Loading...
HomeMy WebLinkAboutE7-00-PARKING-GARAGE-ONE-LINE-DIAGRAM-Rev.0� � RELEA5E0 FOR CONSTRUCTION Suhjec��o compliance with allregula�ions 04 S�a�e antl Local Codes City of Carmel y" �n„� ��.�a,�,a' � onrE: 06/11 /20 ATS-HLSi 480V 260A � 260A/3P � �LSI� 100N3P O�� 100N3P �� � ' rc r � 80N3P w z �� O3 � o- � m � ¢ `O 80N3P �� � o- 100N3P I O o- 60N3P �� � 4#300KCM & 1#4 GND IN 3" C. 48012]1V 3-PHASE 4W 65,000 SCCR �P=HLSHDPIA' (LOCATED IN HOSPITAL FlRST FLOOR ELECTRICAL ROOM) I 4#38 7#8 GND N 1 1/4"C. I 4#3 8 1#8 GND IN 1 1/4"C. 3#3 & 1#8 GN� 30 KVA N 1 il4" Q TR30 I48Q208I120V 3#3 & 1U8 GN� 30 KVA N 1 1l4" Q TR30 4#381#BGND 48a2081120V IN 1 1/4"C. 4#4 8 1#8 GND IN 1" C. I f (APPROXIMATE DISTANCE OF4]5'-0") O7 �(2)100A/3P SPACE GROUND NO SCALE PANEL'HLSHIA' PANEL'ALSH3A' DPM � PANEL'HLSLIA' 4#2 & 1#8 GND N � 1l4" C. PANEL'ALSL3A' DPM 4#2 & 1#8 GNO IN 1 il4" C. � PANEL'MLSH2A' � I / UTILITV PRIMARV SERVICE —(CONDUITAND W IRE BY UTILITV COMPANV) U UTILITV TRANSFORMER PAD BV n EG, PER UTILITV COMPANV REQUIREMENTS. C.T. COMPARTMENT AND �M METERING PER UTILITV COMPANVREpUIREMENTS. (2) SETS OF 4#SOOKCM EACH IN —5" G (CONCRETE ENCASED). 480/2]]V 3-PHASE 4W 65,000 SCCR — �DP-'GNHDPIA' I 600A/3P � 60N3P �� O � I100N3P O � 125AI3P �� I � 0 � � 20N3P w Z Or 4 � 20N3P m �� Oa r a `O 20N3P 0 � I20N3P O � 7 20N3P I O r 8 20N3P O � 20N3P �� 10 r 30N3P �\ 11 � 30N3P Q�� , . I30N3P �\ I 13 r 45N3P �� 14 r 20AI3P Q�� 1 r ISOAI3P �\ I i6 � I SOAI3P I �� 0 T� ' REMOVABLE 18 � (4) 250A SPACES �� L #4 GROUNDING ELECTRODECONDUCTOR CONCRETEENCASED ELECTRODE NEC 25�.52 BONDTOMINIMUMOF20' 2p.0 OF 1/2' REINFORCING BAR 3l4" DIA. x 10'-0" COPPER GROUND ROD. TOP OF ROD SHALL BE 12" BELOW GRADE(TVP.) NO SCALE 4#6 & 1#8 GND IN 1" C. MAXIMUM S-0" LENGTH SPD4 4#38 1#8 GND IN 1 il4" C. PANEL'GNH1A' 24 KVA 3#1 & 1k6 GND 45 KVA IN 1 il4" C. II TR30 3#12 & 1#12 GND 480208/120V �IN 3l4"C. � 3#12 & 1#12 GND IN 3l4" C. 3#12 & 1#12 GND IN 3l4" C. 3#12 & 1#12 GND IN 3l4" C. 3#12 & 1#12 GND IN 3l4" C. 3#12 & 1#12 GND �IN 3l4"C. 3#12 & 1#12 GND IN 3l4" C. 3#10 & 1#10 GND IN 3l4" C. 3#10 & 1#10 GND � N 3l4" C. 3#10 & 1#10 GND IN 3l4" C. 4k8 & 1#10 GND IN 1"C. 4k12 & 1#12 GND �IN 3/4"C. �_I 8 FDS-100 FDS-100 G#1I0 & 1#6 GND IN 2" C. CAB-G-A 10KW CAB-G-A 10KW CAB-G-A 10KW CAB-G-A 10KW UH-G-A 3]KW UH-G-A 3]KW UH-G-A 3]KW EDH-�i �.5KW EDH-01 �.5KW EDH-�i �.5KW EDH-01 �.5KW EDH-�i �.5KW EDH-01 �.5KW D5=60 60AI3P \_ E BCU-0 29.1 KVA D5=30 30AI3P E ACCU-G-BCU-0 8.3 KVA 100A/3P E ELEV4 � 3-70A AUXILIARV CONTACT W IRING TOELEVATORCONTROLLER 100A/3P E ELEV-2 Z� l 3-70A AUXILIARV CONTACT W IRING TOELEVATORCONTROLLER #4 INSUL4TED COPPER GROUNDING CONOUCTOR. PER NEC 250.94. MAXIMUM 20'-0" LENGTH #3/0 GROUNDING ELECTRODE CONDUCTOR EFFECTNELVGROUNDED IBT BUILDING STEEL CONNECT TO METALLIC INTERSYSTEM BONDING WATERMAIN,WITHINS'-�"OF TERMINATION,REFERTO WATER SERVICE ENTRANCE. MATERIAL LIST (IBT). PROVIOEJUMPERACRO55 WATER METER ONE LINE DIAGRAM NOTES 1. AICRATINGSLISTEDFOREQUIPMENTAREMINIMUMREQUIREMENTSFORBUSBRACMGANDDEVICE R/ATING. ALL EQUIPMENT SHALL BE FULLY RATED UNLE55 SPEQFICALLV NOTED AS SERIES RATED. p. 1 INDICATES DIRECT CONNECTION OF GROUND CONDUCTOR TO GROUN� BUS. - SUBSCRIPT"I" INDICATES DIRECT CONNECTION OF ISOLATED GROUND CONDUCTORTO ISOLATED GROUND BUS. 3. �INDICATESO.Z.GEDNEVOREQUALGROUNDBUSHWGBONDEDTOGROUNDBUSWITH CON�UCTOR SIZED TO MAXIMUM FEE�ER GROUND CAPACITV. q, �� INDICATES OVERLOA�S SIZED PER MOTOR NAMEPLATE FULL LOAD AMPERES. 5_ � INDICATES STARTER NEMA SIZE. 6. CIRCUITBREAKERCHARACTERISTICS: a[AF] INDICATES MOLDED/INSULATED CASE BREAKER FRAME SRE, FOR A�JUSTABLE TRIP BREAKERS. b. [AT] INDICATES MOLDED/INSULATED CASE BREAKERTRIP UNIT RATING, FOR A�JUSTABLETRIPBREAKERS. a[LSIG] INDICATES FEATURES PROVIDED W ITH SOLID STATE QRCUIT BREAKER [LONG TIME (W/DELAV), SHORT TIME (WIDELAV), INSTANTANEOUS, GROUND FAULT} d[LSIA] INDICATES FEATURES PROVIDED WITH SOLID STATE QRCUIT BREAKER. [LONG TIME (W/DELAV), SHORT TIME (W/�ELAV), INSTANTANEOUS GROUND FAULT ALARM (NO GROUND FAULT TRIP)]. e. [AER] INDICATES ARC ENERGV REDUCTION SVSTEM C �100 % RATED] INDICATES MOLDED/INSULATEO CASE BREAKER RATED FOR FULL CONTINUOUS CAPACITV OF CIRCUIT BREAKER NAMEPLATE. �� GF INDICATES GROUND FAULT RELAV. 8. CONDUCTOR AN� CON�UIT SIZES ON THE LME AN� LOAD SIDES OF ALL NON-FUSIBLE DISCONNECT SWITCHES SHALL BE IDENTICAL UNLESS NOTED OTHERW ISE. 9. DPM INDICATESDIGITALPOWERMONITOR. �p. OM INDICATES KILOWATT-HOUR METER AS SUPPLIED BV UTILITV COMPANV. 7�, C INDICATESCURRENTTRANSFORMER,SIZEASSPECIFlED. 12. �C INDICATES POTENTIAL TRANSFORMER, SIZE AS SPEQFIED. 13.�H) INDICATESDRAWOUTDEVICE. 74. ST INDICATESSHUNTTRIPBREAKER. 15. Q INDICATES VOLTMETER. i6. VS INDICATESVOLTMETERSELECTORSWITCH 77, � INDICATES AMMETER, RANGE AS REQUIRED FOR FULL CAPAGTV OF EQUIPMENT. �g. AS INDICATESAMMETERSELECTORSWITCH. �g, CN INDICATESLOADBREAKELBOW. 20. � INDICATES MEDIUM VOLTAGE TERMINATION. p�. LA�I�INDICATESLIGHTNINGARRESTORS. py,- �INDICATESMOTOROPERATOR. 23.- �INDICATESMOTORPROTECTIONRELAV. 26. K# INDICATES KEV MTERLOCK. 25. ATO INDICATESAUTOMATICTHROW WER. MSKTD & Associates ArchitecNre I Engineering I Interior Design 1115 Magnavox Way I 930 Nohh Mentlian Fort Wayne, IN 46804 Intlianapolis, IN 46204 260.432.9337 31].917.1190 wwwmskitlmm <:IMEG 8900 KEVSTONE XING SUITE 210 INDIANAPOLIS, IN 46240 31�.848.5045 FAX:31�.8442201 www.imegcorp.com �.,. ....`� 12/12/19 U •� �/� U it� �` O W W^, � � L � � �' U`'� O ^ •� � \ � w � � A � V �- � ca U 00� L /�//J� t � � O • � i� U V � � � � � N � � � � .o � � � � L a I� U � � PROJECT NO. DATE 18004130.00 12-12-19 REV. DATE SET DESCRIPTION BP #4.1 - Parking Garage & Skybridge Arch / MEPT / Interiors Package SHEET TITLE PARKING GARAGE ONE-LINE DIAGRAM SHEETNUMBER E7-00