HomeMy WebLinkAboutT8-10-TECHNOLOGY-DETAILS-Rev.0NOTES:
1. ELECTRONIC DOOR HARDWARE SUCH AS ELECTRIC STRIKES, ELECTRIC LATCH RETRACTION, ETG SHALL BE
PROVIDED AND INSTALLED BV OTHERS. REFER TO THE GENERAL TECHNOLOGV EQUIPMENT SCHEDULE ON T9-00
FOR CREDENTIAL REA�ER TYPE INFORMATION.
2. THIS SCHEDULE REPRESENTS THE FEATURES AND MINIMUM RE�UIREMENTS OF EACH DOOR. THE CONTRACTOR
SHALL PROVIDE CABLING PER THE ACCE55 CONTROL RISER DIAGRAM ON 1IT8-00 AND THE MANUFACTURER
REpUIREMENTS TO EACH DOOR. THE CONTRACTOR SHALL INCLUDE CABLING FOR DOORS THAT HAVE MULTIPLE
OPENINGS. REFER TO THE DOOR HARDWARE SCHEDULE AND SPEGFICATIONS FOR COMPLETE DOOR
RE�UIREMENTS.
3. DOOR POSITION SWITCHES ARE TVPICAL OR EACH LEAF OOOR AND SHALL HAVE A OEDICATED CABLE AND DOOR
POSITION SWITCH FOR EACH LEAF. DO NOT RUN IN SERIES.
4. REFER TO 1/T840 FOR ACCESS CONTROL RISER DIAGRAM.
CONNECT TO GROUND LUG
ON PEDESTAL
ANCHORBOLTS� � OO
FINISHED GRADE
EXOTHERMIC WELD OR�
HVDRAULIC COMPRESSION
CONNECTION
6" LOOP
M6 BARE STRANDED
COPPER BONDING
CONDUCTOR
5/8" x 10'-0" COPPER CLAD -
GROUNDROD
Q STUB (2) 1" CONDUITS 4" -
ABOVE SURFACE OF
FOOTING
CONCRETE BASE (4000 PSI)-
MINIMUM 28 DAV STRENGTH
6 % AIR ENTRAINED +/- 1 %
18" 0
�
(3) #3 TIES @3" OC, BALANCE
AT 12
ENLARGED PLAN VIEW
BASE
�,_�..
NOTES:
1. THIS CONTRACTOR SHALL BE RESPONSIBLE TO FURNISH AND INSTALL THE ENTIRE EMERGENCV PHONE
STATION AND FOOTING.
2. POSITION EMERGENCV PHONE STATION IN THE CENTER OF THE BASE.
3. REFER TO STANCHION MANUFACTURER'S INSTALLATION INSTRUCTIONS.
4. REFERT04/T840FORCALLSTATIONDETAIL.
KEVNOTES:
7. CAST BOLT PATTERN PER EMERGENCV CALL STATION PRODUCT SPECIRCATION.
2 QTV. (2) 1" CONO WTS W ITH BUSHING TO BE STUBBED 4" ABOVE SURFACE OF FOOTING FROM
HANDHOLE, INSTALL BUSHINGS. ONE FOR 120V ELECTRICAL SERVICE AND ONE FOR TELECOM. REFER
TO SITE PLAN ON T7-00 FOR HANDHOLE LOCATIONS.
3. REFERTO GENERALTECHNOLOGV SCHEOULE ITEMS IGECS-0 ON SHEETT9-00 FORADOITIONAL
INFORMATION.
WIRING KEV'.
OA 22 AWG (2) TWO CONDUCTOR STRANDED
OB 18 AWG (4) FOUR CONDUCTOR STRAN�ED
CO 14 AWG (2) TW O CONDUCTOR STRANDED
O 22 AW G(6) SIX CONDUCTOR STRANDED
O CATEGORV6ACA8LE
C55
TVPICAL OF SINGLE DOORS
0
NO SCALE
I� �� TR-#
POWER
ISUPPLIES
I I CC
I �� I
IIAGSCP-1 I
L E I
�
REX DC DC �qp EDH
\ CS�
TVPICAL OF DOUBLE DOORS
Q
NOTES:
1. THIS RISER IS DIAGRAMMATIC ANO NOT INTENDED TO SHOW ACTUAL ROUTING OR
�UANTITIES OF MATERIALS SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF
CONNECTION LOCATIONS AND CABLE TVPE.
2. ALL CABLING SHALL BE PLENUM RATED.
3. REFERT0T9-OOFORGENERALTECHNOLOGVE�UIPMENTSCHEDULE.
4. REQUESTTOEXIT�EVICESAREPROVIDEDBYTHEDOORCONTRACTOR.ACCESS
CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIOING CABLING FROM ACCE55
CONTROL PANEL TO EACH E%ISTING AUTOMATIC DOOR WNTROL INTERFACE WITH
ACCESSCONTROLSVSTEM.
S CONTRACTOR SHALL COORDINATE INSTALLATION OF SECURITV MANAGEMENT
SOFTWARE ON OWNER PROVIDE� WORK STATIONS REFER TO SPEGFICATION.
6. CONTRACTOR SHALL PROVIDE TURN-KEV SOLUTION WITH APPLICATION AND
STORAGE SERVER PC. REFERTO SPECIFICATIONS FORADOITIONAL INFORMATION.
KEYNOTES:O
1. CONNECTION TO THE FlRE ALARM SVSTEM.
2 PROVIDE 8 CONOUCTOR CABLING FOR INTEGRATION OF CARO REAOERS TO
EACH ELEVATOR.
i1 EMERGENCY CALL STATION
4 NO SCALE
NOTES:
1. REFER TO oETAIL 3/T8-10 FOR EMERGENCV CALL STATION FOOTMG DETAIL FOR A�DITIONAL
INFORMATION.
2 REFER TO ARCHITECTl1RAL SPECIFICATIONS FOR BASE STRl1CTl1RAL AND MOUNTING
REQUIREMENTS.
3. CONTRACTORSHALLPROTECTFlNISHATALLTIMESDURINGCONSTRUCTION.
4. CONTRACTOR SHALL ROUTE (2) 1" RGS CONDUITS FOR POWERAND LOW VOLTAGE REQUIRE�
CABLES. REFER TO SITE PLAN SHEET Ti-00 FOR LOCATIONS AND QUANTITIES.
5. CONTRACTORSHALLCOORDINATECOLORAN�SIGNAGEWITHOWNERPRIORTOORDERING
EMERGENCV CALL STATIONS.
V2" EMT CONDUIT
MINIMUM (TVP_)
FOR DOOR
HARDWARE�
POWER
SUPPLIESOO
REpl1EST TO -
EMIT DEVIC�
ROUGH-IN 6
■
MINIMUM 1" EMT
CONDUITO7
CONTACT
ROUGH-IN
DOOR FRAME ROUGH-IN DIAGRAM
(ALL DOUBLE DOORS W ITH OR W ITHOUT MULLION)
FOR DOOR
�HARDWARE
POW ER
SUPPLIES OO
REQUESTTO 5
EXIT DEVIC�
ROUGH-IN 6
FINISHED ACCESSBLE
CEILING
`MINIMUM3l4"EMT DOOR
CONDUITTOABOVE CONTACT 2
THEACCESSIBLE ROUGH-INO
CEILING
� CREOENTIAL REAOER
ROUGH-IN 03
� C
MINIMUM 7" EMT
CONDUITO7
MINIMUM 3/4" EMT
CONDUIT TO ABOVE
THE ACCESSIBLE
CEILING
CREOENTIAL REAOE
ROUGH-IN �)
DOOR FRAME ROUGH-IN DIAGRAM
(ALL SINGLE DOORS)
NO SCALE
NOTES:
1. CONFIGURATIONS SHOWN IN THE DETAIL ABOVE ARE DIAGRAMMATIQ INTENDED TO DESCRIBE THE CONTROLLED SECURITV SCHEME ROUGH-IN
REQUIREMENTS OF THE DOORS. DETAILS ABOVE MAV NOT ACCURATELV REPRESENT DOOR SIZE, DOOR SW ING, DOOR HARDWARE, OR DOOR
FUNCTIONALITY. REFER TO ARCHITECTURAL DOOR HARDWARE SCHEDULE, DOOR HARDWARE GROUPS AND DOOR HARDWARE SPEQFICATIONS
FOR COMPLETE WFORMATION. MIRROR THE DETAILAS REQUIRED.
2. ROUGH IN SHOW N IN THE DETAIL ABOVE REPRESENTS THE MINIMUM REQUIREMENTS FOR ALL CONTROLLED SECURITV SVSTEM DEVICES AND
CABLING UNLE55 OTHERW ISE NOTED. COOROINATE EXACT REQUIREMENTS W ITH SELECTED DOOR MATERIALS, DOOR HARDW ARE, AND
CONTROLLED SECURITV DEVICES AND CABLING PRIOR TO INSTALLATION.
3. ALL CABLING IN WALLS AND WHERE EXPOSED ON VERTICAL SURFACES SHALL BE INSTALLED IN EMT CONDUIT OR SURFACE MOUNT RACEWAV.
CABLING ROUTED HORRONTALLV ABOVE THE ACCESSIBLE CEILING MAY BE INSTALLED FREE-AIR CABLING PROPERLV RATED FOR THE CEILING
ENVIRONMENT.
4. THE ELECTRICAL OR SECURITV CONTRACTOR SHALL NOT MODIFV ANV FlRE RATED DOOR AND/OR DOOR FRAME REFER TO THE ARCHITECTURAL
DOOR SCHEDULE, OOOR HARDWARE SCHEDULE, AND DOOR HARDWARE SPECIFICATION FOR ADDITIONAL INFORMATION. MODIFICATION TO ANV
FIRE RATED DOOR AN�IOR FRAME WILL REQUIRE A RE-CERTIFICATION OF THE DOOR AND FRAME W ITH THE LOCAL AUTHORITV HAVING
JURISDICTION (AHJ).
5. WSTALLING CONTRACTOR SHALL FURNISH ANO WSTALL FIRESTOP MATERIALS FOR ALL CONTROLLED SECl1RITY SCHEME ROUGH-INS PER PROJECT
REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
6. REFER TO THE CONTROLLED SECURITY SCHEME WIRING DIAGRAM ON 1/T8-10 FOR CABLING REQUIREMENTS AND THE CONTROLLED SECURITV
SCHEME SCHEDULE ON T8-00 FOR ADDITIONAL MFORMATION.
]. INSTALLATION SHALL INCWDE ALL POWER REpUIRED FOR SVSTEM OPERATION INCLUDING+120VAC. REFER TO THE SUGGESTED MATRIX OF SCOPE
RESPONSIBILITV FOR A�DITIONAL INFORMATION.
KEVNOTES:
1. PROVIDE JUNCTION BOXES IN THE DOOR FRAME WHERE SHOW N ON THIS DETAIL ROUGH-IN SHALL BE PROVI�ED WHETHER THE CURRENT
SECURITV SCHEME UTILIZES THEM OR NOT. ALL CONDUITS SHALL BE EMT CONDUIT UNLESS OTHERW ISE NOTED. FLEXIBLE CONDUIT OF ANY TYPE
WILL NOT BE ACCEPTED. COORDINATE INSTALLATION WITH ON-SITE DOOR FRAME INSTALLATION CONTRACTOR.
2. ALL DOOR POSITION SW ITCHES ARE REQUIRED TO BE RECESSED UNLESS OTHERWISE NOTED. ELECTRIC HWGE MONITORS ARE NOT AN
ACCEPTABLE REPLACEMENT FOR THE RECESSED DOOR POSITION SW ITCH.
3. DOUBLE GANG BACKBOX W ITH SINGLE GANG PLASTER RING. REFER TO FLOOR PL4N(S) FOR ACTUAL CREDENTIAL READER TVPE AND ROUGH-IN
LOCATIONS.
4. CONOUITSHALLROUTEFROMTHECREDENTIALREADERTOTHESECURESIDEOFTHEDOOR.CONDUITSHALLROUTETOTR-iG.PROVIDEANYLON
BUSHING ON CONDUIT END.
5. MOUNT A MINIMUM 4" SQUARE 2-1I8" DEEP JUNCTION BOX WITH BLANK COVER PLATE ON THE SECURE SIDE OF THE DOOR ABOVE ACCESSIBLE
CEILING. INSTALLING CONTRACTOR SHALL SIZE THE Jl1NCTION BOXES PER SVSTEM INSTALLATION REOUIREMENTS AND APPLICABLE CODES.
MAINTAIN ACCESS TO THE JUNCTION BOX.
6. PROVIDE A HORIZONTALLV MOUNTED SINGLE GANG BACKBOX FOR THE REQUEST TO EXIT SENSOR. REFER TO THE CONTROLLED SECURITY SCHEME
SCHEDULE ON TS-00 FOR DOORS THAT REpUIRE THIS ROUGH-IN.
]. CONOUITSHALLROUTETOTR4G.PROVIOEANVLONBUSHINGONCONDUITEND.
8. CONDUITINSTALLEDINPERMANENTMULLIONSONLV.REFERTOTHEARCHITECTURALDOORSCHEDULEANDDOORHARDWAREGROUPSFOR
LOCATIONS THAT REQUIRE THIS ROUGH-IN. PROVIDE A NVLON BUSHING ON THE CONDUIT END.
ArchitecNre I Engineering I Interior Design
1115 Magnavox Way I 930 Nohh Mentlian
Fort Wayne, IN 46804 Intlianapolis, IN 46204
260.432.9337 31].917.1190
wwwmskitlmm
<:IMEG
8900 KEVSTONE XING SUITE 210
INDIANAPOLIS, IN 46240
31�.848.5045 FAX:31�.8442201
www.imegcorp.com
L
�
�
a
'o
�
Q
U
•�
�/� U
it� �
O � W^,
� � L
� ��
� U`' �
O ^ •�
� w �
� A
1 _
U 00
� ��
• -`
U �%
� +� �
�
� �
�U
�
�
�
�
�
a�
�o �
O �
�U
PROJECTNO. DATE
18004130.00 12-12-19
REV.
SET DESCRIPTION
BP #4.1 - Arch/MEPT/
Garage Documents
�
�
RELEA5E0 FOR CONSTRUCTION
Suhjec� �o compliance with all regula�ions
04 S�a�e antl Local Codes
City of Carmel
�
�{�n„� ��.�a,�,a1
�
onrE: 06/11 /20
SECTION A-A
BASE PLATE SHALL BE INSTALLED
AND LEVELED 2" ABOVE FOOTING
TO FIRM CLEAN
iReeo soi�
SHEET TITLE
TECHNOLOGY
DETAILS
SHEETNUMBER
T8-10
,,.. ...�' iz/iz/ie
DATE
MSKTD
& Associates