ELECTRICAL SYMBOL LIST
SYMBOL: TAG: SPEC DESCRIPTION:
SECTION:
O ECONN 260533 ELECTRICALCONNECTION
0
O JB 260533 JUNCTIONBOX
o -
EPO EPO 260916 EMERGENCVSTOP,N.O.CONTACT
26 32 13
� PANEL'Nttk' 262416 PANELBOARD-SURFACE MOUNT
� TR-N/DTR-ft 26220� TRANSFORMER.REFERTO
TRANSFORMERSCHEDULE
pi DS-#/FDS-#/DSS-ik 262816 DISCONNECT. REFERTODISCISTASCHEDULE
p� MD-SD-# 262816 MOBILEDIAGNOSTICSSERVICEDISCONNECT.
REFER TO DISGSTA SCHE�ULE
� REGDUP 262126 �UPLEXRECEPTACLE,125V
� REC-DUP-GFl 262126 �UPLEXGFIRECEPTACLE,125V
� REGSIM-520R 262126 SIMPLEXRECEPTACLE,125V
$ SW-iP 260933 SWITCH-SINGLEPOLE
$ SW=3W 260933 SWITCH-THREEWAV
OC p SW-OGD 260933 OCCUPANCVSENSOR-DUALTECHNOLOGV
5� SW-OC-P-0 260933 SWITCH-OCCUPANCVSENSOR
WALL SW ITCH
ELECTRICAL SYMBOL LIST
SYMBOL: TAG: SPEC DESCRIPTION:
SECTION:
O LINEAR WMINAIRES
� TROFFER
� WALLSCONCE WMINAIRE
O DOW NLIGHT LUMINAIRE
�O AIMABLE OR WALL WASH WMINAIRE
�� REFERTOLUMINAIRE INDUSTRIALWMINAIRE
� � SCHEOl1LE WqLLBRACKETLUMINAIRE
o-0 POLE MOUNTED WMINAIRE
� SINGLE FACE EXIT SIGN
yQ�p DOUBLE FACE EXIT SIGN
Y � WALLICEILING EMERGENCV EXITSIGN
1
� EMERGENCV 11NIT
ELECTRICAL EQUIPMENT TAGS
TAG: DESCRIPTION: Re�nreo
SPECIFICATION
DP-# DISTRIBUTIONPANEL 262416
DTR-# TRANSFORMER-DISTRIBUTIONTYPE 261219
REFERTOTRANSFORMERSCHEDULE
ELECTRICAL PHASING NOTES:
THESE NOTES APPLV TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
T0, LIGHTING, POWER, AND SVSTEMS.
7. REFERTO[ARCHITECTURAL�DRAWINGSFORGENERALDESCRIPTIONOFPHASES. REFER
TO �CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S� INSTRl1CTIONS
FOR MORE �ETAILS AND PHASING SCHEDl1LE5 AN� FOR CONCURRENT WORK.
MECHANICAL, ELECTRICAL AND TECHNOLOGV DRAW INGS DEPICT THE INTENT OF THE RNAL
DESIGN. THE MECHANICAL, ELECTRICAL AND TECHNOLOGV ORAWINGS DO NOT DEPICT
THE MEANS AN� METHODS TO MEET THE RE�UIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGE$ ETC.
W ITH AFFECTED ADJACENT AREAS.
3. PROVIDETEMPORARVLIGHTING,POWER,SVSTEMS,ETG ASNEEDEDTOMAINTAIN
SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARV LIGHTING, CIRCUITS, ETG AS NECESSARV TO KEEP ALL OCCUPIED
SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE �EMOLITION WORK TO MINIM2E DOWNTIME.
CONTRACTOR SHALL COMPLV WITH APPLICABLE CODES AND LOCAL AMENDMENTS.
BUILDINGCODE: INDIANABUILDINGCODE WITHAMENDMENTS
2014 EDITION
FlRECOOE: INDIANAFIRECOOE WITHAMENDMENTS
2012 EDITION
LIFE SAFETV CODE: NFPA 101 2012 EDITION W ITH AMENDMENTS
MECHANICALCOOE: INOIANAMECHANICALCOOE WITHAMENDMENTS
2014 EDITION
ELECTRICALCOOE' IEC2009EDITION WITHAMENDMENTS
(NFPA ]0-2008)
PWMBINGCODE: INOIANAPWMBINGCODE WITHAMENDMENTS
2012 EDITION
FIRECOOE: INOIANAFIRECO�E WITHAMENDMENTS
2014 EDITION
ACCESSIBIIITV CODE: INOIANA BUILDING CODE CHAPTER-11 W ITH AMENOMENTS
2014 EDITION
ELEVATORCODE: ASME1].3-2005,ASMEQEI-Y200] WITHAMENDMENTS
ANSIIASCE/T & D7 21-08
ENERGVCODE: INOIANAENERGVCONSERVATION WITHAMENDMENTS
CODE 2010
OTHERAPPLICABLE CO�E: FGIGl11DELINESFORDESIGN
AND CONSTRUCTION OF HOSPITALS
AN� HEALTHCARE FACILITIES
2018 EDITION
VIEW KEY
� N�ME � LEVEL NAME Q� INDICATES NOTE USED TO DESCRIBE
10'-0"�HEIGHTABOVE A�DITIONALINFORMATIONABOUT
PROJECTO'-0" WORKREQUIREqSPECIFICTOTHE
SHEET AND/OR DETAIL
INDICATES DIRECTION OF TRUE NORTH
PLAN OR DETAIL NUMBER
� PLAN OR DETAIL NAME
, � VIEW NAME
`� PLAN OR DETAIL SCALE
'�aRT�
INDICATES SIMILAR DETAIL
SI�ftEFERENCED IN MULTIPLE LOCATIONS
DETAIL REFERRED TO BV SECTION CUT
1
M101 SHEET DETAIL IS LOCATED ON
INDICATES SIMILAR DETAIL
REFERENCED IN MULTIPLE LOCATIONS
5�
�DETAIL REFERRED TO BV ELEVATION
4
3 T101� SHEET �ETAIL IS LOCATED ON
LME TVPE KEY:
NEW WORKBVTHISCONTRACTOR
(DARK SOLID LINE)
---- NEW WORK UNDERFLOOR OR UNDERGROUND BV THIS CONTRACTOR
(DARK LONG DASHED LINE)
NEW W ORK BV OTHERS ANOIOR EXISTING TO REMAIN
------- (LIGHT SOLID LINE)
EXISTING TO BE REMOVED BV THIS CONTRACTOR
(�ARK SHORT DASHED LINE)
ELECTRICAL GENERAL NOTES:
1. ##-#!tp INDICATES ELECTRICAL EQl11PMENT DEFINED IN ELECTRICAL SCHEDULES OR
SPECIRCATION. REFERTO DRAWINGS CONTAINING ELECTRICAL SCHEDULES. PERMANENT
NAMEPLATE SHALL MATCH FINAL E�UIPMENT NOMENCLATURE, NOT ELECTRICAL
EQUIPMENTTAG NAME, REFER TO SPECIFICATIONS.
2. "NL"INDICATESLUMINAIREISUNSWITCHEDFORNIGHTLIGHT.
3. SHADE� W MINAIRE OR �EVICE INDICATES LUMINAIRE OR DEVICE IS CONNECTED TO AN
EMERGENCV CIRW IT.
WMINAIRE KEV'
� Fi = FIXTURE TAG
1 =CIRCUIT NUMBER
LUMINAIRE a=SWITCHDESIGNATION
NL = SUBSCRIPT QF APPLICABLE)
9F LABEL IS OPoEMED HORIZONTALLV A SLASH W ILL SEPARATE THIS
INFORMATION. EX'. Fi I 1/ a I NL
DEVICE KEV:
DEVICE� A-MOUNTINGQFAPPLICABLE)
1 =CIRCUIT NUMBER
'IF LABEL IS ORIENTED HORRONTALLV A SLASH W ILL SEPARATE THIS
INFORMATION. EX'. A 11
A MOUNTATt6"TOCENTERLINEABOVECOUNTERORBACKSPLASH
C MOUNTATCEILING
H MOUNTORIENTEDHORIZONTALLV
L MOUNTINCASEWORK
M MOUNTINMODULARFURNITURE
R MOUNT IN SURFACE RACEWAV
ELECTRICAL INSTALLATION NOTES:
1. THE COMPLETE WSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS
ON THIS PAGE FOR ADDITIONAL WFORMATION.
2. CIRCUITNUMBERSARESHOWNFORCIRCUITIDENTIRCATION. CIRCUITINGSHALLAGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAV NOT BE USED FOR
BRANCHCIRCUITS. eALANCETHELOA�ONPANELASEVENLVASPOSSIBLEBETWEEN
EACHPHASE.
3. CIRCUITSSERVINGEMERGENCVANDEXITWMINAIRESWILLBERIININASEPARATE
RACEWAV FROM ALL OTHER CIRCUITS.
4. FWSHMOUNTALLLIGHTINGCONTROLDEVICESAT+46"FROMFLOOR(CENTERLINE
OIMENSION), EXCEPT WHERE OTHERWISE NOTED. OEVICES MAV BE SURFACE MOUNTED
WHEN CONDUIT IS SPECIFlEo EXPOSE�.
S FWSHMOUNTALLDUPLEXRECEPTACLESANDTECHNOLOGYOUTLETSAT+18"FROM
FLOOR(CENTERLMEOIMENSION),EXCEPTWHEREOTHERWISENOTED. RECEPTACLESAN�
OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIRED EXPOSED.
6. ALL MATERIALS USED TO SEAL PENETRATIONS OF RRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIRED AS A SVSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FlRESTOPS. REFER TO DIVISION 7 FOR ADDITIONAL MFORMATION
AND REQUIREMENTS SPECIFlC TO FlRESTOPPWG.
]. CONTRACTORSHALLCOOR�INATETHELOCATIONOFALLCEILINGMOUNTEDDEVICESAND
EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILWG DIFFUSERS. CENTER ALL DEVICES
W CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCVNACANCV SENSORS
SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLV DIFFUSER OR RETURN
GRILLE
8. CONTRACTOR SHALL VERIFV ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT
LOCATIONS W ITH ARCHITECTl1RAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS.
PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL
ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE
FURNITl1RE AND/OR EQUIPMENT.
9. ELECTRICAL AND TECHNOLOGV E�UIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,
OPERATIONOF,ANDIORACCESSTOELECTRICALANDMECHANICALEOUIPMENT. ALL
MOUNTING OF ELECTRICAL AND TELECOMMIINICATIONS EQUIPMENT, ON EQUIPMENT
SUPPLIED eV ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BV THE OTHER
CONTRACTOR.
10. CONTRACTORSHALLBERESPONSIBLEFORALLOPENINGSREQUIREOIN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BV A QUAUFlEo CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALE� INTO OPENINGS.
11. ALL WELDING SHALL BE ACCORDING TO AMERICAN WELOING SOGETV STANOARDS.
CONTRACTOR SHALL FURNISH TO THE ARCHITECTIENG W EER CERTIRCATES QUALIFYING
EACH WELDER, PRIOR TO START OF WORK. THE ARCHITECT/ENGINEER RESERVES THE
RIGHT TO REQUIRE QUALIFVING DEMONSTRATION, AT THE CONTRACTORS EXPENSE, OF
ANV W ELDERS ASSIGNED TO THE JOB.
12. CONTRACTOR SHALL REMOVE AND REINSTALL ALL CEILING TILES AS REpUIREO FOR THE
EXECUTION OF ELECTRICAL WORK. CONTRACTOR SHALL REPLACE CEILING TILES W ITH
IDENTICAL MATERIAL WHERE �AMAGED BV THIS CONTRACTOR.
13. REFERTOARCHITECTURALREFLECTEDCEILINGPLAN,ELECTRICAL,TECHNOLOGV
AUDIONISUAL, AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHERTHAN SPRWKLERS.
14. ELECTRICALINDENTIFICATION. REFERTOSPECIFICATIONSECTION260553FOR
WLORILABELREQUIREMENTSFOR CONDUIT,BOX,CABLENJIRE,ANDEQUIPMENT.
ABBR: I DESCRIPTION:
AFF ABOVEFINISHEDFLOOR
C CONDUIT
GFl GROUNDFAULTIMERRUPTER
N.Q NORMALLV CLOSED
NIC NOT IN CONTRACT
N.O. NORMALLV OPEN
SV SOLENOID VALVE
TVP TYPICAL
UNO UNLESSNOTEDOTHERWISE
SYMBOL: I DESCRIPTION:
� 0 NORMAL BRANCH LUMINAIRE
� � CRITICALBRANCHLUMINAIRE
� � LIFESAFETVBRANCHWMINAIRE
UNSWITCHED FOR NIGHT LIGHT, UNLESS NOTED'SE'
10" MA%. 10"-26" MAX.
INSTALLABOVECOUNTER INSTALLABOVECOUNTER INSTALLDEVICEATIB" INSTALLDEVICEAT44" INSTALLDEVICEAT42"
DEVICEAT46"ABOVE DEVICEAT60"ABOVE ABOVEFINISHEDFLOOR. ABOVEFINISHEDFLOOR. ABOVEFINISHEDFLOOR.
FINISHEDFLOOR. FINISHEDFLOOR.
ADA GUIDELINES - FRONT ACCESS ADA GUIDELINES - SIDE ACCESS
ADA STANDARDS FOR ACCESSIBLE DESIGN
ArchitecNre I Engineering I Interior Design
1�15 Magnavox Way I 930 Nohh Mentlian
Fort Wayne, IN 46804 Intlianapolis, IN 46204
260.432.9337 31].917.1190
wwwmskitlmm
<:IMEG
8900 KEVSTONE XING SUITE 210
INDIANAPOLIS, IN 46240
31�.848.5045 FAX:31�.8442201
www.imegcorp.com
L
�
�
a
'o
I..L
Q
U
•�
�/� U
if� �
O � W^,
� � L
� ��
� U �
O X •�
� w �
� A
U1 _
w 00
v / � r
• —`
U 'W
� +� �
�
� �
�U
�
�
�
�
�
a�
�o �
� �
�U
PROJECTNO. DATE
18004130.00 12-12-19
REV.
DATE
SET DESCRIPTION
BP #4.1 - Parking Garage &
Skybridge Arch / MEPT /
Interiors Package
SHEET TITLE
ELECTRICAL
COVERSHEET
SHEETNUMBER
EO-00
�.,. ....�� 12�12�19
MSKTD
& Associates