HomeMy WebLinkAboutH-501 - HVAC SCHEDULESELECTRIC HEAT FAN COIL UNIT SCHEDULE
MARK LOCATION CONFIGURATION
FAN DATA HEATING COIL DATA DX COOLING COIL DATA FILTER DATA UNIT CONNECTION DATA
UNIT
WEIGHT
(LBS)
MANUFACTURER WITH
MODEL NUMBER NOTESAIRFLOW
(CFM)
OUTDOOR
AIRFLOW
(CFM)
ESP TYPE MBH EAT LAT
TOTAL
MBH
SENSIBLE
MBH
EAT LAT
TYPE MCA VOLTS PH
DB WB DB WB
FCU-1 SEE PLANS HORIZONTAL 979 0 0.0 DIRECT 20.5 70.0 89.4 29.3 23.4 75 61 53.5 50.2 1" MERV 8 38.4 208 1 164 TRANE FCD-08
FCU-2 SEE PLANS HORIZONTAL 979 0 0.0 DIRECT 20.5 70.0 89.4 29.3 23.4 75 61 53.5 50.2 1" MERV 8 38.4 208 1 164 TRANE FCD-08
NOTES:
1.
2.
CONDENSING UNIT SCHEDULE
MARK LOCATION
NOMINAL
TONS
DESIGN
AMB
TEMP
MIN.
EER
ELECTRICAL DATA LIQUID
LINE
VAPOR
LINE
UNIT
WEIGHT
(LBS)
MANUFACTURER WITH
MODEL NUMBER NOTES
MCA MOCP VOLTS PH
CU-11 HOLLAND ROOF 3 95 / 30 13 24 35 208 1 3/8" 3/4" 283 TRANE 4TTR7036A
CU-12 HOLLAND ROOF 3 95 / 30 13 24 35 208 1 3/8" 3/4" 283 TRANE 4TTR7036A
NOTES:
1.
2
ELECTRIC UNIT HEATER SCHEDULE - ALTERNATE ONLY
SPECIFICATION SECTION 238201
MARK LOCATION CONFIGURATION
AIRFLOW
(CFM)
HEATING DATA ELECTRICAL DATA ACCESSORIES
MANUFACTURER WITH
MODEL NUMBER NOTESMIN
KW MBH RISE
FAN
HP AMPS VOLTS PH
DISCONNECT
SWITCH
INTEGRAL
THERMOSTAT
WALL
BRACKET
EWH-1 SEE PLANS WALL 100 2.0 6.8 63.2 - 9.6 208 1 YES YES NO QMARK AWH4408F 1
NOTES:
1.PROVIDE SURFACE MOUNTING KIT.
ROOF
INSTALL CURBS PER NRCA
AND MFGRS RECOMMENDATIONS
EQUIPMENT
SUPPORT CURB OR
RAIL (TYPICAL)
WOOD NAILER
FIELD APPLIED
CANT
EQUIPMENT BASE
REFER TO STRUCTURAL DWGS
FOR SUPPORT ATTACHMENT TO
STRUCTURE BELOW
1-1/4" WIDE METAL STRAPPING
THICKNESS TO BE .031"
ROOF, SEE ARCH
PLANS FOR DETAILS
PROVIDE 2X6 WOOD BLOCKING
BELOW CURBS (TYPICAL)
CONDENSING UNIT
CAULK OR GASKET
2" -#14 LAG
BOLTS
PROVIDE 2 PER SIDE
NOTES:
1.PROVIDE 2 -1-1/4" WIDE METAL STRAPS OVER TOP OF UNIT, ONE ON EACH SIDE. STRAPS SHALL BE ANCHORED TO EQUIPMENT RAILS AT THE
BASE. STRAPS SHALL BE PRIMED AND PAINTEDWHITE, 2 COATS EACH MINIMUM, ON BOTH SIDES PRIOR TO INSTALL.
2.PROVIDE 2 -#14 LAG BOLTS, SPACED 5/8" APART, AT THE END OF EACH METAL STRAP. BOLTS SHALL GO THROUGH METAL STRAPPING AND INTO WOOD NAILER OF EQUIPMENT RAILS TO
ANCHOR UNIT TO EQUIPMENT RAILS.
3.STRAPS SHALL BE PLACED A MINIMUM OF 3" IN FROM TOP EDGE OF UNIT.
4.STRAPPING SHALL BE VERIFIED BY EQUIPMENT MANUFACTURER TO ENSURE ADEQUATE RESTRAINT OF SUPPLIED EQUIPMENT AT 115 MPH WIND LOAD. ANY DEVIATIONS FROM ABOVE MUST
BE SUBMITTED TO ENGINEER FOR REVIEW.
CONDENSING UNIT
1-1/4" WIDE METAL STRAPPING
THICKNESS TO BE .031"
2" -#14 LAG
BOLTS
PROVIDE 2
PER SIDE
CAULK OVER BOLT
HEAD(S)
ROOF MEMBRANE
PIPE
INSULATION
BASE
GALVANIZED
CHANNEL
SECURE PIPING TO
SUPPORT WITH
STRAP
1' - 4"
3' - 0"0' - 8"0' - 4"SEAL CAVITY WITH MINERAL
WOOL INSULATION.
REFRIGERANT PIPING TO
CONDENSING UNITS ON
EACH SIDE.
POWER WIRING AND REFRIGERANT PIPING
FROM BUILDING UP THROUGH ROOF IN
CUSTOM SHEET METAL ENCLOSURE.
FILL CAVITY WITH
INSULATION.3' - 0"1' - 6"ATTACH TO WOOD
NAILER EVERY 3"
REFRIGERANT
LINES
COOLING COIL
CONDENSATE
FAN COIL UNIT
THREADED ROD, UNISTRUT AND NEOPRENE
ISOLATION HANGER PROVIDE ADDITIONAL
RESTRAINT AS REQUIRED BY SEISMIC DESIGN.
CONDENSING UNITS INCLUDED
IN SKYBRIDGE PROJECT
CU-1-210
CU-1-310
CU-1-410
CU-1-510
HP-1-307
HP-1-507HP-1-407
HP-1-207
CU-1-408
CU-1-508CU-1-308
CU-1-208
CU-11
CU-11
B/H-501
D/H-501
SECOND FLOOR
FRAMING
116' -0"
BRIDGE ROOF
125' -4 1/2"
23
FCU-1
1" CONDENSATE AND P-TRAP
MOUNT AT 7'9" ABOVE
FINISHED FLOOR
INSULATED
REFRIGERANT LINES
TIGHT TO STRUCTURE
SPRINKLER PIPE. REFER TO
FIRE PROTECTION DRAWINGS
FOR PLACEMENT AND SIZE.
MOUNT INBETWEEN
STRUCTURE AT 8'1"
1.5 RADIUS ELBOWS
CONDENSATE SLOPED
AT 1/8" PER 1'-0"
INSULATION AND ALUMINUM
JACKETING ON EXTERIOR
OF STRUCTURE
DOWNSPOUT
PROVIDED BY OTHERS
COORDINATE FITTING SIZING
WITH OTHER TRADES
THREADED GALVANIZED
SCHEDULE 40 PIPE
EXTERIOR INTERIOR
DRESSER COUPLING
CIVIL, LIGHTING AND ELECTRICAL DESIGN CONSULTANTS
HEATING, VENTILATION, AIR CONDITIONING, PLUMBING, FIRE PROTECTION,
9229 DELEGATES ROW SUITE 150 INDIANAPOLIS, IN 46240 (317) 781-6200
CIRCLE DESIGN GROUP
19092
Project:
Developer:
Sheet Number:
Engineer:
By:
Sheet Title:
CDG Number:
Last Revision Date:
Set Issue Date
Drawn By Checked By
Sheet Issue DateHolland / Playfair BuildingsCarmel, IN 46032Construction Documents120 West Monon Green Blvd.H-501
HVAC SCHEDULES
09/23/201909/23/2019
Ross MaueThomas Kennedy
NOT TO SCALE
Condensing Unit Support DetailA
NOT TO SCALE
Pipe Roof Support DetailB
NOT TO SCALE
Roof Penetration DetailD NOT TO SCALE
Horizontal Fan Coil Unit DetailC
1/8" = 1'-0"
Holland Building Roof HVAC Plan1
1/4" = 1'-0"
BRIDGE MECHANICAL SECTION2
NOT TO SCALE
Condensate to Downspout Tie-InE