PANELBOAR�S
PART 1 PRO�UCTS
1.01 MANUFACTl1RERS
A. EATON CORPORAiION: WWW.EAiON.COM.
1.02 PANELBOARDS - GENERAL REOUIREMENiS
A. PROVI�E PRO�UCiS LISiED, CLASSIFIED, AND LABELED AS SUITABLE FOR THE PURPoSE INiENDED.
B. UNLESS OiHERWISE INDICATED PROVIDE PRODUCiS SUIiABLE FOR CONiINU0U5 OPERAiION UNDER
iHE FOLLOWING SERVICE CONDITION3
1. ALiIiUDE LE55 iHAN 6,600 FEET.
2 AMBIENT iEMPERAiURE:
a. PANELBOARDS CONTAINING CIRWIT BREAKERS: BETWEEN 23 DEGREES F AND 104 DEGREES F.
C. SFORT CYRCUIi WRRENT RATING
D. NAINS�. CONFIGURE FOR TOP OR BOTTOM INCOMING FEED AS INDICAiED OR AS REQUIRED FOR
iHE INSTALLATION.
E BRANCH OVERCURRENT PROIECTIVE DEVICES: REPLACEABLE WITHOUT DISTURBING ADJACENT
DEVICES.
E BUSSING'. SIZED IN ACCORDANCE WI1H UL 67 IEMPERATURE RISE REQUIREMENTS.
L PRONDE SOIJDLY BONDED EQUIPMENT GROUND BUS W EACH PANELBOARD, IMTH A SUITABLE
LUG FOR EACH FEEDER AND BRANCH CYRCUIT EQUIPMENT GROUNDING CONDUCTOR.
G. CONDUCTOR TERMINAPONS- SUITABLE FOR USE WIiH THE CONDUCTORS TO BE WSTALLED-
H. ENCLOSUkES: COMPLY WI7H NEMA 250, AND LIST AND LABEL AS WMPLYING WITH UL 50 AND
UL WE.
L FNVIRONMENT TYPE PER NEMA 250: UNLESS O7HERWISE INDICATED, AS SPECIFlED FOR THE
Fo��ow�Nc iNSTnunnoN �ocnnoNs�
7. 90XES: GALVANIZED AEEL UNLESS OTHERWISE INDICATED.
a. PROVIDE WIRINC CUTTERS SRED i0 ACCOMMODAiE THE CONDUCiORS i0 BE INSTALLED.
3. FRONTS:
a. FRONTS PoR SURFACE-MOl1NiED ENCLOSURES�. SAME �IMENSIONS AS 60XES.
4. L�CKABLE �OORS ALL LOCKS KEYE� ALIKE UNLESS OTHERWISE IN�ICATE�.
L �JiURE PRONSIONS: PREPARE ALL UNUSED SPACES FOR FUTURE INSTALLATION OF DENCES
INCWDINC BUSSING, CONNECTORS, MOUNiING HARDWARE AN� ALL OiHER REOUIRED PROVISIONS.
1.03 IJGHiING AND APPIJANCE PANELBOARDS
A. DESCRIPiION�. PANELBOARDS COMPLYING WIiH NEMA PB 1, LIGHiING AN� APPLIANCE BRANCH
CIRCUIi iYPE, CIRCUIT BREAKER i1PE, AND IJSiED AND LABELED AS COMPLYING WITH UL 67�,
RAiINGS, CONFIGURATIONS AND FEAiURES AS INDICATED ON THE DRAWINGS
B. CONDUCTOR iERMINAilONS:
1. MAIN AND NEUiRAL WG MAiERIAL�. AWMINUM, SUITABLE FOR TERMINAiING AWMINUM OR
COPPER CONDUCTORS.
Z MAIN AND NEUIRAL WG TYPE MECHANICAL.
C. BUSSYNG
1. PHASE BUS CONNECTIONS ARRANGED FOR SEQUENTIAL PHASING OF OVERWRRENT PROTECTIVE
DEVICES.
2. PHASE AND NEUiRAL BUS MAIERIAL ALUMINUM.
3. GROUND BUS MATERIAC AWMINUM.
D, CIRCUIT BREAKERS- THERMAL MAGNETIC BOLT-ON TWE UNLESS OiHERWISE INDICATED.
E ENCLOSURES
1_ PRONDE SURFACE-MOUNTED Oft FLUSH-MOUNTED ENCYOSURES AS INDICAIED.
2. PRONDE CLEAR PUSTIC CIRGIIT DIRECTORY HOLDEF MOUNTED ON INSIDE OF DOOR.
1-04 OVERCURRENT PROTECTIVE DENCES
A. MOLDED CASE CIRCUIT BREANERS'.
1. �ESCRIPTION' Ol11CK-MAKE, qUICK-BREAK, WEft CEN7ER TOGGLE, TRIP-FREE, TRIP-IN�ICATING
CIRCUIT BREAKERS LISTED AND LABELE� AS COMPLYING WI1H UL 489, AND COMPLYING WITH FS
W-C-375 WHERE APPLICABLE�, RAlINGS, CONFlCl1RATI0NS, AN� FEATORES AS INDICAIE� ON
THE oRnw�Ncs.
2 IVIERRl1PiINC CAPACIiY:
a. °ROVIOE CIkCUIT BREAKERS WITH INTEkRUP11NG CAPACIiY AS REOUIRE� TO PROVI�E 7HE
SHORi CIRCUIi CURRENT RATING IN�ICAiE�, BUi NOT LESS iHAN:
1) 1Q000 RMS SYMMETRICAL NAPERES AT 240 VAC OF 208 VAG
b. FULLY RAIED SYSTEMS PROVIDE CYRCUIT BREAKERS WITH WIERRUP7ING CAPACIiY NOT LE55
7HAN THE SHORT CIftCUIT CURRENT RATINC INDICAIED.
3. THERMAL MAGNETIC CIRCUIT BREANER4 FOR EACH POLE, FURNISH THERMAL WVERSE PME
TRIPPING ELEMENT FOR OVERLOA� PROTECTION AN� I�AGNETIC MSTANTANEOUS 7RIPPING
E_EMENT FOR SHORT CIRCUIi PROTECTION.
4. MULTI-POLE CIRCUIT BREAKERS FURNISH WITH COIAMON iRIP FOR ALL POLES.
PARi 2 E%ECUiION
201 INSTALLA➢ON
A. PERFORM WORK IN ACCORDANCE WI1H NECA I(GENERAL WORKMANSHIP),
B. WSTALL PRODUCTS IN ACCORDANCE WITH MANUFACiURER'S INSiRUCilONS.
G WSTALL PANELBOARDS IN ACCORDANCE WITH NECA 407 AND NEMA PB 1.1.
D. ARRANGE EOUIPMENT i0 PRONDE MINIMUTA CLEARANCES IN ACCOR�ANCE WITH IAANl1FACTURER'S
WSTRUCTIONS AN� NFPA 70.
E. WSTALL PANELBOARDS PWMB.
F. INSTALL FWSH-MOUNiE� PANELBOARDS SO THAT iRIMS FIT COMPLETELY FWSH TO WALL WITH
NO GAPS AND ROUGH OPENING COMPLEiELY COVERED.
G. MOUNT PANELBOARDS SUCH THAT iHE HIGHEST POSIiION OF ANY OPERAiING HANDLE FOR
CIRCUIi BREAKERS OR SWIiCHES DOES NOi E%CEED 79 INCHES ABOVE iHE FLOOR OR WORKING
PLAiFORM.
H. WSTALL ALL FlE.D WSTALLED BRA�C1 DEVICE$ COMPONENTS, AND ACCESSORIES.
I. PROVIDE FILLE4 'LA-t5 10 COV_H UNUSED SPACES IN PANELBOARDS.
„IINCIOA dLX MOUNiED
F�.sH wir- ceuNc ceio, �
SECJRE TO STRl1CTURE . i�� i
noov� �� � I
\ I
� I
(WHTEJ JUNCTION BO%�
GLOSLRE PLAiE, DRILL
-0LE PoR STRAIN RELIEF
�ND SO CORD
(ww�) so weo oowN ro
G�NJOLA BELOW
JUNCTION BOX AT TOP
RAL (FOR BEACON
GOVIIDI n ONLY) -
NOTE:
PROVIDE POWER TO GONDOLA
VIA SO CORD WITH ALL
COMPONENTS INCWDING BUT
NOT LIMITED TO STRAIN RELIEF
FOR A COMPLETE AND
STATIONARY INSTALLATION.
