HomeMy WebLinkAboutEP101 - POWER PLANSCAM
CAM
J
CR
CAM
CAM
J
CR
FCU-1 FCU-2
2#8, #10GND-3/4"C
2#8, #10GND-3/4"C
2
1
21 3
3
2
3
A
4
1
B
5
5
6
7
7
A. SEE SHEET E-001 FOR SYMBOLS AND ABBREVIATIONS.
B. SEE SHEET E-604 FOR KITCHEN EQUIPMENT SCHEDULE.
C. SEE SHEET E-604 FOR MECHANICAL EQUIPMENT POWER SCHEDULE.
D. SEE SHEETS E-601 THROUGH E-603 FOR PANEL SCHEDULES.
E. SEE SHEETS E-501, E-502 AND E-503 FOR ELECTRICAL DETAILS.
F. WIRING SYSTEM SHALL BE CONDUIT AND CONDUCTOR UNLESS NOTED
OTHERWISE. USE SOLID CONDUCTOR FOR SIZE #10 AWG AND SMALLER.
USE STRANDED CONDUCTOR FOR LARGER SIZES.
G. ALL COVER PLATES FOR ELECTRICAL DEVICES SHALL BE OF A COLOR TO
MATCH THE AREA COLOR SCHEME AS DIRECTED BY THE INTERIOR
DESIGNER.
H. ALL WORK SHALL COMPLY WITH ALL NATIONAL, STATE AND LOCAL CODES
AND ORDINANCES PERTAINING TO THE WORK IN THIS PROJECT.
I. EXPOSED CONDUIT SHALL BE RUN PARALLEL TO AND AT RIGHT ANGLES TO
BUILDING LINES.
J. REFER TO ARCHITECTURAL DRAWINGS FOR DESIGNATION AND LISTING OF
FIRE RATED ASSEMBLIES. COORDINATE ALL DESIGN EFFORTS WITH FIRE
RESISTANCE OF MATERIALS AND CONSTRUCTION.
K. ALL EXTERIOR EQUIPMENT AND DEVICES SHALL BE WEATHER PROOF AND
RAIN TIGHT.
L. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL
INTERCONNECT WIRING FOR MECHANICAL AND PLUMBING EQUIPMENT
FURNISHED BY OTHERS.
GENERAL SHEET NOTES
2
3
A
4
1
B
EWH-1EWH-1EWH-1
EWH-1
EWH-1 EWH-1
4
4
4
4 4
4
2#12, #12GND-3/4"C
2#12, #12GND-3/4"C
2#12, #12GND-3/4"C
2#12, #12GND-3/4"C
2#12, #12GND-3/4"C
2#12, #12GND-3/4"C
CIVIL, LIGHTING AND ELECTRICAL DESIGN CONSULTANTS
HEATING, VENTILATION, AIR CONDITIONING, PLUMBING, FIRE PROTECTION,
9229 DELEGATES ROW SUITE 150 INDIANAPOLIS, IN 46240 (317) 781-6200
CIRCLE DESIGN GROUP
19092
Project:
Developer:
Sheet Number:
Engineer:
By:
Sheet Title:
CDG Number:
Last Revision Date:
Set Issue Date
Drawn By Checked By
Sheet Issue DateHolland / Playfair BuildingsCarmel, IN 46032Construction Documents120 West Monon Green Blvd.EP101
POWER PLANS
09/23/201909/23/2019
Barry SimpsonCarlston Elliott
1/4" = 1'-0"
SECOND FLOOR POWER PLAN108'4'2'
SHEET PLAN NOTES
1 PROVIDE A 60A DISCONNECT FOR FAN COIL UNITS FCU-1 AND FCU-2.
CONNECT FAN COIL UNITS TO A 45A/2P CIRCUIT BREAKER WITH IN
PANELBOARD "2HA1" LOCATED ON THE 2ND FLOOR OF THE HOLLAND
BUILDING.
2 PROVIDE A 30A WEATHERPROOF DISCONNECT FOR CONDENSING UNITS CU-1
AND CU-2 LOCATED ON THE ROOF. CONNECT THE CONDENSING UNITS TO A
20A/2P CIRCUIT BREAKER WITH A WIRE SIZE OF 2#12,#12GND-3/4"C FED FROM
PANELBOARD "4HA1" LOCATED ON THE 2ND FLOOR OF HOLLAND BUILDING.
3 PROVIDE A WEATHERPROOF (GFCI) RECEPTACLE ON CONDENSING UNIT
LOCATED ON ROOF. CONNECT RECEPTACLES TO THE SAME 20A CIRCUIT AS
RECEPTACLES WITH IN THE AREA FEDFROM PANEL "4HA1" LOCATED ON THE
4TH FLOOR OF HOLLAND BUILDING.
4 PROVIDE A 20A DISCONNECT FOR ELECTRIC WALL HEATERS "EWH-1".
CONNECT ELECTRIC WALL HEATERS TO A 20A/2P CIRCUIT BREAKER WITH IN
PANELBOARD "2HB1" LOCATED ON THE 2ND FLOOR OF THE HOLLAND
BUILDING.
5 PROVIDE A WEATHERPROOF (GFCI) RECEPTACLE MOUNTED ON STEEL
COLUMN. CONNECT RECEPTACLES TO THE SAME 20A CIRCUIT FED FROM
PANEL "2HA1" LOCATED ON THE 2ND FLOOR OF HOLLAND BUILDING.
6 SKYBRIDGE PASSAGE/DOOR SECURED THROUGH ACCESS CONTROL SYSTEM
FED FROM HOLLAND BUILDING.
7 ROUTE (1) CAT6 CABLE FROM HOLLAND BUILDING IDF ROOM LOCATED ON
THE 2ND FLOOR AREA A TO SECURITY CAMERA. VERIFY LOCATION AND
MOUNTING HEIGHT WITH ARCHITECTURAL DRAWINGS PRIOR TO
INSTALLATION.
1/4" = 1'-0"
SECOND FLOOR POWER PLAN - ALTERNATE20 8'4'2'