25/50 FLAME-SPREAD/SMONE- DEVELOPMENT INDEXES ACCORDING TO ASTM E
84.
8. REFRIGERANT METERING DEVICE: THERMAL E%PANSION VALVE TO ALLOW SPEqFIED
OPERATION WITH ENTERING-WATER TEMPERATURES FROM 25' F TO 120' F.
G. ELECTRIC HEATING COIL: HELI%-WOUND, NICKEL-CHROMIUM WIRE-HEATING ELEMENTS
IN CERAMIC INSULATORS MOUNTED ON STEEL SUPPORTS. ENERGIZE ON CALL FOR
HEATING WHEN ENTERING-WATER-LOOP TEMPERATURE IS LE55 THAN 25 DEG F.
H. FILTERS: DISPOSABLE, PLEATED ttPE, Y' INCH THICK MERV 11.
I. CONTROLS
1. BASIC UNIT CONTROLS: DDC
a. LOW AND HIGH-VOLTAGE PROTECTION.
b. OVER CURRENT PROTECTION FOR COMPRESSOR AND FAN MOTOR.
c RANDOM TIME DELAY, THREE TO TEN SECONDS, START ON POWER UP.
d. TIME DELAY OVERRIDE FOR SERVICING.
e. CONTROL VOLTAGE TRANSFORMER.
2. THERMOSTAT:
a. UNIT-MOUNTED TEMPERATURE SENSOR.
b. LED TO INDICATE FAULT WNDITION AT HEAT PUMP.
c DATA ENTRY AND ACCESS PORT.
1JINPUT DATA INCWDE ROOM TEMPERAIDRE ANO HUMIDIN SEf POIMS FOR
OCWPoE� AND UNOCWPoED PERIODS.
2)OUTPUT DATA INCWDE ROOM TEMPERATURE AND HUMIDItt, SUPPLY-AIR
TEA�PERATURE, ENTERING-WATER TEIAPERATURE, OPERATING MODE, AND
SiATUS.
3. TERMINAL CONiROLLER:
a. REMOTE CONTROL PANEL TO CONTAIN PROGRAMMABLE TIMER AND LED
FOR FAULT CONDITION.
b. COMPRESSOR DISABLE REIAY i0 SiOP COMPRESSOR OPERATION FOR
�EMAND LIMIiING OR SWRCH TO UNOCWPoE� OPERATION.
c. AUTOMATIC RE4ART AFfER RVE MINUiES IF FAULT 0.EAR5. LOCKOUT
ARER THREE ATfElAPTS TO RESiARi FOLLOWING FAULi. INDICAiE
FAULT FOR SERVICE iECHNIqAN.
d. REfURN-AIR TEMPERATURE HIGH-LIMIT (FIRESTAT). STOP UNIT ON HIGH
TEIAPERATURE.
e. BACKUP FOR VOLATILE MEA�ORY.
J. ELECTRICAL WNNECTION: SINGLE ELECTRICAL CONNECiION WITH FUSED DISCONNECi.
�Inregrared
1�En�'meerinp
Consvltants,lnc.
9700 ROCNSIDE RD.SURE290
CLEVELAND.OX 44125
PHONE:21G90L6711
FA%:216A01-6712
NELSOI�
Nelm Architedure, Inc.
a licensed affliate
30 West Monroe Street - Suite 200
Chicago, IL 6060&2409
Phone: (312)263-6605
(312)2]fi-4340
OWNER'S PROJECT MANAGER
Jones Lang LaSalle
Alex Gsneros
540 W. Madison St, Suit eIL9-540-04-55
Chicago, IL 60661
T: 773.502.5562 E: alex.cisneros@am.jlLcom
MEPENGINEER
Integrated Engineering ConsWtants,Inc (IEC)
Tim Vlning
9700 Rockside Road, Suite 290
Cleveland, OH 44125
T. 216.901.67ll E: [im.vining@ieC-inc.cc
GENERALCONTRACTOR
Mid America Contracting, Inc.
Tyler Crawford
107 N. Main Street, Suite 3A
Columbia, [L 62236
T: 618.9779255 E: tic@midamericacontrac[ing.com
ConsWtant'.
MERRILL�
A BANK OF AM ERICA COMPANY
Cllent.
INW-044 BofA Indianapolis MLWM
Expansion & Refresh, 3rd Floor
510 96th Street
Indianapolis, IN 46240
Project TiHe & Nddress:
MECHANICALHVAC
SPECIFICATION SHEET
SheetTiHe�.
;i ,ry
_ ' PE11800595 ,
:�•, •
t �o � STATEOF ; y
=A'. . �.
'- � '.!N�IAN?�'�<+� �
y/����'�S�S/ONA,L) E�G,`��" �S
7 � �"n , �/,��7 "
/ � ,.
Seal: /
Proj. No'. 19.0004J36.000 Designer'. ERO;MBM
�rawn By: ]PH Reviewed By: HHH
Pmjcct Managcr. M]L qppmved By: HHH
M3-1
ALL �IMENSIONS AN� LONDITIONS MOA BE CHECKED AND VERIRED
ON 9TE BY THE CONTRAQOP AND 50B-CONTRAQORS PRIOR TO
PEFFOkMMG THE WOFK. THE PRO]ECT MHNAGEk SHALL RE NOTIFIED IN
wa�nNs oF nrvr o�scaeenmc�es en�oa ra caoceemrve w�rH rHe woae.
c� rve�mry won�owroe, uc zozo nu a�sHTs aFseaveo