JUNCTION BO% TO BE P_JS9
MOUNTED WITH CEILJNG GRID
AND SECURED TO STRUCTURE
ABOVE.
POWEH DFOP TO BE USED AS
LEGRAND WIREMOL� POWER
DROP pPD123180WH
FLOOR
CBLING
RELEA5E0 FOR CONSTRIICTI�N "`Y
Su6jec��ocompliancewithallregula�ions PPLY DETAIL
of S�a�e antl Local Codes
City of Carmel
r
�un��\i lo•rvalM��_
DATE: OH/ZO/2O
SECiION ffi2Z26
wieiNc oewces
PART 1 PRO�UCiS
1.01 WIRING DEVICE APPIJCAiIONS
A. PROVIDE WIRING DEVICES SUITABLE FOR INiENDED USE AND WIiH RAiINGS A�EOUAiE FOR LOA�
SERVED.
B. FOR SINGLE RECEPTACLES INSTALLED ON AN INDIVIDUAL BRANCH CIRCUIT PROVIDE RECEPiACLE
i I F I
WI H AMPERE RAiNG NOi LESS THAN iHAT 0 iHE BRANCH CIRCU i.
G PROVIDE WEATHER RESISTANT GFCI RECEPTACLES WIiH SPEGFIED WFAiHERPR00F COVERS FOR
RECEPiACLES INSTALLED OUIDOORS OR IN DAMP OR WET LOCATIONS.
D. PROVIDE GFCI PROTECTION FOR RECEPTAIXES WSTALLED WITHIN 6 FEET OF SYNKS
E PROVIDE GFCI PROTECTION FOR RECEPTAIXES SERVING ELECTRIC DRINKING FOUNTAINS.
F. UNLE55 NOiE� OTHERWISE, DO NOi USE COMBINAiION SWITCH/RECEPiACLE �ENCES.
1A2 WIRMG DEVICE FINISHES
A. PROVIDE WIRING DEVICE FINISHES AS �ESCRIBED BELOW ONLE55 OTHERWISE IN�ICAiE�.
B. WIRING DEVICES, UNLE55 OiHERWISE INDICAiED�. WHIiE WITH WHITE NYLON WALL PLAiE.
G WIRING DEVICES MSTALLED IN UNFINISHED SPACES: GRAY WIiH GALVANIZED STEEL WALL PLAiE.
D. WIRING DEVICES MSTALLED IN WET OR DAMP LOCATIONS� WHITE N1TH SPECIFlED WEATHERPROOF
COVER.
1.03 WALL SWITCHES
A. WALL SWITCHES - GENERAL REQUIREMENTS: AC ONLY, QUIET OPERATING, GENERAL-USE SNAP
SWIiCHES WITH SILVER ALLOY CONTACiS, COMPLYING WITH NEMA WD I AN� NEMA WD Q AND
IJSTED AS COMPLYING WITH UL 20 AN� WHERE APPIJCABLE, FS W-S-896; TYPES AS INDICATED
ON THE DRAWINGS.
1. WIRING PRONSIONS'. IERMINAL SCREWS PoR SIDE WIRING AND SCREW ACNAIED BINDING
CLAIAP FOR BACK WIRING WITH SEPARAiE GROUND TERMINAL SCREW.
B. STANDAR� WALL SWIiCHES INDUSTRIAL SPECIFICAiION GRADE, 20 A, 120�D7 V WIiH
STANDARD TOGGLE TYPE SWITCH ACiVATOR AND MAINTAWED CONTACiS�, SINGLE POLE SINGLE
THROW, DOUBLE POLE SINGLE THROW, THREE WAY, OR FOUR WAY AS INDICATED ON THE
�RAWINGS.
1.04 RECEPTACLES
A. RECEPiACLES - GENERAL REQUIREMENTS: SELF-GROUNDING, COMPLYING WITH NEMA WD 1 AN�
NEMA WD Q AND LIS7E� AS COMPLYING WITH UL 498, AND WHERE APPLICABLE, FS W-C-596;
TYPES AS INDICATED ON THE DRAWINGS.
1. WIRING PRONSIONS', IERMINAL SCREWS PoR SIDE WIRING OR SCREW ACNATED BINDING CLAMP
FOR BACK WIRING WITH SEPARAIE GROUND TERMINAL SCREW.
2. NEMA CONFIGURATIONS SPECIFlED ARE ACCORDING TO NEMA WD 6-
B. WNVEWENCE RECEPiACLES'
1. STANDARD CONVENIENCE RECEPTACLES: INDUSTRIAL SPECYFlCATION GRADE, 20A, 125V, NEMA
5-20R; SYNGLE OR DUPLEX AS INDICATED ON 7HE DRAWINGS-
C GFCI RECEPTACLES'
1. GFG RECEPTA0.ES - GENERAL REQUIftEIAENTS: SELFIESTING, WITH FEED-THROUGH
PROlEC710N AND LIGHT i0 IN�ICAIE GROUND FAULT 7RIPPED CON�ITION AND LOSS OF
PROIEC➢ON; IJSTE� AS WMPLYING WITH UL 943, CLASS A.
o. PROVIDE TEST AND RESET BUiiONS OF SAME WLOR AS �ENCE.
2. STANDAR� GFCI RWEPTACLES: INDUSTRIAL SPELYFlCATION GeADE, Dl1PLEK 20A, 125V, NEMA
5-20R, RECTANGULAR �ECORAiOR STYLE.
3. WEATHER RESISTANT GFCI RECEPTACLES�. INDl15TRIAL SPECIFICAiION GRA�E, �UPLEX, 20A,
125V, NEMA 5-20R, RECTANGULAR �ECORATOR STYLE, LIS1E� AN� LABELE� AS WEATHER
RESISiANT T1PE COMPLYING WITH UL 498 SUPPLEMENi SE SUIiA6LE FOR MSTALLATION IN
DAMP OR WET LOCAilONS.
1.05 WALL PLATES
A. WALL PLAiES: COMPLY WITH UL 514�.
1. CONFIGURAiION�. ONE PIECE COVER AS REQUIRED FOR OUANiITY AND iYPES OF
CORRESPONDING WIRING DENCES.
2 9ZE: STANDARD�, _ _ _ _ __
S SCREWS: METAL WIiH SLOiiED HEADS FINISHED TO MATCH WALL PNTE FINISH.
B. NYLON WALL PLATES: SMOOTH FlNISH, HIGH-IMPACT THERMOPLAS➢C.
PART 2 EXECUTION
201 INSTALLATION
A. PERFORM WORK IN ACCORDANCE WIiH NECA 1(GENERAL WORKMANSHIP) AND, WHERE
APPLICABLE, NECA 130, INCLUDING MOUNiING HEIGHTS SPECIFIED IN THOSE STANDARDS UNLESS
OTHERW6E INDICATED.
B. COORDINAiE LOCAilONS OF OUTLET BOXES PRONDED UNDER SECTION 26.05.33.16 AS REQUIRED
FOR INSiALLAiION OF WIRING DEVICES PROVIDED UNDER iH15 SECiION.
1. MOUNTING HEIGHTS: UNLE55 OTHERWISE INDICAIEq AS FOLLOWS�.
a. WALL SWITCHES: 48 INCHES ABOVE FINISHED FLOOR.
b. RECEPTACLES: 18 INCHES ABOVE FlNISHED FLOOR OR 6 INCHES ABOVE COUMER.
C. INSiN1 WIRING DENCES IN ACCORDANCE WIiH MANUFACTURER'S INSiROCilONS.
�. INSTALL PERMANENT BARRIER BEi1NEEN GANGE� WIRING �EVICES WHEN VOLiAGE BETWEEN
A�JACENT �EVICES EXCEE�S 300 V.
E. WHERE REOUIRED, CONNECi WIRING DENCES USING PIGiAILS NOT LESS THAN 6 INCHES LONG DO
NOT CONNECi MORE iHAN ONE CONDUCiOR i0 WIRING DEVICE TERMINALS.
F. CONNECT WIRING DEVICES BY WRAPPING CONDUCTOR CLOGCWISE 3/4 TURN AROUND SCREW
TERMINAL AND TIGHTENING TO PROPER TORQUE SPECIFlED BY 1HE MANUFACIDRER. WHERE
PRESENT, �0 NOT USE PUSH-IN PRESSURE TERMINALS THAT �0 NOT RELY ON
SCREW-ACTUATED BINDING.
G UNLE55 O7HERWISE INDICAIE�, CONNECT WIRING �ENCE GROUNDING TERMINAL TO BRANCH
CIRCIIIi EQUIPIAENT GROON�ING CON�UCiOR AND TO OUILET BOX WITH BONDING JUMPER.
H. INSiALL WIRING DENCES PWMB AND LEVEL WIiH MOUNiING YOKE HELD RIGIDLY IN PLACE.
. WSiALL WALL SWITCHES WITH OFF POSITION �OWN.
J. WSiALL VERiICALLY MOUNiED RECEPiACLES WITH GROUNDING POLE ON i0P AN� HOPoZONiALLY
MOUNiED RECEPiACLES WITH GROUNDING POLE ON LEFi.
K. WSiALL WALL PLATES TO FIT COMPLEiELY FWSH TO WALL WIiH NO GAPS AND ROUGH OPENING
COMPLETELY COVERED WIiHOUi SiRNN ON WALL PLAiE. REPAIR OR REINSTALL IMPROPERLY
WSiALLED OUTLEi BO%ES OR IMPROPERLY SIZED ROUGH OPENINGS. DO NOi USE OVERSIZED
WALL PLAIES IN IJEU OF IAEETING THIS REOUIREMENT.
L WSiALL BLANK WALL PLAIES ON JUNC➢ON BO%ES AND ON OU7LET BO%ES WITH NO WIRING
�EVICES WSTALLED OR �ESIGNATED FOR FUiURE USE.
JUNCTION BOX MOUME�
FLUSH WITH CEILING GRID,
SECURE i0 STRUCIDRE
ABOVE
(WHIiE) JUNCiION 8�
CLOSURE PLATE, �RI
HOLE FOR SIRAIN R
AND 50 CORD
(WHIIE) 50 COR�
GI�NDOLA BELOW
JUNCTION BOR Ai
FLOOR LEVEL (FOR
eecuv,e calloo�n
SECiION 2628.16
ENQOSED SWITCHES
PARi 1 PRODUCiS
1.01 ENCLOSED SAFETY SWITCHES
A. DESCRIPTION�. QUICK-MAKE, QUICK-BREAK ENCLOSE� SAFETY SWITCHES IJSTED AND LABELE�
TI F N
AS COMPLYING WI1H UL 98- GENERAL DUTY� RA NGS CON IGURATIO S AN� FEANRES AS
INDICATED ON THE �RAWINGS.
B. PROVIDE PRODUCTS IJSTE�, CLASSYFlED, AND LHBELE� AS SUITABLE FOR THE PURPOSE
INTENDED,
C UNLESS OTHERWISE INDICATED, PRONDE PRODUCTS SUITABLE PoR CONPNUOUS OPERAPON
UNDER THE FOLLOWING SERVICE CONDI➢ONS:
1. AL7ITUDF. LE55 7HAN 6,600 FEET.
2. AMBIENT IEMPERATURE BETWEEN -22 DEGREES F AND 104 DEGREES F.
D. HORSEPOWEft RATING: SUITABLE FOR CONNECTED LOAD.
E. VOLTAGE RAIING'. SUITABLE FOR CIRCUIT VOLTAGE.
F. SHORi CYRCUIT CURRENT RAIING'.
1. PRONDE ENCLOSE� SAFETY SWITCHES, WHEN PROTEC7E� BY THE Fl1SES OR Sl1PPLY SI�E
OVERCl1RRENT PROIECTIVE DEVICES i0 BE INSTALLED, Wlhi LISTE� SHORT CIRCUIT Cl1RRENT
RATING NOT LESS THAN THE AVAILABLE FAULi CURRENT AT THE WSTALLE� LOCATION AS
IN�ICAIE� ON 7HE �RAWINGS.
G. PROVIDE WIiH SWIiCH BLADE CONTACi POSITION THAT IS NSIBLE WHEN iHE COVER IS OPEN.
H. CONDOCiOR iERMINAiIONS SUITABLE FOR USE WIiH THE CONDUCTORS TO BE INSiALLED.
I. PROVIDE SOLIDLY BONDE� EQUIPMENi GROUND BUS IN EACH ENCLOSED SAFEtt SWITGi, WITH A
SVITABLE WG FOR iERMINAiING EACH EOUIPMENi GROUNDING CONDUCiOR.
d ENCLOSURES COMPLY WIiH NEMA 25Q AND L6i AND LABEL AS COMPLYING WITH UL 50 AND
UL 50E.
1. ENVIRONMENi TYPE PER NEMA 250: UNLE55 OiHERWISE INDICATED, AS SPECIFIED FOR iHE
PoLLOWING WSTALLATION LOCAilONS:
K. PROVIDE SAFETY INTERLOCK TO PREVENT OPENING THE COVER WITH iHE SWITCH IN THE ON
POSYTION WI1H CAPABIIJTY OF OVERRIDING INTERLOCK FOR TESTING PURP0.SE5.
L GENERAL �UiY SWIiCHES
1. CON�UCTOR TERMINATIONS:
a. PROVIDE MECHANICAL WGS.
b. LUG MAIERIAL: ALUMINUM, SUITABLE PoR iERMINAiING ALUMINUM OR COPPER CONDUCTORS.
Z PRONDE E%TERNALLY OPERABLE HANDLE W1TH MEANS PoR LOCKING IN THE OFF POSITION,
CAPABLE OF AWEPTING 7VJ0 PADLOCKS.
PART 2 EXEW710N
2.01 WSTALLA710N
A. WSTALL PRODUCTS IN ACCORDANCE WITH MANUFACNRER'S INS7RUCTIONS.
B. PERFORM WORK IN ACCORDANCE WI7H NECA 1(GENERAL WORKMANSHIPJ.
C. ARRANGE EOUIPMENT TO PRONDE MINIMUM CLEARANCES IN ACCORDANCE WITH MANUFACTURER'S
WSTRUCilONS AND NFPA 70-
D. INSTALL ENCLOSED SWITCHES PLUMB.
E EXCEPT WHERE INDICAIED TO BE MOUN7ED ADJACENT TO iHE EOUIPIAENT 7HEY SUPPLY, MOUNT
ENCLOSED SWITCHES SUCH THAT THE HIGHEST POSITION OF 7HE OPERATING HANDLE DOES NOT
EXCEED 79 INCHES ABOVE THE FLOOR OR WORKING PLATFORM.
SECTION 26.51.00
IMERIOR LIGHTING
PARi 1 PRODUCTS
1.01 WMINAIRES
A. PROVIDE PRODUCTS iHAi COMPLY WITH REQVIREMENTS OF NFPA 70.
B. PROVIDE PRODUCTS iHAi ARE LISiED AND LABELED AS COMPLYING WITH UL 159& WHERE
APPLICABLE.
C. PROVIDE PRO�UCTS LISiED, CLASSIFIED, AND LABELED AS SUITABLE FOR THE PURPOSE
INTENDED.
D. UNLESS OTHERWISE INDICATED, PRONDE COMPLEiE WMINAIRES INCW�ING LAMP(S) AND ALL
SOCKETS, BALLASTS, kEFLECTORS, LENSES, HOl1SINGS AN� OTHER COMPONENTS kEQVIRE� TO
P09PON, ENERGIZE AND PROTECT 7HE LAMP AN� �IS7RIBUTE THE LIGHT.
E. UNLESS SPECIFICALLY INDICAiED i0 6E EXCWDED, PRONDE ALL REQUIRE� CONDUIT, BO%E5,
WIRINQ CONNECi0R5, HAf2DWARE, SUPPORTS, TRIMS, ACCESSORIES, EiC. AS NECESSARY PoR
A COMPLEIE OPERATING SYSiEM.
F. PROVIDE PRODUCTS SUITABLE TO WITHSTAND NORMAL HANDIJNG, WSiALLATION, AN� SL4VIGL
WITHOUi ANY DAMAGE, DISi0RTI0N, CORROSION, FADING, DISCOLORING, ETC.
G. RECESSED WMINAIRES:
L CEWNG COMPAiIBWTY: COMPLY WITH NEMA LE 4.
H. LED WMINAIRES:
1. COMPONENTS: UL 8750 RECOGNIZED OR IJSTED AS APPIJCABLE.
2 TESTED IN ACCORDANCE WITH IES LM-79 AN� IES LM-80.
3. LED ESTIIAATED USEFUL LIFE MINIMUM OF SQ000 HOURS AT 70 PERCENT WMEN
MAINTENANCE, CALCULATED BASED ON IES LM-80 TEST DATA.
1A2 EMERGENCY LIGHIING UNIiS
A_ DESCRIP710M EMERGENCY LIGHTING UNITS COMPLYING WITH NFPA 101 AND ALL APPLICABLE
SiAIE AND LOCAL CODES, AND LIS1E� AND LABELED AS WMPLYING WITH UL 924.
B. OPERATION_ UPON INTERRUPTION OF NORMAL POWER SOURCE OR BROWNOUT CONDI710N
EXCEEDING 20 PERCENT VOLTAGE DROP FROM NOMINAL, SOLID-STATE WNTROL
AUTOMATICALLY SWITCHES CONNECIED LAMPS TO IMEGRAL BATTERY POWER FOR MINIMUM OF
90 MINUTES OF RATED EMERGENCY ILLUMINAlION, AND AUTOMATICALLY RECHARGES BAT7ERY
UPON RESTORATION OF NORMAL POWER SOURCE.
C. BATTEkY:
1_ SIZE BATTERY TO Sl1PPLY ALL CONNECTE� LAMP$ INCW�ING EMERCENCY REMOTE HEA�S
WHERE INDICAIED.
�. �IAGNOSIICS�. PROVIOE POWER STATOS IN�ICATOR LIGHT AN� ACCESSIBLE IMEGRAL TEST
SWITCH TO MANUALLY ACTIVATE EMERCENCY OPERAiION.
E. PROVIOE LOW-VOLTAGE �ISCONNECT TO PREVENT BATTERY �AMAGE FROM �EEP �ISCHARGE.
1.03 EqT SIGNS
A. OESCRIPiION�. INTERNALLY ILWMINAiED E%li SIGNS WIiH LEDS UNLESS OiHERWISE INDICAiED�,
COMPLYING WIiH NFPA 101 AND ALL APPLICABLE SiAiE AND LOCAL CODES, AND LISiED AND
LABELED AS COMPLYING WIiH OL 924.
1. NUMBER OF FACES SINGLE OR DOUBLE AS INDICATED OR AS REQUIRED FOR THE INSiALLED
LOCATION.
2 DIREC➢ONAL ARROINS AS INDICAIED OR AS REQUIRED PoR iHE INSTALLED LOCA➢ON.
B. SELF-POWERED EYJi SIGNS�.
1. OPERATION�. UPON WIERRUPTION OF NORMAL POWER SOURCE OR BROWNOUT CONDITION
E%CEE�ING 20 PERCENT VOLTAGE DROP FROM NOMINAL, SOLID-SiAIE CONTROL
AUTOMA7ICALLY SWITCHES CONNECTE� LAMPS TO INTEGRAL BATTERY POWER FOR MINIMUM
OF 90 MINUTES OF RATE� EMERGENCY ILLUMINAlION, AN� AUTOMATICALLY RECHARGES
BAT7ERY UPON RESTORATION OF NORMAL POWER SOURCE
2. DIAGNOSTICS PROVIDE POWER STANS INDICATOR LIGHT AND ACCESSIBLE INTEGRAL IEST
SWITCH TO MANUALLY ACTIVATE EIAERGENCY OPERATION.
3. PROVIDE LOW-VOLTAGE DISCONNECT i0 PREVENT BATTERY DAMAGE FROM DEEP DISCHARGE.
1_04 BALLASTS AND DRNERS
A. BALLASTS�DRIVERS - GENERAL REQUIREMENiS�.
1. PROVI�E BALLASTS WNTAINING NO POLYCHLORINATE� BIPHENYLS (PCBSJ.
2- MINIMUTA EFFlGENCY/EFFlCACY PRONDE BALLASTS COMPLYING WITH ALL CURRENT
APPIJCABLE FEDERAL AND SiAiE BALLAST EFFICIENCY�EFFICACY STANDARDS.
3. ELECTRONIC BALLASTS��kIVERS WkUSH Cl1RRENTS NOT E%CEE�ING PEAK Cl1RkENTS
SPEQFlED IN NEMA 410.
B. �IMMABLE LE� DRIVERS�.
1. �IMMING RANGE CONiINU0U5 �IMMING FROM 100 PERCENT TO FIVE PERCENT RELATIVE
IJGHi OUTPUi 11NLE55 DIMMING CAPABILIiY TO LOWER LEVEL IS IN�ICATED, WIiHOUi FIJGKLI2.
2. CONTROL COMPATIBILITY: FULLY COMPATIBLE WI1H THE �IMMING CONTROLS TO BE
INSiALLED.
1.05 ACCESSORIES
A_ S7EM5 FOk SUSPENDED LUMINAIRES: STEEL TUBING, MINIMUM 1/2° SIZE, FACTORY FlNISHED
i0 MATCH LUMINAIRE OR FlEL�-PAINTED AS DIREC7ED.
PARi 2 EXECUPON
201 INSiALLATION
A. COORDINATE LOCATIONS OF OUTLET BO%ES PROVIDED UNDER SECTION 26.05.33.16 AS
REQUIRE� FOR INSTALLATION OF WMINNRES PROVIOE� UN�ER THIS SECPON.
B. PERFORM WORK IN ACWRDANCE WITH NECA 1(GENERAL WORKMANSHIP).
C. MSTALL PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S WSiRUC➢ONS.
D. MSTALL WMINAIRES SECURELY,IN A NEAT AND WORKMANIJKE MANNER, AS SPECIFlED IN NECA
500 (COMIAERCIAL LIGHTING) AND NECA 502 (INDUSTRIAL LIGHTING).
E. MSTALL WMINAIRES PWMB AN� SOl1ARE AN� ALIGNE� WITH BOIL�ING LINES AN� WITH
ADJACENi WMINAIRES.
F. MSTALL ACCESSORIES FURNISHED WIiH EACH WMINAIRE.
G. 60N� PRODUCTS AND METAL ACCESSORIES TO BRANCH CIRCUIi EOUIPMENT GROUN�ING
CON�UCiOR.
H. EMERGENCY LIGHiING UNITS:
1. UNLE55 OiHERWISE INDICAiED, CONNECi UNIi i0 UNSWITGiED POWER FROM SAME CIRWIi
FEEDING NORMAL LIGHiING IN SAME ROOM OR AREA. BYPA55 LOCAL SWIiCHES, CONTACiORS,
OR OTHER LIGHTING CONiROLS.
L EXIi SIGNS:
1. UNLE55 OiHERWISE INDICAiED, CONNECi UNIT TO UNSWITGiE� POWER FROM SAME CIRWIT
FEEDING NORMAL IJGHTING IN SAME ROOM OR AREA. BYPA55 LOCAL SWITCHES, CONTACTORS,
OR OTHER LIGHTING CON7ROLS.
d NSTAL LAMPS W EACH WMINAIRE.
CVS HAS DEVELOPED SPECIAL PRICMG AND READILY AVAILABLE STOCK WITH
THE NAI PREFERRED SUPPLIER
- WIEDENBACH-BROWN Cq INC.
PHONE: 800 243 0030
� )
EMAIL CVSSUPPORT�WBLIGHT.COM
- NESCO, WC.
PHONE (888)244 6980
EMAIL CVSPLANSOaNEE�HAMELECTRIGCCM
� ��
n
harmac
p Y
HUB�ADA/SSSI/ACO
STORE NUb6ER 01367
13090 PET-IGRU DR.
CAKMtL, IN. 46032
cnPcooe: �so/ii3/aa/�i4)
CS PRo,IECT NUMBER 138457
ARCHITECT OF RECORD�
•
CONSULTANT ENGINEER�
CONSULTANT�
SEAL�
REVISIONS:
04-13-2020
DRAWING BY:
CVS PROJECT MANAGER;
DATE:
JOB NUMBER:
TIT�E:
PERMIT SET
S. BEBA
E ROSARIO
04-13-2020
JCDT19.0397.00
ELECTRICAL
SPECIFICATIONS
SHEET NUMBER:
COMMENTS: