HomeMy WebLinkAboutE1.1-ELECTRICAL-SPECIFICATIONSSECTION 2624.1fi
PANELBOARDS
PART 1 PRODUCTS
1.01 MANUFACIDRERS
A. EAiON CORPORATION�. WWW.EATON.COIA.
1.02 PANELBOARDS - GENERAL REOUIREMENTS
A. PROVIDE PRODUCiS LISTE�, CLASSIFlED, AND LABELE� AS SUITABLE FOR THE PURPOSE INiENDE�.
B. UNLE55 OiHERWISE INDICAiED, PRONDE PRODUCTS SUITABLE FOR CONTINl10U5 OPERATION UNDER
THE FOLLOWING SERNCE CONDI110NS:
1. ALTITODE LESS THAN 6,600 FEET.
2 AMBIENT TEMPERATURE:
a. PANELBOARDS CONiNNING CIRCUIT BREAKERS: BETWEEN 23 DEGREES F AND 104 DEGREES F.
G SHORT CIRCUR CURRENi RATING:
D. MAINS: CANFIGURE FOR TOP OR BOTTOM INCOMING FEED AS INDICATE� OR AS REQUIRED FOR
THE INSTALLAlION.
E BRANCH OVERCURRENT PROlEC71VE DEVICES� REPLACEABLE WITHOUT �ISTURBING ADJACENT
oevices.
E BUSSING: SIZED IN ACCORDANCE WITH UL 67 TEMPERATURE RISE REQUIREMENTS
I. PROVIDE SOLIDLY BONDED EOUIPMENT GROUND BUS M EACH PANELBOARq WITH A SUITABLE
LUG FOR EACH FEEDER AND BRANCH CIRGIIT EQUIPMENT GROUNDING CONDUCTOR.
G CONDUCTOR TEkMINATIONS: SUITABLE FOR USE W1TH THE CONDUCTORS TO BE INSTALLED-
H. EVCLOSURES: COMPLY WITH NEMA 250, AND LIST AND LABEL AS COMPLYING WI7H UL 50 AND
01 SOE
t PNVIRONMENT i1PE PER NEMA 250: UNLE55 O7HERWISE INDICAIED, AS SPEQFlED FOR THE
FouovnNc wsrnunnoN �ocnnoNs:
2. BOXES GALVANIZED STEEL UNLESS OiHERWISE INDICATED.
o. PROVIDE WIRING GUiIERS SIZED TO ACCOMMODATE 7HE CONDUCTORS TO BE INSTALLED.
J. FRONTS:
a. FRONTS FOR SURFACE-MOUN7E� ENCLOSURES SAME DIMENSIONS AS BOXES.
4. LOCKABLE DOORS�. ALL LOCKS KEYED ALIKE uNLESS O7HERWISE INDICAIED.
I. FUTURE PROVISIONS: PREPARE ALL 11NU5ED SPACES FOR Fl1NRE WSTALLATION OF DEVICES
INCWDING 6l1SSING, CONNECTORS, MOUNPNG HARDWARE AND ALL OTHER REQUIRE� PRONSIONS.
1.03 LIGHTING AND APPLIANCE PANELBOARDS
A. DESCRIPTION: PANELBOARDS COIAPLYING WITH NEMA PB 1, LIGHiING AND APPLIANCE BRANCH
GRCWi TYPE, CIRCWi BREAKER iYPE, AND LISiED AND LABELED AS COMPLYING WIiH UL 67;
RA�NGS, CONFIGURATIONS AND FEATURES AS INDICATED ON iHE DRAWINGS.
B. C�NDUCTOR TERMINATIONS�.
1. MNN AND NEUTRAL WG MATERIAL AWMINUM, SUITABLE FOR TERMINATING AWMINUM OR
COPPER CONDUCTORS.
2 MNN AN� NEUTRAL WG TYPE MECHANICAL.
G BUSSING:
I. PHASE BUS CONNECTIONS: ARRANGED PoR SEQUENTIAL PHASING OF OVERCURRENT PROTECTNE
DENCES.
