HomeMy WebLinkAbout01367IN_E1SECTION 2fi.05.05 SELECiIVE �EI�OLI110N FOR ELECIRICAL =ART 1 EXECUTION 1.01 E%AI�INATION A. VERIFY 1HAT ABANDONE� N7RING AN� EOUIPMEM SERVE ONLY ABAN�ONE� FAQLITIES. B. BEGINNING OF DEMOLITION MEANS INSiALLER ACCEPTS EXIS➢NG CON�I➢ONS 1A2 PREPAkATION A. �6WNNECi ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILWGS TO BE REMOVED. . �OOR�INATE U➢LIiY SERVICE OUiAGES WITH U➢LIiY COMPANY. .'ROVIDE IEMPORARY WIRING AND CONNECTIONS TO MAINiAM E%ISTING SYSiEMS IN SERVICE ]URWG CONSTRUCTION. WHEN WORK MUST BE PERFORME� ON ENERGIZED EOUIPMENT OR CIRCUIiS, USE PERSONNEL ENPEPoENCED IN SUCH OPERAiIONS .. 7%ISTING ELECiRICAL SERNCE: I�AINTAW EXISiING SY4EM W SERVICE UNiIL NEW SYSiEI� IS � COI�PLEiE AND READY FOR SERVICE DISABLE SYSiEM ONLY i0 MAKE $WIiCHOVER$ AND CONNECiIONS. I�INIMRE OUiAGE DURAiION. 1.C3 OEI��LIiION AND EXiENSION OF EXISiING ELECiRICAL WORK A. i IAOVE RELOCAiE, AND E%TEND E%ISTING WSiALLAilONS i0 ACCOMMODAiE NEW CONSiRUCiION. 3. � PAIR ADJACENi IX7NSiRUC110N AND FlNISHES �AMAGE� DURING DEMOLITION AN� E%IENSION ltiORK. C. UAINTAIN ACCESS TO EXISiING ELECiRICAL INSTALLAlI0N5 THAT REMAIN AC11VE. MODIFY INSTALLAlION OR PROVIDE ACCESS PANEL AS APPROPRIAiE. SECTION 26.05.19 LOW-VOLTAGE ELEC7RICAL POWER WN�UCTORS AN� CABLES PART 1 PkODUCiS 1�1 CONDUCiOR AN� CABLE APPLICA➢ONS A. �0 NOT USE CON�UCTORS AN� CABLES FOR APPLICAilONS OiHER 1HAN AS PERMITiE� BY NFPA 70 AND PRODUCT LISiING- ?. =ROVIDE SINGLE CONDUCTOR BWL�ING vnRE INSiALLED IN SUIiABLE RACEWAY UNLE55 OIHERWISE INDICAiED, PERNITiED, OR REQUIRED. C. 1�EiAL-CLAD CABLE IS PERMIiiED ONLY AS FOLLOw3 1. WHERE NOT OiHERWISE RESiRICiED, MAY BE USED: a. wHERE CONCEALED ABOVE ACCESSIBLE CBLING$ PoR FlNAL CONNECilONS FROM JUNCiION BO%ES ID WMINAIRES 1) NAXIMUM LENGIH: 6 FEET. o. wHERE CONCEALED IN HOLLOW SiUD WALLS, ABOVE ACCESSIBLE CBLINGS, AND UNDER RAISED FLOORS FOR BRANCH CIRCUIiS UP i0 20 A. 1) E%CEPTION' PRONDE SINGLE CONDUCTOR BUIL�ING WIRE IN RAGEWAY FOR GRGUIi HOMERUN �toM FIRSi OUTLEi TO PANELBOARD- 1A2 CANDUCiOR AND CABLE GENERAL REQUIRE�IENTS A. =ROVIDE PRO�UCi$ iHAi COMPLY WIiH REQUIREMENTS OF NFPA 70. .'FOVIDE PRO�UCiS LISiEq CLASSFlED, AND LABELED AS SUITABLE PoR iHE PURPOSE INiEN�ED. .,.NLESS SPEGFlCALLY IN�ICATED TO BE E%CWDED, PROVIDE ALL REOUIRE� CON�WT, BO%E5, � WIRING, CONNECi0R5, EiC A$ REOUIRED FOR A C01�PLETE OPERAiING $YSiEM_ . COM1IPLY WIiH NEI�A WC 70. =. �FiERMOPLASiIC-INSOLATED CONDUCTORS AND CABLES LIS1E� AND LABELE� AS COMPLYING '�tiITH UL 83. -. -HERMOSET-INSULATED CONDUCTORS AND CABlES IJSTE� AN� LABELE� AS IX7MPLYING WITH UL 44. . CON�UCiORS FOR GROUNDING AND BON�ING: ALSO COMPLY WIRI SECiION 26 0526. -. CON�UCiOR MAiERIAL 1. '40VIDE COPPER CON�UCTOftS ONLY. AWI�INUM CON�UCTORS ARE NOT ACCEPTABLE FOR 7H15 =90JECT CONDUCTOR SRES IN�ICATE� ARE BASED ON COPPER. 2 COPPER CONDUCTORS�. SOFT DRAWN ANNEALE�, 98 PERCENT CONDUCTNITY, UNCOAiE� COPPER CON�UCiORS COMPLYING WITH ASiM 83, ASTM 88, OR AS11A W87/W87M UNLESS OIHERWISE iNoicnTEo. . l\NED COPPER CON�UCTORS: COMPLY WI1H ASTM B33. CON�UCiOR COLOR CO�ING: 1. COLOR CODE CONDUCTORS AS INDICAIED UNLESS OiHEftWISE REQUIRE� BY THE AUiHORITY IIAVING JURIS�ICTION. IAAINTAIN CONSISTENi WLOR CO�ING 1HROUGHOUT PftOJECT. 2 COLOR CODING METHOD�. INTEGRALLY COLORED INSULATION- .,_ COLOR CODE: c EQUIPMENi GROUN�, ALL SYSiE1�S: GREEN. �, FOF N,ODIFlCATIONS OR AD�ITIONS i0 EXISiING WIkWG SYSTEMS, COMPLY WIiH EXISiING COLOR WDE WHEN E%ISiING CODE COMPLIES w1iH NFPA 70 AND IS APPROVED BY iHE AUiHORITY HAVING JURISDICiION_ 1DS SINGLE CONDUCiOR BUILDING wIRE A. ]ESCRIPiION�. SINGLE CONDUCiOR INSULAiED WIRE. ". CON�l1Ci0R SiRANDING�. 1. =EEDER$ AND BRANCH CIRCUIiS: a. SIZE 10 AWG AN� SMALLER: SOLI�. b. SIZE 8 AWG AN� LARGER: SiRANDE�. 2 CONTROL CIRCUITS: STRANDED. c. iNsuv,noN vo�rnc� ennNc sao v. o. iNsu�nnoN�. 1. COPPER BUIL�ING WIRP. TWE 1HHN/THWN OR iHHN/1HWN-2, EXCEPi AS INDICAIED BELOW. c. SIZE 4 AWG AN� LARGER: TYPE NHHW-2. L�4 I�ETAL-CLA� CABLE A. DESCRIPiION�. NWA 70, TYPE MC CABLE LISTED AND LABELED AS COIAPLYING WITH UL 1569, AN� IJS1E� FOR USE IN CLASSIFlE� FlRESTOP SYSIEMS TO BE USE�. B. CON�UCiOR STRAN�ING�. L SIZE 10 AWG AN� SMALLER: SOLID. 