HomeMy WebLinkAboutBasement Door Cut DetailsORIGINAL DESIGN NOTES
CONTRACTOR SHALL:
VERIFY ALL PLAN DIMENSIONS ARE
CORRECT BEFORE CONSTRUCTION AND
NOTIFY THE ENGINEER WITH THE CONTACT
INFORMATION ON THIS SHEET IN WRITING
IF ANY DISCREPANCIES EXIST AND AWAIT
THE ENGINEER OR RECORDS DIRECTION
BEFORE CONTINUING CONSTRUCTION.
DATE:DESCRIPTION: REV: BY:
Notes:
REVISION:DRAWING NO: PROJECT NO:
DRAWN:DATE: CHECKED:
TITLE:
SCALE AT:
CLIENT:
SITE:
STATUS:
DESIGNER:
DESIGN ENGINEER - JANUARY 24, 2020
RICHARD CLAYBORN, PE
1" 1-24-2020 RWC RWC
5 DHS---
Basement Beam Design
3040 Rolling Springs Drive
Carmel IN 46033
RICHARD W CLAYBORN, PE
6003 FERN VALLEY ROAD
LOUISVILLE KY 40228
502-345-4147
Gennifer Grogg
3040 Rolling Springs Drive
Carmel IN 46033
Hamilton County, Indiana
For Construction
6'-10" Rough Opening for 6'-8" Finished Doorcontractor to field verify 8" lintel will fitwithin wall height beneath floor joist andclear 6'-10" Rough OpeningORIGINAL DESIGN NOTES
CONTRACTOR SHALL:
WARNING!
CONTRACTOR MUST USE CAREFUL CONSIDERATION IN SEQUENCING THE REMOVAL OF
THE EXISTING BLOCK WALL HEADER FOR THE FLOOR SYSTEM.
INSTALL AND BRACE NEW SUPPORT EACH SIDE OF WALL BEFORE REMOVING THE
EXISTING SUPPORT.
ENSURE NEW LINTEL HAS 1 EA- #4 40,000 FY PSI REINFORCING BAR IN THE TOP AND
BOTTOM. ISTALL 2 EA LINTELS PER DOOR HEADER
SUGGESTED PHASING
1. CONTRACTOR TO VERIFY PLAN DIMENSIONS WITH FIELD CONDITIONS BEFORE
ORDERING MATERIALS - LENGTH, MINIMUM HEIGHT AFTER FINAL FINISHES,
EXISTING FRAMING DETAILS
2. STOP WORK AND NOTIFY ENGINEER OF ANY ERRORS OR DISCREPANCIES ON
PLANS
3. INSTALL TEMPORARY SUPPORT WALLS
4. SAW CUT WITH WATER SUCH THAT NO DUST IS CREATED
3. RIP CUT SAW CUT HEADER LENGTH CONCRETE BLOCKS TO DEPTH OF 12" BLOCK
THICKNESS
4. CHISEL OUT CUT BLOCK AND INSTALL 1 NEW CONCRETE LINTEL
5. REPEAT PROCESS FOR SECOND SIDE LINTEL
6. AFTER MORTAR HAS CURED SAW CUT AND DEMO EXISTING BLOCK BENEATH
LINTEL IN WIDTH OF DOOR ROUGH OPENING
7. PATCH CONCRETE THRESHOLD
8. INSTALL FINISHED DOOR, JAMB AND HARDWARE
3'-2" Rough Opening
for Finished 3'-0" Door
6'-10" Rough Opening for 6'-8" Finished DoorInstall 2 EA new reinforced
concrete lintels above
rough opening of door
Must have 1 EA- #4
40,000 FY PSI Top and
Bottom
Do not exceed 4'-3" Clear
Span
BASEMENT DOOR CUT ELEVATION VIEW BASEMENT DOOR CUT SECTION VIEW
3 5/8" 7 5/8"3 5/8"7 5/8"4'-6"7 5/8"Install 2 EA new reinforced
concrete lintels above
rough opening of door
Must have 1 EA- #4
40,000 FY PSI Top and
Bottom
8"
Bearing
Typ EA End 8"
Bearing
Typ EA End
1/24/2020 12:33:21 AM08/18/20