HomeMy WebLinkAbout01367IN_M3SPIN-IN
MSULATED RIGID
METAL DUCT
AND ELBOw
INSULATED
REX DUCT
SEISMIC
RESTRAINT.
MIN. 2 ON
OPPOSITE
CORNERS.
(MIN)
WSULATED SUPPLY AIR
TRUNK DUCT - REFER
TO PLAN
INSULATED SPW-IN
FITTING WITH MANUAL
DAMPER AND ACCESSIBLE
INDICATING HAN�LE -
TYPICAL
INSULATED _ DRAW-BAND CLAMP -
FLEX DUCT TYPICAL EACH END
SEISMIC RESTRAINT.
MIN. 2 ON OPPOSITE
CORNERS.
MAX OFFSET ALLOWABLE:
2-WCHES PER FOOT OF
FLEXIBLE DUCT LENGTH
CLAMP -
1 END
MAX OFFSET ALLOWABLE:
2-MCHES PER FOOT OF
FLEXIBLE DUCT LENGTH
INSULATE TOP OF DIFFUSER (MAY
BE OMITiED WHERE CEILING
CAVITY IS USED AS A RETURN
� AIR PLENUM) - TYPICAL
�CBLING AIR DEVICE - �CEIIJNG
TYPICAL
LONG RUN SIDE TAP INSTALLATION
CEILING DIFFUSER/RETURN
�z� GRILLE CONNECTION DETAIL
M3 NOT TO SCALE
MAW SUPPLY DUCT
OR SUB-MAIN
1/4 W. 4" �
MIN.
BRANCH DUCT
PROVIDE VOWME
DAMPER (OBMVD)
W
SUPPLY AIR DUCT
BOTTOM TAP INSTALLATION
z"x2"xi/a
ANGLE OR
UNISTFUT
VO UNE DAMPEd
f�il
�CONICALTAP ROUND
BRANCH
MAIN SUPPLY
DUCT (OR
SUB-MAIN)
RELEA5E0 FOR CONSTRIICTI�N
Su6jec��o compliance with allregula�ions
of S�a�e antl Local Codes
City of Carmel
r
�un��\i lo•rvalM��_
DATE: OH/ZO/2O
TWO SHEET MI
SELF TAPPING
SCREWS
ROUND
DUCTWORK
MAW SUPPLV TWO SHEI
SELF TAF
oucr (oR scRews
SUB-MAIN)
RECTANGULAR
TO ROUND SIDE
DUCT
TAKE-OFF
18 GAUGE
VOWME
DAMPER WITH
LOCKING
QUADRANT SET
(TYR FOR ALL
SUPPLY/RETURN/
EXHAUST AIR
BRANCH DUCT)
OFF DETAILS
ROUND
DUCTWOF
JOIST
RECTANGULAR
DUCTWORK
DUCT SUPPORT PA3ALLEL TO TRUSSES
NOTES:
7. ALL DUCT & SUPPORTS PER UMC.
�� DUCT HANGER DETAIL
M3 NOT TO SCALE
MINI SPLIT SYSTEM SCHEDULE
weF�ow e�ecTeicn�
TAG MANUFACTURER MODEL NUMBER CFM LOW/1AED/HIGH MCA MOCP EER/SEER HSPF REIAARKS
VOLT/PHASE
AHU-1 MITSUBISHI NTxCK512A11A 230/265/335 208/1/60 0.30 -- -- --- 1,2,3,4,5
CU-1 MITSUBISHI NTXSK512A112A -- 208/1/60 9 16 13.3/220 1L4 1,6,7
AHU-2 MITSUBISHI NTXCKS72A17A 230/2fi5/E35 208/7/60 0.3� -- -- -- 1,2,3,4,5
CU-2 MITSUBISHI NixSK512An2A -- 208�1/60 9 16 13-3�220 n.4 1,6,7
nHu—a MiTsueisni NTzcKsiznna �3o/2ss/a3s zoe/i�so 0.30 -- --- --- i,2.a,a,e
CU-3 MITSUBISHI NTXSNS12A112A -- 208/7/60 9 16 13.3/22.0 11.4 1,6,7
NUItS
1. APPROVED MANUFACTURERS INCLUDE PANASONIC, FUJITSU. IF ALTERNATE MANUFACTURERS ARE USED, COORDINATE CHANGES WITH
ELECTRICAL, STRUCTURAL AND ARCHITECTURAL TRADES. ANY ADDITIONAL COSTS DUE TO CHANGES RESULTWG FROM THE USE OF ALTERNATE
MANUFACTURERS SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR.
2 INSTALL PER MANUFACTURER INSiRUCTIONS COMPLEiE WITH REFRIGERANT PIPING, FULL REFRIGERANT CHARGE, AND PROPER STARTUP
PROCEDURES
2. PROVIDE WITH INTEGRATED CONDENSATE DRAIN PU�IP WITH SINGLE POINT POWER CONNECTION TO AHU. PROVIDE WITH INTEGRATED CONDENSATE
DRAIN PAN AND DRAIN UNDER THE UNIT COIL PROVIDE DRAM LEVEL SENSOR (DPLS2), CONNECTED TO CONTROL PANEL, TO PREVENT
CONDENSATE FROM OVERFLOWING.
3. SLP-18FAU GRILLE.
4. TAR-40MAAU (WIRE� PftOGRAMMABLE REMOTE CONTROLLER�
5. PROVIDE 2q12,p12G, 1/7b FROM CU TO AHU
GRILLE, REGISTER, DIFFUSER SCHEDULE
TAG SERVICE CFM NECK SIZE FRAME pAThRN DAIAPER MATERIAL FlNISH MANUFACTURER & MODEL
TWE N0.
SD-1 SUPPLY SEE PLANS SEE PLANS NOTE 1,2 4-WAY YES STEEL OFF-WHIIE METALAIRE 5500 SERIES
RG-1 RETURN SEE PLANS SEE PLANS NOTE 1,2 NONE NO STEEL CF=-WHI-E METALAIRE CC1 CUBE
CORE RET./E%HAUST
NOIE: 1. MODEL NUMBERS ARE METALAIRE UNLESS O7HERWISE NOTED.
2. PRONDE TRANSITION TO DIFFUSER WHERE REQUIRED.
�'��
pharmacyn
HUB/ADA/SSSI/ACO
STORE NUMBER 01367
13090 PETTIGRU DR.
CARMEL, IN. 46032
CAPCODE (90�113�88�114)
CS PRo,IECT NUMBER 138457 I
ARCHITECT OF RECORD�
i-1
U
CONSULTANT ENGINEER�
CONSULTANT�
SEAL�
REVISIONS:
04-13-2020
DRAWING BY:
CVS PROJECT MANAGER:
DATE:
PERMIT SET
R. McCARTHY
E. ROSARIO
04-13-2020
JOB NUMBER: JCDT19.0397.00
TiT�E: MECHANICAL
SCHEDULES & DEfAILS
SHEET NUMBER:
M3
COMMENTS:
DUCT SUPPORT PERPENDICULAR TO TRUSSES