13
\,
/
\
�
(E)LOCAL LTG
/
GENERAL NOTES
n
E.0. SHALL RECENE AND STORE ALL NEW EQUIPMENT IN REMOTE
STORAGE FACILITY. THIS WCLUDES THREE SWITCHGEAR SECTIONS,
ATSs, AND PORTABLE GENERATOR AND LOAD BANK DOCKING
STATION. EC. SHALL MSPECT EQUIPMENT UPON RECEIPT OF
SHIPMENT TO ENSURE NO DAMAGE DURING SHIPPING. E.C. IS THEN
RESPONSIBLE FOR SHIPPING TO SITE AND RIGGING EQUIPMENT INTO
PLACE. ANCHOR TO PAD, AND COMPLETE TERMINATIONS BETWEEN
EQUIPMENT AS REQUIRED PER MANUFACTURER'S INSTALLATION
MSTRUCTIONS. REFER TO ONE—LINE DIAGRAM E42 FOR ADDITIONAL
INFORMATION.
E.C. TO PROVIDE NEW LABELS ON ALL EQUIPMENT, AND ON ALL
BREAKERS IN NEW SWITCHGEAR PER DETAIL A/E32.
Q
CODED NOTES
1. INSTALL NEW 1600A, 480V, 3P, 3W, 65kAIC ASCO SERIES 7000
SWGF—A, PROVIDED BY OTHERS.
2 WSTALL NEW 1600A, 480V, 3P, 3W, 65kAIC ASW SERIES 7000
REMOTE SWITCHGEAR SECTION, PROVIDED BY OTHERS.
3. WSTALL 1600A, 480V, 3P, 3W, 65kAIC ASW SERIES 7000
GENERATOR DISTRIBUTION SWITCHGEAR, PROVIDED BY OTHERS.
4. INSTALL NEW 1600A, 480V, 3PH, 3W PORTABLE GENERATOR AND
LOAD BANK DOCKING STATION, PROVIDED BY OTHERS.
5. PROVIDE NEW EHIT SIGN. FlHTURE TO BE WALL MOUNTED 90"
ABOVE THE FlNISHED FLOOR, CENTERED ABOVE NEW EGRESS
DOOR, AND TIED INTO LOCAL LIGHTING CIRCUIT AHEAD OF ALL
SWITCHING.
6. PROVIDE NEW EMERGENCY REMOTE HEAD. WIRE TO EXIT LIGHT
BATTERY PACK INSIDE. WALL MOUNT APPROXIMATELY 12" ABOVE
DOOR. TIE INTO LOCAL LIGHTING CIRCUIT AHEAD OF ALL
SWITCHING.
7. PROVIDE NEW DISTRIBUTION PANELBOARD. SEE ELECTRICAL
EQUIPMENT SCHEDULE ON SHEET E0.0 AND ONE—LWE �IAGRAM
ON SHEET E4.2.
8. INSTALL NEW 600A, 480V, 3PH, 3W, SERIES 7000 ATS. PROVIDED
BY OTHERS.
9. PROVIDE NEW 112.SKVA, 30 4800-480Y/277V TRANSFORMER,
(SQUARE—D MODEL qEHN112T1814HCU OR EQUAL). FLOOR MOUNT
ON NEW CONCRETE PAD AND FURNISH AND INSTALL ON
VIBRATION ISOLATORS.
10. PROVIDE NEW HEAVY DUTY, 600V, 200A/3P, NEMA 1, S�UARE—D
FUSED DISCONNECT SWITCH (SQUARE—D pH364 OR EQUAL) ON
SECONDARY OF NEW TRANSFORMER TX—LDP1. PROVIDE WITH
175A FUSES. DISCONNECT TO BE WALL MOUNTED ADJACENT TO
TRANSFORMER. REFER TO E4.2.
11. PROVIDE UPGRA�ED EMCP 42 CONTROLLER TO REPLACE
EXISTING EMCP 2+ CAT GENERATOR CONTROLLER EC. TO
SUBCONTRACT GENERATOR PANEL UPGRA�E WITH GENERATOR
VENDOR. SEE DRAWING E3.1 FOR MORE WFOftMATION.
12. PROVIDE NEW HEAVY DUTY, 600V, 30A/2P, NEMA 1, SQUARE—D
FUSED DISCONNECT SWITCH (SQUARE—D �H361 OR EQUAL.
3—POLE SWITCH USED IN 2—POLE APPLICATION) FOR RAW POWER
MONITORING CONNECTION. INSTALL MOUNTED ON END OF NEW
SWGR—A. PROVIDED APPROPRIATE SIZE FUSES AS REOUIRED FOR
TRANSFORMER AND WIRING PROTECTION. SWITCHGEAR PROVIDED
WITH MECHANICAL WG TAPPED INTO A AND B PHASE OF UTILITY
POWER FEED DISCONNECT OUTPUT TO INPUT OF THE RAW
POWER TRANSFORMER LOCATED NEARBY.
13. PROVIDE NEW 480-120V, 750VA TRANSFORMER FOR RAW POWER
MONITORING FEED TRANSFORMER OUTPUT TO RAW POWER
MONITOR W COMPUTER ROOM B. E.C. MAY REUSE COMPONENTS,
ENCLOSURES, WIRE AND CONDUIT FROM EXISTING RAW POWER
MONITORING CIRCUIT WHEREVER POSSIBLE.
14. INSTALL SPARE PARTS CABWET ON WALL, PROVIDED WITH
SWITCHGEAR BY OTHERS.
15. PROVIDE ANO INSTALL ALL CONTROL AND MONITORING WIRWG
AND CONDUIT PER DETAIL D/E3.1.
16. PROVIDE NEW HEAVY DUTY, 600V, 30A/2P. NEMA 1, SQUARE—D
FUSED DISCONNECT SWITCH (SQUARE—D qH361 OR EQUAL.
3—POLE SWITCH USED IN 2—POLE APPLICATION) FOR RAW POWER
MONITORING CONNECTION. INSTALL MOUNTED ON SIDE OF MAIN
UTILITY B. PROVIDE� APPROPRIATE SIZE FUSES AS REQUIRE�
FOR TRANSFORMER AND WIRWG PROTECTION. SWITCHGEAR
PROVIDED WITH MECHANICAL WG TAPPED INTO A AND B PHASE
OF UTILITY POWER FEED DISCONNECT OUTPUT TO INPUT OF THE
RAW POWER TRANSFORMER LOCATE� NEARBY.
— I CSw I 4�16/20 I PERMIT SET
REV I BY I DATE I �ESCRIPTION
V4'=1'-0'
0' 2' 4'
dbb TechSite
�o�,Pe�,aPP,o�ed
missioo-crincel 4e�iliry e.perrs
Tetil$it2 www.techsiteplan.com
8188 Buslness Way . Plain City, Ohio 43064
t 614.873J800 . f 614.873J801
PRo�E�T MISO 701 SWITCHGEAR
REPLACEMENT
�
MISO
,�,��.,Y���,����.
Cumid,IN 4h03?
DRAWN BY: ORIGIN DATE: DESIGNED BY: pATE
�He io/i/ig csw z/�o/20
�
a
N
0
c
RELEA5E0 FOR CONSTRIICTI�N
Su6jec��o compliance with allregula�ions
of S�a�e antl Local Codes
City of Carmel
�
�{�n„� i,.va,�,a!
DATE: Qrj�08�20
0
ELECTRI
►�i I_\ � I ����1
1:7:� �_1 �
\\.
1�4�� = 1�—���
TH
4 15
9���
APPROVED BV: DA1E: CLIENT N0. JOB N0.
JAK 2/10/20 1532 3395
DRAWING NAME:
E20-3395.DWG
SEAL TIRE
ELECTRICAL ROOM A
NEW WORK PLAN
DATE: I DRAWING N0.
4/14/20
�D S�A�E E2.0
1/4,� _ ��_�,