HomeMy WebLinkAboutE0.01-Electrical Cover Sheet1.G. D�R�ISS
ARC�iITfCTS, «<
a�� WALHALLA tOAD
COLUMlUS, OHIO �s�o�
la�l �os.n�o
NOTE' ALL SVMBOLS MAV NOT APPLV
(TYPICAL FOR ALL SYMBOL LEGENDS)
ELECTRICAL SYMBOL LEGEND
Xg CO�E�PLANNOTE yy DETAIL#
%XX SHEET# REFERENCETAG
XX EQUIPMENTDESIGNATION
MDP-22 CIRCUITDESIGNATION
PANEL OESIGNATION - CIRW IT NUMBER
ELECTRICUTILITYKEVBOX 3 WALLSWITCH-NUMBERIN�ICATE52POLE,3
K � OR 4 WAY (NO NUMBER FOR SINGLE POLE]
F� FAN/LIGHTCOMBINATIONFIXTURE $a LOWEROBECONTR011E��BYSWFTCHRE�S)
OERHAUSTFAN $ DIMMERSWITCH
Oj Jl1NCTI0N BOX �F CEILMG FAN SPEED CONTROL SWITCH
� NON-FUSE�DISCONNECTSWITGH $K KEV-OPERATEDSWITCH
� FUSEDDISCONNECTSWITCH $M MOTORRATEDDISCONNECTSWITCH
'a MOTOR � S OCWPANCYSENSORWALLSWITCH
GREENGATE #ONW-0-0001-MV OR EQUAL
O PUSHBUTTON $ R OVERRI�ESWITCH
�g BUZZEWBELL $P� SWITCHWITHPILOTLIGHT
LVT LOWVOLTAGETRANSFORMER T TIMERSWITCH
� GREENGATE#TSW-MVORE�UAL
� SINGLERECEPTACLE20A,12�V OS WALLMOUNTOCWPANCVSENSOR
O GREENGATE#OAWC-0T-020WORE�UAL
� SPECIALRECEPTACLE OS CEILINGMOl1NTOCQIPANCVSENSOR
GREENGATE #OAG-0L2000-R OR E�UAL
� DUPLEXRECEPTACLE20A.120V SP SWITCHPFCKFOROCCl1PANCVSENSOR
� �UA�RUPLERRECEPTACLE20A,120V Pc PHOTOCELL
� GFCI DUPLEX RECEPTACLE 20A, 120V TC TIMECLOCK
� GFCI QUADRUPLEX RECEPTACLE 20A,120V ryp GURRENT LIMITING DEVICE � NUMBER
INDICATES MAX AMPERAGE OF DEVICE
� IG DUPLE%RECEPTACLE 20A, 120V pp POWER POLE
� IGQUADRUPLEXRECEPTACLE20A,12�V -W a�CONDUITSTUBANDBOXFORWALL
PHONE WIRING BY OTHERS
� PLIT WIRE� DUPLEX REGEPTACLE 20A, 120 - a� CONDUIT STUB AND BOX FOR PHONE
WIRING BV OTHERS
� SPLITWIRED�VADRUPLEXRECEPTACLE a"CONDIIITSTUBANDBOXFORDATA
20A.120V � WIRINGBVOTHERS
�T� TWISTLOCKRECEPTACLE � a"CONDUITSTUeAN�BOXFOR
DATNPHONE WIRING BV OTHERS
� FLUSH MTD AS INDICATE� BV BOX AROUND O TELEVISION OUTLET
�EVICE, FLR=FLOOR, CLG-CEILWG
_ Sl1RFACEMOl1NT WA WIRELESSACCESS
PANELBOARD/LOADCENTER
= FWSHMOUNTPANELBOFR�ILOA�CEMER MB ME�IABOXDEMARCLOCATION
a UTILITYSERVIGEMETER p� OVERHEADPROJECTOR
m PWGMOLD-SEEPLANVIEWFORSPEQFlC UPS UNWTERRUPTIBLEPOWERSUPPLY
LENGTHS O
ANNC GENERATORANNUNCIATOR
ELECTRICAL NOTATIONS
AC ABOVECOUNTER LV LOWVOLTAGE
AFF ABOVEFINISHEDFLOOR MBJ MAINBON�INGJUMPER
AFG ABOVEFINISHEDGRADE MC MECHANICALCONTRACTOR
BPS BOLTE�PRESSURESWITCH MTD MOUMED
CLG CEILINGMOUNTED NTS NOTTOSCALE
CKT CIRCUR (PART) INDICATESCIRCUITUSEDELSEWHERE
EC ELECTRICALCONTRACTOR PC PWMBINGCONTRACTOR
EM EMERGENCV SSBJ SUPPLY-SIDEBONDINGJUMPER
ETR EXISTINGTOREMAIN SUC SITEUTILITYCONTRACTOR
FLR FLOORMOIIME� TVP TVPICAL
FSC FIRESUPPRESSIONCONTRACTOR UG UN�ERGROUND
GC GENERALCONTRACTOR UNO UNLESSNOTEDOTHERWISE
GFCI GROUN�FAULTCIRWITINTERRUPTER WP WEATHERPROOF
GFEP GROUNDFAULTE�UIPMENTPROTEGTION WG WIREGUARD
GND GROUND WR WEATHERRESISTANT
HC HVACCONTRACTOR XX" �IMENSIONEDHEIGHT
IG ISOLATEDGROUND
ELECTRICAL LINETYPE LEGEND
------------- GENERALDEMO
GENERAL EXISTING
------------- SWITGHLEG
— — — UGE — — — UN�ERGROUND ELECTRIC
— — (AB)UGE — — UNDERGROUND ELECTRIC (ABANDONED)
— — — (D)UGE — — — UNDERGROUND ELECTRIC (DEMO)
— — (E)UGE — — UNDERGROUND ELECTRIC (EXISTING)
LV LOWVOLTAGE
(AB)LV LOWVOLTAGE�ABANDONED)
— — — (D)LV — — — LOW VOLTAGE (DEMO)
(E)LV LOWVOLTAOE�EXI3TIN0)
— — UGLV — — UNDERGROl1ND LOW VOLTAGE
— — (AB)UGLV — — UNDERGROUND LOW VOLTAGE (ABANDONED)
— — — (D)UGLV — — — UNDERGROl1ND LOW VOLTAGE (DEMO)
— — (E)UGLV — — UN�ERGROUND LOW VOLTAGE (EXISTING)
MAM ELECTRICAL GENERAL NOTES:
A. ALL ELECTRICAL INSTALLATIONS MUST COMPLY WITH THE NATIONAL ELECTRICAL CODE AN� ALL
STATE AND LOCAL CODES ELECTRICAL SERVICE TO BE INSTALLED IN COMPLIANCE WITH NEC
ARTICLE 230.
B. CONTRACTORSHALLOBTAMFAULTCl1RRENTMPoRMATIONFROMIITILITVCOMPANVAND
PERFORM SHORT CIRGUITCALCULATIONS. SRE FUSES AND EQUIPMENT A.IG RATINGS
ACCORDINGLY.
G CONTRACTORSHALLINSTALLASEPARATEE�UIPMENTGROUNDINGCON�UCTORSIZEDPER
NEC TABLE 250.122 FOR ALL BRANCH CIRCUITS INSTALLED IN NON-METALLIC CONDUITS.
METALLIC CONDUITS MAV BE USED AS EQUIPMENT GROUN�ING CONDUCTORS PER NEC.
D. CONTRACTORSHALLVERIFYALLWIRESIZINGDUETOVOLTAGEDROPCAWEDBVIN-FIELD
ROUTING / WSTALLATION �ISTANCES.
E. SERVICE ENTRANCE EDUIPMENT SHALL BE GROUNDED WITH A SEPARATE COPPER OR
AW MINIIM CONDl1CTOR AS INDICATED ON THE DRAWINGS AND PER ARTICLE 250.52(A) OF THE
NATIONAL ELEGTRICAL WDE. GROUNDING CON�UGTOR SHALLAL50 BE GONNEGTE� TO A 518"
DIAMETER X 8'-�" LONG GROUN� ROD FOR SUPPLEMENTAL GROUNDING PER NATIONAL
ELECTRICAL CODE ARTICLE 250.54.
F. CONTRACTOR IS RESPONSIBLE FOR LABELING ALL PANELS. DISCONNECTS. LIGHTING
CONTROLLERS, ETC., AND ALL CIRCUIT BREAKERS IN THE DISTRIBUTION PANELS PRIOR TO
PROJEGT COMPLETION. PROVIDE A TYPED �IRECTORY OF ALL CIRCUITS. BREAKERS USED FOR
SWITCHWG SHALL BE RATED ACCORDINGLV.
G. CONTRACTORSHALLSUPPLVANDINSTALLALLN.E.C.RE�UIREDE�UIPMENTDISCONNECTS
(NOT ALL DISCONNECTS MAY BE SHOWN ON THE DRAWINGS). CONTRACTOR SHALL VERIFV ALL
DISCONNECT SI➢NG WITH EACH EQUIPMENT NAMEPLATE RATING.
H. CONTRACTOR IS RESPONSIBLE TO SECURE AND PAY FOR ALL PERMITS. CONTRACTOR SHALL
COMPLY WITH ALL STATE LOCAL, AND NATIONAL CODES (EG., NATIONAL ELECTRICAL CODE).
CONTRACTOR SHALL SCHEDULE INSPECTIONS SO JOB PROGRESS IS NOT DELAYED.
I. CONTRACTOR SHALL Sl1PPLY AND INSTALL ALL E�IIIPMENT IN NEW CONDITION AN� LLL LISTED
UNLESS NOTE� OTHERWISE.
J. CONTRACTORSHALLMAKEARRANGEMENTSWITHLOCALPOWERCOMPANYFORTHE
INSTALLATION OF NEW ELECTRICAL SERVICE AND METER. INSTALL NEW SERVIGE �ISTRIBUTION
EQUIPMENT AS SPECIFIED ON ELECTRICAL DRAWINGS.
N. CONTRACTORSHALLCOOR�INATEALLELECTRICALWORKWITHOTHERTRADESAND
ARCHITECTURAL �RAWINGS TO ELIMINATE CONFLICTS.
L. PRIORTOWNSTRUCTIONSTART.CONTRACTORSHALLSUBMITSHOP�RAWINGSAND
OPERATION MANUALS FOR ALL EQUIPMENT AND ACCESSORIES FOR OWNER APPROVAL.
M. CONTRACTOR SHALL PERFORM ALL WORK IN A NEATAND PROFESSIONAL MANNER.
N. PROVIDE FLEXIBLE CON�UR FOR ALLVIBRATING EQUIPMENT. PROVIDE FLEXIBLE CONDUIT FOR
LIGHT FIXTURE CONNEGTIONS.
0. CONTRACTOR IS RESPONSIBLE FOR VERIFYING ELECTRICAL E�IIIPMENT MPoRMATION WITH
MANUFAGTURERS. WNTRACTOR SHALL PROVIDE ANY ADDITIONAL ELEGTRICAL WNNEGTIONS
OR SERVICES TO EQUIPMENT WHICH ARE NOT SHOWN ON DRAWINGS.
P. ALL PENETRATIONS OF WALL ROOF, AND CEILINGS TO BE SEALED AS REQUIRE� WITH U.L.
APPROVED FIRE SEALANT TO MAINTAIN FIRE RATING AS REQUIRED. ALL ROOF PENETRATIONS, IF
APPLICABLE, ARE TO BE COORDINATED WITH THE OWNER'S DESIGNATED ROOFlNG
CONTRACTOR.
Q. ELECTRICAL EDUIPMEM EXPOSED TO WFATHER CON�ITIONS SHALL BE WEATHERPROOF TVPE.
CONDUIT EkPOSED TO WEATHER GONDITIONS OR IN GONTACT WITH CONCRETE SHALL BE
POLVVINVL CHLORIDE (PVC) OR GALVANIZED HEAVV WALL STEEL (GRC�.
R. ALL EXTERIOR RECEPTACLES SHALL BE WEATHER RESISTANT AS WELL AS WEATHERPROOF PER
NEC 406.9.
S. CONTRACTORSHALLSUBMITAS-BUILTDRAWINGSTOTHEOWNERIFWSTALLATIONVARIES
FROM THE CONTRACT DRAWINGS.
T. ANVCONDUITAN�WIRESRESSHOWNAREMINIMUMS.CONTRACTORSHALLINCREASESRES
(DUE TO VOLTAGE DROP. QUANTITY OF CURRENT CARRVING CONDUCTORS IN THE SAME
CONDUIT/RACEWAY. ETC.) AS RE�IIIRED BY THE N.EC.
U. IG �EVICES QF APPLICABLE�: CONTRACTOR SHALL INSTALL AN ADDITIONAL CONDUCTOR FOR
ISOLATED GROUND CIRCIIITS TO SUPPLV CONDIICTORS FOR ISOLATED 6ROl1NDING PURPOSES.
SAID GROUNDING GON�UGTOR SHALL BE COVERE� WITH A CONTINUOUS OUTER FINISH THAT IS
GREEN WITH ONE OR MORE YELLOW STRIPES. THE GROUNDING CONDUCTORS SHALL BE
BONDED TO FRAME OF �EVICE AND Rl1N IN CONDl11T BACK TO'CENTRAC GROl1NDING BLOCK(S)
AT SERVIGE DISTRIBUTION E�UIPMENT.
V. ROOFTOPEQUIPMENTQFAPPLICABLE�:CONTRACTORSHALLINSTALLAWEATHERPROOF
DISCONNECT FOR EACH UNIT. CONDUITS SHALL ENTER THE UNDERSI�E OF EAGH HVAC UNIT
FROM WITHIN THE CURBED AREA FOR THAT UNR (THEREBY AVOIDING PENETRATIONS THROUGH
THE ROOF MEMBRANE). IF J-BOX IS USED FOR Sl1PPLYIN6 POWER TO MULTIPLE UNITS, THE
J-BO%MUST BE LOGATED WITHIN 25 FEET OF EACH UNIT'S DISCONNECT PER THE NE.G ARTIGLE
24021(B�(2). CONTRACTORSHALLSUPPLVANDINSTALLA120VACWEATHERPROOFGFCI
RECEPTACLE WITHM 25' OF EACH 11NIT.
W. ALLCONTRACTORS,PRIORTOBIDSUBMISSIONPROCESS,SHALLVISITPROPOSEDWORKSITE
AND FlELD VERIFY ALL EXISTIN6 CONDITIONS. ANY CONDITIONS THAT DIFFER FROM THAT
SHOWN ON THIS PLAN SHALL BE REPORTED TO THE ARCHITECTIENGINEER SO THAT NEW AND
REVISED BID DRAWINGS OR INFORMATION MAY BE ISSUED. MODIFICATIONS TO SCOPE OF WORK
WHICH RESULT FROM CONTRACTORS NEGLECT TO VISIT THE SITE PRIOR TO BID SUBMISSION
SHALL BE CONTRACTOR'S SOLE RESPONSIBILITV.
SHEET WFORMATION
Prolect p: 20013
Issoed Fort BID / PERMIi
Dafe: 5/29/20
Revkions'.
:���\\\\`�� ��s r RR � ///����
� 0 E
�O/? �
o K' 2:
207
TATEOF ;��\
W �
'�.1. P.�? �
/////����///////II�IIIIIN���\\\\\\\\\
., . �...� p.. � �,sLL_
U W
w }
o ��
a }
�
N
�
� � N
� U7 O
�
� in V
U � �
� � C
C � p
Q �
�- N �
O W —
N �
N o �
N �
� N U
6
N
�
C
O
L
U
N
�
N
U
�L
�n�
L
�
�
�
�
t'
19 7q'7_\ 7q�7i�7:i
Aveda Institute
16281 Tri Ridge Blvd
Suite 140
Loveland, Ohio 45140
�
PEServices
ENGINEERING FOH VOUR 5U[[E55
1-513-836-3810
vwuw. pe-servi�es.com
�.y:ieamne
IT IS THE RESPONSIBILITY OF THE W NTRACTOR TO NOTIFY
THEARCHITECT,LAN�LORDANDTENANTOFANY ELECTRICAL COVER
DISCREPANCIES ENCOUMERED ON THE PLANS OR IN
EXISTINGSITECONDITIONSPRIORTOSUBMISSIONOFBID. SHEET
RELEA5E0 FOR CONSTRUCTION
Suhjec� �o compliance with all regula�ions
04 S�a�e antl Local Codes
City of Carmel
`�y,:a���'.�`� �,�:;vaYa/„1��.
DATE: O��0��20
BIDDERS ARE TO VISIT THE SITE AND FAMILIARRE
THEMSELVES WITH EXISTWG CONDITIONS AND SATISFY
THEMSELVES AS TO THE NATURE AN� SCOPE OF THE WORK.
THE BASE BID SHALL REFLECT MODIFICATIONS TO SYSTEMS
AND DEVICES AS REQUIRED BV STATE, LOCAL AND FEDERAL
CO�ES WHETHER IN�ICATED OR NOT ON CONTRACT
DOCUMENTS. THE SUBMISSIONS OF A BID WILL BE EVIDENCE
THAT SUCH AN EXAMINATION AN� COMPLIANCE WITH
GOVERNING CODESIREQUIREMENTS HAS BEEN MADE LATER
CLAIMS FOR LABOR, E�UIPMENT, OR MATERIALS RE�UIRED,
OR PoR DIFFlCULTIES ENCOl1MERED WHICH COULD HAVE
BEEN FORESEEN HA� AN E%AMINATION AN�
CODNREQUIREMENTS REVIEW BEEN MADE, WILL NOT BE
ALLOWED.
FYiIqi�RqJil:7q 7
E0.01