2 PHASE AND NEUTRAL BUS MATERIAL AWMINUM.
3. GROUND BUS MAIERIAL: ALUMINUM.
D. LYRCUIT BREAKERS'. 7HERMAL MAGNETIC BOLT-ON T1PE UNLE55 O7HERWISE INDICAIED.
E. EN��o�,REs
1. PROVIDE SURFACE-MOUNTED OR FLUSH-MOUNTED ENCLOSUftES AS INDICAIED.
2. PRONDE CLEAR PLASTIC CIFCUIT DIFECTORY HOLDER MOUN7ED ON INSIDE OF DOOR
1.04 OVERCURRENT PROIECPVE DEVICES
A. MOLDED CASE CIRCUIT BREANERS:
1. DESCRIPPON: OUICK-MAKE, QUICK-BREAK, OVER CENTER TOGGLE, TRIP-FREE, 7RIP-INDICA➢NG
CIRCUIT BREANERS LISTED AND LABELED AS COMPLYINC W17H UL 489, AND COMPLYING WI7H FS
W-C-375 WHERE APPLICABLE; RAPNGS, CONFlGURATIONS, AND FEANRES AS INDICATED ON
THE DRAWINGS.
2 INTERRUPTING CAPACITY:
o. PROVIDE CIRCWT BREAKERS WI1H INIERRUPPNG CAPACIiY AS REQUIRE� TO PROVIDE THE
SHORi CIRCOIi CURRENT RAiING INDICATED, BUT NOT LE55 THAN�.
1) 10,000 RIAS SYMMETRICAL AMPERES AT 240 VAC OR 208 VAC.
b. FULLY RATED SYSTEMS: PRONDE CIRCUIT BREAKERS WI7H W7ERRUPTING CAPACITY NOT LESS
THAN 7HE SHORT CIRCUIT CURRENT RATING INDICATED.
3. 1HERIAAL MAGNETIC CIRCUIT BREAKERS: FOR EACH POLE, FURNISH THERMAL INVERSE TIME
1RIPPING ELEMENT FOR OVERLOAD PROIECPON AND MAGNETIC INSTANTANEOUS TRIPPING
e�eueNr Foe sHoeT aecwT Peo�cnoN.
4 MULTI-POLE CIRCUIT BREAKERS: FURNISH WI7H COMMON TRIP FOR ALL POLES.
PART 2 EXECUTION
201 INSTALLATION
A. PERFORM WORK IN AWORDANCE WI7H NECA 1(GENERAL WORKMANSHIP).
B. INSTALL PRODUCTS IN ACCORDANCE WIiH MANUFACTURER'S INSTRUCTIONS.
G INSTALL PANELBOARDS IN ACCORDANCE WITH NECA 407 AND NEMA PB 1.1.
�. ARRANGE EQUIPIAENT TO PRONDE MINIIAUM CLEARANCES IN ACCORDANCE Wlhi MANUFACTURER'S
INSIRUCTIONS AND NFPA 70.
E. INSiALL PANELBOARDS PWMB.
F. INSiALL FWSH-MOUNTED PANELBOARDS 50 THAT iRIMS Fli COMPLEIELY FWSH i0 WALL WITH
NO GAPS AND ROUGH OPENING COMPLETELY COVERED.
G. MOUNi PANEL60ARDS SUCH THAi iHE HIGHESi POSITION OF ANY OPERATING HANDLE FOR
GRCUIi BREAKERS OR SWIiCHES DOES NOT ERCEED 79 INCHES ABOVE iHE FLOOR OR WORKING
PLATFORM.
H. INSTALL ALL FIELD-INSiN1ED BRANCH DEVICES, COMPONENTS, AND ACCESSORIES
I. PROVIDE FlLLER PLATES -0 COVER UNUSED SPACES IN PANELBOARDS.
JUNCiION BO% MOUN7ED
nusH vnTH cEiuNc cRio.
SEWRE i0 SiRUCiU&�
ABOVE �
(WHIiE) JUNC110N BO%
CLQSURE PLAIE, �RILL
HOIE PoR SiRNN REIJEF
AND 50 CORD -
CEILING
(WHIIE) SO COR� DOWN i0 I _
GON�OLA BELOW �
JUNCiION 90% Ai TOP
RAIL (FOR BEACON
GONDOLA ONL1� -
NOTE:
PROVIDE POWER TO GONDOLA
VIA SO CORD WITH ALL
COMPONENTS INCWDWG BUT
NOT LIMITED TO SiRAIN RELIEF
FOR A COMPLETE AND
STATIONARY WSTALLATION.
JUNCTION BO% TO BE FLUSH
MOUNTED WITH CEILING GRID
AND SECURED TO STRUCTURE
ABOVE.
POWER DROP TO BE USED AS
LEGRAND WIREMOLD POWER
DROP �jPD123180WH
F�ooR
RELEA5E0 FOR CONSTRIICTI�N r�RE °"`Y
Su6jec��ocompliancewithallregula�ions Inn�`�DCTpI�
of S�a�e antl Local Codes r r i � r�
City of Carmel
r
�un��\i lo•rvalM��_
DATE: 06�QZ�2O
SECTION 2fi2Z2fi
NnRING DEVICES
PARi 1 PRODUCTS
1.01 WIRING DEVICE APPLICATIONS
A. PROVIDE WIRING DENCES SUITABLE FOR INIENDED USE AND W1TH RATINGS ADEQUATE FOR LOAD
SERVED.
B. FOR SINGLE RECEPiACLES INSTALLED ON AN INDIVIDUAL BRANCH CIRCUIi PRONDE RECEPTACLE
WITH AMPERE RATING NOT LE55 iHAN THAi OF iHE BRANCH CIRCUIi.
C. PROVIDE WEAiHER RESISTANi GFCI RECEPiACLES WITH SPECIFIED WEATHERPROOF COVERS FOR
RECEPTACLES INSiALLED OUTDOORS OR IN DAMP OR WET LOCATIONS.
D. PROVIDE GFCI PROTECTION PoR RECEPTACLES INSTALLED WITHIN 6 FEET OF SWKS.
E. PROVIDE GFCI PROTECTION FOR RECEPTACLES SERNNG ELECTRIC DRINKING FOUNTAWS.
F. UNLE55 NOTED OTHERWISE, �0 NOT USE COM6INATION SWIiCH/RECEPTACLE DEVICES.
iD2 WIRING DEVICE FINISHES
A. PROVI�E WIRING DENCE FINISHES AS DESCRIBED 6ELOW UNLESS OhiERWISE INDICATED.
B. WIRING DENCES, UNLESS OiHERWISE INDICATED: WHITE WIiH WHIiE NYLON WALL PLAiE.
C. WIRING DENCES INSiALLED IN UNFINISHED SPACES�. GRAY WITH GALVAMZED SiEEL WALL PLATE.
D. WIRING DENCES INSTALLED IN WEi OR DAMP LOCAiIONS: V4HITE Wlhi SPECIFIED WEAiHERPR00F
COVER.
1.03 WALL SWITCHES
A. WALL SWITOHES - 6ENERAL REQUIREMENTS! AG ONLY, QUIET OPERATINQ 9ENERAL-USE SNAP
SWITCHES WI1H SILVER ALLOY CONTACTS, COIAPLYING W1TH NEMA W� 1 AND NEMA WD 6, AND
IJSTED AS COMPLYING WITH UL 20 AND WHERE APPIJCABLE, FS W-S-896; TWES AS IN�ICAIE�
ON THE DRAWINGS.
1. WIRING PROVISIONS: TERMINAL SCREWS FOR SIDE WIRING AND SCREW ACTUATED BINDING
CLAMP FOR BACK WIRING WITH SEPARATE GROUND IERMINAL SCREW.
B. SiANDARD WALL SWITGiES: INDUSiRIAL SPECIFICAiION GRADE, 20 A, 120/277 V W1TH
SiANDARD TOGGLE i1PE SWIiCH ACTUAiOR AND MAINiNNED CONiACTS; SINGLE POLE SINGLE
iHROW, DOUBLE POLE SINGLE iHROW, iHREE WAY, OR FOUR WAY AS INDICATED ON THE
DRAWINGS.
1.04 RECEPiACLES
A. RECEPTACLES - GENERAL REQUIREMENTS SELF-GROUNDING, COMPLYING W1TH NEMA WD 1 AND
NEMA W� 6, AND IJSTED AS COMPLYING WITH UL 49$ AN� WHERE APPIJCABLE, FS W-C-596;
TWES AS IN�ICATE� ON THE DRANINGS.
1. WIRING PROVISIONS: TERMINAL SCREWS FOR SIDE WIRING OR SCREW ACTUATED BINDING CLAMP
FOR BACK WIRING W17H SEPARATE GROUND IERMINAL SCREW.
2. NEMA CONFIGURATIONS SPEGFlED ARE ACCORDING TO NEMA WD 6,
B. CONVEMENCE RECEPTA0.ES:
1- STANDARD CONVEMENCE RECEPTA0.ES: INDUS7RIAL SPECIFlCAPON GRADE, 20A, 125V, NEMA
5-20R; SINGLE OF DUPLEX AS INDICATED ON THE DFAWINGS.
C. GFCI RECEPTACYES:
1. GFCI RECEPTACLES - GENERAL REQUIREMENTS: SELF-TESIING, W1TH FEED-THROUGH
PROTECTION AND LIGHT TO INDICATE GROUND FAULT TRIPPED CONDIPON AND LOSS OF
PkOTECTION; LIS7ED AS COMPLYING WI7H UL 9<, CLASS A.
o. PRONDE IEST AND RESET BUTTONS OF SAME COLOR AS DENCE.
2. STANDARD GFCI RECEPTA0.ES'. INDUSTRIAL SPECIFlCAPON GRADE, �UPLEX, 20A, 125V, NEMA
5-20R, RECTANGl1LAR DECORATOR STriE.
3. WEATHER RESISTANT GFCI RECEPTACLES INDUSTRIAL SPECIFICAPON GRADE, DUPLEH, 20A,
125V, NEMA 5-20R, RECiANGULAR DECORATOR STriE,IJSTED AND LABELED AS WEAhiER
RESISTANi TYPE COMPLYING Wlhi UL 498 SUPPLEMENT SE SUITABLE FOR INSTALLAPON IN
DNAP OR WEi LOCATIONS.
1.05 WALL PLAiES
A. WALL PLATES�. COMPLY WIiH OL 514D.
1. CONFIGURA➢ON: ONE PIECE COVER AS REQUIRED FOR QUANiIiY AND TWES OF
CORRESPONDING WIRING DEVICES.
2 SIZE: STANDARD; _ _ _ _ _ .
3. SCREWS: METAL WITH SLOTTED HEADS FINISHED TO MATCH WALL PUTE FINISH.
B. NYLON WALL PLATES SMOOTH FlNISH, HIGH-IMPACT 7HERMOPLASTIC.
PART 2 E%ECU➢ON
201 WSTALLAlION
A. PERFORM WORK IN ACCOR�ANCE WITH NECA 1(GENERAL WORKMANSHIP) AND, WHERE
APPLICABLE, NECA 130,INCWDING MOON➢NG HEIGHiS SPEGFIED IN iHOSE STANDARDS UNLESS
OiHERWISE INDICAiED.
B. COORDINATE LOCATIONS OF OUTLEi BOXES PROVIDED UNDER SECTION 26A5.33.16 AS REOUIRED
FOR MSTAWTION OF WIRING DENCES PRONDED UNDER THIS SECTION.
1. MOUNPNG HEIGHiS UNLESS OiHERWISE INDICATED, AS PoLLOWS:
a. WALL SWITCHES 48 INCHES ABOVE FINISHED FLOOR.
b. RECEPTACLES 18 INCHES ABOVE FINISHED FLOOR OR 6 INGiES ABOVE COUNTER.
C. MSTALL WIRING �EVICES IN ACCORDANCE WITH MANUFACNRER'S MSTRUCTIONS.
D. MSTALL PERMANENT BARRIER BETWEEN GANGED WIRING DENCES WHEN VOLTAGE BETWEEN
ADJACENT DENCES EXCEEDS 300 V.
E. WHERE REQUIRED, CONNECT WIRMG DEVICES USING PIGTAILS NOT LE55 iHAN 6 INCHES LONG. DO
NOi CONNECT MORE THAN ONE CONDUCTOR TO WIRING DENCE iERMINALS.
F. CONNECi WIRING DENCES BY WRAPPING CONDUCTOR CLOCKWISE 3�4 TURN AROUND SCREW
lER1AINAL AND 11GH7ENING i0 PROPER TORqUE SPEQFlED BY THE MANUFACTURER. WHERE
PRESENT, DO NOT USE PUSH-IN PRESSURE TERMINALS 7HAT DO NOT RELY ON
SCREW-ACNAIED BINDMG.
G. UNLESS OTHERWISE IN�ICATE�, CONNECT WIRING �EVICE GROl1N�ING IERMINAL TO BRANCH
CIRCUIT EQl11PMENT GROUNDING CON�UCTOR AND TO OUTLET BOH WITH 60NDING JUMPER.
H. MSTALL WIRING �EVICES PWMB AND LEVEL WITH MO11N11NG YOKE HELD RIGIDLY IN PLACE.
I. MSTALL WALL SWITCHES WIiH OFF POSIiION DOWN.
J. INSTALL VERIICALLY MOUNTED RECEPTACLES W1iH GROUNDING POLE ON i0P AND HORIZONTALLY
MOUNTED RECEPTACLES WIiH GROUNDING POLE ON LEFT.
K. INSTALL WALL PLATES i0 Fli COIAPLETELY FWSH i0 WALL WITH NO GAPS AND ROUGH OPENING
COMPLETELY CAVERED WITHOUT SiRAIN ON WALL PLAiE. REPAIR OR REINSiALL IMPROPERLY
INSTALLED OUiLET BO%ES OR IMPROPERLY SIZED ROUGH OPENINGS. DO NOT USE OVERSIZED
WALL PLNTES IN IJEU OF MEEiING THIS REQUIREMENT.
L INSTALL BLANK WALL PLATES ON JUNCTION 80%ES AND ON OUTLET BOXES WITH NO WIRING
DENCES INSTALLED OR DESYGNATE� FOR FUTURE USE.
��nc-iov aox u�ouNreo
FWSH WI1H CEILING GRIq
SECURE i0 SIRUCTUI2�
ABOVE -
C_ILINC
(WHIIEJ JUNCiION BO%
CLOSORE PLAiE, DPoLL
HOLE FOR STRAIN RELIEF
AND SO CORD -
(WHIiE) SO CORD �OWN TO I
GONDOU BELOW �
JUNCiION BO% Ai
ROOR LE�EL (FOR
REGULAR GONDOLA)
F�ooR �i
DETAIL FOR REGULAR FI%TURE
SECTION 2628.16
ENCL0.5ED SWITCHES
PART 1 PRODUCTS
1.01 ENCLOSED SAFETY SWITCHES
A DESCRIPPON: OUICK-MAKE, QUICK-BREAK ENCLOSED SAFETY SWITCHES LIS7E� AND LABELED
AS WMPLYING WITH UL 98� GENERAL DUTP RATINGS CONFIGURA➢ONS AND FEATURES AS
I
IND CAIED ON 7HE DRAWINGS.
B. PROVI�E PRODUCTS IJSTED, CLASSIFlED, AND LABELED AS SUITABLE PoR 7HE PURPOSE
INTENDED.
C. UNLESS OTHERWISE INDICATEq PROVIDE PRODUCTS SUITABLE FOR CONTINUOUS OPERATION
UNDER 7HE FOLLOWING SERNCE WNDITIONS:
1. ALTINDE LESS THAN 6,600 FEET.
2. AMBIENT TEIAPERATURP, BETWEEN -22 DEGREES F AND 104 DEGREES F.
D. HORSEPOWER RAPNG: SUITABLE FOR CONNECIED LOAD.
E. VOLTAGE RATING: SUITABLE FOR CIRCUIi VOLTAGE.
F. SHORT CIRCUIT CURRENT RATING:
1. PROVIDE ENCLOSED SAFETY SWITCHES, WHEN PROTECTED BY THE FUSES OR SUPPLY SIDE
OVERCURRENT PROTECTNE DEVICES TO BE INSTALLED, WITH LISTED SHORT CIRCUIT CURRENT
RAPNG NOT LESS THAN 7HE AVAILABLE FAULT CURRENT AT THE INSTALLED LOCAPON AS
IN�ICATED ON THE �RAWINGS.
G. PRON�E WITH SWITCH BLADE CONTACT POSITION THAT IS VISIBLE WHEN THE COVER IS OPEN.
H. CONDUCTOR IERMINATIONS: Sl11iA6LE FOR USE WITH THE CONDl1CTORS TO BE WSTALLED.
I. PRONDE SOLIDLY BONDED EQUIPMENT GROUND BUS IN EACH ENCL0.5ED SAFEtt SWIiCH, WITH A
SUITABLE WG FOR iERMINATING EACH EQUIPMENi GROUNDMG CONDUCTOR.
J. ENCLOSURES: COMPLY WITH NEMA 250, AND LIST AND LABEL AS COMPLYING WITH UL 50 AND
UL SOE.
1. ENNRONMENT iYPE PER NEMA 250: UNLESS OTHERI�SE INDICATED, AS SPEQFIED FOR THE
PoLLOWING INSTALLATION LOCATIONS:
K. PROVIDE SAFETY INTERLOCK TO PREVENT OPENING THE COVER WITH THE SNITCH IN THE ON
POSIPON WITH OAPABIIJTY OF OVERRIDMS WIERLOOK PoR IESTIN6 PURPOSES.
L GENERAL DUTY SWITCHES:
1. CONDUCTOR TERMINA➢ONS:
a PRONDE MECHANICAL WGS.
d LUG MATERIAL AWMINUM, SUITABLE FOR TERMINATING ALUMINUM OR COPPER CON�UCTORS.
2 PROVIDE E%IERNALLY OPERABLE HANDLE WI1H MEANS FOR LOCKING IN 1HE OFF POSITION,
CAPABLE OF ACCEP➢NG TWO PADLOCKS.
PART 2 EXECUTION
2.01 INSTALLATION
A INSTALL PRODUCiS IN ACCORDANCE WITH MANUFACNRER'S INSTRUCTIONS.
6. PERFORM WORN IN ACCOR�ANCE WITH NECA 1(GENERAL WORKMANSHIP).
C. ARRANGE E�UIPMENT TO PROVIDE MINIMUM CLEARANCES IN AWORDANCE WOH MANUFACNftER'S
INSTRUCTIONS AND NFPA 70.
D. INSTALL ENCLOSED SWITCHES PLUMB.
E EXCEPi WHEkE INDICATED TO BE MOUNTED ADJACENT TO THE EQUIPMENT THEY SUPPLY, MOUNT
ENCLOSED SWITCHES SUCH THAT 7HE HIGHEST POSIPON OF THE OPERATING HANDLE DOES NOT
EXCEED 79 INCHES ABOVE THE FLOOR OR WORKING PLA7FORM.
SECTION 26.51.00
INTERIOR LIGHTING
PART 1 PRODl1CT5
1.01 WMINAIRES
A. PRONDE PRODOCTS THAT COMPLY WIiH REOUIREMENiS OF NFPA 70.
B. PRONDE PRODOCTS THAT ARE LISTED AND LABELED AS COMPLYING W1TH UL 1598, WHERE
APPLICABLE.
C. PRONDE PRODUCiS LISTED, CLASSIFIED, AND LABELED AS SUIiABLE FOR iHE PURPOSE
INTENDED.
D. UNLESS OTHERWISE INDICAIED, PROVIDE COMPLETE LUMINAIRES INCLUDING LAMP(SJ AND ALL
SOCKETS, 6ALLASTS, REFLECi0R5, LENSES, HOUSINGS AN� OTHER COMPONENTS REOUIRED TO
POSITION, ENERGIZE AND PROTECT THE WAP AN� �ISTRIBUTE hiE IJGHT.
E. ONLESS SPECIFICALLY INDICATED i0 BE EXCW�E�, PROVI�E ALL REOWRED CONDWT, 60XES,
WIRING, CONNECTORS, HARDWARE, SUPPORiS, 1RIM5, ACCESSORIES, ETC. AS NECESSARY fOR
A COMPLETE OPERATMG SYSTEIA.
F. PRONDE PRODOCiS SUIiABLE i0 VAiHSiAND NORMAL HANDLING,INSiALLAiION, AND SLIiVIGL
N7iH0UT ANY DAMAGE, DISTORiION, CORROSION, FADING, DISCOLORING, EiC.
G. RECESSED WMINAIRES�.
1. CEILING COMPAiIBILIiY�. COMPLY WIiH NEMA LE 4.
H. LE� WMINAIRES:
1. COMPONENTS: UL 8750 RECOGNIZED OR IJSTED AS APPLICABLE.
2 IESTED IN ACWRDANCE WITH IES LM-79 AND IES LM-80.
3. LED ESTIMAIED USEFUL IJFE MINIMUM OF 50,000 HOURS AT 70 PERCEV- WMEN
MAWIENANCE, CALCULAIED BASE� ON IES LM-80 IEST DATA.
L02 EMERGENCY IJGHTING UNITS
A. DESCWPTION: EMERGENCY LIGH➢NG UNITS COMPLYING WITH NFPA 101 AND ALL APPLIC�BLE
STATE AND LOCAL CODES, AND LISTED AND LABELED AS COMPLYING N7TH UL 924.
B. OPERATION: UPON W7ERRUP710N OF NORMAL POWER SOURCE OR BROWNOUT CONDITION
EXCEEDING 20 PERCENT VOLTAGE DROP FROM NOMINAL, SOLID-STAIE CONIROL
AUTOMAPCALLY SWITCHES WNNECTED LAMPS TO INTEGRAL BAiIERY POWER FOR MINIMUN OF
90 MINUIES OF RAIED EMERGENCY ILLUMINATION, AND AUTOMAIICALLY RECHARGES BATTEd°
UPON RESTORATION OF NORMAL POWER SOURCE.
C. BATTERY
1. SRE BAiIERY TO SUPPLY ALL CONNECTED LAMPS, INCLU�MG EIAERGENCY REMOIE HEADS
WHERE INDICATED.
D. DIAGNOSTICS: PRON�E POWER STATUS M�ICAiOR LIGHT AND ACCESSIBLE INTEGRAL TEST
SWITCH TO MANUALLY ACTIVAIE EMERGENCY OPERATION.
E. PRONDE LOW-VOLTAGE DISCONNECT TO PREVENT 6ATIERY DAMAGE FROM DEEP �ISCHARGE.
1.03 EXIT SIGNS
A. DESCRIPTION: INiERNALLY ILWMINATED EXIT SIGNS WITH LEDS UNLESS OTHERWISE INDICATE�;
COMPLYING WITH NFPA 101 AND ALL APPLICABLE STATE AND LOCAL CODES, AND LISTED AND
LABELED AS COMPLYING WITH UL 924.
1. NUMBER OF FACES: SINGLE OR DOUBLE AS INDICAiED OR AS REQUIRED FOR iHE WSTALLED
LOCATION.
2 DIRECTIONAL ARROWS: AS INDICATED OR AS REOUIRED FOR THE INSTALLE� LOCATION.
B. SELF-POWERED EXIT SIGNS:
1. OPERAiION: UPON INTERRUPTION OF NORMAL POWER SOURCE OR BROWNOUT CONDI➢ON
E%CEEDING 20 PERCENT VOLTAGE DROP FROM NOMINAL, SOLID-STATE WNTROL
AUTOMATICALLY SWITCHES CONNECIE� LAMPS TO W7EGRAL BATTERY POWER PoR MINIMUM
OF 90 MINUIES OF RAIED EMERGENCY ILLUMINATION, AND AUTOMATICALLY RECHARGES
BATTERY UPON RESTORATION OF NORMAL POWER SOURCE.
2. DIAGNOS7ICS: PROVIDE POWER STATUS INDICATOR LIGHT AND ACCESSIBLE W7EGRAL TEST
SWITCH TO MANUALLY ACTIVATE EMERGENCY OPERAlION.
3. PROVIDE LOW-VOLTAGE DISCONNECT TO PREVENT BAT7ERY DAMAGE FROM DEEP DISCHARGE
1.04 BALLASTS AND DRIVERS
A. BALLASTS�DRIVERS - GENERAL REQUIREMENTS:
1. PROVIDE BALLASTS CONTAINING NO POLYCHLORINATED BIPHENYLS (PCBS).
2 MINIMUM EFFlCIENCY�EFFlCACY PftOVIDE BALLASTS COMPLYING WITH ALL CURRENT
APPLICABLE FEDERAL AND STAIE BALLASi EFFIQENCY/EFFICACY SiANDARDS
3. ELECTRONIC BALLASTS/DRNERS: INRUSH CURRENTS NOT EXCEEDING PEAK CURRENTS
SPECIFIED IN NEMA 410.
