HomeMy WebLinkAboutP0-00-PLUMBING-COVERSHEET-Rev.1�
RELEA5E0 FOR CONSTRUCTION
Suhjec� �o compliance with all regula�ions
04 S�a�e antl Local Codes
City of Carmel
�
y�n„� ��.�a,�,a'
�
onrE: 06/11 /20
VIEW KEY
�NAME � LEVEL NAME �� INDICATES NOTE USED TO DESCRIBE
10'-0"�HEIGHTABOVE ADOITIONALINFORMATIONABOUT
PROJECTO'-0" WORKREQUIRED,SPEQFICTOTHE
SHEET ANDIOR DETAIL
INDICATES DIRECTION OF TRUE NORTH
PLAN OR �ETAIL NUMBER
� PLAN OR DETAIL NAME
, � VIEW NAME
il8" = 1'-0"
� PLAN OR DETAIL SCALE
tioRs�
INDICATES SIMILAR DETAIL
SI�REFERENCED IN MULTIPLE LOCATIONS
DETAIL REFERRED TO BV SECTION CUT
1
M101 SHEETDETAILISLOCATE�ON
INDICATES SIMILAR DETAIL
REFERENCED IN MULTIPLE LOCATIONS
SI
�DETAIL REFERRED TO BY ELEVATION
4
3 T101�SHEET DETAIL IS LOCATED ON
LINE TVPE KEV:
NEW WORKBYTHISCONTRACTOR
(DARK SOLID LME)
— — — —NEW WORKl1NDERFLOORORUNDERGROUNDBVTHISCONTRACTOR
(DARK LONG DASHED LINE)
NEW W ORK BY OTHERS AND/OR EXISTING TO REMAIN
(LIGHT SOLID LINE)
------- EXISTING TO BE REMOVED BV THIS CONTRACTOR
(DARK SHORT DASHED LINE)
CONTRACTOR SHALL COMPLV W ITH APPLICABLE CODES AND LOCAL AMENDMENTS.
BWLDINGCODE: INDIANABWLDINGCODE WITHAMENDMENTS
2014 EDITION
FIRECODE: INDIANAFIRECODE WITHAMENDMENTS
2072 EDITION
LIFESAFETVCODE: NFPA1012012EDITION WITHAMENDMENTS
MECHANICAL CODE:
ELECTRICAL CODE:
PWMBING CODE:
FIRE CODE:
ACCESSIBILITV CODE'.
ELEVATORCO�E:
ENERGVCODE:
OTHER APPLICABLE CODE:
ABBR:
A.V.C.
GC.
C.M.
EC.
RP.C.
Fs c.
G.C.
H.C.
M.C.
N.QC.
P.C.
S.C.
T.C.
T.C.C.
V.C.
INDIANAMECHANICALCODE WITHAMENDMENTS
2014 EDITION
IEC2009EDITION WITHAMENDMENTS
(NFPA ]0.2008)
INDIANAPWMBINGCODE WITHAMENDMENTS
2072 EDITION
INDIANAFIRECODE WITHAMENDMENTS
2074 EDITION
INDIANA BWLDING CODE CHAPTER-11 WITH AMENDMENTS
2014 EDITION
ASME1].3-2005,ASMEQEI-1-200] WITHAMENDMENTS
ANSVASCE/T & Di 21-OB
INDIANAENERGVCONSERVATION WITHAMENDMENTS
CODE 2010
FGI GUIDELINES FOR DESIGN
AND CONSTRUCTION OF HOSPITALS
AND HEALTHCARE FAQLITIES
2018 EDITION
CONTRACTOR ABBREVIATION KEY
DESCRIPTION:
AUDIONISUAL CONTR4CTOR
CIVIL CONTRACTOR
CONSTRUCTION MANAGER
ELECTRICALCONTRACTOR
FlRE PROTECTION CONTRACTOR
FOOD SERVICE CONTRACTOR
GENERALCONTRACTOR
HEATING CONTR4CTOR
MECHANICALCONTRACTOR
NURSECALLCONTRACTOR
PWMBING CONTRACTOR
SECURITV CONTRACTOR
TECHNOLOGVCONTRACTOR
TEMPERATURECONTROLSCONTRACTOR
VENTILATION CONTRACTOR
PLUMBING SYMBOL LIST
NOT ALL SYMBOLS MAV APPLY.
SYMBOL: DESCRIPTION:
—AV ACID VENT
—AW ACID WASTE
—CA COMPRESSEDAIR
—CW COLDWATER-POTABLE
—D DRAIN
—DI DEIOMZED WATER
—DT DRAIN TILE
—G NATURALGAS
—GRV GAS REGULATOR VENT
—GSAN SANITARV �RAINAGE (GREASE SANITARY DRAINAGE)
—GV GREASE VENT
—HW HOTWATER-POTABLE
—HW HOTWATERCIRCULATING-POTABLE
—HW14 HOTWATER-POTABLE.Nl1M8ERINDICATESTEMP
—HWC14 HOTWATERCIRC.-POTABLE.NUMBERINDICATESTEMP
—IA INSTRUMENTAIR
—MA MEDICALAIR
—MV MEDICAL VACUUM
—N NITROGEN
—NCW NON-POTABLECOLDWATER
—NHW NON-POTABLE HOT WATER
—N NITROUS OXIDE
—OR OIL RETURN
—OS OILSUPPLV
— OXVGEN
—P PROPANEGAS
—PD PUMPED DISCHARGE
—PW PURE WATER
—R REVERSE OSMOSIS WATER
—SAN SANITARY�RAINAGE
—SCW SOFTCOL�WATER
—SHW SOFTHOTWATER
—ST(1,0�0 STORM DRAINAGE (ROOF SQUARE FOOTAGE)
—STS STORMDRAINAGE(SECONOARY)
—STW SOFTTEMPEREOWATER
—TW TEMPERED WATER
—V VENT
—VA LABVACWM
—W SERVICEWATER-POTABLE
—WAG WASTEANETHESIAGASOISPOSAL
� PIPE CONTINUATION
] PIPE CAP
J PIPEDOWN
� PIPEUPORUPIDOWN
PIPE SERVING FIXTURE ON FLOOR ABOVE
�FD (EXAMPLE:FD=FLOORDRAIN)
PITCH PIPE IN DIRECTION
DIRECTION OF FLOW IN PIPE
l ROUTE TO DRAIN
RD-1 ROOF DRAIN PROPERTIES SVMBOL
8"(1000) SIZE (ROOF SQ FT.)
� NEW CONNECTION
�i �IELECTRICCONNECTION
�I UNION/FLANGE
SHUTOFF VALVE NORMALLV OPEN
SHl1TOFF VALVE NORMALLV CLOSEO
GPM gqLANQNG VALVE (NUMBER IN�ICATES GPM)
�y CHECKVALVE
SOLENOI� VALVE
q ' SAFETY/RELIEF VALVE
� �
� VACUUMBREAKER
�. PRESSUREGAUGE(FURNISHEDWITHBALLVALVE)
��P PRESSURE SENSOR (FURNISHED WITH BALL VALVE)
4 TEMPERATURE SENSOR WITH WELL
QTHERMOMETERWITHWELL(DIALTVPE)
4 THERMOMETERWITHWELL�FILLEDTVPE)
REDUCER-REFERENCE SPEQFICATION
FOR CONCENTRIqECCENTRIC AND FOT/FOB
PRESSURE REDUqNG VALVE (LIQUID/GAS)
PUMP
M METER
= ALIGNMENTGUIDE
PIPEANCHOR
EXPANSION JOINT
CLEANOUTASSEMBLY.
SEE PWMBING
MATERIAL LIST.
CONCRETE SLAB (6") MINIMUM 9"
REMFORCED WITH WIRE ALLAROUND
MESH OR 3/8" DIAMETER
RODS 6" CENTERS EACH GRADE
WAV.SLOPEAWAV _.: f- ti
A56 MBLV TOP T -I I I �° . a. ° .. .�. I�
EXTEND CONCRETE PA[
6"BEVON�THELMEOF
UNDISTURBE� EARTH.
SAND BACKFlLL OR —
CLEAN TAMPED EARTH.
FROSTSLEEVE
PREDICTED DEPTH
OFFROST.
FROST SLEEVE TO BE
6" BELOW PREDICTED
DEPTH OF FROST,
OR-
6" TO 12" ABOVE
SEWER
ABBR: DESCRIPTION:
AD ACCESS�OOR
AFF ABOVEFINISHEDFLOOR
BFP BACKFLOW PREVENTER
BT BATHTUB
CB CATCH BASIN
q CASTIRON
CO CLEANOUT
CS CLINICALSINK
�B DIALVSISBOX
DF DRINKING FOUNTAIN
DI DUCTILE IRON
E EXISTING
EE EMERGENCVEVEWASH
ES EMERGENCVSHOWER
ESE EMERGENCVSHOWER/EVEWASH
EWC ELECTRICWATERCOOLER
FCO FLOOR CLEANOUT
F� FLOOR DR41N
FM FLOW METER
FS FLOOR SINK
GD GARBAGE DISPOSER
GI GREASE WTERCEPTOR
HB HOSE BIBB
I.E. INVERT ELEVATION (FOR REFERENCE ONLV)
LAV LAVATORV
MB MOPBASIN
MH MANHOLE
MV MI%ING VALVE
NC NEW CONNECTION
NIC NOT IN CONTRACT
NT NEUTRALIZATIONTANK
OS OILSEPARATOR
RD ROOF DRAIN
SH SHOWER
SK SINK
SS SERVICESINK
T� TRENCH DRAIN
TP TRAPPRIMER
TVP TYPICAL
UR URINAL
VTR VENTTHROUGH ROOF
WC WATERCLOSET
WCO WALLCLEANOUT
WF WASHFOUNTAIN
WH WATERHEATER
WMF WASHING MACHINE FIXTURE
WM WATERMETER
WS WATERSOFTENER
UB UTILITV BOX
UNO UNLESSNOTEDOTHERWISE
VCO VARD CLEANOUT
BLACKTOP OR CLEAN
TAMPEDEARTH.
FLEXIBLE PVC COUPLING W ITH
STAMLE55 STEEL BAND CLAMPS.
SUITABLE FOR UNOERGROUND
INSTALLATION. INDIANA SEAL, MODEL
NO. 156-88 OR EQUIVALENT.
NEOPRENEGASKET
LINE OF UNDISTURBEO EARTH.
e" SAN PIPE. SEE
SPECIFICATION SECTION 22
10 00 FOR MATERIAL.
1/8 BEND.
i� YARD CLEANOUT DETAIL
� NO SCALE
DOME
ri�m,[eiJ��
UNDERDECK CLAMP—
OUTLET SIZE AS
SHOW N ON DRAW INGS
PLUMBING GENERAL NOTES:
1. THE SVMBOLS AND THE MATERIAL LIST ARE FOR THE CONVEMENCE OF THE CONTRACTOR.
CONTRACTOR SHALL VERIFV QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR
FULLV OPERATIONAL SVSTEMS, W HETHER SPECIFIED OR NOT.
2 CATALOGNUMBERSSHALLNOTBEWNSIOEREDCOMPLETE,BUTAREGIVENASANAIDTO
THECONTRACTORANDTOINDICATETHEQUALITVREQl11RED. CONTRACTORIS
RESPONSIBLE FOR A COMPLETE DESCRIPTION OF MATERIAL ON THESE �RAWINGS AND IN
THESPEQRCATIONSBEFOREORDERING. THEOESCRIPTIONOFTHEMATERIALTAKES
PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANU FACTl1RER LISTE� IS THE
BASIS OF DESIGN.
3. CONTRACTORSHALLVERIFYTHATFIXTURESSUPPLIEOAREAPPROVE�PERALL
APPLICABLE STATE, LOCAL ANO GOVERNING AUTHORITIES.
4. ALL FlXTURES SHALL CONFORM TO FEDERAL ACT 5.38]4
5. INVERT ELEVATIONS ARE FROM ENGINEERING DR4W INGS ANO MAV NOT BE ACCl1RATE.
VERIFV ALL ELEVATIONS BEFORE BEGINNING WORK.
6. VEPoFV UNDERGROUND PIPE SIZES, INVERT ELEVATIONS, AND LOCATIONS PRIOR TO
BEGINNING ANV WORK.
]. REFER TO THE PW MBING ROUGH-IN SCHEDULE FOR THE SIZES OF BRANCH PIPES TO
PLUMBING RXTURES.
8. FOR CLARITV, NOT ALL VALVES HAVE BEEN SHOWN. PROVIDE SHUTOFF VALVES IN
�OMESTIC WATER PIPING SERVING EACH ROOM W ITH FIMURES. ANGLE STOPS SHALL NOT
BE CONSI�ERED SHUTOFF VALVES.
9. PLUMBING CONTRACTOR SHALL CUTAN� PATCH EXISTING AS REQUIRED FOR NEW OR
�EMOLITION WORK UNLESS NOTED OTHERWISE. REFER TO SPECIFICATION SECTION 22 05
05 FOR ADDITIONAL WFORMATION.
MECHANICAL GENERAL NOTES:
THESE NOTES APPLV TO ALL MECHANICAL SHEETS ANO TRADES, INCLU�ING BUT NOT LIMITED
TQ FIRE PROTECTION, PLUMBING. MEDICALGAS, VENTILATION, PIPING AND TEMPERATURE
CONTROL.
1. �RAWINGS SHOW ING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETG ARE
DIAGRAMMATIC AND MAV NOT ALWAVS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,
AND MAV NOT INCWDE ALL OFFSETS ANO FITTINGS REpUIRED FOR COMPLETE
INSTALLATION. THEDRAWMGSSHALLBEFOLLOWEDASCLOSELVASACTUALBUILDING
CONSTRUCTION AND THE WORK OF OTHERS W ILL PERMIT.
2 OONOTSCALEDRAWINGS. VERIFYALLDIMENSIONSANOCLEARANCESFROM
ARCHITECTURAL, STRUCTUR4L, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR
PHYSICALLY AT SITE REVIEW ALL DRAW INGS, INCLUDMG THOSE OF OTHER TRA�ES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE
CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO
VERIFV NON-INTERFERENCE W ITH OTHER WORK. DO NOT FABRICATE PRIOR TO
VERIFlCATION OF NECESSARV QEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES
OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING
WITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEWSPACEREpUIREMENT50FEQUIPMENTSPEQFlEDORSUBSTITUTEDANDMAKE
REASONABLE ACCOMMODATIONS IN LAVOUT AND POSITION W G TO PROVIDE PROPER
ACCE55.
5. ANV CHANGES REOUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO
COORDINATE SHALL BE MADE BV THE CONTRACTOR W ITHOUT A�DITIONAL COST OR
EXPENSETO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOQATED WITH ELECTRICAL
CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF
DESIGN.
]. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGV
AUDIONISUAL, AND OTHER MECHANICAL PLANS FOR E%ACT LOCATIONS OF ALL CEILING
MOUMED DEVICES, OTHER THAN SPRINKLERS.
8. EACH CONTRACTOR IS RESPONSBLE FOR DAMAGE CAUSED BV THEIR ACTIONS TO WALLS,
FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS
RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FlRE RATING, AND
FINISH.
9. IN AREAS W ITH DRV W ALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS W ITH THE
GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETQ COORDINATE
PANEL TVPE AND COLOR WITH ARCHITECT. NOTIFV THE GC OF THE REQUIRED ACCE55
PANELS PRIOR TO BI�DING.
10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT W HERE CONDUITS, PIPING,
AND DUCTS PENETRATE PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE
SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BV MANUFACTURER
FOR OUTDOOR USE.
11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-RRE RATED WALL,
PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE
TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS
WITHIN ROOMS.
12 WHERE PIPES AND DUCTS ARE SHOW N TO PENETRATE FLOORS. PROVIDE SLEEVED
OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE W ITH ALL
RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
13 EQUIPMENTSIZESANDSERVICECLEARANCERE�UIREMENTSVARVAMONGDIFFERENT
MANUFACTURERS. CONSULT APPROVED SHOP DRAW INGS FOR EQUIPMENT SIZES AND
REQUIRED SERVICE CLEARANCES. COORDINATE W ITH LAYOUT OF EQUIPMENT PADS,
PIPING, DUCTWORK, ETC.
14. DONOTBLOCKTUBEPULLORE�UIPMENTSERVICECLEARANCES.
15. MAIMAIN MINIMUM 3'-6" CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR
STARTERS, S W ITCHES, AND �ISCONNECTS.
i6. PROVIOE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL
EXTEND MINIMUM 6" BEVOND ALL SIDES OF EOUIPMENT.
1]. �ONOTSUPPORTEQUIPMENT,PIPING,ORDUCTWORKFROMMETALDECKWGOROTHER
NON-STRUCTURAL BUILDWG ELEMENTS. ANCHORS EMBEDDED W CONCRETE SHALL BE
CRACKE� CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
PLUMBING SHEET INDEX
PO-00 PLUMBING COVERSHEET
P3-OG FOUNDATIONPLAN-PLUMBING
P3-iG RRSTFLOORPLAN-PLUMBING
P3-2G SECONDFLOORPLAN-PLUMBING
P3-3G THIRDROORPLAN-PLUMBING
P3-4G FOURTHFLOORPLAN-PLUMBING
P3-4S SKVBRIDGEFLOORANDROOFPLANS-PLUMBING
P3-SG ROOFPLAN-PLUMBING
SEWNDARV ROOF DRAIN
WATERDAM
PRIMARV ROOF DRAIN
CLAMPING RING
WATER CUTOFF MASTIC
ROOFMEMBRANE
ROOF INSl1LATION
ROOFDECK
EXTENSION
NOTE: THIS DETAIL APPLIES TO RD-1 AND RD-2 ONLV.
2 ROOF DRAIN DETAIL
ArchitecNre I Engineering I Interior Design
1115 Magnavox Way I 930 Nohh Mentlian
Fort Wayne, IN 46804 Intlianapolis, IN 46204
260.432.9337 31].917.1190
wwwmskitlmm
<:IMEG
8900 KEVSTONE XING SUITE 210
INDIANAPOLIS, IN 46240
31�.848.5045 FAX:31�.8442201
www.imegcorp.com
U
•�
�
�
�
O^
i
�
0
i
�
U
L �
Q• �
`� U��
W �
•O �
^L �
I..L
a�
�
U^
i
�
�
�
U
X
W
�
O
�^`
W
i^`
W
U
:/12/19
��
W
L
/���
vi
�
.�
1A_
1 _ �
ti �
� �
� �
��
� �
� �^,
�/-� W
\Y �
� L
� �
�U
PROJECTNO. DATE
18004130.00 01-23-20
REV. DATE
1 A51 #9 - BP4.1 129I2020
SET DESCRIPTION
BP #4.1 - Parking Garage &
Skybridge Arch / MEPT /
Interiors Package
SHEET TITLE
PLUMBING
COVERSHEET
SHEETNUMBER
PO-00
MSKTD