HomeMy WebLinkAboutM3-1MECHANICAL SPECIFICATIONS 1. GENERAL PROVISIONS A. THE PROVISIONS OF iHE INSTRUCTIONS TO BIDDERS, GENERAL CONDIilONS, SUPPLEMENTARY WNDITIONS, ALTERNATES, ADDENDA'S', ANO DIVISION 1 ARE A PART OF THIS SPEQFICATION. WNTRACTORS AN� SUBCONTRACTORS SHALL EXAMINE SAME AS WELL AS OTHER DIVISIONS OF THE SPEQFICATIONS WHICH nFrECT woRK uNocR Tws oivisioN. B. THIS CONTRACTOR SHALL PROVI�E ALL IABOR, EQUIPMENT, SUPPLIES, SERVICES, AND SHALL PERFORM ALL WORK COMPLEfE AND IN S�RICT ACCOR�ANCE WITH THIS SPECIFICATION AND APPLICABLE �RAWINGS. ANY �EVIATIONS SHALL BE CLFARLY DEFINED AND ITEMRED IN ACCORDANCE WITH SECTION 10.F OF THIS SPECIFICATION. C. THIS CONTRACTOR IS INSTRUCTE� TO READ CARENLLY THE SPECIFICATIONS FOR ALL PAR7S OF THE WORK, WHICH INCW�E THE ARCHITECTURAL, ELECTRICAL, MECHANICAL, PWMBING, FIRE PROTECTION, CIVIL, STRUCTURAL AND ALL OTHER �RAWINGS AS WELL AS THE SPECIFlCATIONS FOR ALL THE �IVISIONS THAT ARE PART OF THE CONTRACT DOCUMENTS. �. ALL ITEMS OF UBOR, MATERIAL, AND EQUIPMENT NOT SPECIFICALLY MENTIONE� HEREIN OR SHOWN ON PLAN, BUT INCIDENTAL T0, OR REQUIRE� FOR THE COMPLEfE INSTALUTION ANO PROPER OPERATION OF THE WORK, SHALL BE FURNISHE� AS IF CALLED FOR IN �EfAIL BY THE SPECIFlCATIONS OR DRAWINGS. E. AS USED IN THIS SPECIFICATION, "PROVI�E" MEANS "FURNISH AND INSTALC'. "FURNISH' MEANS "TO PURCHASE AND �ELNER TO THE PRQIECT SITE COMPLEfE WITH EVERY NECESSARY APPURTENANCE AN� SUPPORT; AN� "INSTALC MEANS "TO UNLOAD AT THE �ELNERY POINT AT THE SITE AN� PERFORM EVERY OPERATION NECESSARY FOR PROPER INSTALLATION PER CO�ES AND MANUFACTURERS REQUIREMENTS, TO ESTABLISH SECURE MOUNTING AN� CORRECT OPERATION AT THE PROPER LOCATION IN THE PROJECT' 2 PERMITS, CO�ES, INSPECTIONS AND TES7S A. THE HVAC CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AN� INSPECTIONS REQUIRED FOR THE PROSECUTION OF HVAC WORK. ALL PERMITS AN� CERTIFICATES OF INSPECTION AN� APPROVAL SIGNE� BY THE CONTROLLING BUILDING DEPARTMENT SHALL BECOME PROPERiY OF THE OWNER B. �RAWINGS INDICATE THE MINIMUM �ESIGN REQUIREMENTS. NATIONAL, STATE, AND LOCAL CODES SHALL BE FOLLOWE�, COMPLY WITH THE IATEST E�ITIONS OF THE STATE MECHANICAL CO�E, NFPA, SMACNA, AND ASHRAE STAN�ARDS. THE WNTRACTOR SHALL INCLU�E THE COST OF SATISFYING SUCH CO�ES AND STANDAR�S IN THE BID. C. FOLLOWING COMPLEfION OF THE HVAC WORK, FURNISH TO THE OWNER, IN �UPLICATE, CERTIFICATES OF INSPECTION AN� APPROVAL BY REGUTATORY AGENCIES HAVING JURISDICTION. (1) �EMONSTRATE TO THE OWNER'S SATISFACTION THE PROPER OPERATION OF EACH OF 7HE SYSTEMS COMPRISING THIS COMRACT BEFORE FlNAL PAYMENT. (2) IIAMEDIATELY CORRECT ANY WORK FOUND AT VARIANCE WITH THESE SPEQFlCATIONS, THE NATIONAL, STATE, AND LOCAL WDES, AND REQUIREMENTS OF GOVERNING REGUU+TORY AGENCIES. (3) TEST PIPING FOR LEAKS: REPAIR LEAKS IN COPPER TUBING BY SWEATING OUT JOINT; THOROUGHLY CLEANING BOTH TUBE AND FITfING, AND RESOLDERING. CORRECT LEAKS IN SCREWED JOINT BY REPLACING THREAD OR FITfING OR BOTH. (4) PROVIOE SERNCES OF A CERTIFIEO A.A.B.C. OR N.E.E.B. TEST AGENCY. CONOUCT ALL TESTS IN ACCORDANCE WITH ASSOCIATE� AIR BAIANCE COUNCIL STANDAR�S. IEST AN� A�JUST AIR HAN�LING SYSTEM TO WITHIN 59 OF �ESIGN REQUIREMENTS. 3. VISIT TO THE SIiE A. THE CONTRACTOR SHALL NSIT THE SITE OF THE WORK AN� BECOME FAMWAR WITH ALL CON�ITIONS AFFECTING THE WORK. THE SUBMISSION OF A PROPOSAL SHALL PRESUPPOSE KNOWLE�GE OF ALL SUCH CON�ITIONS AN� NO AD�ITIONAL COMPENSAiION SHALL BE ALLOWE� WHERE EX�RA LABOR OR MATERIALS ARE REQUIRE� BECAUSE OF IGNORANCE OF THESE WNDIiIONS.. 4.PROTECTION A. THE HVAC CONTRACTOR SHALL PROVIDE ALL NECESSARY PROTECiION FROM �IRT AN� WATER DURING WNSTRUCTION NECESSITATEO BY HVAC WORK. PROTECTION MEfHO�S ARE SUBJECT TO APPROVAL BY THE ARCHITECT. S.EQUIPMENT AND MAiERIALS A. ALL EQUIPMENT AN� MATERIALS SHALL BE NEW AND SHALL CONFORM TO UNDERWRRERS' LABORATORIES STANDARDS, WHERE APPLICABLE WHERE SPEQFlCATIONS DESCRIBE, OR PlANS SHOW, MATERIALS OR EOUIPIAENT OF HIGHER QUALIN THAN REQUIRED BY CODE AND LOCAL RULMG, THE DRAWINGS AND SPEQFlCATIONS SHALL GOVERN THE �UALIiY OF THE IAATERIAL OR E�UIPMENT. 11$_F�EOUIPMENT fLR IAATERIALS A�_PROHIBRED UNLESS NOTED OTHERWISE. B. NEW OR ENISTING TO REIAAW EQUIPMENT SHALL NOT BE OPERATED DURING CONSTRUCTION. HVAC CONTRACTOR SHALL COORDINATE WITH OTHER TRADES AND PROVIDE TEMPORARY SPACE CONDITIONING IN ORDER TO IAAINTAIN TEMPERATURES AND HUTAIDIN LEVELS AS RE�UIRED FOR GENERAL CONSTRUCTION. C. THE CONTRACTOR $HALL SUBMIT PROOF, IF REOUESiED BY THE OWNER, THAT THE IAATERIALS, APPLIANCES, E�UIPA�ENT OR DEVICES FURMSHED AND INSTALLED UNDER THIS CONTRACT MEEi THE REQUIREA�ENTS OF THE UNDERWRITERS' U+BORATORIES, INC. IN REGARDS TO FIRE AND CASUALtt HAZAR�S. THE IABEL OF OR LISTING BY THE UNOERWRITERS� LABORATORIES, INC. WILL BE ACCEPTED AS WNFORMING TO THIS REQUIREMENT. W LIEU OF THE LABEL OR LISTING, THE WNTRACTOR MAY SUBMIT INDEPENDENT PROOF SATISFACTORY TO THE ARCHITECT THAT THE MATERIAL, APPLIANCES OR �EVICES CONFORM TO THE PUBLISHE� STAN�AR�S, INCWDING MEfHO�S OF TEST FOR THE UNDERWRIiERS' LABORATORIES INCORPORATED. UN�ERWRITERS UBORATORIES, INC. ANO ITS PUBLICATIONS WILL BE REFERRED TO HEREINAfTER BY THE ABBREVIATION 11L WITH OR WITHOUT AD�ITIONAL IDENTIfYING SYMBOLS. 6.GUARANTEE A. THE HVAC CONTRACTOR SHALL GUARANTEE FOR A PERIOD OF ONE YEAR THAT ALL WORK AN� EQUIPMENT WILL REMAW FREE FROIA ALL DEFECTS IN WORKMANSHIP AND IAATERIALS, AN� THAT IT WILL COMPLY WITH ALL THE SPECIFlC REOl11REMEMS OF THE SPECIFlCATIONS AND OiHER WNTRACT �OCOMENTS GOVERNING THE WORK. B. ALL WORK FOUND BY THE ENGMEER TO BE �EFECTIVE WILL BE REPLACE� WITH NEW WORK MEEfING ALL THE REOUIREMEMS OF THE CONTRACT. THE HVAC CONTRACTOR WILL BEAR ALL COSTS OF Sl1PPLYING SUCH NEW, AN� INSTALLING AN� FlNISHING SAME, AN� WILL fSSUME ALL COSTS FOR REPUCING OTHER WORN �AMAGED BY THE REMOVAL AN� REPLACEMENT OF ANY OF THE WORK. iHE HVAC CONTRACTOR WILL BEAR ALL WSTS FOR fREIGHT, �RAYAGE AND �EMURRAGE, AN� ALL IABOR IN CONNECTION THEREINITH. 7. CUTfING, PATCHING, FIRESTOPPING AN� PAINTING A. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR WTfING ALL HOLES REOUIRED FOR INSTALUTION OF HVAC WORK HOLES SHALL BE COT IN A NEAT IAANNER SATISFACTORY TO THE ARCHITECT. B. COMRACTOR SHALL EMPLOY AN BUILOMG OWNER APPROVED ROOFING COMRACTOR FOR ALL ROOF PENEfRATIONS. ROOF SHALL BE REPAIRED SO AS NOT TO V01� ROOF WARRANIY. _.,.,._,... ..___.. __.,_....,,_� .,. �.-�-- �R DAMAGE CAUSED BY THE RELEA5E0 FOR CONSTRIICTI�N ATioN oF NEw woeK sHnu eE HOLES SHALL BE NEATLY Su6jec��ocompliancewithallregula�ions �TERIAL TO MATCH EX6TING of S�a�e antl Local Codes WALLS SHALL BE SEALE� WITH um, sTeiP oa sHe�r FiRe City of Carmel r �un��\i lo•rvalM��_ DATE: Qrj�Q�j�2O �. fIRESTOP SYSTEM (REQUIRE� FIRESTOPPING MATERIALS) SHALL BE �EiERMWE� BY THE WALL OR FLOOR/CEILING ASSEMBLY AN� PENEfRATION IYPE AND SHALL BE UL LISTED AN� TESTE� IN ACLbR�ANCE WITH ASTM E814, FlRE RATING OF THE FlRESTOP SYSTEM SHALL BE EQUIVALENT TO THE ASSEMBd WHICH IS PENEiRATE�. E ACCEPTABLE FlRE BARRIER PRO�UCTS'. HILTI 'FS-ONE"NELSON FLAMESEAC'OR APPROVED EOUAL AS A�ANOFACTURE� BY 3M. 8. CLEANING AND PAINTING A. CLEAN NEW PIPING AFfER WORK IS COMPLEfE TO REMOVE PIPE DOPE. LOOSE MILL SCALE, AN� OTHER EX�RANEOOS MATERIALS. B. TOUCH OP AN� REPAIR ANY �AMAGEO FACTORY RNISHES ON WUIPMENT AN� MATERIALS FURNISHE�. OTHER PAINTING WILL BE �ONE UN�ER THE PAINTING oivisioN oF THe sPeciFicnTioNs. C. ALL EXISTING AIR �ISTRIBUTION �EVICES THAT ARE TO BE REUSE� SHALL BE CLEANED WITH MIL� SOAP AN� WATER SOWTION AN� THOROUGHLY �RIE�. �. ALL EXISTING TO REMAIN HVAC SYSTEMS SHALL BE CLEANE� PER CURREM NATIONAL NR �UCT CLEANING ASSOCIATION GENERAL SPEQFlCATIONS. 9. COOR�INATION AND WNDOCT OF WORN A. HVAC DRAWWGS ARE DIAGRAMMATIC, INOICATING GENERAL ARRANGEMENT, APPROHIMATE SIZES, GENERAL LOCATIONS OF EQUIPMENT AN� PIPING. VERIFY DIMENSIONS W FlELD; ADJUST TO MANUFACTURER'S SHOP DRAWINGS. DO NOT SCALE DRAWINGS. B, ALL REQUESTS FOR MFORIAATION SUPPLEIAENTAL TO THE CONSTRUCTION DOWMENTS SHALL BE SUBA�ITfED IN WRITING TO THE ARCHIiECT FOR DISTRIBUTION TO THE APPROPRIATE PARtt(S). C. DRAWINGS AND SPECIFICATIONS ARE TO BE CONSIDERED AS SUPPLEMENTING EACH OTHER. WORK SPEGFIED BUT NOT SHOWN, OR SHOWN BUT NOT SPECIFIED, SHALL BE PERFORMED OR FURNISHED AS THOUGH MENTIONED IN BOTH SPECIFICATIONS AND DRAWINGS. D. ANY DISCREPANCIES BEIWEEN THE DRAWINGS AND SPECIFICATIONS SHALL BE BROUGHT TO THE ATfENTION OF THE ARCHITECT AND ENGINEER. E. ARCHITECTURAL AND STRUCTURAL DRAWINGS SUPERSEDE HVAC DRAWINGS. DEfERMINE THAT WORK OF THIS DNISION CAN BE ACCOMMODATED WITHIN SPACES PROVIDED. NOTIFY ARCHITECT OF ANY INTERFERENCE BEFORE STARTING INSiALLATION. E DEfERMME SIZES, LOCATIONS FOR CHASES AND OPENINGS NECESSARY FOR MSTALlATION OF HVAC WORK, COOPERATE WITH OTHER TRADES IN PROVIDING SLEEVES, INSERTS AND HANGERS. G. COORDINATE THIS WORK WITH ALL TRADES. ARRANGE OPERATIONS 50 AS NOT TO DELAY COMPLEfION OF INSTALLATION OF ANY PARTS OF INTERRELATED WORK 50 THAT CONSTRUCTION MAY PROCEED ON SCHEDULE. H. COOPERATE WITH ALL TRADES IN PREPARING INTERFERENCE DRAWINGS FOR AREAS WHERE THERE IS POSSIBLE CONFLICT BEfWEEN TRADES. E%ACT LOCATION OF PIPES, DUCTS AND EQUIPMENT SHALL BE BASED ON FIELD MEASUREMENT WITH FINAL ARRANGEMENT DEfERMWED BY INTRA-TRADE AGREEMENTS SUBJECT TO ARCHRECT'S APPROVAL. I. ARCHITECT RESERVES THE RIGHT TO MAKE REASONABLE CHANGES IN IN�ICAiE� LOCATIONS WITHOUT EXiRA COST TO iHE OWNER. J. ALL WORK SHALL BE INSTALLED IN NEAT AN� WORKMANLIKE MANNER BY FIRST-ClASS MECHANICS. THE COMRACTOR SHALL PROVIDE A�EOUATE AN� COMPEfEM SUPERVISION OF THE JOB AS REQIIIRE�. K. �UC7WORN, PIPING AN� EQUIPMENT SHALL BE ARRANGE� SUBSTANTIALLY AS IN�ICAiE�. ANY CHANGE RESULTING IN A SAVINGS IN UBOR OR MATERIAL SHALL BE MA�E ONLY IN ACWR�ANCE WITH A CONTRACT CHANGE OR�ER. �EVIATIONS SHALL BE MA�E ONLY WHERE NECESSARY TO AV01� INTERFERENCES AN� ONLY AFTER �RAWINGS SHOWING THE PROPOSE� �EVIATIONS HAVE BEEN SUBMITfED TO AN� APPROVE� BY THE ARCHITECT. L COOR�INATE ALL SHUTDOWNS OF ANY HVAC SYSTEM IN A�VANCE WIiH THE OWNER. AS-BUILT �RAWINGS A. AS WORK PROGRESSES, RECOR� ON A SEf OF "AS-BUILP PRINTS ANY �EVIATIONS FROM �ESIGN DRAWINGS. DELNER THIS SEf TO THE OWNER BEFORE SUBMITfING REQUEST FOR FlNAL PAYMEM. 7HE 'AS-BUILT" PRINTS SHALL BE AN ACCl1RATE �EPICTION OF THE PROJECT AS COMPLEfED. WSl1lATI0N A. PROVIDE ALL INSUlATION MATERIAL$ QNSUlATION, JACNETS, FlTiING COVERS, ADHESIVES, CEMENiS, MASTICS, SEALERS AND FIWSHES) WITH A FIAME-SPREAD INDE% OF 25 OR LE55 AND SMOKE DEVELOPED INDEX OF 50 OR LESS. AS TESTED UN�ER PROCE�URE ASTM E-84 (NFPA 255) B. ALL INSUlATION SHALL BE INSTALLED OVER CLFAN, DRY SURFACES. INSUlATION MUST BE ORY AN� M GOOD WNDITION. WEf OR DAMAGE� INSUlATION IS NOT ACCEPTABLE. NO INSUlATION SHALL BE APPLIE� PRIOR TO PRESSURE TEST COMPLEfION OF THE RESPECTIVE SYSTEM. C. ALL INSUlATION SHALL BE CONTINUOUS QNCWDING VAPOR BARRIER) THROUGH WALL AND CEILING OPENMGS AND SLEEVES. OVERIAP AT SEAMS PER MANUFACTURER'S RECOMMENDATIONS. D. ALL MSULATION PRODUCTS SHALL BE APPLIED IN ACCORDANCE WITH MANUFACTURER'S WRITfEN RECOMMENDATION. THE WORKMANSHIP SHALL BE FIRST CLASS AND ALL JOINTS SHALL BE MADE TIGHT. E. INSULATE ALL CONCEALED SUPPLY AIR DUCiWORK WITH 2" THICK OWENS-CORNING FIBERGUSS DUCT WRAP WITH FOIL FACED ALL-SERVICE JACKEf. F. REPAIR EXISTING INSUUTION WHERE REMOVED FOR NEW CONNECTIONS OR MSUUTION DAMAGED DURING CONSTRUCTION. INSUlATION SHALL BE THE SAME AS SPEGFIED FOR NEW SERVICE. G. ALL INSULATION USED AS PLENUM WRAP COVERING FOR COMBUSTIBLE MATERIALS IN A PLENUM SPACE SHALL BE }M PLENUM PROTECTION SYSTEM (PP-10�-P), ONE IAYER OF 3M FIRE BARRIER �l1CT WRAP SA, IN ACCORDANCE WITH UL910 & I1L1887. H. PROVIOE INTERNAL ACOUSTIC LINING AS FOLLOWS: (1) INTERNALLY LME THE FIRST TEN FEET OF DUCiWORK DOWNSTREAIA OF AIR HANDLMG UNITS, VAV TERA�INALS, AND ELSEWHERE INDICATED ON PLANS. (2) OMIi LINING IN THE FIRST 2'-0" DOWNSTREAM OF AN ELECTRIC HEATING COIL AND PROVIDE ExTERNAL INSUlAT10N IN PLACE. (J) FIBROUS GUSS, COMPLYING WITH THERMAL INSULATION MANUFACTURERS ASSOCIATION (TIMA) AHC-101. (4) ASTA� C 7071, iYPE II, WITH COAiED SURFACE EXPOSED i0 AIRSiREAM TO PREVENT EROSION OF GLA55 FIBERS 1"THICK. 1-1/2 LB. DENSItt. COATING MATERIAL SHALL BE ANTI-MICROBIAL AND COMPLY WITH NFPA 90A AND 90B. (5) K-FACTOR EQUAL TO 028 OR BEfTER, AT MEAN TEMPERATURE OF 75 �EG. F. (6) FIAME SPREAD INDE% SHALL BE 25 OR LE55 AND SMOKE DEVELOPED INDEX SHALL BE 50 OR LESS, AS TESTED IN ACCORDANCE WITH ASTM C 411. (7) DUCT LINING ADHESNE SHALL COMPLY WITH ASTM C 916 SPECIFICATIONS FOR AOHESNES FOR "DUCT THERMAL INSUlATIOMI OUCT LINING FASTENERS ALL COMPLY WITH SMACNA DUCT CONSTRUCTION STANDARDS, ARTICLE 5211 (8) ALTERNATE DOCT LINMG MATERIAL - ARMACELL AP ARIAAFLEX SA BLACK DUCi LMER, 3/4" THICK, MICROBAN ANTI-MICROBIAL PROiECTION. 10. 11. 12. MEiAL DUCiWORK A. HVAC CONTRACiOR SHALI VERIFY ALL E%ISiING CONDITIONS PRIOR TO FABRICAiION OF DUCiWORK. ANY CONFLICTS OR IMERFERENCES SHALL BE BROUGHT TO THE ATfENiION OF THE ENGINEER. B. GALVANIZED DUCTWORK SHALL BE FABRICATED OF N0.1 PRIME GALVANIZED SHEEf METAL OF LOCK FORMING QUALIiY. G SEALING MAiERIALS SHALL BE SUITABLE FOR; USE wITH AIR DISTRIBUTION DUCIWORK. ACCEPiABLE 1AANUFACiURERS ARE MONOCO INDUSiRIES, 3M, OR UNRED SHEET MEiAL. D. PROVIDE ALL DUCiWORK AS INDICAiED ON THE DRAWINGS, MAKING ALL NECESSARY OFFSEfS (WHEfHER OR NOT SPEQFICALLY INDICTED) AS REOUIRED TO MEEf THE VARIOUS BUILDING WN�ITIONS DUC7WORK INSTALlATION SHALL NOT CONFLICT WITH EQUIPMENT OR PIPING. E. EXPOSE� �UCIWORK SHALL NEATLY INSTALLED, PRIMED, AN� PAINTED. EXPOSED ROUN� DUCPNORK SHALL BE SPIRAL COORDINATE WITH ARCHITECTURAL PIANS FOR COLOR SELECTION. F. ALL OUCT DIMENSIONS LISTED ON PLANS ARE E%TERIOR ANO INCWDE ANY ALLOWANCE FOR INTERNAL ACOUSTIC LINING. G. ALL CHANGES IN CROSS SECTION SHALL BE MADE WITHOUT REDUCING THE �ESIGN ARFA OF THE DUCT OR RAISING THE PRESSURE �ROP PER 1�� FEEf OF DUCT SHOWN ON OOCUMENTS. H. NO PIPE OR OTHER OBSTRUCTIONS SHALL PASS THROUGH AIR DUCTS, UNLESS SPECIFICALLY SHOWN ON PIANS. I. CAP ALL OPEN ENDS TO �UC7WORK DURING WNS7RUCTION TO PREVENT ENTRANCE OF DUST, �EBRIS, MOISTURE EfC. J. INSTALL �UCiWORK RUN ABOVE CEILING AS HIGH AS POSSIBLE 50 AS TO MAINTAIN DESIGN CEILING HEIGHTS. E%POSE� �UC7WORK SHALL BE INSTALLED TO PROVI�E MAXIMUM HFA�ROOM OR AT HEIGHT SPECIFIE� ON PlANS. K. �UC7WORK SHALL NOT BE HUNG FROM EQUIPMENT, PIPING, CON�UIT, ROOF �ECKING OR OTHER �UC7WORK. L ALL �UCiWORK JOINTS AND SEAMS SHALL BE AIR-TIGHT PER SMACNA TABLE 1.1. POORLY MA�E JOINTS, SPLITS, VISIBLE HOLES AT CORNERS, EfC SHALL BE REWORKED AND REPAIRE�. WHERE E%CESSIVE PULSATING OF DUC7WORK IS FOUND, AD�ITIONAL STIFFENERS SHALL BE A��ED. ANY CRACKING IN THE SEALANT THAT IS APPARENT UPON INSPECTION SHALL BE SUFFlCIENT TO WARRANT REJECTION. M.IF THE INTERIOR OF SHEEf MEfAL IS EXPOSED TO VIEW THROUGH AIR �ISTRIBUTION �EVICES IN FINISHE� AREAS OF THE BUIL�ING, IT SHALL BE COATE� WITH PRIMER ANO A FIAT BIACK FINISH COAT. N. ALL DUC7WORK SHALL BE SUPPORTED PER SMACNA REQUIREMENTS. 0. RECTANGUTAR �UCiWORK FITfINGS. (1) BRANCH CONNECTIONS SHALL BE 45 �EGREES EMRY. STRAIGHT TAPS ARE NOT PERMITiED. (2) CHANGES IN DIRECTION SHALL BE MADE WITH FULL RADIUS ELBOWS WITH RADIUS EQUAL TO 1-1/2 TIMES THE HORIZONTAL WIDTH OF THE DUCT OR WITH SQUARE ELBOWS WITH TURNING VANES. TURNING VANES SHALL BE DOUBLE THICKNESS ttPE WNARUCTED OF THE SAME MATERIAL AS THE SURROUNDING �UCiWORK, PER SMACNA REOUIREMENTS. P. ROUND DUC7WORK FITfINGS: (1) BRANCH WNNEC710NS SHALL BE MADE WOH 45 �EGREE ENTRY TEES. (2) CHANGE IN DIRECTION SHALL BE MADE WITH FULL RADIUS ELBOWS WITH RADIUS EQUAL i0 1-1/2 iIMES THE DIAIAETER OF THE DUCT. Q. LOw PRESSURE DUCTWORK SHALL BE CONSiRUCTED PER SMACNA "HVAC DUCT CONSTRUCTION SiANDARDS'FOR 2 INCH SiATIC PRESSURE, SEAL CLASS B.. R. HANGERS AND SUPPORTS (1) PROVI�E GALVANIZED STEEL STRAPS, ALL-THREA� R0� AN� HORIZONTAL ANGLE SUPPORTS SIZE� PER SMACNA REQUIREMENTS. (2) �UCT ATfACHMEMS SHALL BE MADE USING SHEH MEfAL SCREWS COMPATIBLE WITH OUCT MATERIALS. (J) BUILDING ATTACHMENTS SHALL BE WNCRETE INSERTS OR STRUCTURAL STEEL FASTENERS APPROPRIATE FOR THE BUILDING MATERIALS. DO NOT USE POWER ACTIVATE CONCREiE FASiENERS. 'C ttPE MALLEABLE IRON BEAM CUA�PS ARE ACCEPTABLE ONLY IF USED WITH CARBON 4EEL RETAMER STRAP. REXIBLE DUCTWORK A, TESTED AND CIASSIFlED BY UNDERWRRERS UBORATOPoES ING AS CLA55 I AIR DUCT AND IABELED IN ACCORDANCE WITH U.L. 181, STANDARD FOR AIR DUCiS', THE FUTAE SPREAD RATING SHALL BE 25 OR LE55 AND THE SIAOKE DEVELOPED RATING SHALL BE 50 OR LE55. B. LMER SHALL BE CONSiRUCTED OF ALUTAINUM FOIL, FIBERGUSS AND ALUMINRED POLYESTER, MECHANICALLY LOCKED WITHOUT ADHESIVES, HELI% SHALL BE GALVANIZED STEEL, FORMED AND MECHANICALLY LOCKED i0 FABRIC, C. WHERE DUCTWORK IS TO BE INSULAiED, REXIBLE DUCiWORK LMER SHALL BE COVERED BY A FACTORY WRAPPED, 1-1/2"THICK, 3/4POUND DENSItt FIBERGLASS INSULATION BLANKEf WITH A FIRE REfARDANT REINFORCED ALUMINUM OUTER JACKEf. D. MSTALL FLE%IBLE DUCiWORK FULLY EkTENDED, FREE OF SAGS AND KINKS. MAXIMUM LENGTH OF FLEXIBLE �UC7WORK SHALL BE 3'-P'. FASTEN FLEXIBLE �UC7WORN TO RIGID �UCiWORK ANO OEVICES WIiH SELF-LOCKING 100 PERCEM NYLON, A�JUSTABLE OIAMEfER CUMPS. BAIANCING �AMPERS A. PROVIOE BAUNCING DAMPERS FOR ALL AIR TERMINAL DEVICES (SUCH AS BUT NOT LIMITED T0, DIFFUSERS, REGISTERS, GRILLES, ETC.) AND BRANCH DUCIWORK RE�UIRED FOR PROPER BAIANQNG OF SYSTEM. B. ROUND DAMPERS SHALL BE SINGLE BLADE ttPE CONSiRUCTION, MINIMUM 18 GAUGE GALVANIZED STEEL. PIVOT ROD SHAFf SHALL BE CONTINUOUS. C. RECTANGUTAR DAMPERS SHALL BE SINGLE BU�E OR MULTIPLE (OPPOSE� BLADEJ NPE CONSTRUCTION. MAXIMUM BIA�E WI�TH IS 8 INCHES. D. ALL BALANCING �AMPERS SHALL BE CONSTRUCTED IN ACCORDANCE WITH SMACNA "HVAC DUCT CONSTRUCTION STANDAR�S" E FORNISH ALL BALANCING OAMPERS WITH YOONG REGULATOR COMPANY VALCALOX REGUUTORS WITH HANDLE PERMANENTLY ATfACHED. �AIAPER HAN�LE POSITION SHALL BE SECURELY LOCKE� IN PIACE BY TIGHTENING OF A LOCK NIIC WHERE Dl1CiWORK IS EXTERNALLY INSUTATE�, REGULATOR BASE HEIGHT SHALL ACCOMMO�ATE INSULATION THICKNESS. F. PROVI�E ALL MANl1AL BALANCING �AIAPERS WHERE INDICATED ON THE �RAWINGS AN� WHERE NECESSARY TO PROPERLY �ISTRIBUTE AN� BAIANCE THE AIR. 13. 14. 15. REGISiERS, GRILLES AND DIFFUSERS A. PROVIDE REGISTERS, GRILLS AN� DIFFUSERS WHERE SHOWN ON iHE DRAWINGS, OF SIZE ttPE, AND MATERIAL AS INDICATED AND AS REQUIRED FOR A COMPLEiE INSTALLATION. B. BORDER lYPES SHALL BE COMPATIBLE WITH THE CEILINGS WHERE iHE GRILLES AND DIFFUSERS ARE TO BE INSTALLED. C. ALL GRILLES AND DIFFUSERS SHALL BE FINISHED WITH A FACTORY APPLIED OFF-WHITE FIN6H UNLE55 NOiED OTHERWISE. D. REFER TO ARCHITECiURAL REFLECiED CEILING PLANS FOR E%ACT LOCATION OF GRILLES AND DIFFUSERS. i6. TESTING, ADJUSiING AND BALANCING A. THIS CONTRACiOR SHALL SECURE SERVICES OF AN INDEPENDENT A4BC OR NEEB CERiIFIED TAB COMPANY. iA8 COMPANY SHALL BAUNCE ALL COMPONENTS TO NO MORE THAN 5% ABOVE AND 5% BELOW DESIGN REOUIREMENiS. BALANCED POSITIONS ON DAMPERS, VALVES, EiC. SHALL BE PERMANENTLY MARKED. B. THE FOLLOWING DEVICES AND EOUIPMENT SHALL BE MEASURED AND �OCUMENTEO IN THE BALANCE REPORT: AIR DISTRIBUPON (GRILLES, �IFFUSERS, REGISTERS). 17. PROJECT COMPLEfION A. UPON COMPLEfION OF PROJECT THIS CONTRACTOR SHALL PROVI�E NEW FlLTERS WITHIN ALL E%ISTING AN� FAN POWERE� EQUIPMENT. B. ALL EXISTING AN� NEW FAN POWERE� EOUIPMENT SHALL HAVE THEIR EX7ERIOR CLEANED WITH A IAIL� SOAP AN� WATER SOW710N ANO THOROUGHLY �RIED. C. PROVIOE 3 COPIES OF FlNAL TEST AN� BAIANCE REPORT TO OWNER/ARCHRECT. 18. WATER SOURCE HEAi PUTAP UNITS A. DESCRIPTION: PACKAGED WATER-SOURCE HEAT PUMP WITH TEMPERATURE CONTROLS; FACTORY ASSEMBLED, TESTEQ AND RATED ACCORDING TO ARI-I50-iJ256-1, ETL LISiED. B. CABWEi AND CHA5515: PAINTED STEEL CASING WITH THE FOLLOWING FEATURES: 1. ACCE55 PANEL FOR ACCE55 AND MAINTENANCE OF INTERNAL COMPONENTS. 2. KNOCKOUTS FOR ELECTRICAL CONNECTIONS. NO KNOCKOUTS FOR PIPING. WATER CONNECilONS ARE FLUSH MOUNT WITHOUi REOUIRING BACKUP WRENCH. 3. HORIZONiAL FUT TOP WITH GRILLE AND HINGED CONTROL COVER 4. CABINEf INSUlATION: FOIL FACED, MINIMUM ',� INCH THICK, COMPLYING WITH UL 181. 5. CONDENSATE DRAINAGE: (PVC) PLASTIC DRAIN PAN PITCHED AS REQUIRED IN ASHRAE fi2 WITH CONDENSATE �RAIN PIPMG PROJECTMG THROUGH UNR CABWEf. fi. SOUN� ATTENOATION PACKAGE: a. MINIA�UM 0.598-INCH-THICN COMPRESSOR ENCLOSURE AN� FRONT PANEL IAINIMOM 0.0977-INCH-THICK FOAM GASKEf AROUND THE COMPRESSOR AND PERIMEfER OF END PANEL. b. SOUN� ATTENUATING BIANKEf OVER COMPRESSOR. C. FAN: DIRECT DRNEN, CENTRIFUGAL, WITH IAULTI-SPEED MOTOR RE9LIEMLY MOONTED M FAN MLEf. 1. MOTOR: MULTI-SPEED, PERMANENTLY WBRICATED, ECIA MOTOR OR AS SCHEDOLED. D. WATER CIRCUIT: 1. REFRIGERANT-TO-WATER HEAT EXCHANGERS 25 'F TO 12PF OPERATING TEA�PERATURE RANGE. a. INSULATED, EX�EN�ED RANGE COA%IAL HEAT E%CHANGERS WITH COPPER WATER TUBE WITH ENHANCED HEAT-TRANSFER SURFACES INSIDE A STEEL SHELL; BOTH SHELL AND TUBE LEAK TESTEO TO 45� P9G ON REFRIGERANT SIDE AND 40� PSIG ON WATER SIDE FACTORY-MOUNT HEAT EXCHANGER IN UNIT ON RESILIENT RUBBER VIBRATION ISOIATORS. E REFRIGERANT-TO-AIR-COILS: COPPER TOBES WITH AWMINUTA FWS, LEAK TESTE� TO 450 PSIG. F. REFRIGERANT CIRCUIT COMPONENTS: 1. SEALED REFRIGERANT CIRWIT: CHARGE WITH R-410A REFRIGERANT (R-22 IS NOT ACCEPTABLE). 2 FlLTER-0RYER: FACTORY WSTALLE� TO CLEAN AND �EHYDRATE THE REFRIGERANT CIRCUIT. 3. CHARGING WNNECTIONS: SERVICE FITTINGS ON SUCTION AND LIQUI� FOR CHARGING AND TESTING. 4. REVERSING VALVE: PILOT-OPERATEO SLI�ING-iYPE VALVE �ESIGNEO TO BE FAIL-SAFE IN HFATING POSITION WITH REPIACEABLE MAGNEfIC COIL. 5. COMPRESSOR: DUAL CAPAQ7Y SCROLL COMPRESSOR INSTALLE� ON VIBRATION ISOLATORS AN� HOUSED IN AN ACOUSTICALLY TREATE� ENCLOSURE WITH FACTORY-INSTALLED SAFEfIES AS FOLLOWS: a. DUAL CAPAGN-HEAT PUMP �UiY. b. AMIRECYCLE TIMER. c. HIGH-PRESSURE CUTOUT. d LOW-PRESSURE CUTOUT OR LOSS OF CHARGE SWITCH. e. INTERNAL THERMAL-OVERLOA� PROTECTION. L FREEZESTAT TO STOP COMPRESSOR IF WATER-LOOP TEMPERATURE IN REFRIGERANT-TO-WATER HEAT EXCHANGER FALLS BELOW 25 �EG F. g. CON�ENSATE OVERFLOW SWITCH TO STOP COMPRESSOR WITH HIGH CON�ENSATE LEVEL IN CON�ENSATE DRAIN PAN. 6. REFRIGERANT PIPING MATERIALS: ASTM B 743 COPPER TUBE WITH WROUGHT-COPPER FlTfINGS AND BRAZE� JOINTS. 7. PIPE INSUUTION: REFRIGERANT MINIIAUTA 3/8-MCH-THICK, FLE%IBLE EUSTOMERIC INSUlATION ON PIPING E%POSED TO AIRFLOW THROUGH THE UNIT. MAXIMUM 25/50 FLAME-SPREAD/SMONE- DEVELOPMENT INDEXES ACCORDING TO ASTM E 84. 8. REFRIGERANT METERING DEVICE: THERMAL E%PANSION VALVE TO ALLOW SPEqFIED OPERATION WITH ENTERING-WATER TEMPERATURES FROM 25' F TO 120' F. G. ELECTRIC HEATING COIL: HELI%-WOUND, NICKEL-CHROMIUM WIRE-HEATING ELEMENTS IN CERAMIC INSULATORS MOUNTED ON STEEL SUPPORTS. ENERGIZE ON CALL FOR HEATING WHEN ENTERING-WATER-LOOP TEMPERATURE IS LE55 THAN 25 DEG F. H. FILTERS: DISPOSABLE, PLEATED ttPE, Y' INCH THICK MERV 11. I. CONTROLS 1. BASIC UNIT CONTROLS: DDC a. LOW AND HIGH-VOLTAGE PROTECTION. b. OVER CURRENT PROTECTION FOR COMPRESSOR AND FAN MOTOR. c RANDOM TIME DELAY, THREE TO TEN SECONDS, START ON POWER UP. d. TIME DELAY OVERRIDE FOR SERVICING. e. CONTROL VOLTAGE TRANSFORMER. 2. THERMOSTAT: a. UNIT-MOUNTED TEMPERATURE SENSOR. b. LED TO INDICATE FAULT WNDITION AT HEAT PUMP. c DATA ENTRY AND ACCESS PORT. 1JINPUT DATA INCWDE ROOM TEMPERAIDRE ANO HUMIDIN SEf POIMS FOR OCWPoE� AND UNOCWPoED PERIODS. 2)OUTPUT DATA INCWDE ROOM TEMPERATURE AND HUMIDItt, SUPPLY-AIR TEA�PERATURE, ENTERING-WATER TEIAPERATURE, OPERATING MODE, AND SiATUS. 3. TERMINAL CONiROLLER: a. REMOTE CONTROL PANEL TO CONTAIN PROGRAMMABLE TIMER AND LED FOR FAULT CONDITION. b. COMPRESSOR DISABLE REIAY i0 SiOP COMPRESSOR OPERATION FOR �EMAND LIMIiING OR SWRCH TO UNOCWPoE� OPERATION. c. AUTOMATIC RE4ART AFfER RVE MINUiES IF FAULT 0.EAR5. LOCKOUT ARER THREE ATfElAPTS TO RESiARi FOLLOWING FAULi. INDICAiE FAULT FOR SERVICE iECHNIqAN. d. REfURN-AIR TEMPERATURE HIGH-LIMIT (FIRESTAT). STOP UNIT ON HIGH TEIAPERATURE. e. BACKUP FOR VOLATILE MEA�ORY. J. ELECTRICAL WNNECTION: SINGLE ELECTRICAL CONNECiION WITH FUSED DISCONNECi. �Inregrared 1�En�'meerinp Consvltants,lnc. 9700 ROCNSIDE RD.SURE290 CLEVELAND.OX 44125 PHONE:21G90L6711 FA%:216A01-6712 NELSOI� Nelm Architedure, Inc. a licensed affliate 30 West Monroe Street - Suite 200 Chicago, IL 6060&2409 Phone: (312)263-6605 (312)2]fi-4340 OWNER'S PROJECT MANAGER Jones Lang LaSalle Alex Gsneros 540 W. Madison St, Suit eIL9-540-04-55 Chicago, IL 60661 T: 773.502.5562 E: alex.cisneros@am.jlLcom MEPENGINEER Integrated Engineering ConsWtants,Inc (IEC) Tim Vlning 9700 Rockside Road, Suite 290 Cleveland, OH 44125 T. 216.901.67ll E: [im.vining@ieC-inc.cc GENERALCONTRACTOR Mid America Contracting, Inc. Tyler Crawford 107 N. Main Street, Suite 3A Columbia, [L 62236 T: 618.9779255 E: tic@midamericacontrac[ing.com ConsWtant'. MERRILL� A BANK OF AM ERICA COMPANY Cllent. INW-044 BofA Indianapolis MLWM Expansion & Refresh, 3rd Floor 510 96th Street Indianapolis, IN 46240 Project TiHe & Nddress: MECHANICALHVAC SPECIFICATION SHEET SheetTiHe�. ;i ,ry _ ' PE11800595 , :�•, • t �o � STATEOF ; y =A'. . �. '- � '.!N�IAN?�'�<+� � y/����'�S�S/ONA,L) E�G,`��" �S 7 � �"n , �/,��7 " / � ,. Seal: / Proj. No'. 19.0004J36.000 Designer'. ERO;MBM �rawn By: ]PH Reviewed By: HHH Pmjcct Managcr. M]L qppmved By: HHH M3-1 ALL �IMENSIONS AN� LONDITIONS MOA BE CHECKED AND VERIRED ON 9TE BY THE CONTRAQOP AND 50B-CONTRAQORS PRIOR TO PEFFOkMMG THE WOFK. THE PRO]ECT MHNAGEk SHALL RE NOTIFIED IN wa�nNs oF nrvr o�scaeenmc�es en�oa ra caoceemrve w�rH rHe woae. c� rve�mry won�owroe, uc zozo nu a�sHTs aFseaveo