B. DIMMABLE LED DRNERS
1. DIMMING RANGE�. CONI1NUOl15 DIIAMING FROM 100 PERCENT TO FIVE PERCENT RELATIVE
LIGHT OU7POT UNLESS �IMMING CAPABILITY TO LOWER LEVEL IS INDICAIED, WITHOl1T FLICKER.
2 CONTROL COMPAT161LITY�. FULLY COMPA➢6LE WITH iHE DIIAMING CONIROLS TO BE
WSTALLED.
1.05 ACCESSORIES
A. STEMS FOR SUSPENDED LUMINAIRES'. S7EEL TUBING, MINIMUM 1�2" SIZE, FACTORY FlNISHED
TO IAATCH LUMINAIRE OR FlELD-PAIMED AS DIRECTED.
PART 2 EHECUTION
2.01 INSTALLATION
A. COORDINATE LOCATIONS OF OUILET 60HES PRONDE� 11NDER SECTION 26.05.33.16 AS
REOl11RED FOR WSTALLAlION OF WMINAIRES PRONDED UN�ER THIS SECTION.
B- PERFORM WORK IN ACCORDANCE W17H NECA 1(GENERAL WORNMANSHIP)-
C. INSTALL PRODUCTS IN ACCORDANCE WIiH MANUFACTURER'S INSTRUCTIONS.
D. INSTALL LUMINAIRES SECURELY,IN A NEAT AND WORKMANIJKE MANNER, AS SPEQFIED IN NECA
500 (COMMERCIAL LIGHTINGJ AND NECA 502 (INDUSIRIAL LIGHTINGJ.
E. INSTALL WMINAIRES PWMB AND SQUARE AND ALIGNED Wlhi BUILDING LWES AND Wlhi
A�JACEM WMINAIRES.
F. INSTALL ACCESSORIES FURNISHED WITH EACH WMINAIRE.
G. BOND PRODUCiS AND MEiAL ACCESSORIES i0 BRANCH CIRCUIT EQl11PMENT GROUNDING
CONDUCTOR.
H. EMERGENCY LIGHiING UNIiS�.
L UNLE55 OTHERWISE INDICATED, CONNECT UNIT TO UNSWIiCHED POWER FROM SAME CIRCUIT
FEEDING NORMAL LIGHTING IN SAME ROOM OR AREA BYPASS LOCAL SWITCHES, CANTACTORS,
OR OTHER LIGHTING CONTROLS.
i �iT scNs
1. UNLESS OTHERWISE INDICATED, CANNECT UNIT TO UNSWITCHED POWER FROM SAME CIRCUIT
FEEDING NORMAL IJGHTING M SAME ROOM OR AREA BYPASS LOCAL SWITCHES, CANTACTORS,
OR OTHER IJGHTING CONTROLS.
J. INST�LL LAMPS M EACH LUMINAIRE.
CVS HAS �EVELOPE� SPECIAL PRICING AND READILY AVAILABLE STOCK WITH
THE NAI PREFERRED SUPPLIER:
- WIE�ENBACH-BROWN Co, INC.
PHONE: (800)243 0030
EMAIL CVSSUPPORT�WBLIGHT.COM
- NESCO, MC.
PHONE (888)244 6980
EMAIC CVSPLANSC�IJEEDHAMELECTRIC.COM
r4��
n
harmac
p y
HUB/SSSI
STORE NUMBER 08674
1421 RANGELWE ROAD
CARMEL, IN 46032
CAPCODE: (90/88)
CS PR0,IECT NUMBER 138374
ARCHITECT OF RECORD�
•
CONSULTANT ENGINEER�
CONSULTANT�
SEAL�
REVISIONS:
03-09-2020
DRAWING BY:
CVS PROJECT MANAGER:
DATE:
JOB NUMBER:
TITLE
PERMIT SET
S. BEBA
E ROSARIO
03-09-2020
JCDT19.0401.00
ELECTRICAL
SPECIFICATIONS
SHEET NUMBER:
COMMENTS:
E1.1