DINING ROOM BEAM ELEVATION VIEW
Support column with
solid wood blocking if
fully supported above
block wall exterior
foundation wall or if
location lands in
common floor joist
span, install 1 EA steel
GR 50 W8 x 48 up to
14' length under each
column if needed.
Existing 2" x10"
Perimeter
band board
12'-8" Approx Estimated Dimension Field Verify
Beam clear span not to exceed 14'-0"6'-5" Beam span not to exceed 14'-0"
Existing CMU Wall Original CMU Wall
Install 4 new 2" x 6" Columns
2 @ full height adjacent to beam
2@ bottom of beam bearing min 4.5" of beam
remove and replace existing 2" x4" column
Typical EA End of beam
Secure to Interior 2" x 4" wall entire length
Install solid blocking in
joist span below
exterior wall column
Relocate HVAC
Floor Supply as need
due to stair rough opening
Install new W8 x 48 beneath
columns in joist span shim height
at each end of beam
Relocate Electrical
Install Temporary Falsework
under rafters before demo
designed by contractor, do
not perform work under snow
loading
Wall to be removed
Install 2 EA 1.75" x 16" x 17' LVL MAX Length Ridge Beams. Contractor to
verify span length, plus 9" End bearing to clear span length (4.5" Min End
Bearing EA End) before ordering length Place in new cut birdsmouth of rafter
tails in front of existing load bearing wall. Brace beam in Kitchen side ceiling
along the entire length
Install 4 new 2" x 6"
Columns 2 @ full
height adjacent to
beam 2@ bottom of
beam bearing min
4.5" of beam remove
and replace existing
2" x4" Secure to
Interior 2" x 4" wall
entire length
DINING ROOM BEAM SECTION VIEW
Remove
existing 2" x 4"
wall after new
beam is
installed
Trim out beam
with drywall
Contractor to verify Min 6' - 10" Rough Opening Minimum Height from Floor to Bottom of BeamWARNING!
Contractor to design and
install temporary support
rafters, brace, then install
new beam.
Contractor to demo dining
room ceiling and verify new
beam height would be 6'
-10" minimum from finished
flooring elevation else stop
work and notify engineer.
Cut new birdsmouth into
rafter to receive the new
beam.Install 2 full height exterior 2" x 6" to brace beam at endpoints17'-0" Max Length - Contractor to Field Locate Precise Location
Install new W8 x 48 beneath
columns in joist span shim height
at each end of beam
Splice over Foundation wall
Dining room new beam kitchen section view Viewed from dining room towards kitchen
Install new wall
to block off
staircase
Nail new
column to
new wall full
length
4 EA - 2" x 6"
with 1EA -12"
Plywood Shim
to support
beam EA end.
ORIGINAL DESIGN NOTES
CONTRACTOR SHALL:
WARNING!
CONTRACTOR MUST USE CAREFUL CONSIDERATION IN SEQUENCING THE REMOVAL OF THE
EXISTING SUPPORT FOR THE RAFTERS/ROOF SYSTEM.
INSTALL AND BRACE NEW SUPPORT BEFORE REMOVING THE EXISTING SUPPORT.
SUGGESTED PHASING
1. CONTRACTOR TO VERIFY PLAN DIMENSIONS WITH FIELD CONDITIONS BEFORE ORDERING
MATERIALS - LENGTH, MINIMUM HEIGHT AFTER FINAL FINISHES, EXISTING FRAMING DETAILS
2. STOP WORK AND NOTIFY ENGINEER OF ANY ERRORS OR DISCREPANCIES ON PLANS
3. INSTALL W8 X 48 NEW FLOOR BEAM IN CRAWL SPACE BENEATH EVENTUAL COLUMN
LOCATIONS
4. INSTALL NEW LVL OR TEMPORARY SUPPORT WALL WITH EXISTING WALL IN PLACE
5. INSTALL BRACING ALONG LVL LENGTH INTO ATTIC OF KITCHEN
6. FRAME IN STAIRCASE PROTECTIVE WALL AND ATTACHED TO LVL COLUMNS
7. REMOVE EXISTING 2" X 4" LOAD BEARING WALL
8. REMOVE REMAINING DINING ROOM WALLS
1/23/2020 10:11:45 PMDESIGN ENGINEER - JANUARY 24, 2020