2 SIZE 8 AWG AND LARGER: SiRAN�E�. C. INSULA➢ON VOLTAGE RA➢NG. 600 V. �. INSULAlION�. iYPE 1HHN, THHN/iHWN, OR THHN/iHWN-2. E GROUNDING FULL-SIZE INTEGRAL EOUIPMENT CROUN�ING CON�UCTOR. F. ARMOR: SiEEL,INTERLOCKE� TAPE. 1.U5 N7RING CONNECTORS A. J6CRIPTION�. WIRING CONNECTORS APPROPRIATE FOR THE APPLICATION, SUIiABLE FOR USE WITH illE CONDUCTORS i0 BE CONNECiE�, AN� LIS1E� AS COMPLYING WI1H UL 486A-486B OR UL 486C AS APPLICABLE. B. WIRING CONNECTORS FOR SPLIGES AND TAPS�. L COPPER CONDUCTORS SIZE 8 AWG AND SI�ALLER: USE iW15i-0N INSULAIE� SPRING CONNECiORS 2- COPPER CONDUCTORS SRE 6 AWG AND URGER: USE MECHANICAL CONNECi0R5 OR COI�PRESSION CONNECi0R5. C. iWlSi-ON INSULAiED SPRING CONNECi0R5� RAiED 600 V, 221 DEGREES F FOR STANDARD APPIJCAiIONS AN� 302 DEGREES F PoR HIGH iEMPERAiURE APPIJCAiIONS; PRE-FlLLE� 'MiH $EALANi AND LISiED A$ COMPLYING WIiH UL 48fiD FOR DAI�P AND WEi LOCAilONS. D. I�ECHANICAL IX7NNECiORS: PROVIDE BOLIED TYPE OR SEi-SCREW TYPE. 4. COMPRESSION CONNECTORS: PROVI�E CIRCUMFERENTIAL TYPE OR HE% TYPE CRIMP CONFlGURATION. L�6 N7RINC ACCESSORIES A. '_ ECIRICAL TAPE: 1. VIVYL WLOR CO�ING ELEC7RICAL iAPP. INTEGRALLY WLORED TO MATCH COLOR CODE IN�ICATE��, LISTE� AS COMPLI1NG WITH UL 510; MINIMUI� RIICKNESS OF 7 MIL, RESISiANT TO A�RASION, CORROSION, AN� SUNIJGHT; SUITABLE FOR CONTINUOUS IEIAPERATURE ENVIRONMENT „P TO 221 �EGREES F. 2 VIVYL WSULATING ELECTRICAL TAPE COMPLI1NG N7TH ASTM �3005 AN� LISiE� AS COMPLYING WITH UL 510; MINIMUM iHICKNESS OF 7 Mlb, RESISiANT TO ABRASION, CORROSION, AN� SUNLIGHT�, C�NFORMABLE FOR APPLICATION �OWN i0 � �EGREES F AND SUITABLE F�R CONTINUOUS iEMPERATURE ENVIRONI�ENi UP TO 221 DEGREES F. B, WIRE PULLING LUBRICANT�, L14E4 SUITABLE FOk USE WIiH iHE CONDUCTORS OR CABLES TO BE MSiALLED AND SUIiABLE PoR USE Ai iHE INSiALLAiION iEMPERAiURE. =nr i 2 cxccurioN 201 PREPARAiION A. GFAN RACEWAYS THOROUGHLY i0 REMOVE FORB6N MAiERIALS BEFORE INSiALLIN6 CONDUCiOR$ �ND CABLES. 2.02 INSiALLAiION A. CRCUIiING REQUIREMENTS: 1. ,.NLESS DIMENSIONE�, aRCUIT ROUTING INDICATE� IS �IAGRAMMAiIC. 2 COI�MON NEUiRAL4 UNLE55 OiHERWISE INDICAiED, SHARING OF NEUiRAL/GROUNDED CONDUCiORS AI�ONG UP TO 1HREE SYNGLE PHASE BRANCH CIRCUITS OF �IFFERENT PHASES NSTALLE� IN iHE SAME RACEWAY IS NOT PERMITiE�- PRONDE DE�IWIED NEUIRAL/GROUN�E� CONDUCiOR FOR EACH INDINDUAL BRANCH qRCUIi. '. NSTALL PRODUCTS IN ACCOR�ANCE WI1H MANUFACIURER'S INSIRUC➢ONS C. 'ERFORIA WORK IN ACCOR�ANCE WITH NECA 1(GENERAL WORKMANSHIP). 7. NSTALL I�ETAL-0LAD CABLE (TYPE I�C) IN A(xOR�ANCE WITH NECA 120. : NSTaunnoN w RacEwar. 1. -APE EN�S OF CONDUCTORS AN� CABLES TO PREVENT MFlLiRAlION OF MOISiURE AND OTHER CONTAMINANTS. 2'JLL ALL CONDUCTORS AN� CABLES TOGEIHER INTO RACEWAY Ai SAME ➢ME. RELEA5E0 FOR CONSTRIICTI�N Eo unNUFncTURER's eEcoMMENOEo unziMuu Su6jec��o compliance with allregula�ions of S�a�e antl Local Codes City of Carmel r �un��\i lo•rvalM��_ DATE: OH/ZO/2O SSARY, EXCEPT WHEN WBRICANT IS NOT F. IERMINATE CABLES USYNG SUIiABLE FliTINGS. 1. MEiAL-CLA� CABLE (i1PE MC): I i FliTIN . a. USE LS ED GS b. CUT CABLE ARMOR ONLY USING SPEQALIZE� iO�LS TO PREVENi DAMAGING CONDl1CTORS OR INSULATION. �0 NOT USE HACKSAW OR WIRE WTiERS TO CUi ARMOR. G. INSTAIL CONDUCTORS WIiH A MINIMOM OF 12 INCHES OF SLACK Ai EACH OUTLET. H. NEARY iRAIN AN� BUN�LE CON�UCTORS INSI�E BOXES, WIREWAYS, PANELBOAR�S AN� OTHER EOUIPMENT ENCLOSURES. I. GROUP OR OiHERWISE IDENTIFY NEU7RAL GROUNDED CONDUCTORS WITH ASSOQATED UNGROUNDED / CONDUCTORS INSIDE ENCLOSURES IN ACCORDANCE N7TH NFPA 70. J. MAKE WIRMG WNNECiIONS USING SPECIFlE� N7RING CONNECTORS. 1. MAKE SPIJCES AND iAPS ONLY IN ACCESSIBLE BOXES. DO NOT PULL SPIJCES INiO RACEWAYS OR MAKE SPLICES IN CONDUIT BO�IES OR WIRING GUTIERS. 2 REMOVE APPROPRIAIE AMOUNT OF CONDUCTOR INSULAiION FOR MAKMG CONNECiIONS N7IHOUT CUTIING, NICKING OR �AI�AGING CON�UCTORS. 3. �0 NOT REMOVE CON�UCTOR STRAN�S i0 FACILITATE WSERTION INTO CONNECTOR. 4. CLEAN CONTACT SURFACES ON CONDUCTORS AN� CONNECTORS ID SUITABLE REIAOVE CORROSION 0%I�ES, AND O1HEk CONTAMINATES. �0 NOT USE WIRE BRUSH ON PLATE� CONNECiOR SURFACES K. INSULATE SPLICES AN� TAPS 1HAi AftE MA�E WITH UNINSULAIE� CONNECTORS USING METHO�S SUITABLE FOR THE APPLICA➢ON, WI1H WSULATION AN� I�ECHANICAL SIRENGIH AT LEAST EOUIVALENT TO UNSPLICED CONDUCi0R5. L WSULATE ENDS OF SPARE C�N�UCT�RS USING VINYL INSULATING ELEGiRIGAL TAPE. M. WSTALL FIRESiOPPING TO PRESERVE FIRE RESISTANCE RAiING OF PAR➢➢ONS AND O1HER ELE1�ENi5, USING I�AiERIALS AND MEiHODS SPECIFlED IN SECiION 07B4_00- N. UNLE55 SPECIFlCALLY INDICAiED i0 BE EXCLUDED, PROVIDE FlNAL CONNECIIONS i0 ALL EOUIPMENi AND DEVICES,INCLUDING iHOSE FURNISHED BY OiHERS, AS REQUIRED FOR A COMPLEiE OPERAiINC SKiEM. SECiION 26.0526 GROUNDING AND BONDING PoR ELECiRICAL $YSiE1�$ PARi 1 PRODUCTS 1.01 GROUNDING AND BONDING RE�UIREMENiS A EXISiING WORK�. WHERE E%IS11NG GROONDING AND BON�ING SYSIEM1I COMP�NENTS ARE INDICAiE� TO BE REUSE�, 1HEY MAY BE REUSE� ONLY WHERE iHEY ARE FREE FROM WRROSION,INTECRITY AND CONiIN01TY ARE VERIFlE�, AN� WHERE ACCEPTABLE i0 iHE AUIHORITY HANNG JURISDIC110N. B. DO NOT USE PRODUCTS FOR APPLICAlI0N5 O1HER THAN AS PERMITIED BY NWA 70 AND PRO�UCi LISiWG. C. UNLESS SPECIFICALLY IN�ICAiE� i0 BE EXCLU�ED, PRON�E ALL REQUIRE� COMPONENTS, CON�UCTORS, CONNECTORS, WN�UIT, BO%E$ FlT➢NGS, SUPPORTS, AWESSORIE$ ETC. AS NECESSARY FOR A COMPLETE GROUNDMG AN� BON�ING SYSIEM. �. WHERE CON�UCTOR SIZE IS NOT IN�ICATE�, SIZE TO COMPLY WIiH NFPA 70 BUT NOT LESS THAN APPLICABLE MINII�UM SIZE REOUIREMENTS SPEGFIED. 1.02 GROUN�ING AND BON�ING WMPONENiS A GENEkAL REQUIkEMENiS�. L PROVIDE PRODUCTS LISiEq CLASSIFIEq AND LABELED AS SUITABLE FOR THE PURPOSE INIENDED. 2. PROVIDE PRODUCiS LISiED AND LABELED AS COMPLYING w1iH UL 467 WHERE APPLICABLE B. CONDUCTORS FOR GROUNDING AND BONDING, IN ADDIiION i0 REQUIREMENTS OF SECiION 26 0526�. 1. USE INSULAiED COPPER CONDUCi0R5 UNLE55 OiHERW15E INDICATED. a. EXCEPiIONS: 1) USE BARE COPPER CONDUCTORS wHERE WSTALLED UNDERGROUND IN DIRECT WNiACi WI1H EARiH, 2) USE BARE C�PPER CON�UCTORS WHERE DIRECILY ENCASE� IN CONCREIE (NOT IN RACEWAI�. G CONNECTORS FOR GROUNDING AND BONDING. 1. DESGRIP110N�. CONNECiORS APPROPRIAIE FOR THE APPLICA➢ON AND SUITABLE FOR 1HE CONDUCTORS AND ITEMS i0 BE CONNECiED; LISIED AND LABELED AS COMPLYING wI1H UL 467. 2, UNLESS OiHERWISE INDIGAIE�, USE E%OiHERA1IC WELDED CONNEGilONS FOR UNDERGROUN�, CONCEALE� AND OiHER INAC�SSIBLE CONNECilONS. 3. UNLE55 OiHERWI$E INDICAiED, USE MECHANICAL CONNECi0R5, COI�PRESSION CONNECi0R5, OR EXOiHERMIC WELDED CONNECilONS PoR ACCESSIBLE CONNECiIONi PARi 2 EXECUTION 201 INSTALLATION A WSiALL PRODUCi$ IN ACCORDANCE WIiH MANUFACiURER'S WSiRUCilONS. B. PERFORM WORK IN ACCORDANCE WIiH NECA 1(GENERAL WORKMANSHIP). C. MAKE GROUNDING AN� BON�ING CONNECPONS USING SPECIFIEO fANNECTORS 1. REMOVE APPftOPRIAIE AMOUNi OF CON�UCTOR INSULAiION FOR MAKING CONNEC➢ONS WIIHOUT CUi11NG, NICKING OR DAMAGING CONDUCTORS. DO NOi REMOVE CONDUCTOR SiRANDS TO FACILITATE WSERiIpN INiO CONNECTOR- 2. REMOVE NONCON�UCiIVE PAINi, ENAMEL, OR $IMILAR COAiING Ai iHREADS, CONiACi POINiS, AND CONiACi SURFACES J. EXOiHERMIC WELD4 MAKE CANNECilONS USING �IOLD$ AND WELD MAiERIAL SUIiABLE FOR iHE IiEMS TO BE CONNECiED IN ACCORDANCE wI1H MANUFACiURER'S RECOMMENDAiIONS 4. MECHANICAL CONNECTORS�. SECURE CONNECilONS ACCOR�ING TO MANUFACiURER'S RECOMMEN�E� iORQUE SET11NG5. 5. COMPRESSION CONNECTORS: SEWRE CONNECTIONS USING �IANUFACTURER'S RECOI�MEN�ED SECiION 26.0529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSiEI�S anel i aeooucrs 1.01 SUPPORT AND ATTACHI�ENT COI�PONENTS A GENERAL REQUIREMENTS�. 1. PROVI�E ALL REQUIRE� HANGERS, SUPPORTS, ANCHOR$ FASTENER$ FlTfINGS ACCESSORIES, AND HARDWARE AS NECESSARY FOR iHE COMPLEIE WSTALLATION OF ELECIRICAL WORK. 2 PkOVI�E PRODUCTS LIS7ED, CLASSIFlE�, AND LABFIED AS SUITABIE FOR THE PUftPQSE INIEN�ED, WHERE APPLICABLE. 