HomeMy WebLinkAboutE1-ELECTRICAL-SPECIFICATIONSSECiION 26.0.5A5 SELECIIVE DEM1IOLITION FOR ELECIRICAL PART 1 EXECUTION 1.01 ENAMINATION A VERIFY THAT ABANDONED WIRING AN� EQUIPMENT SERVE ONLY ABANDONE� FAQLI➢E5. B. BEGINNING OF �EMOLIPON MEANS INSTALLER ACCEPTS E%ISTING CONDI110NS. 1.02 PREPARA710N A. DISCONNECT ELECTRICAL SYSIEMS IN WALLS, FLOORS, AN� CEILINGS TO BE REMOVE�. B. COOR�INAIE U11LIiY SERNCE OUTAGES WITH U11LIiY COIAPANY. C. PRON�E TEMPOftARY WIRING AN� CONNECiIONS TO MAINTAIN EXISiING SYS7EIAS M SERNCE DURING CONSTRUCTION. WHEN WORK MUST BE PERFORMED ON ENERGIZE� EQUIPMENi OR CIRCUITS, USE PERSONNEL E%PERIENCED IN SUCH OPERATIONS. D. E%ISiING ELECiRICAL SERNCE- MAINTAIN ERISIING SYSTEM IN SERNCE UN11L NEW SK1EM IS COMPLEiE AND READY FOR SERNCE. DISABLE SYSiE1� ONLY i0 MAKE SWITCHOVERS AND CONNEC110N5. MINIIAIZE OUiAGE DURAiION. L03 DEIAOLITION AND ENiEN510N OF ENISiING ELECiRICAL WORK A. REIAOVE, RELOCAiE, AND ExiEND Ex15iING INSiALLAiION$ TO ACCOMMODATE NEW CONSiRUCiION. B. REPAIR ADJACENT CONSiRUCTION AND FlNISHES DAMAGED DURING DEMOLIiION AND E%TENSION WORK. C. MAINTAIN ACCE55 W ENISIING ELECIRICAL MSTALLATIONS 7HAT REMAIN ACTNE. I�ODIFY INSTALLATION OR PRON�E ACCE55 PANEL AS APPROPRIAIE. SECTION 26.05.19 �ow-va�TncE e�ecmicn� aowee coNoucraes allo cae�Es PART 1 PRODUCTS 1.01 CONDUCTOR AN� CABLE APPLICATIONS A. DO NOT USE CON�UCTORS AND CABLES FOR APPLICAlIONS O1HER THAN AS PERMIT7E� BY NFPA ]0 AND PRO�UCi LISPNG. B. PR�NDE SINGLE CONDUCTOR BUIL�ING W1RE INSTALLE� IN SUITABLE RACEWAY UNLE55 OTHERWISE INDICATEq PERMITIED, OR REQUIRED. C. METAL-CLAD CABLE IS PERMITIED ONLY AS FOLLOWS: 1. WHERE NOi OIHERWISE RESIRICTED, MAY BE USED: a. WHERE CONCEALE� ABO�E ACCESSYBLE CEILINGS PoR FlNAL CONNECiION$ FROM JUNCiION BOXES i0 LUMINAIRES. 1) MARIMUM LENGTH: 6 FEEL b. WHERE CONCEALED IN HOLLOW SND wALLS, ABOVE ACCESSIBLE CEILINGS, AND UNDER RAISED FLOORS PoR BRANCH CIRCUIiS UP i0 20 A. 1) E%CEPTION: PROVI�E SINGLE CON�UCiOR BUILDING WIRE IN RACEWAY FOR CIRCUIT HONERUN FROM FIRST OUiLEi TO PANELBOARD. 1.02 CONDUCTOR AND CABLE GENERAL REQUIREMENTS A. PRONDE PRODUCTS THAT COMPLY W11H REOUIREIAENTS OF NFPA 70. B. PROVIDE PRODUCTS LISiEq CLASSIFIEq AND LABELED AS SUITABLE FOR 1HE PURPOSE INiENDED. C. UNLESS SPECIFlCALLY INDICAiED i0 BE E%CLUDED, PRONDE ALL REQUIRED CONDUIi, BO%ES, WIRING, CONNECi0R5, ETC, AS REOUIRED PoR A COMPLEiE OPERATING SYSiEM. D. COMPLY W1iH NEMA WC 70. E. iHERMOPLASiIC-INSULAiED CONDUCi0R5 AND CABLES: LISTED AND LABELED AS COI�PLYING WITH UL 83. F. iHERMOSET-INSULAiE� CON�UCiORS AN� CABLES LISTE� AN� LABELE� AS COMPLYING WIiH UL 44. G. CONDUCTORS FOR GROUN�ING AND BONDMG ALSO COMPLY WI1H SEC110N 26 052fi. H. CONDUCTOR MAIERIAL. 1. PRON�E COPPER CONDUCTORS ONLY. AWMINUM CONDUCTORS ARE NOT ACCEPTABLE FOR 1HIS PROJECT. CON�UCTOR SIZES INDICATE� ARE BASE� ON COPPER. 2 COPPER CON�UCTORS: SOFT �RAWN ANNEALED, 98 PERCENi CON�UCiIVIiY, UNCOAIED COPPER CONDUCTORS COMPLYING WIiH AS1M B3, AS71A B8, OR ASTM1I B787/B787M UNLESS OTHERWISE iNoicnTEo. 3. PNNE� COPPER CON�UCiORS: COMPLY LN1H ASTM B33. i. coNoucToe co�oe cooiNc: 1. WLOR CO�E CON�UCTOftS AS IN�ICATE� UNLESS O7HERWISE REQUIftE� BY 7HE AU7HORIiY HAVING JURIS�IC110N. MAINTAIN CONSIS7ENT COLOR CO�ING THROUGHOUT PROJECT. 2 WLOR CO�ING MEiHO�: INTEGRALLY COLORE� INSULAiION. J. WLOR CO�E: a. EQUIPMENT GROUND, ALL SYSIEMS: GREEN. b. FOR MO�IFICATIONS OR AD�ITIONS TO ER6➢NG'MRING 5Y4EMS, WMPLY W11H EX6PNG COLOR CODE WHEN E%ISTING CODE CAMPLIES W1TH NFPA 70 AND IS APPROVED BY THE AUiHORItt HAVING JURISDICiION. 1.0.3 $INGLE CONDUCiOR BUILDING WIRE A. DESCRIPiION: SINGLE CONDUCiOR INSULAiED WIRE. B. CONDUCiOR SiRANDING: L FEEDERS AND BRANCH CIRCUITS: a. SIZE 10 AWG AND SMALLER: SOLID. b. 9ZE 8 AWG AND LARGER: SiRAN�E�. 2 CONiROL CIRWITS SiRANDE�. C. INSl1LATI0N VOLTAGE RATING�. 600 V. �. INSULATION: 1. CCPPER BWL�MG W1RE: iYPE THHN/iHWN OR iHHN/THWN-2, EXCEPi AS IN�ICATED BELOW. a. SIZE 4 AWG AND LARGER: TWE %HHW-2. 1.04 NETAL-CLA� CABLE A. DESCRIPPON�. NWA 70, TWE M1IC CABLE LISTE� AN� LABELE� AS COM1IPLYING WIiH UL ISfi9, AND IJSIED Pok USE IN CLASSIFlED FlRESTOP SYSTEMS TO BE USED. B. CON�UCTOR S7RAN�ING: 1. SIZE 10 AWG AN� SMALLER: SOLI�. 2 SIZE 8 AWG AN� LARGER�. S1RAN�ED. C. MSULATION VOLTAGE RATING�. 600 V. �. INSULATION: iYPE THHN, THHN/1HWN, OR THHN/1HWN-2. E GROUN�ING�. NLL-SRE W7EGRAL EQUIPIAENT GROUN�ING CON�UCTOR. E ARMOR�. S1EEL,INTERLOCKE� TAPE. 1.05 WIRING CONNECTORS A. DESCRIPPON�. 'MRING CONNECTORS APPROPRIATE FOR iHE APPLICATION, SUITABLE FOR USE WI1H 1HE CON�UCTORS TO BE WNNEC7ED, AND LIS1E� AS COMPLYING 'M1H UL 486A-486B OR UL 486C AS APPLICABLE. B. WIRING CONNECi0R5 FOR SPLICES AN� TAPS: 1. COPPER CONDUCTORS SIZE B AWG AND SMALLER� USE TWIST-ON INSULAIED SPRING CONNECTORS. 2. COPPER CONDUCi0R5 SIZE 6 AWG AND LARGER: USE MECHANICAL WNNECi0R5 OR COMPRESSION CONNECi0R5. C. i'MSi-ON INSULAiED SPRING CONNECi0R5: RATED 600 V, 221 DEGREES F PoR SiANDARD APPLICATIONS AND 302 �EGREES F FOR HIGH iEIAPERATURE APPLICAilONS; PRE-FlLLED WITH SEALANT AND LISiED AS COMPLYING W1iH UL 486D FOR DAMP AND WET LOCA➢ONS. D. MECHANICAL CONNECTORS PROVIDE BOLTED T1PE OR SET-SCREW iYPE. E. COMPRESSION CONNECTORS: PROVIDE CIRWMFERENTIAL TWE OR HE% TWE CRIMP CONFlGURATION. 1.06 WIRMG AWESSORIES A ELECTRICAL TAPE 1. VINYL COLOR CODMG ELECIRICAL TAPE: INTEGRALLY COLORE� TO MATCH COLOR W�E INDICATE�; LISTE� AS COMPLYING WI7H UL 510; MINIMUM 1HICKNESS OF 7 MIL; RESISTANT TO ABRASION, CORRQSION, AN� SUNLIGHT�, SUITABLE FOft CONPNUOUS IEMPERAiURE ENVIRONMENT UP ID 221 CcGRcES =. 2 VINYL WSULA ING ELcCiRICAL iAPP. COMPLYING WITH ASiM �3005 AND LISIED AS COMPLI1NG WITH UL 510; MIN MUM 1HICKNESS OF 7 MIL; RESISTANT TO ABftA510N, CORROSION, AND SUNLIGHT; CONfORMABLE FOR APPLICAiION DOWN TO 0 DEGREES F AND SUITABLE FOR CONiINU0U5 IEMPERAiURE ENVIRONMENT UP TO 221 DEGREES F. 9. WIRF PULLING LUBRICANT: LISIED�, SUITABLE FOR USE W11H 1HE CONDUCi0R5 OR CABLES TO BE INSInILED AND SUIiABLE FOR USE Ai iHE MSiALLAT10N TEMPERAiURE. vnei � ezeeunoN 2�1 PREPARAiION A. CLEA\ RACEWAYS THOROUGHLY TO REI�OVE FOREIGN MAiERIALS BEFORE INSTALLINC CONDUCiOR$ nNo cne�es. 202 INSTALLATION A. CIRCOIIING REQOIREM1IENTS: 1. UNLESS �IMENSIONE�, CIRCUIT ROUTING INDICAiED IS DIAGRAMMAPC. 2. COMI�ON NEUiRALS: UNLE55 OiHER4n5E INDICATED, SHARING OF NEUiRAL/GROUNDED CONDUCTORS AMONG UP i0 iHREE SINGLE PHASE BRANCH CIRCUITS OF DIFFERENT PHASES INSTALLED IN hlE SAME RACEwAY IS NOi PERMITiE�. PROVIDE �EDICATED NEUTRAL/GROUNDED CONDUCiOR FOR EACH INDIVIDUAL BRANCH CIRWIT. B. INSTALL PRO�UCiS IN ACCORDANCE WITH I�ANUFACIDRER'S INSTRUCTIONS. C. PERFORM WORK IN ACCOft�ANCE WITH NECA I(GENERAL WORKMANSHIP). �. INSTALL M1IETAL-CLA� CABLE (TWE MC) IN ACCORDANCE WITH NECA 120. E INSTALLATION IN RACEWAY: 1. TAPE ENDS OF CON�UCiORS AN� CABLES i0 PREVENT WFlLIRATION OF NOISIURE AN� O7HER CONTAMINAN75. 2 PULL ALL CON�UCTORS AND CABLES TOGETHER INTO RACEWAY AT SAME 11ME. RELEA5E0 FOR CON$TRIICTI�N Eo unNUFncTueEe's REmuMENOEo unxiuuM Su6ject�o compliance with allregula�ions of S�a�e antl Local Codes City of Carmel r �un��\i lo•rvalM��_ DATE: 06�QZ�2O SSARY, E%CEPT WHEN WBRICANT IS NOi F. TERMINAiE CABLES USING SUITABLE FliiINGS 1. MEiAL-CLAD CABLE (i1PE MC): a. USE LISiED FliiINGS. i A ARM R N Y IN P IA I i i PR V Ni AIAA IN N i R R b. CU C BLE 0 0 L US G S EC LZE� OOLS 0 E E � G C CO DUC 0 5 0 IN U Ail N. N i HA K AW R WIR Ti R i Vi ARM R. 5 L 0 DO 0 USE C 5 0 E CU E S 0 C 0 G. INSiALL CONDUCi0R5 WIiH A IAINIMUM OF 12 INCHES OF SLACK AT EACH OUiLEi. H. NEATLY iRAIN AND BUN�LE CONDUCTORS WSIDE BONES, WIREWAYS, PANELBOARDS AND OiHER E UIPI�ENT ENCLOSURES. Q I. GROUP OR OiHERWISE IDENiIFY NEViRAL GROUNDED CONDUCi0R5 wliH ASSOCIAiED UNGROUN�ED / CONDUCiORS INSIDE ENCLOSURES IN ACCORDANCE WITH NFPA 70_ J. MAKE WIRING CANNECilONS USING SPECIFlED WIRING CONNECi0R5. 1. MAKE SPLICES AND TAPS ONLY IN ACCESSIBLE BONES DO NOT Pl1LL SPLICES INTO RACEWAYS OR MAKE SPLICES IN CONDUIi BODIES OR N7RING Gl1TTER5 2. REMOVE APPROPRIATE AIAOUNT OF CONDUCTOR INSULAlION FOR MAKING CONNEC110N5 WITHOUT CUiTING, NICKING OR �AMAGMG WN�UCTORS. 3. �0 NOT RENOVE CONDUCTOR S7RAN�5 TO FAQLITATE INSERPON INiO CONNECTOR. 4. CLEAN CONTACT SURFACES ON CONDUCTORS AND CONNECTORS i0 SUITABIE REMOVE CORROSION OXIDES, AND O1HER CONTAMINAIES. �0 NOT USE WIRE BRUSH ON PLAIE� CONNECTOR SURFACES. K. INSULAIE SPLICES AN� TAPS THAT ARE MA�E WI7H UNMSULATE� CONNECTORS USING METHO�S SUIiABLE FOR THE APPLICATION, LNTH INSULAPON AN� MECHANICAL SIRENGTH AT LEAST EQUIVALENT TO UNSPLICED CON�UCTOftS. L WSULAIE ENDS OF SPARE CONDUCTORS USING NNYL WSULAiING ELEC7RICAL iAPE. M. WSiALL FIRESTOPPING T� PRESERVE FIRE RES6iANCE RA➢NG OF PAR11110N5 AN� O1HER ELEMENiS, USING MAiERIALS AND MEiHODS SPECIFIED W SECiION 07.84-00. N. UNLE55 SPECIFICALLY INDICAIED TO BE ExCLUDED, PROVIDE FINAL CONNECTIONS i0 ALL EQUIPUENi AND DENCES,INCLUDING iHOSE FURNISHED BY O1HER5, AS REQUIRED FOR A COMPLEiE OPERAIING SYSiEM. SECIION 26.0526 GROUNDING AND BONDING FOR ELECiRICAL SYSIEI�S PARi 1 PRODUCiS 1.01 GROUNDING AND BONDING REQUIREMENT$ A ENISiING WORK: WHERE ExISTING GROUNDING AND BONDING SYSTEM COIAPONENTS ARE INDICAiED TO BE REUSED, THEY MAY BE REUSED ONLY WHERE iHEY ARE FREE FR�M CORROSION,INTEGRIiY AND CONIINUITY ARE �ERIFlE�, AND WHERE ACCEPTABLE TO 1HE AUTHORITY HANNG JURIS�ICTION. B. �0 NOT USE PRODUCTS FOR APPLICATIONS OTHER iHAN AS PERIAITIED BY NFPA 70 AN� PRooucT usnNc. C. UNLESS SPECIFlCALLY IN�ICAIED TO BE E%CWDED, PROVIDE ALL REQUIRE� COIAPONENTS, CON�UCTORS, WNNECTORS, CONDUIT, BO%E$ FlTTINGS, SUPPORTS, ACCESSORIE$ ETC. AS NECESSARY FOR A COMPLEIE GROUN�ING AND BONDING SYSIEM. �. WHERE CON�UCTOR SIZE IS NOT IN�ICAIEQ SIZE TO COMPLY W11H NFPA 70 BUT NOT LESS THAN APPLICABLE MINIMUM SIZE REQUIFEMENiS SPECIFIE�. 1D2 GROUN�ING AN� BONDING COMPONENTS A. GENERAL REQUIREMEN7S: 1. PROVI�E PRODUCTS LISIED, CLASSIFIE�, AND LABELED AS SUIiABLE FOR THE PURPOSE INIENDED. 2. PROVIDE PRODUCTS L61ED AND LABELED AS COMPLnNG WTH UL 467 WHERE APPLICABLE. 8- CONDUCiORS FOR GROUNDING AND BONDING,IN ADDI110N TO REOUIREMENiS OF SECiION 26 0526- L USE INSULAiED COPPER CONDUCiOR$ UNLE$$ OiHERvnSE M�ICAiED. a ENCEPilONS: 1) USE BARE COPPER CON�UCiOftS WHERE INSTALLE� UN�ERGROUN� IN DIRECT CONTACT WITH EAR1H. 2) USE BAftE COPPER CON�UCi0ft5 WHERE �IftEC1LY ENCASE� IN CONCREIE (NOi IN RACEWAY). G CONNECiORS FOR GROUN�ING AN� BON�ING: 1. �ESCftIPTION: CONNECTORS APPROPRIATE FOR THE APPLICATION AND SUIiABLE F�R THE CONDUCTORS AND ITEMS T� BE CONNECIE�; LISIED AND LABELE� AS COI�PLYING W1TH UL 467. 2. UNLESS OIHERWISE INDICATED, USE E%OIHERMIC WELDED CONNECIIONS FOR UNDERGROUND, CONCEALED AND OTHER INACCE$$IBLE CONNECTIONS. 3. UNLE$$ O1HERw15E INDICATED, USE MECHANICAL CONNECi0R5, COMPRESSION CONNECTORS, OR E%OiHERNIC WELDED CONNECilONS FOR ACCE55YBLE CONNECilONS. PARi 2 E%ECUiION 2.01 INSiALLAiION A. INSiALL PRODUCTS IN ACCORDANCE WIiH MANUFACiURER�S INSiRUCiIONS. B. PERFORM WORK IN ACCOR�ANCE WI1H NECA 1(GENERAL WORKMANSHIP). C. MAKE GROUN�ING AN� BONDING CONNEC110NS USING SPEQFIED CONNECTORS. 1. REMOVE APPROPRIATE AIAOUNT OF CONDUCTOR INSULA➢ON FOR MAKING WNNEC➢ONS WTHOUT CUiTING, NICKING �R �AMAGING CONDUCTORS. �0 NOT REMOVE CONDUCTOR S1RAN�5 TO FACILITATE INSERIION INTO CONNECTOR. 2. REMOVE NONCONDUCIIVE PAINT, ENAMEL, OR $IMILAR COAIING AT iHREADS, CONTACT POINTS, AND CONiACT $URFACES. 3. E%OiHERNIC WELDS: MAKE CONNECilONS USING MOLD$ AND WELD M1IAiERIAL $UIiABLE PoR iHE IiEMS TO BE CONNECTED IN ACCORDANCE WITH 1AANUFACTURER'S RECOMIAENDAiIONS 4. MECHANICAL CONNECTORS: SECURE CONNEC110NS ACCOR�ING TO MANUFACIURER'S RECOIAMENDED TORQUE SETfINGS. 5. COMPRESSION WNNECiORS SECURE CONNECTIONS USING M1IANUFACTURER'S RECOIAMENDED SECiION 2fi.05.29 HANGERS AND SUPPORTS PoR ELECTRICAL SYSiEMS PARi I PRO�UCTS 1.01 SUPPORT AN� AiTACHMENT WMPONENTS A. GENERAL REQUIREMENTS: 1. PROVIDE ALL FEOUIRE� HANGERS, SUPPORTS, ANCHORS, FAS7ENER$ FIT71NG5, ACCESSORIES, AN� HAR�WARE AS NECESSARY FOR 7HE COMPLETE WSTALLATION OF ELECTRICAL WORK. 2 PROVI�E PRO�UCTS LIS1E�, CLASSIFIE�, AN� LABELE� AS SUITABLE FOR THE PURPOSE INIEN�E�, WHERE APPLICABLE. 3. WHERE SUPPORT AN� AiTACHMENi COMPONENT T1PES AN� SIZES AftE NOT IN�ICATED, SELECT IN ACCOR�ANCE WITH MANUFACTURER'S APPLICATION CRIIERIA AS REQUIRE� FOR THE LOA� TO BE SUPPOR7ED.INCLU�E CONSI�ERAPON FOR NBRATION, EQUIPMENT OPERATION, AND SHOCN LOA�S WH4Pc APPLICABLE. 4. �0 NOi USE PRODUCTS FOR APPLICATIONS OTHER THAN AS PERMITIE� BY NFPA 70 AN� Peooucr usrNc. B. CONDUIT AN� CA�LE SUPPOkiS: S1kAP5, CUMP�, ETC. SUITABLE FOR THE CON�UIT OR CABLE TO BE SUPPORffD. 1- CONDUIT STRAPS�. ONE-HOLE OR TWO-HOLE TYPE; S1EEL OR MALLEABLE IRON. 2. CONDUIi CLAMPS: BOLTED T1PE UNLESS OiHERWISE INDICAiED. C- OUILET BOR SUPPORiS: HANGERS, BRACKEiS, EiG SUITABLE FOR iHE BO%ES i0 BE SUPPORiED. D- HANGER RODS: THREADED ZMC-PLAIED SiEEL UNLE55 OiHERWISE INDICAiED. 1. MINIIAUI� SIZE, UNLESS OiHERWISE INDICAiED OR REQUIRED�. a EQUIPN,ENT SUPPORTS�, 1�2 INCH DIAMEiER. b. SINGLE CONDUIi UP TO 1 INCH (27 IAM) TRA�E SIZE: 1/4 INCH �IAMETER. a SINGIE CON�UIT LARGER THAN 1 INCH (27 MM) TRADE SIZE: 3/8 MCH �IAIAETER. d. OViLET B�XES 1/4 INCH DIAMEiER. e. LUMINAIRES: 1/4 INCH DIAMEiER. E. ANCHOR$ AND FASiENERS: 1. UNLE55 OiHERW15E INDICATED AND WNERE NOT OTHERWISE RESiRICiED, USE iHE ANCHOR AND FASiENER TWES INDICAiED PoR iHE SPECIFlED APPLICATIONS. 2. HOLLOW MASONRY: USE iOGGLE BOLTS. 3. HOLLOW S1V� WALLS�. USE iOGGLE BOLTS. 4. S7EEL USE BEAM CLAMPS,I�ACHME BOLT$ OR WEL�E� THREADE� SIDDS. 5. SHEET MEiAL USE SHEET METAL SCREWS. PARi 2 EXECUTION 201 INSTALLATION A. WSiALL PRODUCTS IN ACCORDANCE WIiH MANl1FACIDRER'S WSiRlICilONS. B- PERFORN WORK IN ACCORDANCE W1iH NECA 1(GENERAL WORKMANSHIPJ. C. PROVIDE INDEPENDENi SUPPORi FROM BUILDING SiRUCiURE. DO NOi PROVIDE SUPPORT FROM PIPING, DUCTWORK, OR OiHER SYSiE�15. D. UNLE55 SPEQFlCALLY INDICAiED OR APPRO�ED BY ARCHIiECi, DO NOT PRONDE SUPPORi FR01� SUSPEN�E� CEILING SUPPORT SYSiEM OR CEILWG GRID. E 11NLE55 SPEQFlCALLY IN�ICAIED OR APPROVED BY ARCHIIECT, �0 NOT PRONDE SUPPORT FR01� ROOF DECK. F. �0 NOT PENE1RAlE OR OIHERWISE NOTCH OR CUT S7RUCIVRAL MEMBERS WI7HOUi APPROVAL OF S7RUCNRAL ENGWEER. Q EQUIPMENT SUPPORT AN� ATTACHMENT: 1. 11SE METAL FABRICAIE� SUPPORTS OR SUPPORTS ASSEMBLED FROM IAETAL CHANNEL (S1RUT) TO SUPPORi EQOIPMENi AS REQUIRED. 2. USE MEiAL CHANNEL (SiRUi) SEWRED TO SiUDS i0 SUPPORi EOUIPMENi $URFACE-M1IOUMED ON HOLLOW $iUD WALL$ WHEN WALL $iRENGTH I$ NOT $UFFlCIENi i0 RESISi PULL-OUT. 3. USE MEiAL CHANNEL (S1RUT) i0 SUPPORT SURFACE-MOUNiED EQUIPMENT M WET OR DAMP LOCATIONS i0 PROVIDE $PACE BEiwEEN EQUIPIAENi AND 1�OUNiING $URFACE. 4. SECURELY FASiEN FLOOR-MOUNiED EQUIPIAENi. DO NOT INSTALL EQUIPMENT SUCH iHAi IT RELIES ON IT$ OWN WEIGHi PoR $UPPORT. H, SECURE FASIENERS ACCORDING TO MANUFACiURER'S RECOMMENDED TORQUE SEiTINGS L REMOVE iEIAPORARY SUPPORiS. SECTION 2fi.05.31.13 CONDUIT FOR ELECiRICAL SYSTEMS PART 1 PRO�UCiS i.oi callowr aaaucnnaNs A. DO NOT USE CONDUIT AN� ASSOCIAIED FITiINGS FOR APPLICATIONS OTHER 7HAN AS PERMIiTE� BY NFPA 70 ANO PRO�UCi 115PNG. B. UNlESS OTHERINSE IN�ICAIED AND WHERE NOT O7HERWISE RES7RICIE� USE THE CON�UIT iYPES INDICATE� FOR THE SPEQFIE� APPLICATIONS. WHERE MORE THAN ONE LISTE� APPLICAlION APPLIES, COIAPLY WITH 1HE MOST RESIRICPVE REQUIREMENTS. WHERE CON�UIT TYPE FOR A PARTICULAR APPLICA➢ON IS NOT SPECIFIED, USE GALVANIZED STEEL RIGI� METAL coNouiT. G CONCEALE� 'M1HIN MASONRY WALLS: USE GALVANIZE� S1EEL RIGI� MEiAL CONDUIT, INTERME�IATE METAL CON�UIT (IMC), OR ELEC7RICAL METALLIC 1UBING (EMT). �. CONCEALE� W11HIN HOLLOW SND WALLS�. USE GALVANIZED STEEL RIGI� METAL CON�UIT, INTERMEDIATE METAL CON�UIT (IMC), OR ELECTRICAL NETALLIC 1UBING (EMT). E CONCEALE� ABOVE ACCESSIBLE CEILINGS USE GALVANIZED S1EEL RIGI� METAL CON�UIT, IMERMEDIATE MEiAL CONDUIi (IMC), OR ELECiRICAL I�EiALLIC IDBING (EMT). F. INTERIOR, �AMP OR WET LOCAlI0N5: USE GALVANIZE� S1EEL RIGID MEiAL CONDUIi. G E%POSE�, INTERIOR, NOT SUBJECT TO PHY9CAL DAMAGP. USE GALVANRED STEEL RIGID IAETAL CONDUIT, WiERIAEDIAiE MEiAL CONDUIi QMC), OR ELECTRICAL MEiALLIC iUBING (EMT). H. ExPOSED, IMERIOR, SUBJECT TO PHYSICAL DAI�AGE USE GALVANIZED SiEEL RIGID METAL WNDUIT OR INTERME�IATE MEiAL CONDUIi (IMC). I. LOCAiIONS SUBJECT i0 PHYSICAL DAMAGE INCLUDE, BUi ARE NOi LIMIiED i0: a. WHERE E%POSED BELOW 8 FEET, ENCEPT WIiHM ELECiRICAL AND COMMUNICATION ROOMS OR c�osers. b. WHERE E%POSED BELOW 20 FEEi IN WAREHOUSE AREAS. I. E%POSED, ExTERIOR: USE GALVANIZED STEEL RIGID METAL CONDUIT, WIERM1IEDIAIE METAL CONDUIT Q1�C), OR PVC-COAIED GALVANRED SiEEL RIGID METAL WNDUIT. J. CONNECilONS i0 VIBRAiING EQUIPI�ENi: I. DRY LOCAilONS� USE RE%IBLE MEiAL CONDUIi. 2. DAM1IP, WET, OR CARROSI�E LOCAilONS: USE LIOUIDTIGHi RE%IBLE �AEiAL CONDUIi. 3. IAAXIMUM1I LENGiH: fi FEET UNLE55 OiHERWISE INDICATED. 4. VI6RAiING EQl11PMENi WCWDES, BUT IS NOT LIIAITED T0: a. I�OTORS. K FlSHED W EXISTING WALLS, WHERE NECESSARY: USE FLERIBLE MEiAL CONDUIi. 1.02 CON�UIT REOUIRENEMS A E%ISTING WORK: WHERE EXISPNG CON�UITS ARE W�ICATE� TO BE REUSE�, THEY MAY BE REUSE� ONLY WHERE 7HEY COMPLY WI7H SPEQFIE� REQUIREMENTS, ARE FREE FROM1I CORROSION, AN� INTEGRITY IS VERIFlE� BY PULLING A NAN�REL 1HROUGH THEM. B. PRON�E ALL CON�UIT, FITPNGS, SUPPORTS, AN� ACCESSORIES REQUIRED FOft A COMPLETE RACEWAY SYSIEM. C. PRONDE PRO�UCTS LISTE�, CLASSIFIED, AN� LABELE� AS SUITABLE FOR 7HE PURPOSE INTEN�ED. �. WHERE CON�UIT SIZE IS NOi INDICAIED, SIZE TO COIAPLY WITH NFPA 70 BUT NOT LESS 1HAN APPLICABLE 1�INIMUM SIZE REQUIREMENTS SPECIFlED, L03 GALVANIZE� STEEL RIGI� METAL CON�UIT (ftMC) A. �ESCRIPiION: NFPA 70, T1PE RMC GALVANIZED S7EEL RIGI� METAL CON�UIT COIAPLYING WITH ANA C80.1 AN� LISIED AN� LABELED AS COMPLYING 'M1H UL 6. B. FITfINGS: L NON-HAZARDOUS LOCATIONS: USE FIiTINGS COMPLYING WITH NEMA FB 1 AND LISIED AND LABELED AS COMPLYING W11H UL 514B. 2 IAAiERIAC USE SiEEL OR MALLEABLE IRON. A CANNECi0R5 AND COUPLINGS: USE iHREADED i1PE FlTiINGS ONLY. iHREADLESS SEi SCREw AND fAMPRE5510N (GLAND) iYPE FITIINGS ARE NOi PER1�ITffD. 1.04 INTERME�IATE METAL CON�UIT (IMC) A. �ESCRIPiION: NFPA 70, T1PE IMC GALVANIZE� STEEL INTERMEDIATE MEiAL CON�UIT COMPLYING WITH ANSI C80.6 AN� LISiE� AN� LABELE� AS COMPLYING WI7H UL 1242. B. FITfINGS: 1. NON-HAZAR�OUS LOCATIONS: USE FITTINGS COMPLYING WITH NEMA FB 1 AN� LIS1E� AN� LABELED AS COMPLYING Wlhl UL 514B. 2 1AATERIAL USE SiEEL OR MALLEABLE IRON, 3- WNNECTORS AND CAUPLINGS: USE iHREADED i1PE FlTiINGS ONLY. hIREADLESS SEi SCREw AN� WMPRESSION (GLAN�) iYPE FIT➢NGS ARE NOi PERI�ITIE�. L05 PVC-COAIE� GALVANIZE� S7EEL klGl� METAL CONDUIT (RMC) A. �ESCRIPiION: NFPA 70, T1PE RMC GALVANIZE� S7EEL RIGI� METAL CONDUIT WI1H EXIERNAL PoLYVINYL CHLORI�E (PVC) WATING COMPLYING WI7H NEI�A RN 1 AN� LISIED AN� LABELE� AS COMPLYING WIiH UL 6. 9. E%TERIOR COAiING: P�LYNNYL CHLORIDE (PVC), NOMINAL iHICKNESS �F 40 MIL. C. PVC-COAIED FITPNGS�. I. IAANUFACIURER SAME AS I�ANUFACIDRER OF PVC-COAIED CONDUIT TO BE INSTALLED. 2 NON-HAZARDOUS LOCATIONS USE FITTINGS LIS7ED AN� LABELED AS COMPLYING WI7H UL 514B. 3. MATERIAL USE STEEL OR MALLEABLE IRON. 4. E%TERIOR COA➢NG: POLYNNYL CHLORIDE (PVC). M1IINIMUM THICKNESS OF 40 MIL. D. PVC-COAIED SUPPORTS: FURNISH WIiH E#ERIOR COAIING OF POLYNNYL CHLORIDE (PVC), MINIMUM THICKNES$ OF 15 MIL. 1.06 FLE%IBLE METAL CONDUIi (FMC) A. DESCRIPiION: NFPA 70, T1PE FMC STANDARD WALL S1EEL FLExIBLE METAL CONDUIT LISTED AND LABELED AS COMPLYING wliH UL 1, AND LISTED FOR USE IN CLASSIFlED FIRESiOP SYSiE1�5 i0 BE USED. B. FIiiINGS: I. DESCRIPiION: FlTiINGS C01�PL11NG N7iH NEI�A FB 1 AND LISiED AND LABELED AS COMPLYING WITH UL 514B. 2 IAATERIAC USE 4EEL �R MALLEABLE IRON. 1.07 LIOUIDTIGHT RE%IBLE MEiAL CONDUIi (LFN,C) A. �ESCRIPiION: NFPA 70, T1PE LFMC POLYNNYL CHLORI�E (PVC) JACKEIED SiEEL FLEXIBLE METAL CONDUIT LISIED AND LABELED AS COIAPLYING WITH UL 360. fl FITfINGS: L DESCRIPiION: FlTIINGS C01�PLnNG Wlhi NEMA FB 1 AND LISiED AND LABELED AS COMPLYING WITH UL S4B. 2 IAAiERIAC USE SiEEL OR MALLEABLE IRON. L08 ELECIRICAL METALLIC TUBING (E1AT) A. DESCRIPiION: NFPA 70, T1PE EMT STEEL ELECTRICAL METALLIC iUBING COMPLYING WIiH ANSI C80.J AND LISiED AND LABELED AS COMPLYING W11H UL 797. B. FIiiINGS: 1. DESCRIPiION: FliiINGS CO�IPLnNG wlhi NEMA FB 1 AND LISiED AND LABELE� AS COMPLYING WITH UL 514B. 2 IAATERIAL: USE SiEEL OR MALLEABLE IRON. 3- WNNECTORS AND CAUPLINGS: USE COMPRESSION (GLAND) OR SET-SCREW TYPE. a. DO NOT USE INDENTER TYPE WNNECi0R5 AND CAUPLINGS. 4. �AMP OR WET LOCAlIONS (WHERE PERIAITIED): USE FITiINGS LISIED FOR USE IN WET LOCAilONS. 1.09 ACCESSORIES A. WNDUIT JOINT COMPOUND�, CORROSION-RESISTANT, ELECiRICALLY CONDUCTIVE; SUIiABLE FOR USE WIiH iHE CONDUIi TO BE INSTALLED. B. PULL $TRING4 USE NriON CORD w1TH AVERAGE BREAKING $iRENGTH OF NOi LE55 iHAN 200 POUND-FORCE. Q SEALING COMPOUND PoR SEALING FliiINGS: LI4ED FOR USE W1iH THE PARiICULAR FlTiINGS i0 BE INSTALLED. PART 2 E%ECUiION 2.01 INSTALLAlION A. INSiALL PRODUCi51N ACCOR�ANCE Wlhl MIANUFACiURER�S INSiRUCilONS. B. PERFORM WOftK IN ACCOR�ANCE WITH NECA 1(GENERAL WORKMANSHIP). C. INSTALL GALVANRE� STEEL ftIGID METAL CON�UIT (RMC) IN ACCOR�ANCE WI1H NECA 101. D. INSTALL INiERMEDIATE I�ETAL CON�UIT QMC) IN ACCOR�ANCE WI7H NECA 101. E INSTALL PVC-COATED GALVANIZED SiEEL RIGD M1IEiAL CONDUIi (RMC) USING ONLY TOOLS APPROVED BY iHE MANUFACiURER. r. coNowT suPPoaT: I. SEQIRE AND SUPPORT C�NDUITS IN ACCOR�ANCE N71H NFPA 70 AN� SECP�N 26.0529 USWG SOITABLE SUPPORTS AND METHODS APPROVED BY 7HE AUIHORIiY HANNG JURIS�IC110N. 2. 'ROVI�E INDEPEN�E\T SUPPORT FROM BWLDMG S1RUCIVRE. �0 NOT PRON�E SUPPORT FRON 'IPINC, �UCTWORK, OR OTHER SYSIEMS. G CONNECTONS AN� TERMINA710NS: L USE APPROVE� ZINC-RICH PAINT OR CON�UIT JOINT WMPOUN� ON FIEID-CUT 1HREA�S OF GALVANRE� STEEL CONDUITS PRIOR TO MAKING CONNECTIONS. 2 WHERE iW0 1HREA�ED CON�UITS MUST BE JOINE� AN� NEITHER CAN BE ROTAIE�, USE THREE-PIECE COUPLINGS OR SPLIT COUPLINGS. �0 NOT USE RUNNING 1HREA�S. 3. USE SUITABLE ADAPTERS WHERE REOUIRE� TO 1RANSI110N FROM ONE iYPE OF CONDUIT TO ANO7HER. 4. PRONDE DRIP LOOPS FOR LIOUIDTIGHT FLE%IBLE CONDUIT CONNECIIONS TO PREVENT DRAINAGE OF LIQUID INiO CONNECTORS, 5. iERMINAiE iHREADE� CONDUITS IN BOxES AND ENCLOSURES USING iHREADED HUBS OR DOUBLE LOCK NUiS PoR DRY LOCAiION$ AND RAINiIGHi HUBS FOR WEi LOCAiION$. 6. PRONDE WSULAiING BUSHINC$ OR INSULAiED iHR0Ai5 Ai ALL CONDUIi iERNINAlI0N5 i0 PROiECi CONDUCi0R5. 7. $ECURE JOINT$ AND CONNECTION$ TO PROVIDE I�ANII�UM I�ECHANICAL $iRENGiH AND ELECiRICAL CONiINWTY. H. PENEiRAilONS: 1. DO NOT PENETRAiE OR OTHERWISE NOTCH OR CUT STRUCTURAL ME�IBERS,INCLUDING FOOTINGS AND GRADE BEAMS, WITHOUT APPROVAL OF SiRUCiURAL ENGWEER. 2 MAKE PENETRATIONS PERPENDICULAR TO SURFACES UNLESS OIHERWISE IN�ICAIED. 3. PRON�E SLEEVES FOR PENETRAiIONS AS INDICAIE� OR AS REQUIRED TO FACILITATE INSTALLAlION. SET SLEEVES FWSH WITH E%POSE� SURFACES UNLESS OIHERWISE INDICATE� OR REowREo. 4. CONCEAL BEN�S FOR CONDUIT RISERS EMERGING ABOVE GROUN�. i SEAL IN1EftI0R OF CONDUITS ENTERING 1HE BUILDING FROM UNDEftGROUN� AT FIRST ACCESSIBLE POINT TO PREVENT EN1RY OF MOISIURE AN� GASES. 6. WHERE CON�UITS PENETRATE WAIERPft00F MEMBRANE, SEAL AS ftEQUIRE� TO MAINTAIN INTEGRIiY OF MEIABRANE. 7. MAKE PENETRATIONS FOR ROOF-IAOUNTED EQUIPMENT WIiHIN ASSOCIATED EQUIPIAENT OPENINGS AND CURBS WHERE POSSIBLE TO IAINIMIZE ROOFING SYSiEM PENETRAilONS. WHERE PENETRATIONS ARE NECESSARY, SEAL AS INDICAIED OR AS REQUIRED TO PRESERVE INTEGRIiY OF ROOFlNG SK1EM AND MAINiAIN RWF WARRANiY.INCLUDE PROPOSED LOCAilONS OF PENEiRAilONS AND I�ETHODS FOR SEALING WIiH SUBMIiTALS. 8. INSTALL FlRESiOPPING i0 PRESERVE FlRE RESISiANCE RAiING OF PARiIiIONS AND OiHER ELEMENTS, USINC 1�ATERIALS AND MEiHODS SPECIFlED IN SECTION 07.84.00. I. CONDUIT MOVE�IENT PROVISIONS�. WHERE CONDUIT$ ARE SUBJECT i0 MOVEMENT PROVIDE E%PANSION AND EXPANSION/DERECiION FlTiINGS i0 PREVENT DAMAGE TO ENCLOSED CONDUCi0R5 OR CONNECiED EQUIPMENL iHl$ INCLUDES, BUi IS NOi LIIAIiED i0: 1. WHERE CONDUIiS CRO55 $iRUCiURAL JOINiS IMENDED FOR E%PANSION, CONiRACiION, OR DEFLECiION. 2. WHERE CONDUITS ARE SUBJECT W EARiH I�OVEMENT BY SETiLEM1IENi OR FROSi. J. CONDENSAiION PREVENTION: WHERE CON�UITS CROSS BARRIERS BEiWEEN AREAS OF POiENiIAL suasTaNnn� rEMPERnTURE oiFFEaENnn�, aRowoE sEnuNc FirnNc oR naaRovEo sEnuNc COMPOUNO AT AN ACCESSIBLE POINT NEAR THE PENETRATION TO PREVENT CON�ENSAPON. THIS INCLU�ES, BUi IS NOT IJMIiE� T0: 1. WHERE CON�UITS =ASS FROM OUIDOORS INTO CONDIPONE� INIERIOR SPACES. 2 WHERE CONDUITS 7AS5 FROM UNCON�IPONE� W7ERIOR SPACES INTO CON�ITIONE� INTERIOR SPACES. SECiION 26.05.3316 BOxES PoR ELECiRICAL SYSiEuS PART 1 PRODUCiS 1.OI BOXES A. GENERAL REOUIREI�ENTS. 1. DO NOT USE BONES AN� ASSOCIATE� AWESSORIES FOR APPLICAlI0N5 O1HER THAN AS PERMITTE� BY NFPA 70 AN� PRODUCT LISTING. 2 PRON�E ALL BO%ES, FlTIINGS, SUPPORTS, AN� AWESSORIES REQUIRE� FOR A COMPLEIE RACEWAY SYSTEM AN� TO ACCOMMO�ATE DEVICES AN� EQUIPMENT TO BE INSTALLED. 3. PRON�E PRODUCTS LIS7E�, CLASSIFlE�, AN� LABELED AS SUITABLE FOR 1HE PURPOSE mTEnoEo. 4. WHERE BOX SIZE IS NOT IN�ICAIE�, SRE TO COMPLY WITH NFPA 70 BUT NOT LESS 1HAN APPLICABLE IAINIMUM SRE REOUIREMENTS SPEQFIED. i PRONDE GROUN�ING TERMINALS N7THIN BORES WHERE EOUIPMENT GROUNDING CONDUCTORS iER1�INAlE. B. OUiLEi AND �EVICE BOXES UP TO 100 CUBIC INCHES,INCLUDING iHOSE USED AS JUNCPON AND PULL BOXES: 1. USE SHEET-SiEEL BOXES FOR DRY LOCATIONS UNLE55 OiHERWISE INDICAIED OR REQUIRED. 2 USE CASi IRON BOxES OR CAST ALUMINU�I BOxES FOR DAMP OR WEi LOCATIONS UNLE55 OhiERW15E INDICAiED OR REQUIREP, FURNISH W1iH COIAPATIBLE WEAiHERPR00F GASKEiED CO�ERS. 3. USE SUITABLE I�ASONRY i1PE BONES WHERE FLUSH-MOUMED IN I�ASONRY WALLS. 4. SHEET-STEEL 90%ES: COMPLY 'MiH NEMA OS I, AND LIST AND LABEL AS COI�PLYING WIiH UL 514A. 5. CASi I�ETAL BO%ES: COM1IPLY WI7H NE�IA FB 1, AND LIST AN� LABEL AS G�MPLYING WITH UL 514A; FURNISH WI7H 1HREADED HUBS. fi. BOXES FOR SUPPORIING WMINAIRES AND CEILMG FANS'. LISTE� AS SUITABLE FOR THE TYPE AND WEIGHT OF LOA� TO BE SUPPOR7ED; FURNISHED WITH FlXTURE STU� TO ACCOMMO�AIE MOUNTING OF WMINAIRE WHERE ftEQUIRE�. 7. BOXES FOR GANGED DENCES USE MULIIGANG BO%ES OF SINGLE-PIECE CONSIRUC110N. �0 NOT USE FIEL�-CONNECTE� GANGABLE BOXES UNLESS SPECIFlCALLY INDICATE� Oft PERMIiTE�. G CABINETS AN� ENCLOSURES, INCLU�ING JUNCTION AN� PULL BO%ES LAftGER 1HAN 100 CUBIC INCHES. 1. COMPLY W11H NEMA 250, AN� LISi AN� LABEL AS COMPLYING WIiH UL 50 AND UL SOE, OR UL 508A. 2 NEMA 250 ENVIRONMENT iYPE, UNLE55 OTHERWISE INDICATED� 1 JUNCTION AND PULL BOxES LARGER iHAN 100 CUBIC INCHES: o. P40NDE SCREW-COVER OR HINGED-COVER ENCLOSURES UNLE55 OIHERWISE INDICAiED- P�HI L tXt'.�lilON 2�1 INSTALLAiION a MSTAIL PkODUCiS IN ACCORDANCE WITH 1�ANUFACNRER'S INSTRUCTIONS, B. MSTALL BOXES IN ACCOR�A\'CE WI1H NECA 1(GENEftAL WORNMANSHIP) ANQ WHERE APPLICA�LC, NECA 130, INCWDING IAOUNIING HEIGHTS SPECIFIED IN 7HOSE STAN�ARDS WHERE MOUNTING HEIGHTS ARE NOT IM CATE�. C. ARRANGE EQUIPMENT TO PROVIDE MINIMUM CLEARANCES IN ACCOR�ANCE W11H MANUFACIDRER'S INSIRUCTIONS AND NFPA 70. D. BOX SUPPORTS 1. SECUftE AND SUPPORT BORES IN ACCOR�ANCE 'M1H NFPA ]0 AN� SECiION 26 0529 USING SUITABLE SUPPORTS AND MEiHODS APPROVE� BY 1HE AUIHORITY HANNG JUftI5DIC110N. 2. PRONDE INDEPEN�ENT SUPPORT FROM BUIL�ING SIRUCIDRE E%CEPT FOR CAST METAL BOXES (OTHER THAN BOXES USE� FOR FIXTURE SUPPORT) SUPPORIED BY THREA�E� CON�UIT CONNEC110NS IN ACCOR�A\CE WI1H NFPA 70. �0 NOT PRONDE SUPPORT FROM PIPING, DUCTWORK, OR OiHER SYSiEMS. E. MSTALL BOXES PLUMB AN� LEVEL. F. FWSH-MOUNiE� BO%ES: L MSTALL BOXES IN NONCOMBUSTIBLE MAiERIALS SUCH AS WNCRETE, PLE, GYPSUM, P_AST R, ETC. SO 1HAT FROM EDGE OF BOR OR ASSOCIATED RAISED CO�ER IS NOT SET BACK FROM FINISHED SUftFACE MOftE 1HAN 1/4 INCH OR DOES NOT PROJECT BEYON� FINISHE� SURFACE. 2 MSTALL BOXES M WMBUSIIBLE IAATERIALS SUCH AS W00� SO iHAT FRONT E�GE OF BOX OR ASSOCIATED RAISE� COVER IS FWSH WITH FINISHE� SURFACE. 3. REPAIR ROUGH OPENINGS ARCUND BORES IN NONCOMBUSTIBLE MAIERIALS SUCH AS WNCREiE, iILE, GYPS.,M, PLASEf+, ETC. SO THAT iHERE ARE NO GAPS OR OPEN SPACES GREATER THAN 1/B INCH AT THE E)Gc CF THE BO%. G. MSTALL BOXES AS 9cCUiRED TO PRESERVE INSULATION INTEGRITY. H. MSTALL FIRCSiOPPING i0 PRESERVE FIRE RESISTANCE RATING OF PARTIPONS AND Oill R ELEMENTS, bSING MATERIALS AND MEIHODS SPECIFIED IN SECTION OZ84.00. L CLOSE UNUSED BO% OPENINGS J. INSTALL BLANK WALL PLAlES ON JUNC110N BOxES AND ON OUTLEi BOxES wliH No ofVICFs oR EQUIPMENi INSTAIlED OR DESIGNAiED FOR FUiURE USE. K. VHONDE GROJNI]ING dND BONDING IN ACCORDANCE WIIH StCIION 26 05.16. SECiION 26.0.5.53 IDEN➢FlCATION FOR ELECiRICAL SYSiEMS PART 2 PRODUCiS 1.01 I�ENiIFlCATION REQUIREIAENTS A. I�ENiIFlCATION FOR EQUIPMENi: i. use ioENnFicnnaN NnMea�nTe To ioeNnFr enc� aiece oF e�ECTeica� oisTeiaunoN allo CONTROL EOUIPMENT AN� ASSOCIATE� SEC110NS COMPARIMENTS AN� COMPONENTS. a. PANElBOAR�S: I) I�ENTIFY POWER SOURCE AN� QRCUIT NUMBER.INCLU�E LOCAiION WHEN NOT WITHIN SIGHi OF EOUIPMENT. 2) USE NPEWRITiEN CIRCWT DIRECTORY TO IDENTIFY LOAD(5) SERVED PoR PANELBOARDS WITH A DOOR.IDENIIFY SPARES AND SPACES USING PENQL. b. ENCLOSE� SWITCHES, CIRWIT BREAKERS, AN� MOTOR CONIROLLERS: I) IDENiIFY POWER $OURCE AND CIRCUIi NUMBER.INCLUDE LOCAiION WHEN NOi WIiHIN SIGHi OF EQVIPMENi. B. IDENiIFlCATION FOR CONDUCi0R5 AND CABLES'. 1. WLOR CODING FOR POWER CONDUCTORS 600 V AND LE55: COM1IPLY WIiH SECiION 26.05.19. 2 USE I�ENPFlCATION NAMEPLATE OR IDENiIFlCATION LABEL TO IDENiIFY COLOR CODE FOR UNGROUNDED AND GROUNDED POWER CONDUCTORS INSIDE DOOR OR ENCLOSURE AT EACH PIECE OF FEE�ER OR BRANCH-CIRCUIi DISTRIBU110N EOUIPMENT WHEN PREMISES HAS FEEDERS OR BRANCH CIRCUIiS SERVE� BY MORE 1HAN ONE NOMINAL VOLTACE SYSIEM. 1.02 I�EN7IFlCATION NAMEPLAlES AN� LABELS A. I�EN7IFICATION NAMEPLAIES: 1. MATERIALS�. a. INDOOR CLEAN, DRY LOCAiIONS: USE PLASIIC NAMEPLAIES. b. OUIDOOR LOCAlI0N5: USE PLASTIC, SiAMLESS S7EEL, OR AWMINU�I NAMEPLAiES SUITABLE FOft E%TERIOR USE. 2. PLAS➢C NAMEPLAIES: iW0-LAIER OR THREE-LAYER LAMINATED ACRYLIC OR ELECT9ICALLY NON-CONDUCTIYE PHENOLIC W17H BEVELE� EDGES; MINIMUM 7HICKNESS OF 1/16 INC-; ENGRAVE� TEXT 3. STAWLESS STEEL NAI�EPLATES: I�INIMUM 1HICKNESS OF 1/32 INCH; ENGRAVED OR LASER-ETCHED TEHT. 4. MOUNTING HOLES FOR MECHANICAL FASTENERS: 7W0, CENIERE� ON SI�ES FOft SIZES UP TO I INCH HIGH; FOUR, LOCATE� AT CORNERS FOR LARGEft SIZES. B. I�ENiIFICATION LABELS: 1. MATERIALS: USE SELF-ADHESIVE LAMINATE� PLASTIC LABELS; UV, CHEMICAL, WATER, HEAi, AN� ABRASION RESISTANT. 2. iEkT�. USE FACiORY PRE-PRINTED OR MACHINE-PRINiEO iE%T. DO VOT USE HANOWRITT N iE%T UNLE55 OiHERWISE INDICAIED. L0.3 WARNING SIGNS AND LABELS A- COMPLY W1iH AN51 Z5352 OR AN51 Z535.4 AS APPLICABIt, B. WARNING SIGNS: 1. MAiERIALS: o. INDOOR DRY, CLEAN LOCAilONS: USE FACTORY PRE-PRINiEO alGl� PLAS'IC OR SELF-ADHESI�E NNYL SIGNS. b. OOTDOOR LOCAlI0N5 11SE FACTORY PRE-PRIMED RIGID AWMINOIA SYGNS. 2 RIGI� SIGNS PROVI�E FOUR MOUNPNG HOLES Ai CORNERS FOR MECHANICAL FASiENERS. 3. IAINIMUM SIZE: 7 BY 10 WCHES UNLESS OTHERWISE INDICATE�. C. WARNING LABELS: 1. MATERIALS: USE FACiORY PRE-PRINTE� OR MACHME-PRW7ED SELF-ADHESIYE POLYESIER OR SELFA�HESIVE VINYL LABELS UV, CHEMICAL, WAIER, HEAT, AN� ABRASION RESISTANT; PRO�UCED USMG MATERIALS REWGNRE� TO UL 969. 2 MACHME-PftINTE� LABELS: USE 1HERMAL TRANSFER PROCESS PRINTING MACHINES AN� ACCESSORIES RECOMIAEN�ED BY LABEL MANUFACIDRER. 3. IAINIMUM SIZE 2 BY 4 INCHES UNLESS OTHERWSE INDICAiED. PART 2 E%ECU➢ON 2.01 INSTALLAlION A. INSTALL PftO�UCTS IN ACCOR�ANCE WITH MANUFACIURER'S INSIRUC110N5. B. INSTALL I�ENPFICATION PRODUCTS TO BE PLAMLY VISIBLE FOft EXAMINATION, A�JUSIMENT, SERVICING, AN� �IAINIENANCE. C. MSTALL I�ENPFICATION PRODUCTS CEN1EftED, LEVEL, AND PARALLEL WITH LINES OF IIEM BEING IDENiIFIED. D. SECURE NAMEPLAffS TO E%TERIOR SURFACES OF ENCLOSURES USING STAINLE55 STEEL SCREWS AND i0 INiER10R SURFACES USING SELF-ADHESIVE BACKING OR EPO%Y CEMENT. E INSTALL SELF-ADHESNE LABELS AND MARKER$ TO ACMEVE I�ARIMUM ADHESION, lNh' NO BUBBLES OR WRINKLES AN� EDGES PROPERLY SEALED. F. $EWRE RIGID SIGNS USING SiNNLE55 SiEEL SCREwS. G. MARK ALL HANDWRIiIEN iEXi, WHERE PERM1IIiiED, i0 BE NEAi AND LEGIBLE. r4���/S n harmac p y HUB/SSSI STORE NUMBER 08674 1421 RANGELWE ROAD CARMEL, IN 46032 CAPCODE: (90/88) CS PR0,IECT NUMBER 138374 ARCHITECT OF RECORD� • CONSULTANT ENGINEER� CONSULTANT� SEAL� REVISIONS: 03-09-2020 DRAWING BY: CVS PROJECT MANAGER: DATE: JOB NUMBER: TITLE PERMIT SET S. BEBA E ROSARIO 03-09-2020 JCDT19.0401.00 ELECTRICAL SPECIFICATIONS SHEET NUMBER: E1 COMMENTS: