Sprinkler Inspection Certificate
For
Carmel City Center Pedcor -
61155
720 S Rangeline Road
355 City Center Drive
Carmel, IN 46032
Tested to NFPA 25 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages
of this report provide performance measurements, listed ranges of acceptable results, and complete
documentation of the inspection. Whenever discrepancies exist betrveen acceptable performance
standards and actual test results, notes and/or recommended solutions have been proposed or provided
for immediate review and approval.
Inspection Date
Nov 1, 2019
Building: Carmel City Center Pedcor - 61155
Contact: Mike Polston
Title: Manager
Company: Dalmatian Fire
Contact: Chad Schmidt
Title: inspector
I� . .J. � � �R'�' •/'�
SHAMBAUGN & SON, LV. � p��9�l1
mxm�tias•aawms•swia W P tl
Y`FV9�C1yp' �
Executive Summa�y
Generated by: BuildingReports.com
Building Information
Building: Carmel City Center Pedcor - 61155
Address: 720 S Rangeline Road
Address: 355 City Center Drive
City/State/Zip: Carmel, IN 46032
Country: United States of America
: Inspection Performed By
Company: Dalmatian Fire
Address: 5670 West 73rd Street
Address:
City/State/Zip: Indianapolis, IN 46278
Country: United States of America
System Control Unit
Contact: Mike Polston
Phone: 317-690-0325
Fax:
Mobile:
Email: mpolston@pedcor.net
Inspector: Chad Schmidt
Phone: 317-664-0182
Fax:
Mobile:
Email: scmidtbeer2l @gmail.com
. ORTHSTRR fIRE PROIELTIQY OF TEXAS
� O�v��iox or Sx�xaFucx 8 Sox. L.P
�
Devices
32
1
11
1
9
9
9
11
65
32
7
2
� System Type System Location
i —
Dry Pipe
Dry Pipe
Dry Pipe
Dry Pipe
Dry Pipe
Dry Pipe
Dry Pipe
Dry Pipe
Wet Pipe
Wet Pipe
Wet Pipe
Wet Pipe
Inspection Summary
Category:
Device
Alarm
Valve
Pump
Sprinkler
Totals
Total Items
aty � ��o
95 50.26%
29 15.34%
50 26.46%
11 5.82%
4 2.12%
189 100%
Zone-1,5,6
Zone-2
Zone-2,3,4
Zone-3
Zone-4
Zone-5
Zone-6
Building
Zone-1
Zone-1,5,6
Serviced
at,, ��o
37 38.95%
11 37.93%
17 34.00%
2 18.18%
0 0%
67 35.45%
Passed
ari ��o
37 100.00%
11 100.00%
16 94.12%
2 100.00%
i
0 0%
66 98.51 %
FailedJOther
aty ��o
0 0%
0 0%
1 5.88%
0 0%
0 0%
7 1.49%
Certification
Company: Dalmatian Fire
Inspector: Chad Schmidt
Protected Area
Building: Carmel City Center Pedcor - 61155
Contact: Mike Polston
Dalmatian Fire Page 1 of 42 02/21/2020
III�.� i.
SHAMBAUGN &SON, LP.
mxnucraas•eusn[oa� srw[F
w♦pm�bYe�'
�,+� •=�� - -.-1.-
Ualmatian �THSTRflFIPEPPOTE iOMDFTE[AS
___...________.. ... . ._'
� � Div��io� aF Sx��eaucx 1 Sox. l.V.
�
Signed: Oct 28, 2019 Signed: Nov 1, 2019
Dalmatian Fire Page 2 of 42 02/21/2020
1' .. �'i..
SHAMBaUGH & SON, LA.
mwnunou • u+cm[on� su�rF
r�orm�a�wo�
:�g. :'� :
W��{�Q� � OPTXSTAF F RE PRCTEC'ION b TE •AS
�� . ,.._ .. ._ _. . . ...
. e orvnmx or sx..awcx a sox. �.v.
Discrepan cy Report
Generated by.• BuildingReports.com
� Building: Carmel City Center Pedcor - 61155 �
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where
appropriate, code references are listed for your convenience. Any item that was inspected that is listed on the Consumer
Product Safety Commission's website and is subject to a recall by the manufacturer is included.
Device Type ' Manufacturer ModelNumber Date Qty �
ltems lisfed for Recall by Manufacturer
No recalled items found during this inspecfion.
� ScanlD i Location _I Problem � I Reference _
Wet Pipe
� Backflow Prevention
40503398 Water pump room Check # 2 Didn't Hold
Dalmatian Fire Page 3 of 42 02/21/2020
If _ �'. - ,� : �
SNAMBAl/GN & SON. LP. IIDIII101IY11
wrmunae•u+axm�s�su�
�.�nre�oi.q ��
P�oposed Solutions Repo�t
Generated by: BuildingReports.com
09THSTaR FIRE FfiOTEC'qN 0- . Ewl4
a orvis�ox or Sx�ueaucx 8 Sou. L.P.
Building: Carmel City Center Pedcor - 61155
The Proposed Solution Report provides a solution far each discrepancy listed on the Discrepancy Report. Provide a check
mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time
and Materials basis.
ScanlD 1Location Solution � Model� Cos� Fix
Backflow Prevention
40503398 water pump room
Wet Pipe
Rebuild it
975XL T/M ❑
PO #: (none) T!M
Dalmatian Fire Page 4 of 42 02/21/2020
IIIf► .�.''t. '� . ,, • I � �
SIIAMBAUGH & SON, LP, �I��11
mnnunas•wcr�ms•sorvcx 11 ... __ ORiHSTRq. '._ PP ... IW� 0' �EYAS
Y����°�°� . -_ .... A Oivii�Ox Oi 8x�ue�ucx 8 40u. L.P.
Inspectiorc c� Testing
Generated by: BuildingReports.com
Buildin�: Carmel City Center Pedcor - 61155
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or
Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing
occurred.
Device Type _ Location
Seroice
Time
Date
Dry Pipe
Pressure Switch
Pressure Switch
Drain
Drain
Drain
Drain
Drain
Drain
Drain
Drain
Drain
Drain
Drain
Drain
Drain
Drain
Gauge
Gauge
Gauge
Air Compressor
Control Valve
Dry Pipe Valve
Wet Pipe
Pressure Switch
Pressure Switch
Waterflow Switch
Waterflow Switch
WaterFlow Switch
WaterFlow Switch
Waterflow Switch
Waterflow Switch
Waterflow Switch
Drain
Drain
floor 7
floor 7
dry stand pipe parking garage
dry stand pipe parking garage
floor 7
floor 7
zone 2 parking garage
zone 2 parking garage
zone 2 parking garage
zone 2 parking garage
zone 3 parking garage
zone 3 parking garage
zone 4 parking garage
zone 4 parking garage
zone 4 parking garage
zone 4 parking garage TA4
floor 7
floor 7
floor 7
floor 7
floor 7
floor 7
floor 4 end of hallway
floor 4 end of hallway
floor 2 stair 3
floor 3 stair 3
floor 4 stair 3
floor 5 stair 3
floor 6 stair 3
floor 7 stair 3
hallway
floor 2 stair 3
floor 3 stair 3
Passed
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
1:59:55 PM
2:02:15 PM
9:26:09 AM
1:33:47 PM
1:55:26 PM
1:55:40 PM
9:04:13 AM
9:04:40 AM
9:05:29 AM
9:19:13 AM
9:20:24 AM
9:26:44 AM
9:29:45 AM
9:31:25 AM
9:32:45 AM
2:05:34 PM
1:54:34 PM
1:54:53 PM
1:55:10 PM
2:01:44 PM
1:54:30 PM
2:00:06 PM
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
1:58:38 PM
1:59:01 PM
2:44:48 PM
2:41:30 PM
2:38:37 PM
2:33:24 PM
2:29:40 PM
2:23:37 PM
2:50:51 PM
2:45:17 PM
2:41:57 PM
11 /01 /2019
11 /01 /2019
1 D/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
Dalmatian Fire Page 5 of 42 02/21/2020
Since 1926
III� 1 �Yi
SNAMBAUGH &SON, LP.
mr1lR�tloM1s•1xaa1�l5•StM+iR
Y+FNM1�Ii�11�0Y
Device Type
Drain
Drain
Drain
Drain
Drain
Drain
Drain
Gauge
� Gauge
Gauge
Gauge
Gauge
Gauge
Gauge
Gauge
Gauge
Gauge
Gauge
Air Compressor
Backflow Prevention
f� -:�
�a� " `�
Da en
�
ILocation
floor 4 end of hallway
floor 4 end of hallway
floor 4 stair 3
floor 5 stair 3
floor 6 stair 3
floor 7 stair 3
hallway
floor 2 stair 3
floor 3 stair 3
floor 4 end of hallway
floor 4 end of hallway
floor 4 end of hallway
floor 4 stair 3
floor 5 stair 3
floor 6 stair 3
floor 7 stair 3
floor 7 stair 3
hal Iway
floor 4 end of hallway
Penthouse 5 th floor west end go out on the
roof
Seroice
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Backflow Prevention pump room water meter A133 behind
restau rant
Backflow Prevention pump room water meter A133 behind
restau rant
Backflow Prevention water pump room
Backflow Prevention water pump room
Controi Valve floor 2 stair 3
Control Valve floor 3 stair 3
Control Valve floor 4 end of hallway
Control Valve floor 4 stair 3
Control Valve floor 5 stair 3
Control Valve floor 6 stair 3
Control Valve floor 7 stair 3
Control Valve hallway
Dry Pipe Valve floor 4 end of hallway
Wet Pipe
Backflow Prevention water pump room
Dry Pipe, Zone-1,5,6
Air Compressor
Dry Pipe, Zone-2
Pressure Switch
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Annual
Failed/Other
Untested
Basement The Residence Riser Room
Basement
Annual
i . ORTHSTAH FIflE PRO C?10N OF TE%AS
A Oivifiox or Sx��e�ucx d Sox.�L.P.