3. WHEftE SUPPORT AND ATTACHMENT COI�PONENT TYPES AN� SIZES ARE NOT INDICAIED, SELECT IN ACCORDANCE WITH I�ANUFACTURER'S APPLICATION CRITERIA AS REQUIRED PoR THE LOAD TO BE SUPPORTE�.INCLU�E CONSI�ERAiION FOR VIBRATION, EQUIPMENi OPERATION, AN� SHOCK LOA�S WHERE APPLICABLE. 4. �0 NOT USE PRO�UCTS FOR APPLICA➢ONS O1HER THAN AS PERI�ITIE� BY NFPA 70 AN� Peooucr usnNc. B. CONDUIi AND CABLE SUPPORTS�. S1RAP$ CLAMPS, ETG SUITABLE FOR 1HE CON�UIT �R CABLE TO BE SUPPORIE�. 1. CON�UIi S1RAP5: ONE-HOLE OR TWO-H�LE iYPE; S1EEL OR MALLEABLE IRON. 2. CONDUIi CLAI�PS- BOLiED iYPE UNLE55 OTHERWISE INDICAiED- C. OUiLET BOX SUPPORT4 HANGERS, BRACKEiS, ETC. SUIiABLE FOR iHE BOXES i0 BE SUPPORiED. D. HANGER ROD4 iHREA�ED ZINC-PLAiED $iEEL UNLES$ OiHERW6E INDICAiEO. 1. MINIMIUM 9ZE, UNLESS OTHERWISE INDICAiE� OR REOUIRE�: a EQUIPMENi SUPPORT4 1/2 INCH DIAMEiER b. SINGLE CONDUIT UP i0 1 INCH (27 M�I) 1RA�E SIZE: 1�4 INCH DIAIAEIEft. c. SYNGLE CONDUIT LARGER 1HAN 1 INCH (27 MM) TRA�E SIZE: 3�8 INCH DIAMEIER. d. OUiLEi BO%E5: 1/4 INCH DIAMETER. e. LUI�INAIRE4 1/4INCH DIAMEiER E. ANCHOR$ AND FASiENERS'. 1. UNLE55 OiHERW15E INDICAiED AND WHERE NOi OiHERW15E RESTRICiED, uSE iHE ANCHOR AND FASiENER iYPES INDICAiED PoR iHE SPECIFlED APPLICAilONS. 2 HOLLOW MASONRY�. 11SE TOGGLE BOLiS. b. HOLLOW SiU� WALLS�. 11SE TOGGIE BOLiS. 4. SiEEb. USE 6EAM CLAMPS, MACHWE BOLTS, OR WELDED 1HREADED STO�S. 5. SHEET METAL�. USE SHEEi I�ETAL SCREWS. PART 2 EXECUTION zoi wsruunoe A INSTALL PRODUCTS IN ACIX7RDANCE WIiH MANUFACTURER'S INSTRl1CilONS. B. PERFORM WORK IN ACCORDANCE WIiH NECA 1(GENERAL WORKMANSHIPJ_ C. PROVIDE INDEPENDENi SUPPORi FR01� BUILDING SiRUCiURE DO NOi PROVIDE SUPPORi FROM PIPING, DUCiWORK, OR OiHER $YSiEMS. D. UNLE55 SPECIFlCALLYINDICAiED OR APPROVED BY ARCHIiECi, DO NOi PROVIDE SUPPORi FROM SUSPENDED CEIIJNG SUPPORT SYSiEI� OR CEIIJNG GRI�. E. 11NLESS SPECIFlCALLY INDICAiEO OR APPROVEO BY ARCHIiECT, DO NOi PROVIDE SUPPORT FROM ROOF DECK. F. DO NOT PENEiRAIE OR OiHERWISE NOTCH OR CUT SiRUCiURAL MEMBERS WITHOUT APPROVAL OF SiRUCiURAL ENGWEER. G. EOUIPMENT SUPPORT AND ATTACHI�ENT: 1. USE MEiAL FABRICAIED SUPPORTS OR SUPPORTS ASSEMBLED FROM MEiAL CHANNEL (S1RUT) TO SUPPORT EQUIPMENT AS REQUIRED. 2. USE MEiAL CHANNEL (SiRUi) SECURED i0 STUDS TO SUPPORi EQUIPI�ENi SURFACE-MOUNTED ON HOLLOW $iUD WALL$ WHEN WALL $iRENGiH I$ NOi $UFFlGENi i0 RESIST PULL-OUi. A USE MEiAL CHANNEL (SiRUi) i0 SUPPORT SURFACE-MOUNiED EQUIPMENi W WEi OR DAMP LOCAl10N5 i0 PROVIDE SPACE BEiWEEN EQUIPIAENi AND MOUNiING SURFACE 4. $ECURELY FASiEN FLOOR-MOUMED EQUIPNENi. DO NOi MSiALL EQUIPMENi $UCH THAiIi RELIES ON Ii5 OWN WEIGHi FOR $UPPORi. H. SECURE FASIENERS ACCOR�ING i0 MANUFACTURER'S RECOMMENDE� iORQUE SET➢NGS L REMOVE iEMPORARY SUPPORiS SECTION 26.OS.,x3.13 WN�UIT PoR ELECTRICAL SYSIEMS PARi 1 PRO�UCTS 1.01 WN�UIT APPLICATIONS A. �0 NOi USE CONDUIT AN� ASSWIAIED FITfINGS FOR APPLICATIONS OTHER THAN AS PERIAITIED BY NFPA 70 AN� PRO�UCT LISTING. B. UNLESS OTHERPoSE W�ICATE� AN� WHERE NOT OTHERN75E kESTRICiED USE 1HE CON�UIT T1PES INDICAIED FOR WE SPEQFIE� APPLICATIONS. WHERE MORE 1HAN ONE LISTED APPLICAiION APPLIES, COMPLY WITH THE MOST RESTRICiIVE REQUIREMENiS. WHERE CONDUIT T1PE FOR A PARIICULAR APPLICAiION IS NOT SPECIFIE�, USE GALVANIZED S1EEL RIGID MEiAL CONDUIT. G CONCEALED WIiHIN M1IASONRY WALL4 USE GALVANIZED SiEEL RIGD MEiAL CONDUIi, INTERMEDIAIE MEiAL CON�UIT QMC), Ok ELECTkICAL MEiALLIC iUBING (EMT). �. CONCEALED WIiHIN HOLLOW STU� WALLS USE GALVANIZE� S1EEL RIGID MEiAL CONDUIi, INTERME�IAIE METAL CONDUIT QIAC), OR ELECTRICAL METALLIC IDBING (EMT). E WNCEALE� ABOVE ACCESSIBLE CEILINGS: USE GALVANIZE� S1EEL RIGI� METAL CON�UIT, INTERME�IAIE MEiAL CONDUIT QMC), OR ELECTRICAL MEiAWC iUBING (EMT). F. INTERIOR, �AI�P OR WET LOCAiIONS: USE CALVANIZE� SiEEL RIGID METAL CON�UIT. Q E%PQSE�,INTEkIOk, NOT SUBJECT i0 PHYSICAL �AMAGP. USE GALVANIZED STEEL RIGI� MEiAL IX7NDOIT,INiERMEDIAIE METAL CbN�UIT QMC), OR ELEOIRIOAL METALLIC TUBIN6 (EMT). R E%POSED,INTERIOR, SUBJECT TO PHYSYCAL DAMAGE: USE GALVAMZED SiEEL RIGID METAL CONDUIi OR IMERI�EDIAiE I�EiAL CONDUIi QI�C). L LOCAilONS Sl1BJECi i0 PHYSICAL DAM1IAGE INCLU�E, BUT ARE NOi LIM1IIiE� i0: a. wHERE E%POSED BELOW 8 FEEi. EXCEPi W1THW ELECiRICAL AND COI�MUNICAiION ROOMS OR aos�rs. b. WHERE ENPOSED BELOW 20 FEEiIN WAREHOUSE AREAS. L E%POSEq E%lERIOR�. USE GALVANRED STEEL RIGI� I�ETAL CI�NDUIT, WIERMEDIAiE METAL Q9NDWT QMC), OR PVC-COAiE� GALVANIZED STEEL RIGI� �IEiAL CONDWT. J_ CONNECiIONS TO VIBRAiING EQUIPMENL I. �RY LOCAlI0N5: OSE FLEXIBLE METAL CON�UIT. 2. DAMP, WEi, OR Q�RROSYVE LOCAlI0N5: USE LIQUID11GHi FLENIBLE M1IETAL CON�UIT. 3. MAYJM01� LENGRI: 6 FEET UNLESS O7HERWISE IN�ICAIED. 4. VIBRAiING EOUIPMENT INCWDES, BUT IS NOi LIMIIED T0: a. MOTORS. K FlSHED M E%ISTING WALLS, WHERE NECESSARN. USE FLE%IBLE METAL CONDUIT. 1.02 WN�UIT REQUIREMENTS A E%IS➢NG WORN: WHERE EXISTING CON�UIiS ARE INDICATE� TO BE REUSED, THEY MAY BE REUSED ONLY WHERE THEY COI�PLY WIiH SPEQFIED REOUIREMENTS, ARE FREE FROM CORROSION, AN� WIEGRITY IS VERIFlE� BY PULLING A MANDREL iHftOUGH 1HEM. B. PROVI�E ALL CONDUIi, FIiTING$ SUPPORT$ AND ACCESSORIES ftEQUIRE� FOR A COI�PLETE RAGEWAY SYSiEM. G PROVIDE PRODUCiS LISTED, CLASSIFlED, AND UBELED AS SUIiABLE FOR iHE PURPOSE INTENDEO. D- WHERE CONDUIi SIZE IS NOiINDICAiED, SRE i0 COMPLY WITH NFPA 70 BUi NOT LE55 iHAN APPLICABLE MINIM1IUN SIZE REQUIREMENi$ SPECIFlED- 1_03 GALVANIZED STEEL RIGID MEiAL CONDUIi (RMG) A. �ESCRIPTION' NFPA 70, TYPE RMC GALVANRED SiEEL RIGI� IAETAL CON�UIT COMPLI1NG WI1H ANSI C801 AND LISiED AND LABELED AS COMPLYING w11H UL 6- B- FliTING4 L NON-HAZARDOUS LOCAilON4 USE FliiINGS COMPLnNG w1TH NEMA FB 1 AND LISiED AND LABELED AS COMPLYING WIiH UL 514B. 2. MAiERIAL' 115E SiEEL OR MALLEABLE IRON. 3. CONNECiOR$ AND COUPLINGS'. USE iHREADED iWE FliiINGS ONLY. iHREADLE55 SEi $CREW AND COI�PftESSION (GLAN�) T1PE FITiINGS ARE NOT PERMITiE�. 1_04 INTERME�IAIE METAL CON�UIT QMC) A. �ESCRIPTION: NFPA 70, TYPE IMC GALVANIZE� S1EEL INTERME�IATE METAL CON�UIT COMPLYING WI1H ANSI CBO-6 AND LISTED AND LABELED AS COMPLYING WITH UL 1242. B. FIiTINGS' L NON-HAZARDOUS LOCAl10N4 USE FIT11NG5 C01APLnNG wITH NEMA FB 1 AND LISiED AND LABELEO AS WMPLYING WIiH UL 514B. 2. MAiERIAL: USE $iEEL OR MALLEABLE IRON. 3. CONNECiOR$ AND COUPLINGS: USE iHREADED imE FIiiING$ ONLY. iHREADLE$5 $Ei SCREW AND COAIPRESSION (GLAN�) T1PE FlTiINGS ARE NOT PERMITiE�. 1.05 PVC-COAiE� GALVANRED STEEL RIGID I�ETAL CON�UIT (RMC) A. �ESCRIPTION: NFPA 70, TYPE RMC GALVANRED SiEEL RIGI� METAL CON�UIT WIiH EXiERNAL PoLYVINYL CHLORI�E (PVC) COAiMG COMPLYING WIiH NEMA RN 1 AN� IJSiE� AN� LABELED AS WMPLI1NG WITH UL 6. B. E%lERIOR COATING: PoLYVINYL CHLORI�E (PVC), NOI�INAL THICKNESS OF 40 MIL. C. PVC-COAiED FIiiINGS'. 1. MANUFACIDRER: SAIAE AS MANUFACIDRER OF PVC-COAiE� G�N�UIT TO BE INSTALLE�. 2. NON-HAZAR�OUS LOCA➢ONS: USE FlTIINGS IJSiE� AND LABELE� AS COMPLYING WIiH UL 5148. 3. MAIERIAL USE STEEL OR MALLEABLE IRON. 4. E%lERIOR COATING: PoLYVINYL CHLORIDE (PVC), MINIMUM THIG(NESS OF 40 MIL. D- PVC-COAiED SUPPORi4 FURNISH WIiH E%iERIOR COAiING OF POLYVINYL CHLORIDE (PVC), MINI�U� iHICKNES$ OF 15 MIL. L06 FLERIBLE METAL CON�UIT (FMC) A, DESCRIPiION- NFPA 70, iYPE FMC SiAN�ARD WALL SiEEL FLEXIBIE METAL CONDUIi IJSiED AND LABELED AS COMPLnNG wliH UL I, AND LISIED PoR USE W CLASSIFlED FlRESiOP SYSiEMS i0 BE USED. B. FIiTINGS: 1. DESCRIPTION: FlTiINGS COMPLYING WI1H NE1�A FB 1 AND LISTED AND LABELED AS COMPLYING WIiH 11L 514B. 2. MAIERIAL: USE STEEL OR MALLEABLE IRON. 1_07 LIOUI�TIGHi RE%IBLE MEiAL CONDUIi (LFMC) A. �ESCRIPTION' NFPA 70, TYPE LFN,C POLYNNYL CHLORIDE (PVC) JACKEIE� STEEL FLEYJBLE MEiAL CONDUIi LISIED AND LABELED AS COMPLYING Wlhl UL }60. B- FIiTING4 L DESCRIPiION_ FlTiINGS COMPLYING w1iH NE1�A FB 1 AND LISiED AND LABELED A$ CAMPLnNG Wlhl UL 514B. 2. MAiERIAL: USE $iEEL OR MALLEABLE IRON. 1.08 ELECIRICAL I�ETALLIC TUBING (EMi) A. �ESCRIPTION_ NFPA 70, TYPE EMT STEEL ELECiRICAL METALLIC TUBING COMPLnNG WIiH ANSI C80.3 AND LIAE� AND LABELE� AS COMPLYING WIiH UL 79Z 8. FliiINGS: 1. DESCRIPTION: FlTiINGS COMPLYING w11H NE1�A FB 1 AND LISTED AND LABELE� AS COIAPLnNG WIiH UL 514B. 2. MAiERIAL: USE $iEEL OR MALLEABLE IRON. 3. CONNEGiOkS AND COUPLINGS USE COMPRESSION (GLAN�) OR SET-SCREW i1PE a. DO NOi USE INDEMER iYPE CONNECiOR$ AND COUPLINGS. 