1.GENERAL:
A. THE'GENERALWN�ITIONSOFTHECONTRACTFORCONSTRUCTION,"AIA�OCUMENTA201,
LATEST E�ITION, AND THESE SPEQFICATIONS AS APPLICABLE ARE PART OF THIS CONTRACT.
B. ALLAPPLICABLECO�ES,LAWSAN�REGULATIONSGOVERNINGORRELATINGTOANVPORTION
OF THIS WORK ARE HEREBV INCORPORATED INTO AN� MA�E A PART OF THESE
SPECIFICATIONS, AN� THEIR PROVISIONS SHALL BE CARRIED OUT BY THE CONTRACTOR WHO
SHALL INFORM THE OWNER. PRIOR TO SUBMITfING A PROPOSAL OF ANV WORN OR MATERIAL
WHICH VIOLATES ANV OF THE ABOVE LAWS AN� REGIILATIONS. ANV WORN DONE BY THE
CONTRACTOR CAUSING SUCH VIOLATION SHALL BE CORRECTED BY THE CONTRACTOR.
G INVESTIGATEEACHSPACETHROUGHWHICHEpUIPMENTMUSTBEMOVE�.WHERE
NECESSARV, EQl11PMENT SHALL BE SHIPPE� FROM MANUFACTURER IN SECTIONS OF SIZE
SUITABLE FOR MOVING THROUGH AVAILABLE RESTRICTNE SPACES. ASCERTAW FROM
B111L�ING OWNER AND TENANT AT WHAT TIMES OF DAV EQUIPMENT MAV BE MOVED THROUGH
ALLAREAS.
�. �RAWINGSAREDIAGRAMMATICANDIN�ICATEGENERALARRANGEMENTOFSVSTEMSAN�
WORK. WN�UIT ROUTING IS SHOWN DIAGRAMMATICALLV AN� �OES NOT SHOW ALL OFFSETS,
�ROPS AN� RISES OF RUNS. THE CONTRACTOR SHALL ALLOW IN HIS PRICE FOR ROIITING OF
CON�UIT TO AV01� OBSTRUCTIONS.
E. INSTALL WORK SO AS TO BE RFADILV ACCESSIBLE FOR OPERATION. MAINTENANCE AND
REPAIR. MINOR DEVIATIONS FROM �RAWINGS MAV BE MA�E TO ACCOMPLISH THIS, BUT
CHANGES WHICH INVOLVE EXTRA COST SHALL NOT BE MA�E WITHOUT APPROVAL.
F. THECONTRACTORSHALLKEEPALLEQUIPMENTAN�MATERIALS,ANDALLPARTSOFTHE
BOIL�ING, EXTERIOR SPACES AND A�JACENT STREETS, SIDEWALKS AN� PAVEMENTS, FREE
FROM MATERIAL AN� �EBRIS RESULTING FROM THE EXECUTION OF THIS WORK EXCE55
MATERIALS WILL NOT BE PERMITfED TO ACCUMIILATE EITHER ON THE INTERIOR OR THE
EXTERIOR.
G. SEALOPENINGSTHROUGHPARTITIONS,WALLSAN�FLOORSWITHMWERALWOOLOROTHER
NONCOMBUSTIBLE MATERIAL.
H. PROVI�EALLNECESSARVFLASHINGAN�COUNTERFLASHINGTOMAINTAINTHE
WATERPROOFING IMEGRIN OF THE Bl11LDING AS RE�UIRED BV THE INSTALLATION OR
REMOVAL OF CONDUIT AND EQUIPMENT. PROVIDE EQUIPMENT CURBS AS REQUIRED.
I. THECONTRACTOR'SPROPOSALFORALLWORKSHALLBEPRE�ICATE�ONTHE
PERFORMANCE OFTHE WORK DURING REGIILAR WORKING HOURS. WHEN SO �IRECTE�,
HOWEVER, THE CONTRACTOR SHALL INSTALL WORK DIIRING OVERTIME HOURS AND THE
ADDITIONAL COST TO BE CHARGED THEREFORE SHALL BE ONLY THE "PREMI OM" PORTION OF
THE WAGES PAID.
J. ALLMATERIALAN�E�UIPMENTSHALLBENEWUNLESSOTHERW6ENOTE�AN�SHALLBEIN
ACCOR�ANCE WITH BUILDING STANDARDS.
K. INSURANCP. IN ACCORDANCE WITH BUIL�ING REQUIREMENTS AN� SHALL INC W �E A HOLD
HARMLE55 CLAIISE FOR OWNER AN� ENGWEER.
L THEFINALACCEPTANCESHALLBEMA�EAFTERTHECONTRACTORHASADJUSTEDHIS
EQUIPMENT, TESTE� THE VARIOUS SVSTEMS, �EMONSTRATED THAT IT FULFILLS THE
REQUIREMENTS OF THE �RAWINGS AND SPEQRCATIONS AND HAS FURNISHE� ALL THE
REQUIRE� CERTIFICATES OF INSPECTION AND APPROVAL.
2. SCOPE OF WORK:
A. SCOPEOFWORKSHALLCONSISTOFPROVI�INGLABOR,MATERIALS.EQl11PMENT,SERVICES
AN� FEES NECESSARV FOR COMPLETE AND SAFE MSTALLATION IN CONFORMITY WITH THE
NATIONAL ELECTRICAL CO�E (NEC) AN� ALL OTHER APPLICABLE INOUSTRY. NATIONAL ANO
LOCAL CODES AN� Al1THORITIES HAVING JURIS�ICTION, AS IN�ICATED ON DRAWINGS ANO
HEREM SPECIFIE�.
B. ALLORAWINGS.PLANS,OETAILS,SPECIFICATIONSAN�SPEQFICATIONA��EN�AAREMA�E
PART OF THIS CONTRACT AN� SHALL APPLV TO ALL WORK UNDER THE CONTRACT UNLE55
OTHERWISE AMEN�E�. MO�IFIE�, SUPPLEMENTE� OR SPECIFIE� HEREIN.
G THECONTRACTORSHALLFURNISHAWRITTENGUARANTEETOREPLACEORREPAIR
PROMPRV AND ASSIIME RESPONSIBILITV FOR ALL EXPENSES MCIIRRED FOR ANY
WORKMANSHIP AN� EQUIPMENT IN WHICH DEFECTS �EVELOP WITHIN ONE VEAR FROM THE
�ATE OF FINAL CERTIFICATE FOR PAVMENT AN��OR FROM �ATE OR ACTUAL I15E OF
EOl11PMENT OR OCCUPANCY OF SPACES BV OWNER INCLU�E� UNDER THE VARIOUS PARTS
OF THE WORK, WHICHEVER �ATE IS EARLIER. THIS WORK SHALL BE �ONE AS DIRECTE� BY
THE OWNER. THIS GUARANTEE SHALL AL50 PROVIDE THAT WHERE �EFECTS OCCUR, THE
CONTRACTOR WILL ASSUME RESPONSIBILIN FOR ALL EXPENSES INCURRED IN REPAIRING
AN� REPLAQNG WORK OF OTHER TRA�ES AFFECTE� BY �EFECT$ REPAIRS OR
REPLACEMENTS M EQUIPMENT SUPPLIEO BV THE CONTRACTOR.
�. THECONTRACTORSHALLGIVENECESSARYNOTICE,FILEDRAWINGSANDSPECIFICATIONS
WITH ALL �EPARTMEMS HAVING JURIS�ICTION, OBTAIN PERMITS OR LICENSES NECESSARY
TO CARRY OUT THIS WORK ANO PAV ALL FEES THEREFORE THE CONTRACTOR SHALL
ARRANGE FOR INSPEQION AND TESTS OF ANY OR ALL PARTS OF THE WORK IF SO REpUIRE�
BV AUTHORITIES AND PAY ALL CHARGES FOR SAME. THE CONTRACTOR SHALL PAV ALL COSTS
FOR. AN� FURNISH TO THE OWNER BEFORE FINAL BILLING, ALL CERTIFICATES NECESSARY AS
EVI�ENCE THAT THE WORK INSTALLED CONFORMS WITH ALL REGULATIONS WHERE THEY
APPLV TO THIS WORK.
3. SHOP DRAWINGS:
A. PRIORTOTHEINSTALLATIONOFANVWORKANDPROCUREMENTOFE�UIPMENT.
CONTRACTOR SHALL PROVIOE COMPLETE SETS OF COORDINATED SHOP �RAWINGS OF ALL
E�UIPMENT, IN�ICATWG CAPACITK DIMENSIONS AND SE�UENCE OF OPERATION FOR
WRITfEN APPROVAL BY THE ARCHITECL ENGINEER, AND OWNER.
B. IN�ICATE ON EACH SHOP DRAWIN6S SUBMITfED: t) PROJECT NAME AND LOCATION.2) NAME
OF ARCHITECT AND ENGWEER. 3) ITEM IDENTIFlCATION.4) APPROVAL STAMP OF PRIME
CONTRACTOR.
C. SUBMISSIONSI�SUBMISSIONSIIIN.X1]IN.ORSMALLER�JFTHESUBMISSIONISACATALOG
CUT, THEN THE CONTRACTOR SHALL SUBMIT ONE ORIGINAL AND TWO COPIES. OTHERWISE,
HE SHALL SUBMIT THREE COPIES. THE ARCHITECT WILL PoRWARD THE ORIGINAL AND ONE
COPV (TWO COPIES WHEN NO ORIGINAL IS RECBVE�) TO THE ENGWEER. ALL CATALOG CUTS
SHALL BE COMPLETE 2) SUBMISSIONS LARGER THAN 11 IN. X n IN.: SUBMIT TWO PRINTS AND
ONE PAPER SEPIA TO THE ARCHITECT. THE ARCHITECT WILL FORWARD ONE PRINT AND THE
PAPER SEPIA TO THE ENGWEER.
D. SUBMITSHOPDRAWINGSFORTHEPoLLOWING:1)SWITCHES.2)FUSE5.3�qRCUITBREAKERS.
a) PANELBOARDS QNCLUDING DIMENSIONS. SCHEDULES, AND CATALOG CUTS�. 5) RACEWAYS.
fi) WIRE AN� CABLE.1) WALL SWITCHES. 8) INSERTION RECEPTA0.ES.9) MOMENTARV
CONTACT SWITCHES 10) TIME SWITCHES. t 1) SURFACE METAL RACEWAY. 12) LIGHTING
LUMINAIRES.I3�TRANSFORMERS.
4. AS-BUILT DRAWINGS AND EQUIPMENT OPERATIONAL
INSTRUCTIONS:
A. UPONCOMPLETIONAN�ACCEPTANCEOFWORK,CONTRACTORSHALLFURNISHWRITTEN
INSTRUCTIONS AND EpUIPMENT MANUALS AND �EMONSTRAiE TO THE OWNER THE PROPER
OPERATION AN� MAINTENANCE OF ALL EpUIPMENT AND APPARATUS FURNISHED UNDER THIS
CONTRACT.
B. THESEINSTRUCTIONSSHALLBENPEDONB-V21N.X111N.PAPERAND800NDINTHREERING
BINDERS WITH CLEAR ACETATE COVERS. CONTRACTOR SHALL GIVE THREE COPIES OF THE
INSTRUCTIONS TO THE OWNER AND ONE COPY TO THE ENGINEER.
G THEMSTRUCTIONBOOKLETSHALLBEARTHENAME,ADDRESSAN�TELEPHONENUMBEROF
THE PROJECT, ARCHITECT AN� ENGINEER.
D. REPRODUCIBLE"AS-BWLP'DRAWINGSSHALLBEPROVIDEDIN�ICATMGTHEASINSTALLED
CONDITIONS OF THE WORK. "AS-BNLP' �RAWINGS SHALL BE PROVIDED TO THE ARCHITECT
AFTER COMPLETION OF THE INSTALLATION.
5. GENERAL PROVISIONS FOR ELECTRICAL WORK:
A. SPECIFICATIONSAREOFSIMPLIFIEOFORMANOMCLUOEMCOMPLETESENTENCES. WORDSORPHRASES
SUCH AS'THE CONTRACTOR SHALL," "SHALL BEf "FIIRNISH," "PROVIDE; "'A." "THE;' AN� "ALL" HAVE BEEN
OMITTE� FOR BREVIN.
B. �EFINITION5:1�"PROVIOE":TOSUPPLY,INSTALLANOCONNECTUPCOMPLETEANOREAOVFORSAFEAN�
REGIILAR OPERATION THE PARTICULAR WORK REFERREO TO UNLE55 SPECIFICALLY OTHERWISE NOTE�.2)
"INSTALL"'. TO ERECT. MOUNT AN� CONNECT COMPLETE WITH RELATE� ACCESSORIES. 3) "FURNISH" OR
"SUPPLV: TO PURCHASE, PROCIIRE, ACpUIRE AN� DELIVER COMPLETE WITH RELATE� ACCESSORIE5.4)
"WORK"'. LABOR, MATERIALS, EpUIPMENT. APPARATl15. CONTROLS. ACCESSORIES AN� OTHER ITEMS
REQIIIRED FOR PROPER AN� COMPLETE INSTALLATION.S�'WIRING". RACEWAY, FITTINGS, WIRE, BOHES AND
RELATE�ITEM5.6)"CONCFALE�":EMBEDDE�INMASONRYOROTHERCONSTRUCTION,MSTALLE�IN
FURRE� SPACES, WITHIN �OUBLE PARTITIONS OR HUNG CEILINGS, IN TRENCHES. IN CRAWL SPACES, OR IN
ENCLOSURES. ])"EXPOSED": NOT INSTALLE� UNDERGROOND OR "CONCEALEO" AS �EFINED ABOVE. 0)
"SIMILAR" OR "EpUAL". EpUAL IN MATERIALS. WEIGHT. SIZE, �ESIGN AND EFFIQENCY OF SPEQFIEO
PRODUCT.
C. TEMPORARYLIGHTAN�POWER'.PROVI�ETEMPORARYLIGHTAN�POWERSYSTEMSATEARLIESTPOSSIBLE
�ATE WITHIN THE CONSTRUCTION AREAS FOR THE REQUIREMENTS OF ALL TRADES AS HEREIN DESCRIBE�.
E%TEND SYSTEMS TO NEW CONSTRIICTION AS SOON AS PHVSICALLY POSSIBLE. MAWTAIN SYSTEM �URING
WORKING HOURS OF ALL TRADES. COST OF ENERGY WILL BE PAID FOR BY OWNER. PROVIDE ALL REQUIRE�
MAINTENANCE. INCLUDING LAMPS AND SOCKETS.
�. OUALITY ASSURANCE:1) pUALITY AN� GAUGE OF MATERIALS: NEW, BEST OF THEIR RESPECTIVE KIN�S,
FREE FROM DEFECTS AND LISTED BY UN�ERWRITERS LABORATORIES, MG, OR OTHER NATIONALLV
APPROVED TESTING AGENCV AND BEARING THEIR LABEL. MATERIALS ANO EOUIPMENT OF SIMILAR
APPLICATION SHALL BE OF SAME MANUFACTURER. EXCEPT AS NOTE�. 2) GUARANTEE: ALL MATERIALS AN�
WORKMANSHIP SHALL BE GUARANTEE� AS �EFINE� IN PARAGRAPH 2C.3) CURRENT CHARACTERISTICS'. a.
SERVICE'. 120/200 VOLT, 3 PHASE, 4 WIRE, 60 HERTZ WITH GROUNDE� NEUTRAL. b. DISTRIBUTION:120/208
VOLT, 3 PHASE, 4 WIRE, 60 HERTZ WITH GROUN�E� NEUTRAL. 4) HEIGHTS OF OUTLETS: (UNLE55 OTHEWISE
SPEQFIE� BY ARCHITECT) a. FROM FINISHE� FLOOR TO CENTERLWE OF OUTLETS FOR'. - RECEPTACLES AND
TELEPHONES 1'-6". - WALL SWRCHES'. 3'2". - WALL W MINAIRES: ]'-0". - MOTOR CONTROLLER5:5'�0". - STROBE
LIGHTS'.6' 8'. OR fi" BELOW CEILING (WHICHEVER IS LOWER) - FIRE ALARM PULL STATION5:4'-0". b.
E%CEPTIONS: AT JUNCTION OF DIFFERENT WALL FINISH MATERIALS, ON MOLDING OR BRFAK IN WALL
SURFACE, IN VIOLATION OF CO�E, OR AS NOTED OR DIRECTE�.
E. PRODUCT�ELIVERY,STORAGEANDHAN�LING:1)MOVINGOFEQUIPMENT:WHERENECESSARY,SHIPIN
CARTED SECTIONS OF SIZE TO PERMIT PASSING THROUGH AVAILABLE SPACE5.2) ACCESSIBILIN'. FOR
OPERATION, MAINTENANCE AN� REPAIR. MINOR �EVIATIONS SHALL BE PERMITTE�. CHANGES OF
MAGNITU�E OR INVOLVING EXTRA WST ARE NOT PERMISSIBLE WITHOUT REVIEW. GROUP CONCEALE�
ELECTRICAL EpUIPMENT REQl11RING ACCE55 WITH EpUIPMENT FREELY ACCESSIBLE THROUGH ACCESS
000Rs.
F. MATERIALS'.1�NAMEPLATES:PROVI�EBIACKLAMIC0I�SHEETWITH%"WHITELETTERING,FASTENEDWITH
EPDXV CEMENT FOR EACH �ISCONNECT SWITCH. CIRCUIT BREAKER, PANEL, CABINET, TRANSFORMER,
ENCLOSURE,MOTORCONTROLLERAN�THELIKE NAMEPLATESSHALL�ESCRIBETHENAMEAN�Nl1MBER
OF FACH COMPONENT. 2) CABLE TAGS'. TAG FACH CON�UCTOR PASSING THROUGH SPLICE OR PULLBOX
WITH A WHITE LINEN TAG, IN�ICATING POI�T OF ORIGIN AN� TERMINATION OF THE CIRCUIT.3) INSERTS AN�
SUPPORTS: a. MSERTS: STEEL, SLOTfED iVPE, FACTORY PAINTE�. - SINGLE RO�: SIMILAR TO GRINNELL FIG.
281. - MULTI-R0�'. SIMILAR TO FEE AN� MASON SERIES 9000 WITH EN� CAPS AN� CLOSURE STRIPS. - CLIP
FORM NAILS F W SH WITH INSERTS. - MAXIMUM LOA�ING ]5 PERCENT OF RATING. b. SOPPORTS FROM
BUILDING CONSTRl1CTI0N: MSERTS, BEAM CLAMPS, STEEL FISHPLATES QN CONCRETE FlLL ONLV),
CANTILEVER BRACNETS OR OTHER MEANS. SUBMIT FOR REVIEW. c. GROUPE� LINES AN� SERVICES'.
TRAPEZE HANGERS OF BOLTED ANGLES OR CHANNELS. d. WHERE BUIL�ING CONSTRUQION IS INAOEpUATE'.
PROVIDE ADDITIONAL FRAMING. SUBMIT FOR REVIEW.
G. PAINTSHALLBETHEBESTGRADEFORITSPIIRPOSE.DELNERINORIGINALSEALEDCONTAINERSANDAPPLV
IN ACCOR�ANCE WITH MANUFACTURER'S INSTRUCTIONS. COLORS SHALL BE AS SELECTE� BY ARCHITECT
OR ENGINEER. UTILIZE GALVANIZEO IRON PRIMER ON PANEL AN� PULL BO%E5, AFTER FABRICATION. UTILIZE
HOT �IPPE� GALVAWZE� OR �IPPED M ZMC BASE� PRIMER FOR: OUTLET BOXES, JUNCTION BOXES.
CONDOIT HANGERS, RODS, INSERTS AN� SUPPORTS. ZINC BASED PRIMER OF STEEL EpUIPMENT AND
RACEWAVS. A FIELO APPLIE� ZMC BASEO PRIME COAT SHALL BE UTILIZE� FOR STEEL OR IRONWORK.
H. BRUSHAN�CLEANWORKPRIORTOCONCEALING,PAINTINGANDACCEPTANCEPAINTE�EXPOSE�WORK
SOILE� OR �AMAGED', CLEAN AN� REPAIR TO MATCH ADJOINING WORN BEFORE FINAL ACCEPTANCE.
REMOVE OEBRIS FROM INSIDE ANO OUTSIOE OF MATERIAL AN� EQUIPMENT.
I. FINALLOCATIONSAN�MOUNTINGORIENTATIONSOFALLSWITCHES.RECEPTACLESANDLIGHTWMINAIRES
FYAII\-1aVa:�I�la�Ppl11:I9dN:I11iN�
11�911{NNSY.Y�PItl:iPINAI[tl�6YN:L11�8iY911�M19q�lY%9:LN:IIISN�J:![tl:iPl@FYLIICV P]J
6. LOW-VOLTAGE DISTRIBUTION EQUIPMENT:
A. PROVIDECOMPLETEEpUIPMENTINCWDING�.SWITCHES,FUSE$CIRWITBREAKERS.PANELSAND
TRANSFORMERS.
B. ALLEpUIPMENTSHALLCONFORMTONEMA,AN51,lEEESTANDARDSANDBUIL�INGSTANDARDS.
C. �ISCONNECTSWITCHESSHALLBEFUSE�ORNONFUSEDASNOTE�ANDHORSEPOWERRATEDFORMOTOR
LOADS. TOGGLE TYPE SWITCHES SHALL BE NONFUSE�. LOA� BRFAN, HAVING MAXIMUM RATINGS OF 20 AMP
AT 600 VOLTS AND 30 AMP AT 240 VOLTS. TWO-POLE SWITCHES SHALL BE LEVITON MO�EL SIMILAR TO HART
AN� HEGEMAN N0. ]810F. KNIFE-BLA�E TVPE SWITCHES SHALL BE LOA� BREAK, pUICK-MAKE-pUICK�BREAK,
UL CLASS R UP TO 600 AMP MA%IMUM RATING EXCEPT AS NOTED �FA� FRONT, NEMA TVPE 1. E%CEPT AS
NOTE�.
D. FOSES'.1�CIRCUIT6�iTO6000AMPERE55HALLBEPROTECTEDBYFU5E551MILARTOCURREMLIMITING
BUSSMANN LOW-PEAK iIME-DELAY FUSES KRP�C (AMP�SP, CLASS L LISTE� BV UL WITH AN INTERRUPTING
RATWG OF 300,000 AMPERES RMS SYMMETRICAL 2) CIRCUITS 0 TO 600 AMPERES SHALL BE PROTECTE� BY
FOSES SIMILAR TO W RREM LIMRING BUSSMAN LOW-PEAK DUALELEMENT TIME-0ELAV LPN-RK (AMP)SP
(250V�1LPSRK (AMP)SP (60�V) OR LPJ (AMP�SP (600V) (ULCLASS RKi OR GLASS J). AND BE LISTED BY UL WITH
AN INTERRUPiING RATING OF 300,000 AMPERES RMS SYMMETRICAL 3) MOTOR CIRCUITS - ALL INDNI�UAL
MOTOR CIRCUITS WITH FULL LOAD AMPERE RATINGS (FLA) OF 48� AMPERES OR LESS SHALL BE PROTECTE�
BV FUSES SIMILAR TO CURREM LIMITING BOSSMANN LOW-PEAK �UALELEMENT TIME-DELAY LPN-RK
(AMP)SP (250V) /LPS�RK (AMP�SP (600V) OR LPJ (AMP�SP (600V) (ULCLASS RKi OR CLASS J). AND BE LISTE� BV
UL WITH AN INTERRUPTING RATING OF 30q�00 AMPERES RMS SYMMETRICAL 4) ALL FUSES SHALL BE
PROVI�E� BY SAME MANUFACTURER. 5) PROVI�E 1 SPARE MATCHING FIISE FOR EACH SET OF 3.
E. CIRCUITBREAKERS'.MOL�E�CASEBREAKERSSHALLBETHERMALMAGNETIGpUICK�MAKE-pUICK-BREAK.
BOLT-ON TYPE, MANUALLY OPERATE� WITH INSULATE� TRIP-FREE HAN�LE. MULTI-POLE TYPE BREAKERS
SHALL CONTAIN INTERNAL TRIP BAR. TERMINALS SHALL BE SUITABLE FOR COPPER OR AW MINUM CABLE.
FORNISH AU%ILIARY �EVICES WHERE REQUIRE�. ENCLOSURES SHALL BE DEAD FRONT. NEMA TYPE 1,
E%CEPT AS NOTE�. FRAMES, IC AN� INTERCHANGEABLE TRIPS SHALL BE AS PoLLOWS. UNLESS OTHERWISE
NOTE�:1)120 VOLTS, ID��AMP FRAME'.10,000 AMP5.1 POLE 2) 240 VOLT5.100-AMP FRAME:18 000 AMPS, 2
AN�3POLE5.
F. �ISTRIBOTIONPANELS:SWITCHINGUNITSSHALLBE3PHASE,4WIRECIRCUR�BREAKERTVPEONLE55
OTHERWISE NOTED ON PANEL SCHEDULES. BUS BARS SHALL BE HAR� �RAWN COPPER, MINIMUM 98
PERCENT CON�UCTIVIN, SILVER OR TIN-PLATE� JOINTS. CABINETS SHALL BE WELDE� CORNERS.
HARDWARE SHALL 8E CHROME-PLAiED WITH F W SH LOCKILATCH HANDLE ASSEMBLV (UP T0481N. HIGH
DOORS) OR VAULT HANDLE LOCK AN� 3-POINT CATCH (LARGER THAN 481N. HIGH DOORS�. HINGES SHALL BE
SEMLCONCEALE�.S-KNUCKLE STEEL WITH NONFERROUS PINS, 180-0EG OPENING. LOCATED A MA%IMUM 26
W. ON CENTERS. MINIMUM GUTTER SPACES FOR LIGHTING PANELS SHALL BE 5314IN. SI�ES, PLASTIC,
TRANSPARENT COVER. A TYPEWRITTEN LIST IN�ICATWG FEEDER CABLE AN� CONDUIT SIZE. CIRCUR
NUMBERS, OUTLETS SUPPLIED AND THEIR LOCATIONS SHALL BE PROVIDED.
G. BAIANCETHELOA�OVERPHASESWHENNEWCIRCUITSAREADDE�TOPANELS.PROVI�EMULTLCABLE
W GS WHERE REpUIRED. �OUBLE W GGING SHALL NOT BE PERMITTED. MOl1NTING HEIGHT SHALL BE A
MAXIMUM OF 6 FT�61N. FROM FLOOR TO TOP SWITCH UNR. UP�ATE DIRECTORIES ON E%ISTING
PANELBOAR�S WHERE CIRCUITING IS CHANGED.
H. TESTS:OPENANDCLOSELOA�BREAKSWITCHWGDEVICESUNDERLOA�.
7.RACEWAYS:
A. PROVIDERACEWAYSCOMPLETEWITHBOXESFITTINGSAN�ACCESSORIES.CONDUITOR
TUBWG 9ZES REFERRED TO IN SPEQFICATIONS AND ON DRAWINGS ARE NOMINAL
�IAMETERS.
8. MATERIAL5:1)RACEWAVS�.a.RIGIDSTEELCON�UIT�.FULLWEIGHTPIPE,GALVAMZE�,
THRFADED. b. ELECTROMETALLIC TUBING (EMT�'. THIN WALL PIPE, GALVAMZED, THREADLE55.
c. FLEXIBLE STEEL CON�UIT: CONTINUOUS SWGLE STRIP. GALVAWZED. d. WIREWAYS: WIRE
SHALL BE AS NOTED, MINIMUM N0. i6 GAUGE STEEL WITH GROUN� CONTINUITV. FINISH SHALL
8E BAKED ENAMEL. COVERS SHALL 8E SCREW-ON. e. SURFACE METAL RACEWAV�. SIZE AS
NOTED. BASE 0 041N., COVERy'. MATERIAL SHALL BE STEEL. FINISH SHALL BE BAKE� ENAMEL.
COVERS SHALL BE SCREW�ON. 2) FITTINGS AND ACCESSORIES: a. RIGI� STEEb. NONSPLIT.
THREADED, STEEL OR MALLEABLE IRON. ZINC �IE CAST NOT PERMITTED. b. ELECTROMETALLIC
TUBWG COMPRESSION TVPE. GALVAMZE� RIGID STEEL ELBOWS, Y OR LARGER. u FLE%IBLE
METALLIC CONDUIT: ANGLE WE�GE TYPE WITH INSUTATED THROAT. d. BOSHINGS: METALLIC
INSULATE� TYPE. 3) BOXES: a.OUTLET BO%E5: EXCEPT AS OTHERWISE REpUIRED BV
CONSTRUCTION, �EVICES OR WIRING. BOXES SHALL BE STAMPED STEEL, 4" SQOARE OR
OCTAGON FOR LUMINAIRES. BOXES ABOVE CEILING SHALL 8E �" �EEP. BO%ES IN CEILING OR
SLAB SHALL BE 3" DEEP. BOXES IN WALL FOR W MINAIRES SHALL BE 2�" �EEP. BOXES IN WALL
FOR RECEPTACLES AND SWITCHES SHALL BE 1y' DEEP. FURNISH WITH RAISED COVERS AND
LUMINAIRE STUDS WHERE REpUIRED. WITHOUT LUMINAIRE OR �EVICE'. FURNISH BLANK
COVER. OFFSET BACK-TO�BACK OUTLETS WITH MINIMUM 6" SEPARATION. b. JUNCTION AN�
PULL BOXES: GALVAWZED SHEET STEEL WITH SCREW-ON COVERS, E%CEPT AS NOTE�.
FURNISH WITH INSULATED SUPPORTS FOR CABLES LOCATIONS SHALL BE AS NOTE� OR
REQUIRED AND ACCESSIBLE. FLOOR BO%ES SHALL BE SUITABLE FOR CONDUIT AND DEVICES
NOTED. RAISE� OUTLETS SHALL BE HUBBELL dB2d16 SERIES WITH ABOVE FLOOR FITTING.
TELEPHONE: BOSHED HOLE. POWER: �UPLE%RECEPTACLE OR OTHER AS NOTED. INCREASE
SIZE TO SI11T AS NECESSARV. FLUSH OUTLETS SHALL BE HUBBELL %B2014 SERIES WITH FLUSH
FLOOR FITTWG FOR TELEPHONE AND FLUSH DUAL FLAP COVER WITH DOPLE%RECEPTACLE
FOR POWER AS NOTE�. WCREASE SIZE TO SUIT AS NECESSARV.
C. PROVIDE RACEWAYS ONLV AS HEREIN SPECIFIE�. E%CEPT AS NOTED. RACEWAYS SHALL BE
RON CONCEALE�, E%CEPT AS NOTE�. PROVIDE RACEWAY SUPPORT UTILIZING CEILING
TRAPEZE, STRAP HANGERS, OR WALL BRACKETS. SECURE ALL RACEWAVS TO SUPPORTS WITH
PIPE STRAPS OR U-BOLTS. SPACING OF SUPPORTS SHALL BE A MINIMUM OF 10' ON CENTER
FOR METALLIC RACEWAY AN� AS REQUIRED FOR NONMETALLIC RACEWAV. SPACING SHALL BE
5' ON CENTER FOR WIREWAVS AND PER CO�E AN� AS NOTE� FOR OTHERS. MOUNT
SUPPORTS TO STRUCTURE MASONRV WITH TOGGLE BOLTS ON HOLLOW MASONRV,
EXPANSION SHIELDS OR INSERTS IN CONCRETEAN� BRICK. MACHINE SCREWS ON METAL,
BEAM CLAMPS ON FRAMEWORK, WOOD SCREWS ON W00�, AND PAN THROUGH STRAPS IN
METAL DECK. NAILS, RAWL P W GS OR WOOD P W GS SHALL NOT BE PERMITTED. WHERE
REpUIRED BY STRUCTURE FURNISH THROUGH BOLTS AN� FISHPLATES. E%POSE� RACEWAVS
SHALL BE RUN PARALLEL WRH OR AT RIGHT ANGLES TO WALLS. PROVIDE CLEARANCE WITH
WATER STEAM OR OTHER PIPING MINIMUM 31N. SEPARATION FROM STEAM AN� HOT WATER
(
PIPES, EXCEPT 1" FROM PIPE COVER AT CROSSINGS AND 18" FOR PARALLEL RUNS�. FOR HUNG
CEILING OUTLETS. RUN IN HUNG CEILING AND CONNECT TO CEILING SUPPORT CHANNELS. IN
MASONRV AND POURE� WNCRETE. RUN VERTICALLY ONLV. MAINTAIN GROONDING
CONTINWTV OF INTERRUPTE� METALLIC RACEWAYS WITH GROUND CONDUCTOR, AND IN
FLEXIBLE CONDUIT FOR FEE�ERS AN� MOiOR TERMINAL CONNECTIONS. EMPTV RACEWAVS
OVER 1P LONG: PROVIDE FISH OR PULL WIRE GALVAWZED OR NVLON ROPE. RIGID STEEL
CON�UIT SHALL BE PERMITTE� FOR FEEDERS AND BRANCH CIRCUITS. PAINT MALE THREADS
OF FIELD�THREADED CONDUIT WITH GRAPHITE�BASE PIPE COMPOUND AND BUTT CONDUIT
EN�S. TOUCH UP MARRE� SORFACES AND FIELD�CUT THREADS, CRGWL� GALVAMZED. EMT
SHALL BE PERMITfED FOR BRANCH CIRCUITS ONLV, IN DRY LOCATIONS. �RV WALLS. HUNG
CEILINGS, HOLLOW BLOCK WALLS AND FURRED SPACES. EMT SHALL NOT BE PERMITTE� IN
RAISE� FLOORS. FLEXIBLE STEEL CON�UIT SHALL BE UTILIZED FOR SHORT CONNECTIONS
WHERE RIGI� CONDUIT IS IMPRACTICAL. FROM OIITLET BOX TO RECESSE� LIGHTWG
W MINAIRE: PROVIDE MINIMUM d' AN� MA%IMUM 6' LENGTHS. FOR FINAL CONNECTION TO
MOTOR TERMINAL BOX, TRANSFORMER AN� OTHER VIBRATING EpUIPMENT'. PROVI�E WITH
POLYVINYL SHEATHING AND GROUND CONDUCTOR. MINIMUM LENGTH'. 18" WITH SLACK.
CONNECT GROUND CONDUCTOR TO ENCLOSURE OR RACEWAV AT EACH END. FOR EXPANSION
JOINT CROSSMGS. CROSS AT RIGHT ANGLES AND ANCHOR ENDS. CUT CONDUIT ENDS
SpUARE. REAM SMOOTH. PAINT MALE THREADS OF FIELD THREA�E� RACEWAYS WITH
GRAPHITE BASE PIPE COMPOUND. DRAW UP TIGHT WITH RACEWAV COUPLING. EXPANSION
FITTINGS SHALL BE INSTALLED AT RIGHT ANGLES WITH CLIP JOINT CENTERED IN EXPANSION
JOINT. PROVIDE A LENGTH OF RUN IN ACCOR�ANCE MANUFACTURER'S RECOMMENDATIONS.
PRESET FITTINGS SHALL ALLOW FOR TEMPERATURE VARIATION. RACEWAYS PASSING
THROUGH FIRE�RATED CONSTRUCTION: SEAL OPENING WITH FIRE SEALANT.
�. ERECTWALLANDSWITCHOUTLETSINADVANCEOFFURRINGAN�FIREPROOFING.OUTLET
BO%ES SHALL BE SET SQUARE AND TRUE WITH BUILDING FINISH. SECURE TO BUIL�ING
STRUCTURE 8Y ADJUSTABLE STRAP IRON OR GROUT IN WITH MASONRV. VERIFV OUTLET
LOCATIONS IN FINISHE� SPACES WITH ARCHITECTIIRAL DRAWINGS OF INTERIOR DETAILS AND
FINISHES. PROVIDE BARRIERS BETWEEN SWITCHES CONNECTE� TO DIFFERENT PHASES FOR
VOLTAGES EXCEEDING 150 VOLTS TO GROUND.
E. PANEL,JUNCTIONANDPOLL80%ESSHALLBELOCATEDCLEAROFOTHERTRADES.CONCEAL
JUNCTION AN� PULL 80%ES IN FINISHE� SPACES. WHERE NECESSARV, REROUTE RACEWAVS
OR MAKE OTHER ARRANGEMENTS FOR CONCEALMENT. BOXES SHALL BE ACCESSIBLE.
SUPPORT BO%ES FROM BUILDING STRUCTURE, IN�EPENDENT OF CON�UR. PROVIDE
FLOOR�TO�CEILING CHANNELS FOR MOONTWG ON �RVWALL AND LIGHTWEIGHT
CONSTRUCTION. OUTLET BO%ES FOR LUMINAIRES RECESSED IN HUNG CEILINGS SHALL BE
ACCESSIBLE THROUGH OPENING CREATED BV REMOVAL OF W MINAIRE. SECURE TO BLACK
IRON SIIPPORT. MOTOR TERMINAL BOXES'. COORDINATE WITH MOTOR BRANCH CIRCUIi
CON�OIT AN� WIRING: ADD BOX VOW ME WHERE REQOIRED.
F. FIRESEALANTS:PROVIDEFORRACEWAVSANDWIREPASSINGTHROUGHFLOORSLOTS,
SLEEVES OR OPENINGS IN FIRE-PARTITIONS ROOMS.
G. PERFORMCONTINUITVTESTSOFRESISTANCEOFFEEDERCON�UITSFROMSERVICETO
POINT OF FINAL DISTRIBUTION USING 1 CONDUCTOR RETURN. MA%IMUM RESISTANCE SHALL
BE250HM5
H_ METALCLA�CABLE(TVPEMCJWITHGROUN�WIREMUSTCOMPLYWITHNEMAWCIO/ICEA
5-95-658. MC CABLE IS ACCEPTABLE FOR BRANCH CIRCUITS THAT ARE CONCEALED WITHIN
CEILINGS, WALL PARTITIONS.OR FLOORS. INSTALL E%POSED CABLES PARALLEL AND
PERPENDICULAR TO SURFACES OF EXPOSED STROCTURAL MEMBERS AN� PoLLOW SIIRFACE
CONTOURSWHEREPOSSBLE.
8. WIRE AND CABLE:
A. PROVIDEWIREANDCABLECOMPLETEWITHACCESSORIES.SIZEREFERENCESHALLBEAWG
E%CEPT AS NOTE�.
B. CONDUCTORSSHALLBECOPPER,ASTMSTANDARDSOLID�N0.10ANDSMALLER)OR
STRANDED (N0.8 AN� LARGER). GENERAL USE CABLING SHALL BE N0. 12 MINIMUM. AT 12�
VOLTS AND OVER 100' CIRCUIT LENGTH PROVIDE N0.10 MINIMOM. AT 265 VOLTS AND OVER
200' CIRW IT LENGTH PROVIDE N0.10 MINIMIIM. CONTROL AND ALARA4 CABLING. E%CEPT AS
NOTED. SHALL BE N0. 1A MINIMUM. AT 120 VOLTS AN� OVER 200' CIRCUIT LENGTH PROVIDE N0.
8 MINIMUM. OTHER VOLTAGES AN� PHASES: ADJUST CABLE SILNG AS REQUIRE� TO MAINTAIN
VOLTAGE DROP. INCREASE RACEWAV SIZES FOR LARGER WIRE AS REpUIRED.
C. INSULATION SHALL 8E RU86ER AND THERMOPLASTIC MEETING ASTM AND IPCEA STANDAR�S.
TVPE THW OR THWN SHALL BE OTILIZED FOR FEEDERS AN� BRANCH CIRCOIiS E%CEPT AS
NOTED. TVPE SFF2 SHALL BE UTILIZED FOR BRANCH CIRCWTS LOCATE� IN WIRWG CHANNELS
OF CONTINUOUS F W ORESCEM W MINAIRES AN� IN AM1IBIENT TEMPERATl1RE5 OVER 90 DEG
G FOR UNGROUNDED ISOLATED BRANCH CIRCOITS PROVIDE CRO55-LINKED POLVETHYLENE
INSULATION (NPE XHHW).
D. COLORCODINGSHALLBEASFOLLOW5:1�120p08VOLT5V5TEM-BLACKFORAPHASERE�
FOR B PHASE BLUE FOR C PHASE 2) NEUTRAL WIRE SHALL UTILIZE 4NHITE OUTER COVERING
THROUGHOUT. EQUIPMENT GROON� WIRE SHALL UTILIZE GREEN OUTER COVERING
THROUGHOUT. WHERE WLOR-CODED CABLE IS NOT AVAILABLE, CERTIFY IN WRITWG AND
REQUEST PERMISSION TO OVERLAP CONDUCTORS WITH 6" OF COLOR TAPING IN ACCESSIBLE
LOCATIONS.
E. PROVIDEFLAMEPROOFLINENORFIBERTAGSINACCESSIBLELOCATIONS.FORFEEDERS
INDICATE FEE�ER NOMBER, SIZE, PHASE AN� POINTS OF ORIGIN AND TERMINAilONS. FOR
CONTROL AND ALARM WIRING IN�ICATE TYPE (CONTROL OR ALARM). SIZE OF WIRE. AND
POINTS OF ORIGIN AND TERMINATIONS.
8. WIRE AND CABLE: (CONTINUED)
F. TERMINATIONS,SPLICESANDTAPSUN�ER600VOLTS:COPPERCONDUCTORSN0.10AN�
SMALLER SHALL UTILIZE COMPRESSION-TVPE OF TWIST-ON SPRINGLOADED CONNECTORS
AND CLEAR NYLON-INSULATE� COVERING. COPPER CON�UCTORS N0. 8 AND LARGER SHALL
UTILIZE MECHANICAL BOLTED PRESSURE OR HYDRAULIC COMPRESSION TVPE USWG
MANUFACTURER'S RECOMMEN�ED TOOLING. CABLE LUGS AND CONNECTORS SHALL UTILIZE
COMPRESSION TVPE OF SAME METAL AS CONDUCTOR. PROVI�E TO MATCH CABLE, WITH
MARKWG INDICATING SIZE AND TVPE. COPPER W G CONNECTIONS TO BUS BARS'. USE
ANTISEIZE COMPOUND ON TANG.
G. NOTMORETHAN3LIGHTINGORCONVENIENCEOUTLETCIRCUITSSHALLBEINSTALLEDINONE
CONDUIT UNLE55 OTHERWISE IN�ICATED. PULL NO THERMOPLASTIC WIRES AT
TEMPERATlIRES LOWER THAN 32 DEG F. PROVI�E SEPARATE RACEWAYS FOR CON�OCTORS
OF 1201208 AND 265/d60 VOLT SVSTEMS, E%CEPT 660 VOLT MOTOR BRANCH CIRCUIT WIRWG
AND RELATE� 120 VOLT CONTROL WIRING. THERMOPLASTIC WIRES SHALL NOT BE INSTALLE�
IN COMPUTER AREA RAISED FLOORS.
H. LEAVEWIRESWITHSUFFICIENTSLACKTOPERMITMAKINGFINALCONNECTIONS.
I. PERFORM CONTINUITVAN� INSULATION TESTS. MEGGER TEST 100 PERCENT OF FEEDERS.10
PERCENT OF BRANCH CIRW ITS AND ALL MOTOR BRANCH CIRCUITS OVER 25 HP. PERFORM
TESTS PRIOR TO CONNECTING EpUIPMENT AND IN PRESENCE OF AUTHORIZED
REPRESENTATIVES. SUBMIT WRITTEN REPORT OF RESULTS. CORRECT OR REPLACE CABLE
TESTING BELOW MANUFACTURER'S STANDARDS.
J. TVPENMCABLEISACCEPTABLEINACCORDANCEWITHTHENEGNECARTICLE511�OESNOT
APPLY DUE TO NO PATIENT CARE AREAS ON THE PROJECT.
9. DEVICES:
A. PROVI�ECOMPLETEMATERIALANDACCESSORIESASPERBUIL�INGSTANDARDS.
B. LOCAL WALL SWITCHES SHALL BE SPEGFlCATION GRADE, T06GLE. QUIET iVPE RATED 20
AMP,12�21] VOLT, AG LEVITON MODEL SIMILAR TO HUBBELL NOS. 122� (SINGLE POLE�, 1222
(�OUBLE POLEJ.1223 (3WA1� AND 1224 (4WAV1.
C. INSERTION RECEPTA0.ES SHALL BE SPEqFICATION 6RA�E �UPLEX CONVEMENCE 125
VOLTS, 2 POLE, 3 WIRE, U GROUND SLOT. GROUNDEq EXCEPTAS NOTE�. MEETING NEMA
STANDARDS. PUBLICATION WD-1-09]i. LEVITON MODEL SIMILAR TO HUBBELL NOS 53fi2 (20
AM� AND 5262 (15 AMPJ. �) SIN6LE, EXCEPT AS NOTE�: e. 20 AMP STRAIGHT BLADE, SIMILAk
TO HUBBELL NQ 53fi1. b.125 VOLT, 2 POLE, 3 WIRE, 6ROUNDED.2) SPECIAL USP.
NONIMERCHANGEABLETYPESAN�RATINGS.3)GROUNDFAULTIMERRUPTER
RECEPTAQES'. a FEE�-THRU NPE LEVITON MODEL SIMILAR TO HUBBELL NOS. GF5362 (20
AM� AND 6F5282 (�5 AMP).
D. MOMENTARVCONTACTSWITCHESFORREMOTECONTROLSWITCHES,LEVITONMODEL
SIMILAR TO HUBBELL N0. 4354.
E PILOTLI6HTS:NEONLAMP,LEVITONMODELSIMILARTOHUBBELLNO.T1315,WITH125VOLT
LAMP.
F DEVICEPLATES'.SEEARCHITECTFORNPEFORRECEPTA0.ESWITHOTHERTHAN120VOLT,
INSCRBE� VOLTAGE AVAILABLE.
G. WLORS:WORDINATECOLORSWITHARCHITECT.
H. MOUNTIN60RIENTATIONOFRECEPTAQES�VERTICAL):COORDINATEWITHARCHITECT.
L RlI5HFL00RM0UNTE�POKETHR0UGH0URETPOKETHROUGHFL00RRTTINGWITH2
HOUR FlRE RATING. MOUNTS 4' �IAMETER HOLE PAINTABLE DIE CAST ALUMINUM CARPET
FLAN6E PROVIDE MODIRE� LEXAN SLIDE HOLDER TO SIIPPORT A QUA� ELECTRICAL OUTLET.
COMPLETE WITH ALL NECESSARV HAR�WARE FOR COMPLETE INSTALLATION. SIMILAR TO
WIREMOL� PARTNO. RC-0.
10. LUMINAIRES:
A. PROVIDELUMINAIRESCOMPONENTSANOLAMPS.LUMINAIRESSHALLBECOMPLETELV
FACTORV ASSEMBLED. WIRE� ANO E�UIPPED WITH ALL NECESSARV SOCKETS, BALLASTS,
SUPPORTING HARDWARE AND ACCESSORIES. REFER TO ARCHITECTURAL DRAWINGS FOR
INDIVIDUAL LUMINAIRE DESCRIPTIONS.
B. LUMINAIRECATALOGNUMBERSUSEDTOILLUSTRATEEQUIPMENTTVPEDONOTNECESSARILV
DENOTE RE�UIREO MOUNTING EQUIPMENT OR ACCESSOPoES. PROVI�E ACCESSORIES TO
SUIT.
G BALLAST�.CLASSP,HIGHPOWERFACTOR,LOWESTAVAILA&ENEMARATE�NOISELEVELETt
AND CBM APPROVE�. ENERGY SAVING iVPE TRIGGER START FOR 2a-INCH LAMPS AND RAPID
START PoR 48-INCH. TWO LAMP BALLASTS; NO THREE LAMP BALLASTS. BALLASTS SHALL BE
ADVANCE MAGNETEK. UNIVERSAL OR EQUAL.
11. TELEPHONE AND SECURITY CONDUIT SYSTEM:
A. PROVIDECOMPLETESVSTEMOF:EMPTYCONDUIT,PULLBOXES.OIITLETS.SLEEVESAN�
FISHWIRES.
B. OUTLETS SHALL BE 1) WALL: a" S�UARE WITH BUSHEO COVER PLATE.2) FLOOR: CAST IRON
WITH LOW TENSION FITTING.
C. PROVIDEFISHWIRES,INRACEWAVSOVERIPLONG.
D. CONDUITSHALLBE%'MINIMUM.PROVIDEEMPTYWNDUITFROMOIITLETTONEAREST
ACCESSIBLE HUNG CEILING.
� R
_
] 207
4TEOF ;'�
W�
� � A NP.G2��
�
N A L Ea p����
p=c.,..,,s....�� os�
u � a� a� �
"� � � U7 O
o � ���
a U
� � � �
C � p
� � � �
�- N �
O W -
N `" co �
N O
U �N �
•L � U
� 6
N
n\ N
W =
L �
� U
� <
�n`
W\
/
Q
�,»��»�ii�id
Aveda Institute
16281 Tri Ridge Blvd
Suite 140
Loveland, Ohio 45140
SHEET WFORMATION
Prolect p: 20013
Issoed Fort BID / PERMIi
Dafe: 5/29/20
Revkions'.
�
PEServices
ENGINEERING FOH VOUR 5U[[E55
1-513-836-3810
vwuw. pe-servi�es.com
�.y:ieamne
IT IS THE RESPONSIBILITY OF THE W NTRACTOR TO NOTIFY
THE ARCHITECT, LAN�LORD AND TENANT OF ANY
°'S�REP""�'ESE"°°°"TERE°°"T"E"""S°R'" ELECTRICAL SPECS
EXISTING SITE CONDITIONS PRIOR TO SUBMISSION OF BID.
RELEA5E0 FOR CONSTRUCTION
Suhjec� �o compliance with all regula�ions
04 S�a�e antl Local Codes
City of Carmel
`�y,:a���'.�`� �,�:;vaYa/„1��.
DATE: O��0��20
BIDDERS ARE TO VISIT THE SITE AND FAMILIARRE
THEMSELVES WITH EXISTWG CONDITIONS AND SATISFY
THEMSELVES AS TO THE NATURE AN� SCOPE OF THE WORK.
THE BASE BID SHALL REFLECT MODIFICATIONS TO SYSTEMS
AND DEVICES AS REQUIRED BV STATE, LOCAL AND FEDERAL
CO�ES WHETHER IN�ICATED OR NOT ON CONTRACT
DOCUMENTS. THE SUBMISSIONS OF A BID WILL BE EVIDENCE
THAT SUCH AN EXAMINATION AN� COMPLIANCE WITH
GOVERNING CODESIREQUIREMENTS HAS BEEN MADE LATER
CLAIMS FOR LABOR, E�UIPMENT, OR MATERIALS RE�UIRED,
OR PoR DIFFlCULTIES ENCOl1MERED WHICH COULD HAVE
BEEN FORESEEN HA� AN E%AMINATION AN�
CODNREQUIREMENTS REVIEW BEEN MADE, WILL NOT BE
ALLOWED.