I Time � Date �
1:58:46 PM
1:58:54 PM
2:39:06 PM
2:33:00 PM
2:29:17 PM
2:23:07 PM
2:50:26 PM
2:45:00 PM
2:41:37 PM
1:57:56 PM
1:58:13 PM
1:58:27 PM
2:38:48 PM
2:33:14 PM
2:29:29 PM
2:22:54 PM
2:23:44 PM
2:50:58 PM
1:59:09 PM
2:18:51 PM
11 /01/2019
11/01/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
11/01/2019
11/01/2019
11/01/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
11/01/2019
11/01/2019
11:57:31 AM 11/01l2019
11:57:52 AM 11/01/2019 I
11:11:53 AM
11:26:16 AM
2:45:08 PM
2:41:47 PM
1:44:04 PM
2:38:57 PM
2:33:56 PM
2:29:48 PM
2:22:45 PM
2:50:40 PM
1:59:24 PM
11 /01 /2019
11 /01 /2019
10/17/2019
10/17/2019
11 /01/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
10/17/2019
11 /01/2019
11:20:56 AM 11 /01/2019
Dalmatian Fire Page 6 of 42 02/21/2020
�� ,
�r .�.� ,� �:� .
SHAMBAUGN & SON. LV. �[IIIIf41W11
mw�R�noM1s•nmxmR�Stnxs i ' FIRE' � C'IOhO! TEXA3
Y���W . .. . �i o�vi.iu. or s-x..e.ucx a 9ou. L.P.
Device Type 1
Pressure Switch
Drain
Drain
Gauge
Gauge
Gauge
Gauge
Quick Opening Device
Control Valve
Dry Pipe Valve
Dry Pipe, Zone-2,3,4
Air Compressor
Dry Pipe, Zone-3
Pressure Switch
Pressure Switch
Drain
Drain
Gauge
Gauge
Gauge
Control Valve
Dry Pipe Valve
Dry Pipe, Zone-4
Pressure Switch
Pressure Switch
Drain
Drain
Gauge
Gauge
Gauge
Control Valve
Dry Pipe Valve
Dry Pipe, Zone-5
Pressure Switch
' Pressure Switch
Drain
� Drain '
Gauge
Gauge
Gauge
Control Valve
Dry Pipe Valve
Dry Pipe, Zone-6
Pressure Switch
Location
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement The Residence Riser Room
Basement The Residence Riser Room
Basement The Residence Riser Room
Basement The Residence Riser Room
Basement The Residence Riser Room
Basement The Residence Riser Room
Basement The Residence Riser Room
Basement The Residence Riser Room
Basement The Residence Riser Room
Basement The Residence Riser Room
� Service
Time Date
Dalmatian Fire Page 7 of 42 02/21/2020
III�I,I
SHAMBAUGX 850N, LP.
mxnucrau. wum�as. s[x+rt
r�ema.r.e
Device Type
Pressure Switch
Drain
Drain
Gauge
Gauge
Gauge
Gauge
Quick Opening Device
Control Valve
Dry Pipe Valve
Dry Pipe
Drain
Drain
Drain
Drain
Drain
Drain
Drain
Drain
Drain
Drain
Wet Pipe, Building
Tamper Switch
Tamper Switch
Tamper Switch
Gauge
Gauge
Gauge
Gauge
� Gauge
I Controller
' Electrical Driver
Fire Pump Gauge
� Fire Pump Gauge
Jockey Controller
Jockey Pump
Pump
Sprinkler Box
Sprinkler Box
Check Valve
Check Valve
Check Valve
Control Valve
Control Valve
Control Valve
w�. ti�
�almat�n
�
� Location
Basement The Residence Riser Room
Basement The Residence Riser Room
Basement The Residence Riser Room
Basement The Residence Riser Room
Basement The Residence Riser Room
Basement The Residence Riser Room
Basement The Residence Riser Room
Basement The Residence Riser Room
Basement The Residence Riser Room
Basement The Residence Riser Room
zone 5 parking garage
zone 5 parking garage PDA6
zone 5 parking garage TA6. PMA. 4 room
zone 5 parking garage TA5 ENVAC
zone 5 parking garage
zone 5 parking garage
zone 5 parking garage
zone 6 parking garage
zone 6 parking garage
zone 6 parking garage
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
Basement
easement
Basement
Basement
Basement
Basement
IService
'k
NORT FIREPPO 'IOMOrTETAB
m m�uo. ar 8u.ue�ucx i B�ox. l.v-
Time Date
Dalmatian Fire Page 8 of 42 02/21/2020
�f _A.�,L '
SHAMBAUGH & SON, LP.
u�cu+[[in•surxf
N�O�W�q�q
Device Type � Location
Control Valve Basement
Control Valve Basement
Control Valve Basement
Control Valve Basement
Control Valve Basement
Control Valve Basement
Control Valve Basement
Control Valve Basement
Control Valve Basement
�� . S I�
�al�
Wet Pipe, Zone-1
WaterFlow Switch Basement The Residence Riser Room
Drain Basement The Residence Riser Room
Gauge Basement The Residence Riser Room
Gauge Basement The Residence Riser Room
Sprinkler Box Basement The Residence Riser Room
Sprinkler Box Basement The Residence Riser Room
Control Valve Basement The Residence Riser Room
Wet Pipe, Zone-1,5,6
Gauge
Control Valve
Wet Pipe
WaterFlow Switch
Waterflow Switch
Waterflow Switch
WaterFlow Switch
Drain
Drain
Drain
Drain
Expansion Tank
Gauge
Gauge
Gauge
Gauge
Gauge
Backflow Prevention
Backflow Prevention
Control Valve
Control Valve
Control Vaive
Control Valve
Basement The Residence Riser Room
Basement The Residence Riser Room
floor 1 stair 2
floor 1 stair 5
floor 2 stair 2
floor 3 stair 2
floor 1 stair 2
floor 1 stair 5
floor 2 stair 2
floor 3 stair 2
floor 3 stair 2 penthouse
floor 1 stair 2
floor 1 stair 5
floor 2 stair 2
floor 3 stair 2 penthouse
floor 3 stair 2
4th DSV
fire pump room
floor 1 stair 2
floor 1 stair 5
floor 2 stair 2
floor 3 stair 2
lService
.�.
...� '..`...c�.vn-v cua
A �i�if�ox o� Sx��aAu[x 8 Sox. L.V.
Time � Date
Dalmatian Fire Page 9 of 42 02/21/2020
IIII 1 � t. Ar �
i' :t ■
• . /w.AS
SHAMBAUGX & SON, LA. �9�m�A�
m�+•���� YYI�11 �
r�umm+.n' �,
Wet Pipe Fire Sp�inkler S'ystems
Generated by: BuildingReports.com
. ORTHSTRP FIPE PROTECTI04� S
i orviuo+ o� sx.�eeucx i Sox. l.v.
Building: Carmel City Center Pedcor -
61155
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details
as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then
that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Air Compressor
Location l Mfr. � Model # I Phase On psi Off psi � Serial No. I
floor 4 end of hallway � General 1 phase 36
Rated
Type _ Description Speed
Automatic Tank
I
Horsepower I Volts _ Amps 1 OK� ScanlD
.17 115..... 5.2...... � 40501862
230 2.6
Alarms
Pressure Switch
Type Description
Pressure Switch Alarm
Low Supervisory
Waterflow Switch
Type Manufacturer
Vane Potter Electric
Vane Potter Electric
Vane Potter Electric
Vane Potter Electric
Vane Potter Electric
Vane Potter Electric
Vane Potter Electric
Vane Potter Electric
Vane Potter Electric
Vane Potter Electric
Vane Potter Electric
Backflow Prevention
Manufacturer I Low I High Zone/Address I OK I ScanlD
System Sensor 1 � 40501748
System Sensor 15 1 � 40501859
Model #
Sec Size � ZonelAddress
51 2 1
45 2 1
35 2 1
57 2.5 1
31 3 1
34 2.5 1
31 3 1
3 1.
3 1
2.5 1
2.5 1
Components
OK
�
�
�
�
�
�
�
❑
❑
❑
❑
Manufacturer
Watts
ScanlD
40503401
Initial Test
ScanlD
40501720
40501724
40501728
40501733
40501737
40501742
40501716
40501703
40501746
40501706
40501713
Model # Size Type Service Type I Install Date I
4000B 1.25" Reduced Pressure Fire Line 07/08/2016
Water Purveyor Location Meter Account # I Serial Number
Penthouse 5 th floor west end go out A00376
on the roof
Check Valve 1 Check Valve 2 Relief Valve � Pressure Vacuum Breaker
Dalmatian Fire Page 10 of 42 02/2]/2020
'� . .'_• i�l
SHAMBAUGH�&�N,� L�P.
Y♦�0�q
8.1
Held At
Final Test
Check Valve 7
8.0
Repairs or Notes
0.0
� Check Valve 2
Held At �Condition of Control Valve 7
Backflow Prevention
,��
118�118�18d1
�
2.1
1�, .F,��or �& �
_" __ ....._ ._...__ . ... ..... ....
A D�vi[�e� Of Sxa�a�ucx 6 9oW. l.V.
Relief Valve IPressure Vacuum Breaker
� Condition of Control Valve 2
Manufacturer Model # Size ,Type IService Type
Wilkins 375 3" Reduced Pressure Potable
ScanlD Water Purveyor Location Meter Account #
40503402 pump room water meter A133 behind
restaurant
Initial Test
Install Date
07/08/2016
Serial Number
L66575
Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker
�8.3 8.0 2.0
Held At Repairs or Notes
Installed complete new rubber kit on &11-16
Final Test
Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker
8.0 Closed Tight 2.0
Held At Condition of Control Valve 1 ICondition of Control Valve 2
Backflow Prevention
Manufacturer Model # Size Type Service Type
Wiikins 375 3" Reduced Pressure Potable
ScanlD Water Purveyor I Location Meter Account #
40503403 pump room water meter A133 behind
restaurant
Initial Test
' Instali Date �
07/08/2016
.Serial Number
L65913
Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker
9.2 -- -- — — 6.6 2.0
Held At I Repairs or Notes
Installed complete new rubber kit on 8-11-16
Final Test
Check Valve 1
8.0
Held At
Check Valve 2 Relief Valv
5.0
Condition of Control Valve 1
Backflow Prevention
3.0
e _ �Pressure Vacuum Breaker
, Condition of Control Valve 2
Dalmatian Fire Page 11 of 42 02/21/2020
a� �{���
'� l �. .. l, [IO��
SHAMBAU6N & SON, LP.
Enoer.[is•sr�un
Y`OW�fY�p �
Manufacturer IModel # �Size IType
Wilkins 975XL 2" Reduced Pressure
:ScanlD �Water Purveyor �Location
I40503397 water pump room
Initial Test
Check Valve 1 Check Valve 2 Relief Valve
9.0 8.9 3.9
Held At � Repairs or Notes
Final Test
Check Valve 1 � Check Valve 2 � Relief Valve I Pressure Vacuum Breaker
Held At ICondition of Control Valve 1 ICondition of Control Valve 2
Backflow Prevention
Manufacturer Model # Size IType
Wilkins
ScanlD
40503399
linitial Test
I Check Valve 1
7.8
Held At
I
,final Test
350XL 2" Double Check
Water Purveyor Location
water pump room
, Check Valve 2 i Relief Valve
8 2.8
I Repairs or Notes
�'Check Valve 1
� Held At
Check Valve 2 _ _
Condition of Control Valve 1
'f� �.
NOR I• FIRE P �OH & 7E%AS
A Divi[io� oo Sx�ve�u:x 8 90u, L.V
Service Type Lnstall Date �
Potable 07/08/2016
�MeterAccount# lSerial Number
60566054 W252455
Pressure Vacuum Breaker
Service Type I Install Date I
fountain 07/08l2016
Meter Account # Serial Number l
022737 A320666
1
� Pressure Vacuum Breaker
Relief Valve 1Pressure Vacuum Breaker
Condition of Control Valve 2
2.3
Backflow Prevention
Manufacturer Model # Size Type
Wilkins 975XL 2" Reduced Pressure
ScanlD Water Purveyor Location
40503398 water pump room
Initial Test
Check Valve 1
9.0
Held At
Final Test
Check Valve 1
�Check Valve 2
3.5
I Repairs or Notes
, Check Valve 2
2.7
Service Type Install Date
Potable 07/08/2016
Meter Account # Serial Number
43408952 2387356
I Relief Valve
f 3.3
Relief Valve
; Pressure Vacuum Breaker
I Pressure Vacuum Breaker
Dalmatian Fire Page 12 of 42 02/21/2020
ll�'�' :, - .-:�
• t �8�m8
srw��aaucx a soN, �v.
mMm.crcRs•uaauws. suus�
Y�F��Eeql�oY ��
Held At +Condition of Control Valve 1 �
Backflow Prevention
Manufacturer Model # Size Type
Watts 4000B 2" Reduced Pressure
ScanlD WaterPurveyor ILocation
40503400 4th DSV
lnitial Test �� �
Check Valve 1 � Check Valve 2 Relief Valve
9.8 Closed TighU9.4 2.8
Held At Repairs or Notes
! Leak on #2 check nipple Antifreeze -4
Final Test
Check Valve 7 Check Valve 2 Relief Valve
Held At Condition of Control Valve 1 �
Backflow Prevention
Condition of Control Valve 2
Service Type Install Date
Fire Line 07/08/2016
1Meter Account # I Serial Number
Condition of Control Valve 2
Wilkins
ScanlD
40503396
Initial Test
�Model # �Size �Type
360A 8" Double Check
Water Purveyor Location
fire pump room
Service Type
Fire Line
� Meter Account #
Install Date
07/08/2016
Serial Number
U01853
Check Valve 1
Held At
Final Test
Check Valve 2
Repairs or Notes
Check Valve 1 Check Valve 2 � Relief Valve � Pressure Vacuum Breaker I
Held At ICondition of Control Valve 1 �Condition of Control Valve 2
2.2 2.2
Control Valve
Type Manufacturer � Model Location � Size I Position Status OK ScanlD
Butterfly Victaulic floor 2 stair 3 2 Open Supervised � 40501721 �
Description
Main Control
Control Valve
Type IManufacturer f Model Location Size Position Status OK ScanlD
Butterfly Victaulic floor 3 stair 3 2 Open Supervised � 40501725 i
Dalmatian Fire Page 13 of 42 02/21 /2020
A320666
Pressure Vacuum Breaker
Pressure Vacuum Breaker
,� ,
ONTHS � � ION OF TE.xAS
� Olvlii0x af Sx�ve�U4x E Sox. �.P
Relief Valve I Pressure Vacuum Breaker
lll�l�i.
SWIMBAUGM &SON, LP.
cnxn�cras•fxcu�¢�u•uart
r�rum�troq.v
Description
Main Control
Control Valve
Type Manufacturer Model
Butterfly Victaulic
Description
Main Control
Control Valve
Type Manufacturer Model
Butterfly fVictaulic
�Description
Main Controi
Control Valve
Type � Manufacturer Model
ButterFly Victaulic
Description
Main Control
Control Valve
Type I Manufacturer Model
Butterfly Victaulic
1 � �� � �
y{l4��(IuYli L \ORTHSTRPFIREPRO .+OhOFTEY,AS
�-�� A oir�aio. or s...exucx a sux, i.r.
Location � Size j Position Status OK I ScanlD I
floor 4 end of 2„ Open Supervised � 40501691
hallway
_ 1
Location Size Position Status OK ScanlD
floor 4 stair 3 2 Open Supervised � 40501729
l
Location 1Size �Position �Status OK ScanlD �
floor 5 stair 3 2.5" Open Supervised � 40501734
l
Location ISize IPosition �Status � OK ScanlD
floor 6 stair 3 3" Open Supervised � 40501738
Main Control
Control Valve
Type Manufacturer Model
Butterfly Victaulic
Description
Location �Size IPosition Status OK ScanlD
floor 7 stair 3 2.5" Open Supervised � 40501741
Main Control
Control Valve
Type Manufacturer �Model
ButterFly Victaulic
Description
I Location 1Size I Position Status OK ScanlD �
hallway 3" Open Supervised � 40501717 �
Main Control
Control Valve
Type Manufacturer Model
Butterfly Victaulic
Location I Si
floor 1 stair 2 3"
Description
Position Status
OK ScanlD
❑ 40501701
Main Control
Control Valve
Type � Manufacturer Model
ButterFly Victaulic
Location� Si
floor 1 stair 5 3"
Position �Status OK ScanlD
❑ 40501745
Dalmatian Fire Page 14 of 42 02/21/2020
I' ...`'�. �
SHAMBAUGH & SON, LP.
mxm�noxs•waxeus. srmu
4�Fllm�ta�q
Description
Main Control
Control Valve
Type IManufacturer Model
Location Size I Position
Butterfly Victaulic. floor 2 stair 2 2.5
Description
Main Control
Control Valve
�Type Manufacturer Model Location Size Position
I ButterFly Victaulic floor 3 stair 2 2.5"
Description
Main Control
Dry Pipe Valve
Manufacturer Model # Location
Victaulic S/768 floor 4 end of haliway
Type Status IPosition
Grooved Sealed
Water psi �Air Pressure Trip Air Trip Time
145 26 5
Devices
Drain
Size Supply psi --------� Residual psi Sec OK ScanlD
psi ,
1.25" 155 51 � 40501722
1.25" 150 45 � 40501726
Internal Date
11l01/2019
Size
2"
Total Timing
(sec)
Type Location
Combination floor 2 stair 3
Combination floor 3 stair 3
Current Inspection
Main floor 4 end of haliway
Previous Inspections
October 18, 2018
Type Location
Main floor 4 end of hallway
December 8, 2077
Type Location
Main floor 4 end of hallway
Current Inspection
Type Location
Main floor 4 end of hallway
0.75" 26
Status
OK ScanlD
❑ 40501714
OK I ScanlD J
� 40501861
Serial # _ l
Partial Trip
Date Full Trip Date
11/01/2019 11/01/2019
�i 40501855
Size Supply psi Static psi �Residual psi ISec OK I ScanlD
0.75" 26 � 40501855
�Size Supply psi Static psi IResidual psi ISec OK I ScanlD l
0.75" 26 � 40501855 �
Restored
Size Supply psi Residual psi Sec OK ScanlD
psi
0.75" 145 � 40501856
Previous Inspections
October 18, 2018
: . '' :�
Dalma6a�
�,
, Ou •_ • 0.01ECT.IONOFTEYAS
R Urvi�iox or Sx��o�u4x f SOx. L.P.
Status OK ScanlD
❑ 40501708
Dalmatian Fire Page 15 of 42 02/21/2020
�1 . _I.,'i..
SHAMBAUGH &SON, LP.
mxnucrcu • wowF[as• ve�rt
w`am��+w
Type I Location
Main floor 4 end of hallway
� K � �
�` 1 �
•�] �y}����h
{i��(�{��1 OR TRRFIREPROTEC*q1.OFiEXAS
— _- ... p orrinon or se..eeucx a sox.�i.a,
Size Supply psi �Static psi Residual psi .Sec I OK � ScanlD 1
0.75" 145 � 40501856
December 8, 2017
Type Location Size Supply psi Static psi � Residual psi I Sec OK ScanlD
Main floor 4 end of hallway 0.75" 145 � 40501856
Type Location
Combination floor 4 stair 3
Combination floor 5 stair 3
Combination floor 6 stair 3
Combination floor 7 stair 3
Combination hallway
Combination floor 1 stair 2
Combination floor 1 stair 5
Combination floor 2 stair 2
Combination floor 3 stair 2
Expansion Tank
Size Supply psi psstored Residual psi Sec OK ScanlD
1.25" 145 35 � 40501730
1.25" 145 57 � 40501731
1.25" 135 31 �i 40501735
1.25" 130 34 � 40501740
1.25" 160 31 � 40501718
1.25" 155 ❑ 40501702
1.25" 160 ❑ 40501744
1.25" 155 ❑ 40501707
1.25" 140 ❑ 40501712
�or 3 stair 2 penthouse
Gauge
Size
Maximum
Pressure
2.1
gallons
Current Pressure I UL Listed OK ScanlD
❑ 40501710
Location
floor 2 stair 3
Type Manufacturer Model #
Supply Pressure Ashcroft
Gauge
Service Date
07/08/2016
�Static psi Fill Type ISize OK � ScanlD
155 1/4 � 40501719
Location
floor 3 stair 3
Type Manufacturer Model #
�Supply Pressure Ashcroft
Gauge
�Service Date I
07/08/2016
_ � Static psi I Fill Type ISize OK ScanlD �
150 1/4 � 40501723
ILocation
floor 4 end of hallway
Type Manufacturer
Air Pressure Victaulic
Gauge
Location
floor 4 end of hallway
Type Manufacturer
Supply Pressure Victaulic
Model #
Model #
Service Date I
07/08/2016
Static psi I Fill Type Size OK ScanlD I
26 1/4 � 40501860 I
Service Date
07/08/2016
Static psi Fill Type _ Size OK� ScanlD
145 1/4 �, 40501858 I
Dalmatian Fire Page 16 of 42 02/21/2020
'f . 1.�'i. �
SHAMBAUGN & SON, L.P.
eaYnueieu•rxo�s.uwia
a�nrm��s�n.e
Gauge
.,-�
��` �:a��
YIFAEI �1
�t
ORTHSTRR FIRE 7fl0 . �ON OF TEXAS
A D�v��iox o� Sx�Ma�ucx i Sox. L.P.
� Location
�floor 4 end of hallway
Type Manufacturer (Model #
Supply Pressure Victaulic
Gauge
145 1/4 � 40501857
Location
floor 4 stair 3
iType Manufacturer Model #
�Supply Pressure Ashcroft __
' Gauge
IService Date
07/08/2016
Static psi Fill Type Size � OK ScanlD
145 _ 1/4 �i 40501727
Location
floor 5 stair 3
Type Manufacturer Model #
Service Date
07/08/2016 � �
Static psi IFill Type ISize ' OK � ScanlD
5upply Pressure Ashcroft 145 1/4 � 40501732
Gauge
Location Service Date
floor 6 stair 3 07/08/2016
Type Manufacturer IModel # ;Static psi �Fill Type Size OK ScanlD
Supply Pressure Ashcroft 135 1/4 � 40501736
Gauge
Location Service Date
floor 7 stair 3 07/08/2016
Type IManufacturer � Model # Static psi Fill Type Size OK ScanlD
Supply Pressure Argco 130 1/4 � 40501739
Gauge
Location
floor 7 stair 3
Type Manufacturer Model #
System Pressure Argco
Gauge
Service Date
07/08/2016
Static psi IFill Type Size OK ScanlD
130 1/4 �i 40501743
5ervice Date
07/08/2016
Location
hallway
Type
Service Date
07/08/2016
Manufacturer Model # Static psi IFill Type Size OK , ScanlD
Supply Pressure Ashcroft 155 1/4 � 40501715
Gauge
floor 1 stair 2
Type Manufacturer __ Model #
Supply Pressure Ashcroft
Dalmatian Fire
Service Date
07/08/2016
Static psi IFill Type ISize � OK i ScanlD
155 1/4 ❑ 40501704
Page 17 of 42
02/21/2020
11 .a, �' L. . J1
SHAMBAUGH i SON, L.D.
mrmuttais • u+owvns • s.wcx
N�9100�4M�m
Gauge
i . •::�
�I�
�2
N6RTN5...:. .. �Tq1.�
A D�vi�iox a� Sx4�e�ucx 8 Soq, L.P
Location
Floor 1 stair 5
Manufacturer
� Service Date
07/08/2016
Model # IStatic psi Fill Type
Size OK � ScanlD
System Pressure Ashcroft
165
Gauge
Location
�floor 2 stair 2
+.Type Manufacturer �Model #
Supply Pressure Ashcroft
Gauge
Service Date
07/08/2016
J Static psi Fill Type
150 �
1/4 ❑ 40501747
Size OK ScanlD
1/4 ❑ 40501705
Location
floor 3 stair 2 penthouse
Type Manufacturer
System Pressure Ashcroft
Gauge
Model #
Service Date
07/08/2016
_ Static psi Fill Type
150
Location
floor 3 stair 2
Type Manufacturer
System Pressure Ashcroft
Model #
I Service Date
07/08/2016
Static psi Fill Type
140 �
Size OK _ ScanlD
1/4 ❑ 40501709
Size OK I ScanlD 1
1/4 ❑ 40501711
Building: Carmel City Center Pedcor - Building
61155
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details
as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then
that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
COiZt)'OIIBY
Manufacturer �odel # Location _ I Install Date � Serial Number l
, FireTrol FTA1000--AM100B Basement 07/08/2008 598118-01 RE
AC Power I Time Meter l Start psi Stop psi I Battery Supervised I Generator Backup I
� Normal Phase 150 175 No Yes
�- —
� Elect�ical
� Manufacturer I Model # Location I Serial Number ScanlD
WEG 365TS Basement 40500605
TimingMin/Sec �
Full Run Volts � Amps Horsepower Rated Speed�
10 minutes 460 111 100 3560
� Fire Pump Gauge
, Location Discharge psi Suction psi OK ScanlD
Basement ❑ 40501683
Basement ❑ 40501684
COIZti"OIIBY
Dalmatian Fire Page 18 of 42 02/21/2020
' ��
� '� �
.
� eAUGN��&�5 N�,LP.
5 .� �almat�
Y♦�O�y ��.
Manufacturer Model # Location Install Date
FireTrol FTA500-BF02B-BN Basement 07/08/2008
AC Power I Time Meter Start psi 5top psi I Battery Supervised I
Normal Phase 160 175 ` No
I Jockey Pumps
Manufacturer Model # Location Install Date
Grundfos CR3-11 Basement 07/08/2008
Power On Type � Turn On psi Turn Off psi Volts
Automatic 160 175 460
Pump
Manufacturer � Model # Location
Peerless 5AEF11 G Basement
Serial Number j Type
757285 � Pump Primary
�ORTHS�� FIREPPOTEC'q1u0�TEXAS
R Oivi�io� or 8x��e�ucx b Box., L.V.
I Serial Number
457566-04 RE
Generator Backup
Yes
Serial Number
_ I _ Horsepower
1.5
Install Date Rated Speed
07/08/2008 3550
Orientation I Impeller Size
Horizontal 8.43
Alarms
Tamper Switch
Type
Lever
Lever
Lever
OK� ScanlD
■
40501675
40501672
40501680
Compo�ents _ _
Check Valve
Type Location Internal Date Size OK ScanlD
_ , - -- --
Grooved Basement 07/08/2016 8" ❑ 40501682
Grooved Basement 07/08/2U16 8" ❑ 40501687 �
Grooved Basement 07/08/2016 6" ❑ 40501754 �
Control Valve
Type Manufacturer Model Location Size Position 5tatus OK ScanlD
OS&Y Clow 2638 Basement 8" ❑ 40501673
Description _ _ I
Isolation
Control Valve
Type Manufacturer Model Location Size � Position Status OK ScanlD
OS&Y Clow 2638 Basement 8" ❑ 40501674
Description
Isolation
Control Valve
:Type Manufacturer Model Location Size Position Status OK ScanlD
Butterfly Victaulic 728 Basement 1" ❑ 40501676
Description J
� Suction
Dalmatian Fire Page 19 of 42 02/21/2020
� Description
Supervisory
Supervisory
Supervisory
Manufacturer
Potter Electric
Potter Electric
Potter Electric
ZonelAdd ress
1
1
1
1� .. ! i. .
SHAMBAUGX�B� N, L.P.
.smn¢
Y«�C�q�v1
Control Valve
Type I Manufacturer Model
OS&Y Kennedy KS FW
Description
�
NORTNSTRft FIRE PPOlEC10N D� TEXAS
A Diriiiox os 6x�uo�ucx 8 Sox. L.P.
Location � Size � Position ; Status
Basement 8"
�� ::�
�IU��W'
�
❑ 40501681
�Suction _ _
Control Valve
Type Manufacturer Model Location Size ' Position I Status
Butterfly Victaulic 728 Basement 1"
Description
Discharge
Control Valve
�Type Manufacturer Model Location Size Position � Status
ButterFly Victaulic 707 Basement 8"
Description
Isolation
Control Valve
Type I Manufacturer I Model Location I Size Position Status
ButterFly Victaulic 705W Basement J 8"
Description
� Discharge
OK ScanlD
❑ 40501685
OK ' ScanlD
❑ 40501689
Control Valve
Type Manufacturer Model Location Size Position Status
IButterfly Victaulic 705W Basement 8"
Description
�By-pass
Control Valve
=Type Manufacturer I Model Location Size Position Status
�Butterfly Victaulic 705W Basement 8"
Description
By-pass
Control Valve
;Type I Manufacturer I Model Location , Size l Position Status
ButterFly Victaulic 705W Basement 8"
Description
Isolation
Control Valve
OK ScanlD
❑ 40501679
Type I Manufacturer Model Location � Size �Position Status
Butterfly Victaulic 705W Basement 8"
Description
OK I ScanlD
❑ 40501749
Isolation
OK ScanlD
❑ 40501690
OK ScanlD
❑ 40501677
OK ScanlD I
❑ 40501678
--1
OK ScanlD
Dalmatian Fire Page 20 of 42 02/21 /2020
11�`.' i .1
SNAMBAUGH & SON. L.P.
taxrnu om•murtu[irc•um�¢
M�F}Im�[a�p
Control Valve
Type �Manufacturer IModel
Butterfly Victaulic 705W
Description
Isolation
`� '��
11{1���
Devices
Gauge
� Location
� Basement
Type Manufacturer
Supply Pressure Argco
Gauge
Location
Basement
Type fManufacturer
Supply Pressure Argco
Gauge
Service Date �
07/08/2016
I Static psi I Fill Type
175
Service Date
07/08/2016
Static psi Fill Type
175
�Location ISize �Position ,Status OK ' ScanlD
Basement 8" ❑ 40501753
Model #
2009
Model #
2009
�
� ' PPr.. pHp'TEXAS
A Uiuif�nx o� Su��eaucx E Sou. l.V.
�Size OK ScanlD
1/4 0 40501686
�
_Size OK ScanlD �
1/4 ❑ 40501688
I Location
IBasement
IType Manufacturer
ISupply Pressure Argco
Gauge
Basement
Type Manufacturer
Service Date
07/08/2016
I Model # Static psi Fill Type
2009 175
Model #
Size OK I ScanlD
1/4 ❑ 40501750
Service Date
07/08/2016
Static psi I Fill Type
Supply Pressure Argco
Gauge
2009 175
Size OK I ScanlD �
1/4 ❑ 40501751 �
Location
Basement
Type Manufacturer Model #
Supply Pressure Ashcroft 2009
Sprinkler Box
Service Date I
07/08/2016
Static psi Fill Type Size , OK ScanlD
165 1/4 ❑ 40501752 �
Q� Tool SIN List? Size Manufacturer Location
Available?
2 Yes 12 unit Unknown Basement
2 Yes 12 unit Unknown Basement
OK
❑
❑
ScanlD
40501776
40501777
Building: Carmel City Center Pedcor - Zone-1
61155
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details
as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then
that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Dalmatian Fire Page 21 of 42 02/21 /2020
11 ...'..'t .
SHAMB0.UGH & SON. LP.
canmuciaa•eaam[ns•s[ientt
Y�N�oO�pMe�'
Waterflow Switch
Type I Manufacturer I Model #
Vane Potter Electric VSR
:• . �"'3
Dalmatian
�
Alarms
� Sec
Components
Control Valve
Type I Manufacturer I Model
Butterfly Victaulic 705W
Description
1 ORM.TRRFIpE P0.0TEC71IX.OF TEIUS
A D�visiox oF Sx��e�ucx 1 Sox. L.P.
Size ZonelAddress I OK I ScanlD
4" 1 ❑ 40501801
I Location Size Position I Status OK ScanlD
Basement The
Residence 4" ❑ 40501802
Riser Room
Main Control
Drain
Type Location
Combination Basement The Residence
Riser Room
Gauge
Devices
Size Supply psi �Sstored IResidual psi Sec I OK ScanlD
2" ❑ 40501803
Location
Basement The Residence Riser Room
Type Manufacturer
Supply Pressure Argco
Gauge
� Service Date
07/08/2016
Model #_ Static psi Fill Type _ ISize OK ScanlD
2009 120 1/4 ❑ 40501799
Location
Basement The Residence Riser Room
Type Manufacturer
System Pressure Wika
Sprinkler Box
Service Date
07/08/2016
I Model # IStatic psi � Fill Type
2009 115
Size , OK � ScanlD �
1/4 ❑ 40501800
Tool
�ty Available? SIN List? Size
13 No 12 unit
12 No 12 unit
Unknown
Unknown
Basement The �
Residence Riser Room
Basement The �
Residence Riser Room
40501815
40501816
Building: Carmel City Center Pedcor -
61155 Zone-1,5,6
� This section lists out adl the devices and components that have been associated with a Wet Pipe System and provides details
as to type of component, pressure readings, response time> etc. If a component has an OK checkbox that is checked, then
that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Components
Control Valve I
Manufacturer Location OK ScanlD
Dalmatian Fire Page 22 of 42 02/21/2020
11 � � ",�:.J
SXAMBAUGN & SON, LV.
fnwrton.suu�
b Ole^p
�Type IManufacturer �Model
; --- -
Butterfly Victaulic 705
Description
� Isolation
�
�
� Gauge
Location
Basement The Residence Riser Room
Type Manufacturer
Supply Pressure Argco
:�. ��`:!
���I'dUBA
�Location ISize Position IStatus
Basement The
Residence 6"
Riser Room
_ _ Devices
.Op . .'F '�07ENTqNOFTE%AS
• Oivi�io� oi 8x�ua� E Sox. L.V.
� OK � ScanlD
❑ 40501787
�
�
I Service Date I
07/08/2016
Model # �Static psi Fill Type Size OK ScanlD �
2009 175 1/4 ❑ 40501788
Dalmatian Fire Page 23 of 42 02/21/2020
J ■� ;� ��'�
�1� 1�
SHAMBAUGN & SON, LP. �a,m�911
wEoaus•srxxE YYI�11 011
Y♦FI�W�EYry,q �
D�y Pipe Fire Sprinkler Systems
Generated by: BuildingReports.com
- . ORTHSTRR FlRE PROiEC'IDN Or TEXAS
A Divifiox ov Sx��B�ucx i Sox. L.Y.
Building: Carmel City Center Pedcor -
61155
This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details
as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then
that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Air Compressor ,
Location Mfr. Model # Phase � On psi Off psi Serial No.
floor 7 General I 1 phase I
Rated
Type Description Speed � Horsepower Volts Amps OK ScanlD
Automatic Tank 17 115..... 5.2...... ' E 40501693
230 2.6 I
Alarms
Pressure Switch
Type � Description Manufacturer I Low I High I Zone/Address � OK ScanlD
Low Supervisory System Sensor 15 1 � 40501700
Pressure Switch Alarm System Sensor 1 � 40501694
Components
Control Valve
�Type Manufacturer Model
ButterFly Victaulic 728
Description
Main Control
Dry Pipe Valve
Location I Size � Position Status
floor 7 2" Open Supervised
Manufacturer
Victaulic
Type
Grooved
Water psi
i 135
Model # I Location
S/768 floor 7
T I Status
Sealed
Air Pressure Trip Air
32
Internal Date
Position
Trip Time
10/17/2019
� Size
2„
Total Timing
(sec)
OK � ScanlD !
� 40501697
— �
I OK I ScanlD �
�i 40501696
�Serial # �
Partial Trip
Date Full Trip Date
10! 17/2 019 10/17/2 019
Devices
Drain
Type Location Size Supply psi Restored Residual psi Sec OK
psi
Low dry stand pipe parking garage 1" �
Point
Low dry stand pipe parkin
Point 9 9arage 1" �
Dalmatian Fire Page 24 of 42
ScanlD �
40501839 �
40501840
02/21 /2020
Illh � � �.
SHAMBAl1GH & SON, LP.
<oxm�arau•ex¢w[ris• s�an�
r�um�on.n
Current Inspection
Main floor 7
Previous Inspections
October 18, 2018
Type Location
0.75"
��
I��ma1�8�
32
�t '
NOFTXST/3i FIPE PRO q# P' TEYAS
a o�vis�o.'or s.:.e.ucx 6 Sox, l.P.
J
� 40501853
Size Supply psi Static psi Residual psi ISec OK ScanlD
Main floor 7
December 8, 2017
0.75" 40
� 40501853
Type Location
Main floor 7
Current Inspection
Type Location
Main floor 7
Previous Inspections
Size Supply psi Static psi �Residual psi ISec OK � ScanlD
0.75" 40 � 40501853
�
Size Supply psi Restored 'Residual psi �Sec OK ScanlD
pSi �
0.75" 135 � 40501854
�Dctober 18, 2018
'.Type Location
Main floor 7
Size Supply psi �Static psi �Residual psi Sec OK � ScanlD
0.75" 120 � 40501854
December 8, 2017
Type
Main
Type
Low
Point
Low
Point
Low
Point
Low
Point
Law
Point
Low
Point
Low
Point
Low
Point
�
Low
Point
Low
Point
Low
Point
Location
floor 7
I
Location
zone 2 parking garage
zone 2 parking garage
zone 2 parking garage
zone 2 parking garage
zone 3 parking garage
zone 3 parking garage
zone 4 parking garage
zone 4 parking garage
zone 4 parking garage
zone 4 parking garage TA4
zone 5 parking garage
Size Supply psi ,Static psi IResidual psi Sec OK ScanlD
0.75" 120 � 40501854
Restored
Size Supply psi Residual psi Sec OK ScanlD
psi
1" �i 40501845
I
1" � 40501844 '
I
1" � 40501843
1" � 40501842
1" � 405U1841
1" � 40501838
1" � 40501846
1" � 40501851
1" � 40501852
1" � 40501833
1" ❑ 40501692
Dalmatian Fire Page 25 of 42 02/21/2020
If ... ` l'1
SNAMBAIIGM & SON, LP.
mnm�nors•f++axc[�c� s[xvia
Y�Cq�er
I Low
Point zone 5 parking garage PDA6
Low zone 5 parking garage TA6.
Point PMA. 4 room
Low zone 5 parking garage TA5
Point ENVAC
Low Zone 5 parking garage
Point
Low Zone 5 parking garage
Point
Low
Point zone 5 parking garage
Low Zone 6 parking garage
Point
Low Zone 6 parking garage
Point
�OW zone 6 parking garage
Point
� Gauge
1"
1"
1"
1"
1"
1.5"
1.5��
1.5"
1"
�`m���j�
� '�
.
,
�911YLYi1 . ,ORI FIREPNO" . qMO�TE
��� A Divisiov oF Sx�ua�u6x b Sox. L.V.
❑ 40501832
❑ 40501834
❑ 40501835
❑ 40501836
❑ 40501847
❑ 40501850
❑ 40501837
❑ 40501848
❑ 40501849
Location
floor 7
Type
Air Pressure
Gauge
Manufacturer
Victaulic
I Service Date
07/08/2016
Model # Static psi � Fill Type
32
Size OK I ScanlD
1!4 � 40501698
Location
floor 7
Type lManufacturer
System Pressure Victaulic
Gauge
Service Date
07/08/2016
�Model # Static psi 'Fill Type
135
Size � OK J ScanlD
1/4 �i 40501699
Location I Service Date
floor 7 07/08/2016
Type Manufacturer IModel # Static psi IFill Type ISize OK ScanlD
� System Pressure Victaulic 135 1/4 � 40501695
Building: Carmel City Center Pedcor -
61155 Zone-1,5,6
This section lists out adl the devices and components that have been associated with a Dry Pipe System and provides details
as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then
that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Air Compressor
Location I Mfr. Model # Phase On psi Off psi Serial No.
Basement The General
Residence Riser Room Electric
Rated
Type Description Speed Horsepower Volts Amps OK ScanlD
Dalmatian Fire Page 26 of 42 02/21/2020
1� .�!
SHAMBAUGX & SON, LP.
mrmucrae•oww�s.Qena
Y♦9m�6A�
Automatic
Tank
:� �� "�
DalmaGan
�
1725 1
* ��
N� �
A Divi�iox or Ex�rexucx l Sox, L.V.
6.2 ❑ 40501789
Building: Carmel City Center Pedcor -
61155 Zone-2
This section lists out all the devices and camponents that have been associated with a Dry Pipe System and provides details
as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then
that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Pressure Switch
Type I Description
Pressure Switch Supervisory
Pressure 5witch Alarm
AlllYrilS
_ I Manufacturer _ Low I High I 2onelAddress
System Sensor 10 1
System Sensor 1
Components
230
OK ScanlD
❑ 40501763
❑ 40501764
Control Valve
Type Manufacturer �Model Location
Butterfly Victaulic 705W Basement
Description
Main Control
Dry Pipe Valve
Manufacturer Model # Location
FireLock S/768 Basement
Type Status IPosition
Grooved
Water psi Air Pressure Trip Air Trip Time
Size 1Position
4"
Internal Date
_ Size
4"
Total Timing
(sec)
Devices
Drain
Current Inspection
Type Location
Main Basement
Previous Inspections
October 17, 2079
Type Location
Main Basement
October 18, 2018
Type I Location
Main Basement
Current Inspection
Type Location
Status OK � ScanlD
❑ 40501755
I OK I ScanlD
❑ 40501756
_ �Serial #
Partial Trip
Date Full Trip Date
12/31/1969
Restored �
Size Supply psi Residual psi Sec OK ScanlD
psi
2" 155 ❑ 40501761
Size Supply psi Static psi Residual psi � Sec OK ScanlD
2" 170 � 40501761
Size Supply psi Static psi I Residual psi I Sec OK I ScanlD
2" 155 � 40501761
Restored
Size Supply psi Residual psi Sec OK ScanlD
psi
Dalmatian Fire Page 27 of 42 02/21 /2020
II�?��'
SNAM9AUGH 8 SON, L.P.
mxmitrocs• cxwx�ric. sum¢
r���n
�n
Main Basement
Previous Inspections
October 17, 2079
_Type Location
Main Basement
October 18, 2018
Type Location
� Main Basement
� Gauge
�a� .`,�
/
UaNna�an
�
2" 155
Basement
Type � Manufacturer
System Pressure Wika
; Gauge
Size Supply psi Static psi Residual psi I Sec OK ScanlD
2" 170 � 40501762
Size Supply psi , Static psi I Residual psi I Sec OK ScanlD
2" 155 � 40501762
Service Date
07/08/2016
IModel #
2009
Static psi I Fill Type
140
Basement
Type
Air Pressure
Gauge
Manufacturer
Wika
�r
�� ORT �STRR FIPE GROIEC. i0N'JF TEXAS
a o�rv�s�o. �oo sx..ewcx a s�o.. Lv.
❑ 40501762 �
'Size OK I ScanlD
1/4 ❑ 40501757
Size OK I ScanlD I
1/4 ❑ 40501758 j
Location
Basement
Type IManufacturer IModel#
Quick Opening Wika
Device
Gauge
Service Date
07/08/2016
Model # I Static psi I Fill Type
2009 15
2009
ISize OK
1/4 ❑
ScanlD I
40501759
Location I Service Date
Basement 07/08/2016
Type Manufacturer �Model #� �Static psi IFill Type ISize I OK � ScanlD
Supply Pressure Wika 2009 155 1/4 ❑ 40501766
Quick Opening Device
Manufacturer Model # Serial # �Trip psi Low psi High psi Air Pressure OK ScanlD
Victaulic /Firelock S/746 LPA ❑ 40501760
Building: Carmel City Center Pedcor -
61155 Zone-2,3,4
This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details
as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then
that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Air Compressor
Location , Mfr. Model # Phase I On psi Off psi � Serial No.
Basement General �
Air � .
Service Date
07/08/2016
�Static psi I Fill Type
0
Dalmatian Fire Page 28 of 42 02/21/2020
!1 . ...' t . y�` �,.� �
SMAMBAWH & SON, LP. �9�j�{'OII
mxn�+aws•rx�ixmis.srwaa Pr��NuPli OFIMSTRRFINEPP YWOrTEXAS
����d�4 A Oi�ifiox o� Su�ueaucx E Box. l.V.
�,
Rated
Type Description Speed Horsepower Volts Amps OK ScanlD
Automatic Tank� 1725 1 � 230 6.2 ❑ 40501775
Building: Carmel City Center Pedcor - Zone-3
61155
This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details
as to type of coinponent, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then
that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
AZllY1iZS
Pressure Switch
; Type � Description
Pressure Switch Alarm
Pressure Switch Supervisory
I Control Valve
Type Manufacturer I Model
ButterFly Victaulic 705W
Description
rMain Control
Dry Pipe Valve
Manufacturer Model # Location
I FireLock S/768 Basement
I Type Status
Grooved
Water psi Air Pressure Trip Air
Position
I
�Trip Time
�
Devices
Drain
Internal Date OK ScanlD
❑ 40501769
Size Serial #
3"
Total Timing Partial Trip
(sec) Date Full Trip Date
--- -- - -12/31/1969 - - --- ---
Current Inspection
�Type Location
I
Main Basement
Previous Inspections
Restored
Size Supply psi Residual psi Sec OK ScanlD
psi
1.25" 150 ❑ 40501773
October 17, 2019
.Type I Location
Main Basement
October 78, 2018
Size Supply psi Static psi Residual psi Sec OK ScanlD
1.25" 170 � 40501773
�-Type I Location
Main Basement
Current Inspection
Manufacturer � Low , High � ZonelAddress � OK � ScanlD
System Sensor 1 ❑ 40501765 �
System Sensor 9 1 ❑ 40501770
Components
Location Size Position
Basement 3"
Status OK ScanlD
❑ 40501768
Size Supply psi Static psi Residual psi �Sec OK ScanlD
1.25" 150 � 40501773
Dalmatian Fire Page 29 of 42 02/21/2020
�����
SHPA1BAUGX & SON, LP.
enmiuerau•oowm¢.ssM¢
.r.um�a.wn
Type Location
Main Basement
Previous Inspections
�!�_ :.� � t �i+
:.�j�}�q�n
iryill�{�I�IYII ORTNSiARFIREPPO ?IONOfTE1U5
� n o�r�no. or sx�..o.ucx a sox. i.r.
Restored '
Size Supply psi Residual psi Sec , OK ScanlD
psi
1.25" 150 ❑ 40501774
October 17, 2019
Type Location Size Supply psi Static psi Residual psi Sec OK ScanlD
Main Basement 1.25" 170 � 40501774
:tober 18, 2018
�pe I Location Size Supply psi Static psi Residual psi Sec OK ScanlD
Main Basement
Gauge
Location
Basement
�Type 1 Manufacturer
lSupply Pressure Wika _
IGauge
_ 150 _ _
Size � OK I ScanlD
1/4 ❑ 40501767
I Location
Basement
jTYpe
�Air Pressure
Gauge
Manufacturer
�Seroice Date
07/08/2016
IStatic psi �Fill Type
1.25"
Model #
2009
Model #
2009
150
EE 40501774
Wika
19
Size I OK ScanlD C
1/4 ❑ 40501771 �
-- — -- —�
Location JService Date _ _ _ _ _�
rBasement 07/08/2016
Type �Manufacturer �Model #_ �Static psi IFill Type Size I OK I ScanlD �
� System Pressure Wika 2009 135 1/4 � 40501772
Building: Carmel City Center Pedcor -
61155 Zone-4
This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details
as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then
that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms
, Pressure Switch I
Type Description I Manufacturer I Low I High ZonelAddress OK ScanlD
Pressure Switch Alarm System Sensor 1 �❑ 40501779 �
Pressure Switch Supervisory System Sensor 9 1 ❑ 40501782
Control Valve
Type Manufacturer I Model
ButterFly Victaulic 705W
Description
Service Date
07/08/2016
IStatic psi �Fill Type
Components
Location Size I Position Status
Basement 4"
Main Control
OK ScanlD I
❑ 40501781 I
I
�
Dalmatian Fire Page 30 of 42 02/21/2020
�IIF}.��,�� ~• � i � �
SHAMBAUGN &SfJµ L.P. ��1
mmuaaas•n+r+4as•umn¢ WiNiWY�O OHfHSTFR �REPH07EC:IONOFTEfAS
'y���m�d �. R Oivisio� os Sx�uoRucx i Sox, L.P.
Dry Pipe Valve
Manufacturer Model # Location Internal Date OK ScanlD
FireLock S/768 Basement ❑ 40501780
�Type IStatus Position Size Serial #
Grooved 4"
' — Total Timing Partial Trip �
Water psi Air Pressure Trip Air Trip Time �sec) Date Full Trip Date
12/31/1969
Drain
Current Inspection
Type Location
Main Basement
Previous Inspections
October 17, 2019
Type Location
Main Basement
October 78, 2018
Size Supply psi Static psi Residual psi Sec OK ScanlD
2" 170 � 40501785
Type � Location
Main Basement
Current Inspection
Type Location
Main Basement
Previous Inspections
�Size Supply psi Static psi Residual psi Sec OK ScanlD
2" 155 � 40501785
Restored �
Size Supply psi Residual psi Sec OK ScanlD
psi
2" 155 ❑ 40501786
October 17, 2019
;Type Location
Main Basement
Devices
Size Supply psi Restored Residual psi Sec OK ScanlD
psi
2" 155 ❑ 40501785
Size Supply psi Static psi Residual psi Sec OK ScanlD
2" 170 � 40501786
October 18, 2018
Type Location
Main Basement
Gauge
Size Supply psi Static psi Residual psi i Sec OK , ScanlD
2" 155 � 40501786
Location
Basement
Type Manufacturer
Supply Pressure Wika
Gauge
IService Date
07/08/2016
Model # �Static psi IFill Type �Size � OK ScanlD
2009 155 1/4 ❑ 40501778
Location I Service Date _ J
Basement
Type Manufacturer Model #
Dalmatian Fire
07/08/2016
Static psi I Fill Type Size OK I ScanlD
Page 31 of 42 02/21 /2020
1��.. `.`'■�1
SHAMBAUGH &SON, �o.
mHAMals • umeaFAs• Ylrt'K£
M♦W�p�p
Air Pressure Wika
Gauge
'Location
Basement
�Type �Manufacturer
System Pressure Wika
2009
,� ':�
Oalmatia�
�
15
I Service Date
07/08/2016
Model # �Static psi I Fill Type
2009 140
,�NT.STAA - PI70TfCT10A0?TE1fA5
_".'"._'".___.__..._" _..__"._
R Orv��iox ar Sx�te�ucx i Sox. L.P.
1/4 ❑ 40501783
Size I OK ScanlD �
1/4 0 40501784 �
Building: Carmel City Center Pedcor - Zone-5 '
61155
This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details
as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then
that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms
Pressure Switch
Type Description � Manufacturer I Low I High Zone/Address OK � ScanlD
Pressure Switch Supenrisory System Sensor 10 1 ❑ 40501792
Pressure Switch Alarm System Sensor 1 ❑ 40501797
Control Valve
Components
_Type I Manufacturer Model � Location ! Size I Position ; Status OK � ScanlD I
Basement The �
Butterfly Victaulic 705/W Residence 4" O 40501793 �
Riser Room
Description _ _ _ �
Main Control
Dry Pipe Valve
Manufacturer Model # Location Internal Date OK ScanlD
FireLock Sl768 Basement The Residence Riser Room ❑ 40501796
Type Status I_Position _� Size __ _jSerial # �
Grooved 4"
— Total Timing— Partial Trip
Water psi �Air Pressure Trip Air Trip Time (sec) Date Full Trip Date
12/31/1969
Drain
Devices
Current Inspection
Restored
Type Location ISize ISupply psi IResidual psi iSec I OK ScanlD
psi
Main gasement The Residence Riser 2„ 120 ❑ 40501794
Room
Previous Inspections
October 17, 2019
Type Location Size Supply psi Static psi Residual psi Sec OK ScanlD
Dalmatian Fire Page 32 of 42 02/21/2020
llI 1� �. � • ���
SHAMBIIUGH�B SSON,LP. ��j%j�n
•+� NII[IW
Y+E00�p �
Main Basement The Residence Riser 2„ 120
Room
l�[
T '�+
OIiTHS FIflEPRD 'IONOFiEY.�S
� Orv�tio� or Sx�vo�ucx 6 SOM. L.P.
� 40501794
October 78, 2018
Type ILocation Size Supply psi Static psi Residual psi ISec OK ScanlD
Main Basement The Residence Riser 2„ 120 � 40501794
Room
Current Inspection
Type Location Size Su � Restored
pp y psi Residual psi Sec OK ScanlD
PS� I
Main Basement The Residence Riser 2„ 120 ❑ 40501795
Room
Inspections
17, 2019
�Type I Location _ Size Supply psi Static psi Residual psi Sec OK ScanlD
Main Basement The Residence Riser Z„ 120 � 40501795
Room
October 78, 2018
fType Location Size Supply psi Static psi ! Residual psi Sec OK ScanlD
I Main Roo� ent The Residence Riser 2„ 120 � 40501795
Location
Basement The Residence Riser Room
Type Manufacturer Model #
System Pressure Wika 2009
Gauge
Seroice Date
07/08l2016
Static psi Fill Type
115
ISize � OK � ScanlD
1/4 ❑ 40501790 �
I Location _ I Service Date J
Basement The Residence Riser Room 07/08/2016
Type Manufacturer Model # �Static psi I Fill Type ISize , OK ; ScanlD l
Air Pressure Wika 2009 15 1/4 ❑ 40501791
Gauge
Location I Service Date
Basement The Residence Riser Room 07/08/2016
Type _ Manufacturer Model # IStatic psi IFill Type Size OK � ScanlD
Supply Pressure Wika 2009 140 1/4 ❑ 40501798
Building: Cannel City Center Pedcor - Zone-6
� 61155 _ I
This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details i
as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then
that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms
Pressure Switch
Dalmatian Fire Page 33 of 42 02/2l/2020
�� . ��, `,��
SHAMBAIIGN & SON, LA.
mxm.nou•vmams•s�
r�um�o�.o'
Type
Pressure Switch
Pressure Switch
Description
Supervisory
Alarm
J �� '�
�q11YRf111
�
Manufacturer Low High I2one/Address
System Sensor 10 1
System Sensor 1
�♦
OATH'.' REPH .IONO�TElu3
,i orv�s�ox os s�..e.ucx i so.,��i.d,
1 OK � ScanlD
❑ 40501806
❑ 40501812
Components
Control Valve
Type Manufacturer I Model I Location Size Position Status
Basement The
Butterfly Victaulic 705/W Residence 4"
Riser Room
Description
Main Control
Dry Pipe Valve
Manufacturer I Model # Location Internal Date
FireLock S/768 Basement The Residence Riser Room
Type Status �Position ISize
Grooved
Water psi (Air Pressure Trip Air
4"
Trip Time Total Timing Partial Trip
(sec) Date
12/31/1969
OK I ScanlD
❑ 405U1804
OK I ScanlD
❑ 40501805
Serial #
Full Trip Date
Devices
Drain
Current Inspection
Type , Location Size Supply psi psstored Residual psi Sec OK ScanlD
Main Basement The Residence Riser 2„ 120 ❑ 40501809
Room
Previous Inspections
October 17, 2019
Type Location Size Supply psi Static psi Residual psi ISec OK ScanlD
Main Basement The Residence Riser 2„ 120 � 40501809
Room
Type � Location Size Supply psi Static psi Residual psi I Sec OK ScanlD
Main Basement The Residence Riser 2„ 120 � 40501809
Room
Current Inspection
Restored i
Type Location Size Supply psi f Residual psi Sec OK ScanlD
� psi
Main Basement The Residence Riser 2„ �20 ❑ 40501810
Room
Previaus Inspections
October 17, 2079
Dalmatian Fire Page 34 of 42 02/21/2020
11���,�.� '�.� '�
,�
�,� �
R
���&�N,�^. palrnatian
mxmaas•vrwma•suNa OR7H6TRR FIRE PROTEC*IOW b' iE1US
�°.��o � A UivitiaM o� Sxa�BauGx b 90x. L.P.
Type Location ISize �Supply psi .Static psi �Residual psi Sec OK I ScanlD
Main Basement The Residence Riser 2„ 120 � 40501810
Room
� Oetober 18, 2018
Type I Location Size Supply psi Static psi Residual psi Sec OK
Main Basement The Residence Riser 2„ 120 �
Room
Gauge
`Location Service Date
Basement The Residence Riser Room 07/08/2016
Type �Manufacturer �Model # �Static psi IFill Type ISize OK I ScanlD
Air Pressure Wika 2009 10 1/4 ❑ 40501807
Gauge
I Location I Service Date
Basement The Residence Riser Room 07/08/2016
IType Manufacturer Model # IStatic psi Fill Type Size I OK
System Pressure Wika 2009 120 1/4 ❑
' Gauge
Location Service Date
Basement The Residence Riser Room 07/08/2016
Type I Manufacturer Model # �Static psi I Fill Type �Size OK
Supply Pressure Wika 2009 125 1/4 ❑
Gauge
Location Service Date
Basement The Residence Riser Roo
Type _ Manufacturer
Quick Opening Wika
Device
Quick Opening Device
Manufacturer � Model #
Victaulic /Firelock S/746 LPA
ScanlD
40501808
ScanlD
40501811
m 07/08/2016
Model # Static psi Fill Type _ ISize OK ScanlD �
2009 15 1 /4 ❑ 40501814
Serial # Trip psi � Low psi High psi Air Pressure OK ScanlD
15 ❑ 40501813 I
40501810
ScanlD
Dalmatian Fire Page 35 of 42 02/21/2020
�i►!J� ..��.. .�. ���y=�.
SHAMeAUGH & SON, L.P. �y���
us•4un� �A��{ry� .ORTMSTARFIREPRO' C'bNbTEJ1A5
�°���4' ,._ -_.,1-_�.Y-.�.,. A Drvit�oM or Sx��e�utM 8 Box, l.V.
Inventory & Wa�ranty Report
Generated by: BuildingReports.com
Building: Carmel City Center Pedcor - 61155
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A
complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last
year, and devices installed for two years or more are grouped together for easy reference.
Device or Type � Category f % of Inventory __ Quantity
Control Valve Valve 16.93% 32
Gauge Device 23.28% 44
Check Valve Valve 1.59% 3
Dry Pipe Valve Valve 3.70% 7
Quick Opening Device Device 1.06% 2
Drain Device 25.40% 48
Pressure Switch Alarm 7.41% 14
Air Compressor Pump 2.12% 4
Sprinkler Box Sprinkier 2.12% 4
Waterflow Switch Alarm 6.35% 12
Tamper Switch Alarm 1.59% 3
Fire Pump Gauge Pump 1.06% 2
Pump Pump 0.53% 1
Electrical Driver Pump 0.53% 1
Jockey Pump Pump 0.53% 1
Jockey Controller Pump 0.53% 1
Controller Pump 0.53% 1
Expansion Tank Device 0.53% 1
Backflow Prevention Valve 4.23% 8
)evice Type � Qty1 Model # Type Description � Install Date
Dry Pipe
Air Compressor
Drain
Pressure Switch
Pressure Switch
Control Valve
Drain
Dry Pipe Valve
Gauge
Gauge
Wet Pipe
Drain
Expansion Tank
Gauge
Dalmatian Fire
In Service - 3 Years to 5 Years
1
22
1
1
1
2
1
1
2
728
S/768
Automatic
Low Point
Low
Pressure Switch
Butterfly
Main
Grooved
Air Pressure
System Pressure
Tank
2 Main
1 FPT5C
1 Supply Pressure
Page 36 of 42
Supervisory
Alarm
Main Control
�
07/08/2016
07/08/2016
07/08/2016
07/08/2016 I
07/08/2016
07/08/2016 '
07/08/2016
07/08/2016 �
07/08/2016
07/08/2016
07/08/2016
07/08/2016
02/21/2020
1���'�
SHAMBAUGH�SON,s�P.
M`�C�4�
Gauge
Gauge
Gauge
Air Compressor
WaterFlow Switch
Pressure Switch
Pressure Switch
Drain
Drain
Control Valve
Dry Pipe Valve
Gauge
Gauge
Backflow Prevention
Backflow Prevention
Backflow Prevention
Backflow Prevention
Backflow Prevention
Dry Pipe, Zone-1,5,6
Air Compressor
Dry Pipe, Zone-2
Dry Pipe Valve
Pressure Switch
Pressure Switch
Control Valve
Drain
Quick Opening Device
Gauge
Gauge
Gauge
Gauge
Dry Pipe, Zone-2,3,4
Air Compressor
Dry Pipe, Zone-3
Dry Pipe Valve
Pressure Switch
Pressure Switch
Control Valve
Drain
Gauge
Gauge
1
8
3
1
11
1
1
7
4
12
1
1
2
2
1
1
2
2
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
2
1
1
A � ��
�YI . 11
A�i�
System Pressure
Supply Pressure
System Pressure
Automatic Tank
Vane Alarm
Low Supervisory
Pressure Switch Alarm
Combination
Combination
Butterfly Main Control
S/768 Grooved
Air Pressure
Supply Pressure
4000B Reduced Pressure
350XL Double Check
360A Double Check
375 Reduced Pressure
975XL Reduced Pressure
In Service -10 Years to 15 Years
Automatic Tank
S/768 Grooved
EPS10-2 Pressure Switch Alarm
EPS45-2V Pressure Switch Supervisory
705W Butterfly Main Control
Angle Main
S/746 LPA
2009 Air Pressure
2009 Quick Opening
Device
2009 Supply Pressure
2009 System Pressure
Automatic Tank
S/768 Grooved
EPS10-2 Pressure Switch Alarm
EPS45-2V Pressure Switch Supervisory
705W Butterfly Main Control
Angle Main
2009 Air Pressure
2009 Supply Pressure
f�� �
�OR TFRFIPEPROIE .qNO�TEXAS
P Oivniox or Sx�uer,ucx i SOM, L.P.
07/08/2016
07/08/2016
07/08l2016
07/08l2016
07/08/2016
07/08/2016
07/08/2016
07/08l2016 '
07f08/2016 �
07/OS/2016 I
07/08/2016
07/08/2016
07/08/2016
07/08/2016 �
07/08/2016 ,
07/08/2016
07/08/2016
07/08/2016 �
07/08/2008 �
07/08/2008 �
07/08l2008
07/08/2008
07/OS/2008
07/08/2008
07/08/2008
07/08/2008
o�ros�2oos
07/08/2008
07/08l2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
Dalmatian Fire Page 37 of 42 02/21/2020
11 �..��,.
SIIAMBAUGX &SON, LP.
mwnucrou. �xcwma• suma
r��m.�+n
Gauge
Dry Pipe, Zone-4
Dry Pipe Valve
Pressure Switch
Pressure Switch
Control Valve
Drain
Gauge
Gauge
Gauge
Dry Pipe, Zone-5
Dry Pipe Valve
Pressure Switch
Pressure Switch
Control Valve
Drain
Gauge
Gauge
Gauge
�ry Pipe, Zone-6
Dry Pipe Valve
Pressure Switch
Pressure Switch
Control Valve
Drain
Quick Opening Device
Gauge
Gauge
Gauge
Gauge
Wet Pipe, Building
Gauge 4 2009 Supply Pressure
Gauge 1 2009 Supply Pressure
Control Valve 2 2638 OS&Y
Controller 1 FTA1000--AM100B
Jockey Controller 1 FTA500-BF02B-BN
Jockey Pump 1 CR3-11 Automatic
Control Valve 1 KS FW OS&Y
Pump 1 5AEF11 G Pump Primary
Tamper Switch 3 OSYSU-2 Lever
Sprinkler Box 2
Check Valve 3 717 Grooved
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
2009
S/768
EPS10-2
EPS45-2V
705W
Angle
2009
2009
2009
S/768
EPS10-2
EPS45-2V
705/W
Angle
2009
2009
2009
S/768
EPS10-2
EPS45-2V
705/W
Angle
S/746 LPA
2009
2009
2009
2009
�. ',�
oa�
System Pressure
Grooved
Pressure Switch
Pressure Switch
Butterfly
Main
Air Pressure
Supply Pressure
System Pressure
Grooved
Pressure Switch
Pressure Switch
Butterfly
Main
Air Pressure
Supply Pressure
System Pressure
Grooved
Pressure Switch
Pressure Switch
Butterfly
Main
Air Pressure
Quick Opening
Device
Supply Pressure
System Pressure
Alarm
Supervisory
Main Control
Alarm
Supervisory
Main Control
Alarm
Supervisory
Main Control
Isolation
Automatic
Suction
Supervisory
�
NOPTN FIREFRO qMOFTEVS
� m�i.io. -oi s�-..:.uc. L-sox. i.v.
07/08l2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
i
Dalmatian Fire Page 38 of 42 02/21/2020
11 �.� i..
SHAMBAIIGH i SON, L.P.
mnm�nou•uraxns•uxri¢
N+BIm�EM�ry
Control Valve 2
Control Valve 1
Control Valve 3
Control Valve 1
Control Valve 1
Control Valve 1
Electrical Driver 1
Fire Pump Gauge 1
Fire Pump Gauge 1
Wet Pipe, Zone-1
Drain 1
Gauge 1
Waterflow Switch 1
Sprinkler Box 2
Control Valve 1
Gauge 1
Wet Pipe, Zone-1,5,6
Gauge 1
Control Valve 1
A `� ��
.` . :�
an
Il�lfll�ll�
705W ButterFly
705W ButterFly
705W Butterfly
707 ButterFly
728 ButterFly
728 Butterfly
365TS
2008 Discharge
2008 Suction
TesUDrain Combination
2009 Supply Pressure
VSR Vane
705W ButterFly
2009 System Pressure
2009 Supply Pressure
705 ButterFly
By-pass
Discharge
Isolation
Isolation
Discharge
Suction
Alarm
Main Controi
Isolation
,.s �
.ORTX_ REPPOTEC7qAbTElUS
A �rvitiox oe Sx�ua�u6x 8 4ox, L.P.
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08l2008
07/08l2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
07/08/2008
Dalmatian Fire Page 39 of 42 02/21 /2020
Since 1974
III� J� L '�� S''� � �
•
SHAMBAUGN &SON, LP. ��11
wmw.+as•va+�s•wma 11 -
M♦F��Ltiql�d � . . . i .
Notes � Recommendations
Generated by: BuildingReports.com
Building: Carmel City Center Pedcor - 61155
_
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the �
building inspection. Notes are grouped by SystemlD. �
Note � Device Type Location Comment ScanlD
General Note
Fifth floor penthouse glycerin is at zero
Dry Pipe, Zone-2 �
2 Gauge Basement 40501759
Out of service.
3 Quick Opening Device Basement 40501760
Out of service
Dry Pipe, Zone-6
4 Quick Opening Device Basement The Residence Riser Room 40501813
IYs off
Dry Pipe
5 Drain dry stand pipe parking garage Passed 40501839
No water
6 Drain dry stand pipe parking garage Passed 40501840
No water
7 Dry Pipe Valve floor 7 Passed 40501696
Had to reset by hand
8 Drain zone 2 parking garage Passed 40501842
No water
9 Drain zone 2 parking garage Passed 40501843
No water
10 Drain zone 2 parking garage Passed 40501844
No water
11 Drain zone 2 parking garage Passed 40501845
No water
12 Drain zone 3 parking garage Passed 40501838
No water
13 Drain zone 3 parking garage Passed 40501841
No water
14 Drain zone 4 parking garage TA4 Passed 40501833
No water
15 Drain zone 4 parking garage Passed 40501846
No water
16 Drain zone 4 parking garage Passed 40501851
No water
17 Drain zone 4 parking garage Passed 40501852
No water
Dalmatian Fire Page 40 of 42 02/21/2020
�1 ..�'.• t , �n y':�
SHAM9AUGN 850N, LP. ,19I��n
cONINCfORS•UlOPY4f•suuRF YY 1�
Y♦FMm�OyAey �
Note Device Type I Location
18 Drain zone 5 parking garage
No water
19 Drain zone 5 parking garage PDA6
No water
20 Drain zone 5 parking garage TA6. PMA. 4 room
No water
21 Drain zone 5 parking garage TA5 ENVAC
No water
22 Drain zone 5 parking garage
No water
23 Drain zone 5 parking garage
No water
24 Drain zone 5 parking garage
No water
25 Drain zone 6 parking garage
No water
26 Drain zone 6 parking garage
Little water
27 Drain zone 6 parking garage
One cup of water
Wet Pipe, Building
28 Check Valve Basement
Bypass
29 Check Valve Basement
Discharge
30 Check Valve Basement
FDC
31 Control Valve Basement
#1 BFP
32 Control Valve Basement
#2 BFP
33 Control Valve Basement
Jockey Pump Line
34 Control Valve Basement
Jockey Pump Line
35 Control Valve Basement
Fire Pump Test Header
36 Gauge Basement
Jockey Pump Line
37 Gauge Basement
Jockey Pump Controller
38 Gauge Basement
Fire Pump Controller
39 Pump Basement
1/4" nipples,valves, and gages need to be replaced.
Comment
��• � InC' tL�M11HlF {l1�
4 Divis�aM oi Sx��e�ucx 8 Sox, L,P.
ScanlD
40501692
40501832
40501834
40501835
40501836
40501847
40501850
40501837
40501848
40501849
40501682
40501687
40501754
40501673
40501674
40501676
40501685
40501689
40501686
40501750
40501751
40500604
Dalmatian Fire Page 41 of 42 02/21/2020
///� _�,. ,r :�:�
. ..,
.�l—.
SNAMBAUGX & SON. L.P. ' �y
mxnucras•ur,urc[c�s[nn¢ Y{1
Y.��Y ��
Note � Device Type _ � Location
1000 GPM
3/15. 3/32
Wet Pipe
40 Backflow Prevention 4th DSV
Leak on #2 check nipple
Antifreeze -4
41 Drain floor 1 stair 5
Need to run a hose to drain system
42 Expansion Tank floor 3 stair 2 penthouse
Glycerine �4
43 Gauge fioor 7 stair 3
At the top of riser
Comment
Passed
44 Backflow Prevention Penthouse 5 th floor west end go out on the Passed
roof
0.0
45 Backflow Prevention pump room water meter A133 behind
restaurant
Installed complete new rubber kit on
8-11-16
46 Backflow Prevention pump room water meter A133 behind
restaurant
Installed complete new rubber kit on
8-11-16
Passed
Passed
, :;