HomeMy WebLinkAboutE6-HEALTHHUB-POWER-PLANHEALTHHUB GENERALNOTES
t PROVIDE HOSPIiAL GRADE WIRING, 5. INSiALL HOSPITAL GRADE, ISOLAiED
RECEPiA0.E5 AN� S�iCHES PoR iHE GROUN� RECEPiA0.E5 SIMILAR i0 LENiON
'�HEALIHHUB°. INSTALL WIRING AN� �8J00-IG TIPICAL PoR RECEPTACLES IN
�EVICES IN ACWRDANCE WIiH NEC ARPCLE HEALTHHUB. CABLING FOR iHESE
5�7. RECEPTAQES 1AAY USE RIGID CONDUIi OR
TmE HCF-90 C�9LE (MC CABLE IS NOT
2. REFER TO LOW VOLTAGE SPEC M1IANUAL ACC PiA�LC).
(RE�BOOK) FOR ADDITIONAL INFORMATION.
6. WnTkACTCR TO VERIFY EXISiENCE OF
3. ALL HEALiHHUB CIRCUITS SHALL BE ON A VOICc CABI\ET (WH TE CABINET),IF NO
DEDICATED CIRCUIL WHITE CABWEi E%ISTS ALL GRAY JACKS
SHOWN IN THIS FIGURE WILL BE REPLACE�
4. CONNECi HEALiHHUB LIGHiING i0 WI1H BLACK JACKS AN� CABLES RUN TO
EMS�iIMER ALONG WITH OTHER REiAIL THE FULL SIZE CABINET, EIIHER 7' OR 8'.
LIGHTING.
KEYED NOTES - HEALTHHUB POWER
p� PROVIDE MOTOR-RATED DISCONNECT SWITCH MOUNTED AT 78' AFF FOR
INSTANTANEOUS WATER HEATER. CONNECT TO DEDICATED GFCI 30A-2P
CIRCUIT BREAKER WIiH 2 g10 & 1 p10(G) - 3/4" C.
pp JUNCTION BOX MOUNT AT 53" AFF FOR UNDERCABINET LIGHTS. CONNECT
TO ROOM'S CEILING LIGHiING CIRCUIT.
p3 RELOCATE/ PROVIDE WIRING CHASE TO BE AS MANUFACTURED 8Y
WEIDENBACH-BROWN WITH ALL COMPONENTS FOR A COMPLETE AND
STAiIONARY INSTALLATION FOR CONCIERGE TABLE PROVIDE JUNCTION BOX
fi" ABOVE CEILING FOR WIRING CHASE CONNECTION. VERIFY LENGTH OF
WIRING CHASE REQUIRED PRIOR TO ORDERING. PROVIDE LOAD CENTER
ACCESS PANEL ON TABLE AS NEEDED.
pq PROVIDE FWSH MOUNTED DUPLEX RECEPTACLE FOR LEARNING TABLE RUN
CON�UIT BEHIND �RYWALL ALONG THE LOW WALL PROVIOE LOAD CENTER
ACCESS PANEL ON TABLE AS NEE�ED.
PS PROVIDE FWSH MOUNTED DUPLEX RECEPTACLE FOR CHARGING TABLE.
p5 PROVI�E 1/7'C AND PULL WIRE FROM 6" ABOVE CEILWG TO SINGLE GANG
JUNCTION BOX LOCATED 40" AFF FOR VOWME CONTROL.
P7 ALARM PUSH Bl1TTON. PROVIDE JUNCTION BOX WITH 3/4"C WITH Pl1LLWIRE
TO 6" ABOVE CEILING.
pg DEDICAiED GFCI DUPLEx RECEPTACLE FOR DRAIN PUMP. COORDINATE wITH
MECHANICAL TRADE FOR PLACEMENT.
p9 INSTALL HOSPIiAL GRADE, ISOLAiED GROUND RECEPTACLES SII�ILAR TO LEVIiON �8300-IG
iVPICAL FOR RECEPiACLES IN REiAIL HEALIH CENiERS. CABLING PoR THESE
RECEPTACLES MAY USE RIGI� CONDUIT OR T1PE HCF-90 CABLE (MC CABLE I$ NOT
ACCEPTABLE),
GC TO COORDINATE WITH CVS VENDOR FOR RELOCATION /REWSTALLATION OF
ALL CAMERAS, MOTION DETECTORS, SECURITY EQUIPMENT INCLUDING FlRE
ALARM EQUIPMENT.
�'��
pharmacy"
HUBISSSI
STORE NUMBffh 08674
1421 RANGELWE ROAD
CARMEL, IN 46032
CAPCODE: (90�88�
CS PRo,IECT NUMBER� 138374
ARCHITECT OF RECORD�
C�
CONSULTANT ENGINEER�
CONSULTANT�
SEAL�
�
REVISIONS:
03-09-2020 PERMIT SET
RELEA5E0 FOR CONSTRIICTI�N
Su6jec��ocompliancewithallregula�ions pLAN
of S�a�e antl Local Codes
City of Carmel
r
�un��\i lo•rvalM��_ _
DATE: 06�QZ�2O
�=�
MECHANICAL EQUIPMENT ELECTRICAL CONNECTION SCHEDULE
ITEM EQUIPMENT CHARACTEPoSTICS DISCONNECT SWITCH
DESCRIPTION CIRCUIT FEEDER
N0. VOLTS PH MCA SIZE PL FUSE FEATURES
1� CU-1 208 1 12 E-22,24 2�'12 & 1�'12G - 3/d' C. 30 2 15 3R
NOiE COORDINATE EYaCT LOCATIONS AN� ELECiRICAL REQUIREMENTS OF ALL 1AECHANICAL EOUIPMENT
REMARKS
COMPLETE CONNECTION BETWEEN INDOOR AND
OVIDOOR UNIT. SEAL, CORE AND FIRE CAULK
PENEiRATI0N5 AS NEEDED.
DRAWING BY: S. BEBA
CVS PROJECT MANAGER E ROSARIO
DATE: 03-09-2020
JOB NUMBER: JCDT19.0401.00
T�T�E:
HEALTHHUB
POWER PLAN
SHEET NUMBER:
E6
COMMENTS: