'L1'HOLLAND BUILDINGPARK EAST PARKING GARAGE8
8
GENERAL SHEET NOTES
A. SEE SHEET E-000 FOR SYMBOLS AND ABBREVIATIONS.
B. REFER TO E-500 SHEETS FOR ELECTRICAL SCHEDULES.
C. REFER TO E-600 SHEETS FOR ELECTRICAL DETAILS.
D. COORDINATE INSTALLATION OF LIGHTING FIXTURES WITH ARCHITECTURAL
REFLECTED CEILING PLANS, ARCHITECTURAL ELEVATIONS, MECHANICAL
EQUIPMENT, DIFFUSERS, SUPPORTS, PIPING, DUCTWORK AND STRUCTURAL
PLANS PRIOR TO ROUGH-IN AND INSTALLATION OF LIGHTS.
E. ALL MOUNTING HEIGHTS NOTED ON THE PLANS ARE TO THE BOTTOM OF THE
FIXTURES UNLESS NOTED OTHERWISE.
F. LOCATE CEILING MOUNTED OCCUPANCY SENSORS TO PROVIDE COMPLETE
AREA COVERAGE OF THE SPACE THEY ARE INSTALLED IN. SELECT PROPER
SENSOR COVERAGE PATTERN FROM MANUFACTURER'S PRODUCT DATA TO
DETERMINE COVERAGE. ADDITIONAL SENSORS REQUIRED DUE TO LACK OF
COVERAGE SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND THE
MANUFACTURER. SENSORS SHALL INCLUDE ALL POWER SUPPLIES AND
RELAYS NECESSARY FOR PROPER OPERATION.
G. WIRING SYSTEM SHALL BE CONDUIT AND CONDUCTOR UNLESS NOTED
OTHERWISE. USE SOLID CONDUCTOR FOR SIZE #10 AWG AND SMALLER.
USE STRANDED CONDUCTOR FOR LARGER SIZES.
H. ALL COVER PLATES FOR ELECTRICAL DEVICES SHALL BE OF A COLOR TO
MATCH THE AREA COLOR SCHEME AS DIRECTED BY THE INTERIOR
DESIGNER.
I. LABEL ALL RELAYS AND POWER SUPPLIES (ON THE DEVICE OR ON THE BOX
THEY ARE CONNECTED TO) WITH THE AREA THE DEVICES SERVES, THE
BRANCH CIRCUIT IT CONTROLS AND THE DEVICE ADDRESS (IF APPLICABLE).
J. EMERGENCY LIGHTING SHOWN ON THIS DRAWING INDICATES CODE
REQUIRED EMERGENCY LIGHTING FED FROM THE 'EMERGENCY BRANCH' OF
THE ESSENTIAL ELECTRICAL SYSTEM.
K. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS, ROOM AND AREA
FINISHES, CEILING PLANS, DOOR SWINGS, FIRE-RATED PARTITIONS, CABINET
AND CASEWORK AND BUILT-IN DETAILS.
L. ALL WORK SHALL COMPLY WITH ALL NATIONAL, STATE AND LOCAL CODES
AND ORDINANCES PERTAINING TO THE WORK IN THIS PROJECT.
M. EXPOSED CONDUIT SHALL BE RUN PARALLEL TO AND AT RIGHT ANGLES TO
BUILDING LINES.
N. REFER TO ARCHITECTURAL DRAWINGS FOR DESIGNATION AND LISTING OF
FIRE RATED ASSEMBLIES. COORDINATE ALL DESIGN EFFORTS WITH FIRE
RESISTANCE OF MATERIALS AND CONSTRUCTION.
O. ALL EXTERIOR EQUIPMENT AND DEVICES SHALL BE WEATHER PROOF AND
RAIN TIGHT.
2
3
A
4
1
B
'L2''L2''L2''L2''L2''L2''L2'HOLLAND BUILDINGPARK EAST PARKING GARAGECIVIL, LIGHTING AND ELECTRICAL DESIGN CONSULTANTS
HEATING, VENTILATION, AIR CONDITIONING, PLUMBING, FIRE PROTECTION,
9229 DELEGATES ROW SUITE 150 INDIANAPOLIS, IN 46240 (317) 781-6200
CIRCLE DESIGN GROUP
19092
Project:
Developer:
Sheet Number:
Engineer:
By:
Sheet Title:
CDG Number:
Last Revision Date:
Set Issue Date
Drawn By Checked By
Sheet Issue DateHolland / Playfair BuildingsCarmel, IN 46032Construction Documents120 West Monon Green Blvd.EL101
LIGHTING PLANS
09/23/201909/23/2019
Barry SimpsonMelissa Laviolette
1/4" = 1'-0"
SECOND FLOOR LIGHTING PLAN208'4'2'
SHEET PLAN NOTES
1 CORNER MOUNT LINEAR DOWNLIGHT BETWEEN CEILING AND STEEL TUBE
STRUCTURE WITH LUMINOUS SURFACES FACING OUT. FIXTURES TO BE
MOUNTED END TO END WITH MINIMAL JOINTS.
2 CONNECT LIGHTING WITHIN SKYBRIDGE TO AN AVAILABLE 20A/1P CIRCUIT
WITH IN PANELBOARD "2HA1" IN HOLLAND BUILDING. VERIFY AVAILABLE
CIRCUITS PRIOR TO WORK.
3 LIGHT FIXTURES INSTALLED WITH REMOTE EMERGENCY BATTERY PACK AS
INDICATED PER DRAWING.
4 JBOX MOUNTED FIXTURE RECESSED INTO UNDERSIDE OF BRIDGE.
5 EXISTING FIXTURE SHOWN FOR REFERENCE.
6 CONNECT LIGHTING UNDER SKYBRIDGE TO AN AVAILABLE 20A/1P CIRCUIT
WITH IN PANELBOARD "2HA1" IN HOLLAND BUILDING. VERIFY AVAILABLE
CIRCUITS PRIOR TO WORK.
7 BELOW CONNECTOR LIGHTING TO BE CONTROLLED WITH BUILDING
MOUNTED LIGHTING ON HOLLAND BUILDING WITH PHOTOCELL AND
TIMECLOCK BY WAY OF CONTACTOR.
8 SURFACE MOUNT SENSOR TO STRUCTURE/CEILING.
LIGHTING FIXTURE SCHEDULE
FIXTURE
TYPE BASE MANUFACTURER EQUAL MANUFACTURER WATTAGE LAMP TYPE
VOLTS
MOUNT DESCRIPTION
L1 AXIS:
ED2S-800LM-80-30K-UB-S79-X-SC
O-UNV-DP-1-SC-FL-B#4
ALW: NOVENTA, LUMIUM: NB3,
LUMENWERX: CUBITO
7W/LF LED
800LM/FT
3000K
120 SURFACE 79' LINEAR LED DOWNLIGHT WITH ALUMINUM EXTRUSION & DIFFUSE
LENS. MINIMIZE NUMBER OF FIXTURE JOINTS. CORNER MOUNT WITH
(2) LUMINOUS SURFACES POINTED DOWN AND OUT. 80 CRI MIN.
0-10V DIMMING TO 10%. REMOTE EMERGENCY BATTERY PACK
MOUNTED EVERY 18'-0" ON CENTER. 800LM/FT MIN. (SKYBRIDGE)
L2 HALO: SMD6S-12-930-X-X PROVIDE ALLOWANCE OF $50
PER FIXTURE.
16 LED 1200LM
3000K
120 JBOX 6" JBOX MOUNTED LED DOWNLIGHT WITH DAMP LOCATION. TRIM
FINISH PER ARCHITECT. FIXTURE TO MATCH HOLLAND BUILDING.
(UNDERSIDE OF BRIDGE)
NOTES:
1. FIXTURES LISTED IN THE EQUAL MANUFACTURER COLUMN TO BE PROVIDED WTIH COMPONENTS, PERFORMANCE, AESTHETIC, FABRICATION, AND CONSTRUCTION EQUAL TO OR BETTER THAN BASE BID.
2. MANUFACTURER TO PROVIDE ALL NECESSARY POWER SUPPLIES, MOUNTING ACCESSORIES, AND COMPONENTS TO FOR LIGHT FIXTURE TO OPERATE NORMALLY.
3. REFER TO ARCHITECTURAL/INTERIOR/SITE DRAWINGS FOR EXACT MOUNTING LOCATIONS, DETAILS, AND CONFIGURATION OF LIGHT FIXTURES. IF DRAWINGS DO NOT CLARIFY EXACT DETAILS, CONTRACTOR TO ISSUE RFI TO CLARIFY PRIOR TO FIXTURE ROUGH-IN. ELECTRICAL DRAWINGS SHALL NOT BE USED TO VERIFY
LIGHT FIXTURE PLACEMENT.
4. CONTRACTOR TO VERIFY COMPATIBILITY OF LIGHT FIXTURES WITH CEILING MATERIALS, ADJACENT FINISHES, CONSTRUCTION AND MATERIALS PRIOR TO SHOP DRAWING SUBMITTAL. NOTIFY ARCHITECT OF ANY CONFLICTS WITH INSTALLATION.
5. CONTRACTOR RESPONSIBLE FOR ALL NECESSARY HARDWARE AND COMPONENTS REQUIRED TO INSTALL LIGHT FIXTURES.
6. SEISMIC PROTECTION OF ALL LIGHT FIXTURES SHALL COMPLY WITH SPECIFICATION SECTIOSN AND LOCAL CODES AND ORDINANCES.
1/4" = 1'-0"
FIRST FLOOR LIGHTING PLAN108'4'2'
4 4 4
4 4 4 4
5
5
5
6 6 6
6 6 6 6
N
N
7