4. �AMP OR WET LOCA➢ONS (WHERE PERMIT7E�)'. USE FIiTINGS LISiE� FOR USE IN WET LOCATIONS. L09 ACCESSORIES A. CONDUIT JOINi COMPOUN�- CORROSION-RESISTANT, ELECTRICALLY CONDUCTIVE; SUIiABLE FOR USE WITH THE C�N�UIT TO BE INSTALLE�, B- PULL $iRINGS: USE NriON CORD wI1H AVERAGE BREAKING SiRENGhI OF NOT LE$$ iHAN 200 POUN�-PoRCE, C. SEALING COM1IPOUND PoR $EALING FlTiINGS: LISiED PoR USE WIiH iHE PARiIG1LAR FIiiINGS i0 BE INSTALLED. PARi 2 E%ECOiION 2.01 INSiALLAiION A. WSiALL PRODUCi$ IN ACCORDANCE W1iH MANUFACiURER�$ INSiRUCiIONS B. PERFOR�I WORK IN ACCORDANCE W11H NECA 1(GENERAL WORKMANSHIP). C. INSTALL GALVANIZED STEEL RIGI� METAL CON�UIT (RMC) IN ACCORDANCE WITH NECA 101. �. INSiALL INTERME�IATE MEiAL CON�UIi (IMC) IN ACCORDANCE WITH NECA 101. E INSiALL PVC-COAiED GALVANRED $iEEL RIGID MEiAL CONDUIT (RMC) USING ONLY i00L$ APPROVED BY iHE MANUFACTURER. F. CONDUIi SUPPORT�. 1. SECURE AND SUPPORi CONDUITS IN ACCORDANCE W11H NWA 70 AND SECTION 26.0529 USING SUIiABLE SUPPORiS AND METHODS APPROVED BY iHE AUiHORITY HAVING JURISDIC➢ON. 2 PROVIDE INDEPEN�ENi SUPPORT FROM BUIL�ING SiRUCiURE. �0 NOi PROVIDE SUPPORT FROM PIPING, DUCTWORK, OR ORIER SYSIEMS. G. WNNECiIONS AN� TERMINATIONS: 1. USE APPROVE� ZMFRICH PAINi OR CONDUIT JOINT COI�POUN� ON FIEL�CUT iHREA�S OF GALVANIZE� STEEL CON�UITS PRIOR TO MAKING CONNECTIONS. 2 WHERE TWO 7HREA�ED CON�UITS �IUST BE JOINE� AND NEIIHER CAN BE ROiAIE�, USE THREE-PIECE WUPLINGS OR SPLIi WUPLINGS. �0 NOi USE RUNNING iHREA�S. 3. USE SUITABLE ADAPTERS WHERE ftEQUIRED TO TRANSI➢ON FROM ONE T1PE OF CONDUIi TO ANOiHER. 4. PROVI�E DftIP LOOPS FOR LIpUIDTIGHi FLFXIBLE CONDUIi CONNEC➢�NS TO PREVENi �RAINAGE OF LIpUID INTO WNNECiORS 5. TERMINAiE THREADED CONDUTA IN BO%ES AN� ENCLOSURES USING iHREADED HUBS OR DOUBLE LOCK NUiS FOR DRY LOCAilONS AND RAINTIGHi HUBS PoR WEi LOCAilONS. 6. PROVIDE INSULAiING BUSHINGS OR INS1LAiED iHR0Ai5 Ai ALL CONDUIi iERMINAilONS i0 PROiECi CONDUCiORS. 7. $ECURE JOINiS AND CONNECTIONS i0 PROVIDE MA%IMUM MECHANICAL SiRENGiH AND ELECIRICAL CANiINl11iV. H. PENETRATIONS'. I. �0 NOi PENETRATE OR OIHERWISE NOiCH OR Wi S1RUCIVRAL MEMBERS,INCWDINC FOOIINGS AN� GRME BEAMS N7IHOUT APPROVAL OF STRUCTURAL ENCWEER. 2 I�AKE PENE1RAlI0N5 PERPEN�ICULAR i0 SURFACES UNLESS OiHERWISE IN�ICAIED. 3. PROVIDE SLEEVES FOR PENETRATIONS AS INDICATE� OR AS RE UIRE� TO FAQLITATE 0 INSTALLAPON. SET SLEEVES FWSH N7TH EkPOSE� SURFACES UNLE55 OIHERWISE IN�ICAIE� OR REQUIRED. 4. WNCEAL BEN�S FOR WN�UIT kISEkS EIAERGING ABOVE GROUND. 5. SEAL INiERIOR OF CON�UITS ENTERING 1HE BWL�ING FROM UNDERGROUN� AT FIRSi ACCESSIBLE POINT TO PREVENT ENiRY OF MOISIURE AND GASES. 6. WHERE CONDUITS PENE1RAlE WAiERPRO�F MEI�BRANE, SEAL AS RE�UIRED TO MAINiAIN INTEGRITY OF MEMIBRANE. 2 NAKE PENEiRAilONS PoR ROOF-MOUMED EQUIPMENi WIiHIN ASSOCIATED EQUIPMENi OPENINGS AND CURBS WHERE POSSIBLE TO MINII�IZE ROOFlNG SYSiEM PENEIRATIONS, WHERE PENEiRAilONS ARE NECESSARY, SEAL AS INDICAiED OR AS REOUIRED i0 PRESERVE IMEGRITY OF ROOFlNG SYSiE�I AND MAINiNN ROOF WARRANtt.INCLUDE PROPOSED LOCAilONS OF PENEiRAilONS AN� MEiH00S FOR SEALMG WITH SOBMITiALS. 8. INSiALL FlRESiOPPINC TO PRESERVE FlRE RESISTANCE RAiING OF PARTIilONS AND OiHER ELEMENiS, USING MAIERIALS AN� MEiH�DS SPECIFlED IN SEC110N 07.84.00. L WNDUIT MOVEMENT PRONSIONS WHERE CON�UITS ARE SUBJECi TO I�O�EMENi, PRONDE E%PANSION AND E%PANSION/DERECiION FliiING$ i0 PREVENi DAMAGE i0 ENCLOSED CONDl1Ci0RS OR CONNECTED EOUIPMENT. THIS MCWDES, BUT IS NOT LII�ITED T0: I. WHERE CbNDUITS CROSS SiRUCiURAL JOINTS IMENDED PoR E%PANSION, CONiRACiION, OR oEF�EcnoN. 2. WHERE IX7N�UITS ARE SUBJECT i0 EARTH I�OVEMENi BY SETfLEMENT OR FROST. J. CON�ENSAiION PREVEN110N�. WHERE G�N�UITS CROSS BARRIERS BEiWEEN AREAS OF POTENiIAL SUBSTANTIAL iEMPERAIDRE �IFFERENiIAL, PROVI�E SEALMG FliiING OR APPRWED SEALING COMPOUN� AT AN ACCESSIBLE POINT NEAR WE PENE1RAlI0N TO PREVENT CON�ENSATION. RIIS INCW�ES, BUT IS NOT IJI�ITE� T0: L WHERE WN�UITS PASS FROM OUIDOORS INTO CON�IiIONED INiERIOR SPACES. 2 WHERE WN�UITS PASS FROM UNCON�ITIONE� INTERIOR SPACES INiO CONDI110NE� WIEWOR SPACES. SECiION 26.05.33.16 BOXES FOR ELECiRICAL SYSiEMS PART 1 PRODOCTS 1.�7 BO%ES A. GENERAL REQUIREMENTS: I. �0 NOi USE BOXES AN� ASSOaATED A(xES50RIES FOR APPIJCAlI0N5 OiHER THAN AS PERI�ITIE� BY NFPA 70 AN� PRODUCT LIS➢NG. 2 PROVIDE ALL BOXE$ FlT➢NGS, SUPPORiS, AN� ACCESSORIES REQUIRE� FOR A COMPLETE RACEWAY SYSIEM AN� TO ACCOMMO�ATE �EVICES AN� EOUIPMENT TO BE INSTALLE�. 3. PROVIDE PRO�UCTS LISTE�, CLASSIFlE�, AN� LABELE� AS SUITABLE FOR THE PURPOSE INTEN�ED. 4. WHERE BOX SIZE IS NOT W�ICAIE�, SIZE TO COMPLY WI1H NFPA ]0 BUT NOT LESS THAN APPLICABLE MINIMUI� SIZE REQUIREMENTS SPECIFIED. 5. PROVI�E GROUNDING IERMINALS WIIHIN BOXES WHERE EpUIPMENT GROUN�ING CON�UCTORS iERMINAiE. B. OUTLET AND DEVICE BO%ES UP i0 100 CUBIC INGHES, INCLU�ING THOSE USE� AS JUNCiION AND PULL BOxES: I. USE SHEEi-SiEEL BOxES FOR DRY LOCAl10N5 UNLE55 OiHERW6E INDICAiED OR REOUIRE�. 2 USE CASiIRON BOkES OR CASi ALUMINUM BOXES FOR DAMP OR WET LOCAilONS UNLESS OiHERW15E INDICATED OR REQUIRED; FURNISH WIiH COMPAiIBLE WEAiHERPR00F GASKEiED COVERS. 3. USE SWiABLE MAS�NRY TYPE BOXES WHERE FWSH-MOUNTED IN MASONRY WALLS. 4. SHEEi-S1EEL BO%ES: COMPLY WI1H NEI�A OS I, AN� LISi AN� LABEL AS COMPLYING WIiH UL 514A. S CAST METAL BOXES�. CO�IPLY WITH NEMA FB 1, AND LIST AN� LABEL AS COIAPLYING N7TH UL 514A�, FURNISH WIiH iHREMED HUBS. 6. BORES FOR SUPPORPNG WMINAIRES AN� CEIIJNG FANS: IJSTE� AS SUITABIE FOR THE TYPE AN� WEIGHT OF LOAD i0 BE SUPPORTE�; FURNISHE� WI1H FIXIURE S1V� TO ACCOMMO�ATE MOUN➢NG OF WMINAIRE WHERE REQUIRE�. 7. BOHES FOR GANGE� �EVICES: USE MULPGANG BOXES OF SINGLE-PIECE CONS7RUCPON. �0 NOT USE FIELD-CONNECIED GANGABLE BOXES UNLE55 SPEC7FICALLY IN�ICATED OR PERMITIED. G CABWETS AND ENCLOSURES,INCW�ING JUNCTION AND PULL BO%ES LARGER iHAN 100 CUBIC MCHES: L COMPLY WI1H NEMA 250, AND LIST AND LABEL AS COMPLYING WITH UL 50 AN� UL S�E, OR UL 508A. 2. NEMA 250 ENVIRONMENi T1PE, UNLE55 O1HERw15E INDICATED: 3- JUNCiION AND PULL BO%E$ LARGER iHAN 100 CUBIC MCHES: o. PROVIDE SCREW-COVER OR HINGED-COVER ENCLOSURES UNLES$ OiHERWI$E INDICATED. PART 2 E%ECl1ilON 2.01 INSiALLniION A_ MSiALL PRODUCiS IN ACCOR�ANCE wI1H MANUFACiURER'S INSiRUC1lONS B. INSTALL BO%ES IN ACWk�ANCE WIiH NECA 1(GENERAL WOkKMANSHIP) AND, WHERE APPLICABLE, NECA 130, INCW�ING MOUN➢NG HEIGHTS SPECIFIE� IN THOSE STANDAR�S WHERE I��UNIING HEIGHTS ARE NOiINDICATED. C. AkkANGE EQVIPMENT TO PkOVI�E �IINIMUTA CLEAkANCES IN ACCOR�ANCE WIiH MANUFACiURER'S INSIRUC➢ONS AN� NWA 70. �. BOX SUPPOftiS: L SECURE AN� SUPPORT BOXES IN ACCORDANGE W11H NFPA 70 AN� SECTION 26 0529 USING SUITABLE SUPPOkiS AND METHODS APPkOVE� BY iHE AUiH�RIiY HAVING JURIS�IC➢ON. 2 PROVI�E INDEPEN�ENT SUPPORT FROM BWLDING SIRUCIDRE ERCEPT FOR CASi METAL BO%ES (ORIER 1HAN BO%ES USE� FOR FIXIURE SUPPORi) SUPPORiED BY THREA�ED CONDUIi WNNECPONS IN ACCOR�ANCE WI7H NFPA 70. �0 NOT PROVIDE SUPPORT FROM PIPING, DUGIWORK, OR OTHER SYSTEMS. E. INSTALL BOXES PWMB AND LEVEL. F. FLUSH-MOUNTED BO%ES�. L INSTALL BOXES IN NONCOMBUSIIBLE I�ATERIALS SUCH AS CONCRETE, TILE, GIPSUM, PLASiER, EiG SO iHAi FRONi EDGE OF BOx OR ASSOCIATED RAISED WVER IS NOi SET BACK FROM FINISHE� SURFACE MORE iHAN 1/4 MCH OR DOES NOT PROJECi BEYOND FINISHED SURFACE. 2 INSTALL BOXES IN COI�BUSiIBLE MAIERIALS SUCH AS WOOD 50 THAT FRONT EDGE OF BO% OR ASSOCIAIED RNSE� WVEk IS FLUSH WI1H FINISHED SURFACE. 3- REPAIR ROUGH OPENINGS AROUN� BOXES IN NONGOMBUSTIBLE MAiERIALS SUCH AS CONCRETE, iRE, GIPSUM1I, PLASiER, EiC. 50 THAi iHERE ARE NO GAPS OR OPEN SPACES GREAItIt I-AN 1/8 INCH AT 1HE E�GE OF 1HE BO%. G. INSTALL BO%ES AS REQUIRE� TO PRESERVE INSULATION INIEGRITY. H. INSTALL FIRESTOPPING TO PRESERVE FIRE RESISTANCE ftAIING OF PARTITIONS AND OTHER ELEMENiS, USING MAIERIALS AND MEIHODS SPECIFIED IN SEC110N 07.84.00. I. CLOSE UNUSED BOX OPENINGS d MSiALL BLANK WALL PLAiES ON JUNCiION BOxES AND ON OUTLEi BOxES WnH No ]-VIC}5 oH EQUIPMENi WSiALLED OR DESIGNAIED PoR FUTURE USE. K. PROVIDE GROUNOING AND BONDING IN ACCORDANCE wliH SECiION 26_05.76. SECTION 2fi.05.53 I�ENTIFlCATION FOR ELEC7RICAL SYSTEMS PART 2 PRO�UCTS L01 IDENTIFlCA➢ON RE UIREI�ENTS Q A. IDENTIFICAlION FOR EQUIP�IENT: 1. USE I�ENiIFICAlION NAMEPLAIE TO I�ENTIFY EACH PIECE OF E_ECTRICAL �ISIRIBUTION AN� CONTkOL E UIPMENT AN� ASSOQATE� SEC➢ONS COMPAftiMENTS AN� COMPONENTS. Q a. PANELBOAR�S�. 1) I�ENTIFY POWER SOURCE AN� CIRCUIT NUMBER. INCLU�E LOCATION WHEN NOT WIIHIN SICHT OF EQUIPMENT. 2) USE iYPEWRIiTEN CIRCUIi DIRECTORY TO I�EN➢FY LOAD(S) SERVED FOR PANELBOARDS N7TH A DOOR. I�ENIIFY SPARES AN� SPACES USING PENCIL. b. ENCLOSE� SWITCHES, CIRCUIT BREANERS, AND MOiOR CONiROLLERS: 1) IDENTIFY POWER SOURCE AND CIRCUIT NUMBER.INCLUDE LOCATION WHEN NOT WIIHIN SYGHT OF EQOIPMENi. B. IDENTIFlCAlION PoR CON�UCTORS AN� CABLES: 1. WLOR CO�ING PoR POWER CON�UCTORS fi00 V AND LESS�. COI�PLY WIiH SECTION 26.05.19. 2. USE I�EN➢FlCAlION NAMEPLAIE OR I�ENTIFlCAlION LABEL TO IDENTIFY COLOR CO�E FOR UNGROUN�E� AN� GROUNDED POWER CONDUCTORS INSI�E DOOR OR ENCLOSURE Ai EACH PIECE OF FEE�ER OR BRANCH-CIRCUIT �ISTRIBUiION EQUIPMENT WHEN PREMISES HAS FEEDERS Oft BRANCH CIRCUITS SERVE� BY IAORE 7HAN ONE NO�IINAL VOLTAGE SYSIEM. L02 IDENTIFICA➢ON NAMEPLAIES AN� LABELS A. IDENTIFICA➢ON NAMEPLAlES: 1. MATERIALS�. a INDOOR CLEAN, �RY LOCATIONS�. USE PLAS➢C NAMEPLAIES b. OUTDOOR LOCAiIONS USE PLASTIQ STAINLE55 STEEL, OR ALUI�INUM NAMEPLATES SUITABLE FOR E%TERIOR USE 2 PLASiIC NAI�EPLAiE4 iW0-LAYER OR THREE-LAIER LAMINAIED ACRYLIC OR ELECiRICALLY NON-CON�UC➢VE PHENOLIC WIiH BEVELE� E�GES�, MINIMUM THICKNESS OF 1/16 INCH; ENGRAVED lE%T. 3. STAWLESS S1EEL NAMEPLATES�. MINIMUM 7HICNNESS OF 1�32 INCH�, ENGRAVED Ok LASER-ETCHE� TEXT 4. MOUN➢NG HOLES FOR AIECHANICAL FASIENERS�. TWO, CEN7ERED ON SI�ES FOR SIZES UP TO 1 INCH HIGH; FOUR, LOCAIE� AT CORNERS FOR LARGER SIZES. B IDENTIFICAPON LABELS�. '- MATEkIALS USE SELF-A�HESIVE LAI�INAIED PLAS➢C LABELS�, UV, CHEMICAL, WATEk, HEAT, AN� A9RASON kF515iANT. 2. iEXi�. USE F1Ci09Y PRE-PRWIED OR I�ACHME-PRINTE� TEXi. ;0 NCT USE HdNDWR T EN IhXI ..N1-S5 OIHhHWI$E INDICAiED- ' CS vInRN NG SIGNS nno LABELS 4. C�InVLY WI-H nNsl C5352 OR ANSI Z535.4 AS APPLICABIt_ H. WFHN NG 516NS: '_ M�TERNLS�. a. INDOOR DRY, CLEAN LOCATIONS; USE FACiORY PRE-PR NiED RIGD PLASiIC OR SELF-A7HESVE VINYL SYGNS. b. OUTDOOR LOCAilONS: USE FACTORY PRE-PRWIED RIGI� AWMINUM SIGNS. 2. RICI� SIGNS: PROVI�E FOUR MOUNTING HOLES AT CORNERS PoR MECHANICAL FASTENERS. 3. MINIMUM SYZP. 7 BY 10 INCHES UNLESS OIHERWISE IN�ICATE�. C. WARNMG LABELS: 1. MATERIALS�. USE FACTORY PRE-PRINTE� OR I�ACHINE-PRINTE� SELF-ADHESIVE POLYESiER Oft SELF-A�HESNE VINYL LABELS; UV, CHEMICAL, WAiER, HEAi, AN� ABRASION RESISTANT; PRODUCE� USING MAIEftIALS RECOGNIZE� TO UL 969. 2 MACHINE-PRINTED LABELS�. USE iHERMAL 1RANSFER PROCESS PRINTING MACHWES AN� ACCESSORIES RECOMMENDED BY LABEL MANUFACiURER. 3. MINIMUM SIZE: 2 BY 4 INCHES UNLE55 OIHERNISE IN�ICATED. PART 2 E%ECU➢�N 201 INSiALLAiION A. WSTALL PRO�UCTS IN ACCOR�ANCE WITH MANUFACiURER'S INSIRUC➢ONS. B. INSiALL IDENiIFICA➢ON PRODUCTS TO BE PLAWLY NSIBLE FOR EXAIAINATION, ADJUSiM=NT, SERNCING, AN� MAINiENANCE. C. INSiALL IDENiIFlCAlION PRO�UCTS CENIERE�, LEVEL, AN� PARALLEL WITH LMES OF IiEM BEING IDENiIFlED, D- SECURE NN,IEPLAiES TO Ex1ER10R SURFACES OF ENCLOSURES USING STAINLE55 S1EEL SCREwS AND TO INTERIOR SURFACES USING SELF-ADHESNE BACKING OR EPORY CEMENL E WSiALL $ELF-ADHESNE LABEL$ AND MARKER$ i0 ACMEVE MA%IM1IUN ADHESION, WIiH NO BUBBLES OR WRINKLES AND EDGES PROPERLY SEALED. E SECl1RE RIGI� SIGNS USING STAWLE55 STEEL SCREWS. G MARK ALL HANDNRIiiEN TE%i, WHERE PERMIiiED, TO BE NEAi AND LEGIBLE. ��� n harmac p Y HUB�ADA/SSSI/ACO STORE NUb6ER 01367 13090 PET-IGRU DR. CAHMEL, I�. 46032 cnPcooe: �so/ii3/aa/�i4) CS PRo,IECT NUMBER 138457 ARCHITECT OF RECORD� • CONSULTANT ENGINEER� CONSULTANT� SEAL� REVISIONS: 04-13-2020 DRAWING BY: CVS PROJECT MANAGER; DATE: JOB NUMBER: TIT�E: PERMIT SET S. BEBA E ROSARIO 04-13-2020 JCDT19.0397.00 ELECTRICAL SPECIFICATIONS SHEET NUMBER: E1 COMMENTS: