HomeMy WebLinkAboutE020 Electrical SpecsPART1-GENERAL 1.1RELATEDDOCUMENTS A. THIS SECTION SUPPLEMENTS DIVISION 1 GENERAL REQUIREMENTS. B. WHERECONTRADICTIONSOCCURBETWEENTHISSECTIONANDDIVISIONI,THEMOSTSTRIN6ENT OF THE TW O SHALL APPLV. ARCHITECT SHALL �ECIDE W HICH IS MOST STRINGENT. C. PROVISIONS OF DIVISIONS 21, 22, 23, 2] AND 28 SHALL ALSO APPLV TO THE WORK OF THIS SECTION AS IF FULLV REPEATED HERE. D. PROVISIONINDICATESECTION23 05 01/26 05 01"MECHANICALANDELECTRICAL COORDINATION" SHALL ALSO APPLV TO THE WORK OF THIS SECTION AS IF FULLV REPEATED HERE. L2 REGl1LATORV REQl11REMENTS A. ALL MATERIALS SHALL CONFORM WITH THE CURRENT APPLICABLE INDl15TRV STANDAROS. W ORKMANSHIP AND NEAT APPEARANCE SHALL BE AS IMPORTANT AS ELECTRICAL AND MECHANICAL OPERATION. DEFECTNE OR DAMAGED MATERIALS SHALL BE REPLACED OR REPAIRED PRIOR TO RNAL ACCEPTANCE IN A MANNER MEETING APPROVAL OF THE ARCHITECT AND AT NO ADDITIONAL COST TO THE OW NER. B. THE LATEST EDITIONS OF THE FOLLOWING STANDARDS ARE MINIMUM REQUIREMENTS. L UNDERWRITERS'LABORATORIES,INQ(UL) 2. NATIONALELECTRICALMANUFACTURER'SASSOG(NEMA) 3. AMERICAN NATIONAL STANDARDS WSTITUTE (AN51) 6. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS QEEE) 5. INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA) 6. INSULATED CABLE ENGMEER'S ASSOCIATION (ICEA) G ALL WORK AN� MATERIALS SHALL COMPLV W ITH LATEST RULES, CODES AND REGULATIONS INCLUDING, BUT NOT LIMITED TO THE FOLLOW ING: 1. OSHA. 2. NATIONAL FIRE CODES OF NATIONAL FIRE PROTECTION ASSOC. (NFPA) 3. NATIONAL ELECTRICAL SAFETY CODE (NESC, ANSI C2) 4. NATIONAL ELECTRICAL CODE (2008 EDITION) WITH QTV, COUNTV AND STATE AMENDMENTS. 5. INTERNATIONAL BUILDING CODE BUILDING COOE (2008 EDITION) W ITH CITY, COUNTV AND STATE AMEN�MENTS. 6. AMERICANSwITHDISABILITIESACT(ADA). �. ALLAPPLICABLEFEDERAL,STATEANDLOCALLAWS.CODEAMENDMENTSAN� REGULATIONS. 0. NO WORK SHALL BE CONCEALED UNTIL AFTER WSPECTION AND APPROVAL BY PROPER AUTHORITIES. IF WORK IS CONCEALED WITHOUT INSPECTIONANDAPPROVAL, CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO OPEN AND RESTORE THE CONCEALED AREA MCLUDING ALL RE�UIRED MODIFlCATIONS. 6 CONTRADICTIONS'. WHERE CODES ARE CONTRADICTORV, FOLLOW THE MOST STRINGENT. ARCHITECTIENGINEER SHALL DETERMINE W HICH IS MOST STRINGENT. 1.3CONTRACTDOCUMENTS A. DRAW MGS IN�ICATE GENERAL ARRANGEMENT OF CIRCUITS AND LOCATIONS OF Ol1TLET5, CONDUIT, AND OTHER W ORK. MFORMATION SHOwN ON DRAW INGS IS AS ACCURATE AS PLANNIN6 CAN DETERMME, BUT NOT GUARANTEED AN� FlELD VERIFICATION OF ALL DIMENSIONS, LOCATIONS, LEVELS, ETC., TO SUIT FIELD CONDITIONS IS OIRECTED. REVIEW ALL ARCHITECTURAL, STRUCTUR4L AND MECHANICAL DRAW W G5, AND ADJUST ALL W ORK TO CONFORM TO ALL CONDITIONSSHOWNTHEREIN. ARCHITECTURALDRAWINGSSHALLTAKEPRECEDENCEOVERALL OTHERDRAWINGS. DISCREPANGESBETWEEN�IFFERENTDR4WINGSORBETWEENDRAWINGS AND SPEQFICATIONS OR REGUL4TION5 AND COOES GOVERNING INSTALLATION SHALL BE BROUGHT TO ATTENTION OF THE ARCHITECT. B. WHERE THE DRAW MGS AND SPEQFICATIONS DO NOT COMPLV W ITH THE MINIMUM REQUIREMENTS OF THE CODES. EITHER NOTIFV THE ARCHITECT/ENGMEER IN W RITING DURING THE BIDDING PERIOD OF THE REVISIONS RE�UIRED TO MEET CODE RE�UIREMENTS, OR PROVIDE AN INSTALLATION W HICH COMPLIES W ITH THE CODE REQUIREMENTS. AFTER ENTERING WTO WNTRACT, CONTRACTOR W ILL BE HELD TO COMPLETE ALL WORK NECESSARV TO MEET THESE REQUIREMENTS W ITHOUT ADDITIONAL EXPENSE TO THE OW NER. Q FOLLOW DRAW INGS AND SPECIFlCATIONS W HERE THEV ARE SUPERIOR TO CODE REQUIREMENTS. THE MORE STRINGENT OF PLANS AND DRAW ING SHALL APPLV. 1 4 RECORD DRAW INGS A. REFERTODIVISIONiFORADDITIONALREQUIREMENTS. B. MAINTAIN A BLUE-LINE SET OF ELECTRICAL CONTRACT DRAW INGS IN CLEAN, UNDAMAGED CONDITION, FOR MARK-UP OF W STALLATIONS W HICH VARV FROM THE CONTRACT DRAW INGS. THESE �RAW INGS SHALL BE A SEPARATE SET OF DRAW INGS, NOT USED FOR CONSTRUCTION PURPOSES, AND SHALL BE KEPT UP TO DATE AS THE JOB PROGRESSES. THIS SET SHALL BE MADE AVAILABLEFORINSPECTIONBVTHEENGINEERORARCHITECTATALLTIMES. UPONCOMPLETION OF THE CONTRACT A SET OF COMPUTERRED "AS BUILTS" CAPABLE OF IMERFACING W ITH AUTOCAD SOFTWARE, SHALL BE DELNERED TO THE ARCHITECT. Q PREPARE RECORD DOCUMENTS IN ACCORDANCE W ITH THE REQUIREMENTS IN DIVISION 1 SECTION "PROJECT CLOSEOUT" IN ADDITION TO THE REpl11REMENTS SPECIFIED IN DNISION 1, INOICATE INSTALLED CONDITIONS FOR: 1. MNOR RACEWAV SVSTEMS, SIZE AND LOCATION. 2. PANELBOAR�CIRCUITDIRECTORIESRERECTINGALLFlELOCHANGES. 3. APPROVEDSUBSTITUTIONS,CONTRACTMODIFICATIONS,ANDACTUALEpUIPMENTAND MATERIALS INSTALLED. 6. RESULTS OF ALL TESTING PERFORMED AS SPEGFIED IN THE SPECIFICATION. 5. CERTIRCATION OF INSPECTION FROM AUTHORITIES HAVING JURISDICTION. 1.5 OPERATING AND MAINTENANCE MANUALS A. REFERTODNISIONIFORA�OITIONALREQUIREMENTS. B. SUBMISSION: 1. SUBMITELECTRONICCOPIESOFOPERATINGANDMAINTENANCEMANUALSPRIORTO SCHEDULING SVSTEMS DEMONSTRATION FOR THE OWNER. G MARK THE BACK SPME OF EACH BINDER WITH SYSTEM IDENTIFICATION AND VOLUME NUMBER. REQUIREMENTCONTENTS: 1. MANUALSSHALLHAVEINDE%FOREACHSUBMITTALSECTIONIDENTIFVINGALLEQUIPMENTAND MATERIALS INSTALLED ON THE PROJECT WCLUDING A LOCAL SUPPLIER FOR REPLAqNG A SPECIFIC PIECE OF EOUIPMENT. 2. PROVIDE CERTIFICATES FORSUCH ITEMS OF EQUIPMENT WHICH HAVE WARRANTIES W EXCE55 OF ONE VEAR. 1.6 DELIVERV, STORAGE. AND HANDLING A. DELNER PRODUCTS TO THE PROJECT PROPERLV IDENTIRED W ITH NAMES, MODEL NUMBERS, TVPES, GRADES, COMPLIANCE LABELS, AND OTHER MFORMATION NEEDED FOR IDENTIFlCATION. B. PROTECTION OF EOUIPMENT: 1. ALL ELECTRICAL EQUIPMENT TO BE USED IN THE CONSTRUCTION SHALL BE PROPERLV STOREO AND PROTECTED AGAINST THE ELEMENTS. ALL EQUIPMENT SHALL BE STORED UNDER COVER, AND SHALL NOT BE STORED ATTHE CONSTRUCTION SITE ON THE GROUND, IN MUD, WATER, RAIN, SLEET, OR DUST. LARGE DIAMETER CABLES MAV BE STORED ON REELS OUTSIDE; HOW EVER, ALL CABLE ENDS SHALL BE WATERPROOFED AN� THE REELS COVERED WITH WEATHERPROOF MATERIALS. SUCH WEATHERPROOF MATERIALS SHALL BE HEAVV-DUTV, SEWRELV FASTENED, AND MADE IMPERVIOUS TO THE ELEMENTS. 2. CONVENTIONALELECTRICALCONSTRUCTIONMATERIALSSUCHASBUILDINGWIRE,OUTLETANO JUNCTION BOXES, WIRING DEVICES. CONDUIT, LIGHTING FlXTURES, FlTTING$ ETC., SHALL BE STORED IN CONSTRl1CTION BUILDINGS, COVERE� TRAILERS, OR PORTABLE COVERED WAREHOUSES. ANV EQUIPMENT SUBJECT TO DAMAGE OR CORROSION FROM E%CESSNE MOISTURE SHALL BE STOREo IN DRV, HEATEo AREAS. ANV EQUIPMENT CONTAINING PLASTIC OR MATERIAL SUBJECT TO DAMAGE CAUSED BY EXCESSNE HEAT OR SUNLIGHT SHALL BE STORED TO PREVENT SUCH DAMAGE. THIS INCW DES PLASTIC DUCTS AND LENSES. 3. EpUIPMENTDAMAGEDASARESl1LTOFTHEABOVECONDITIONSSHALL6EPROPERLVREPAIRED AT THE CONTRACTOR'S EMPENSE OR SHALL BE REPLACED AT THE CONTRACTORS EXPENSE, IF IN THE OPINION OF THE ENGMEER, THE E�UIPMENT HAS BEEN DAMAGED TO SUCH AN EXTENT THAT IT CANNOT OPERATE PROPERLY AFTER REPAIRS ARE MADE. 4. ALL ELECTRICAL ENCLOSURES EXPOSED TO CONSTRUCTION DAMAGED SUCH AS PAINT SPOTS, SPACKLING ORPLASTERSPATTER,GROUTSPLASHES,WATERPROOFMGCOMPOUND,TARSPOTS OR RUNS, ANo PIPE COVERING COMPOUND SPLASHES, SHALL BE COMPLETELV COVERED AND PROTECTED AGAINST OAMAGE. 5. IN THE EVENT LEAKAGE INTO THE BUILDING OF ANY FOREIGN MATERIAL OR FLUID OCCURS OR MAY OCCUR, THE CONTRACTOR SHALL TAKE ALL STEPS AS DESCRIBED ABOVE TO PROTECTANV AND ALL EQUIPMENT. 6. AFfER CONNECTIONS TO ELECTRICAL W UIPMENT ARE COMPLETE AND THE E�UIPMENT IS READY FOR OPERATION, ALL CONSTRUCTION DEBRIS SHALL BE REMOVED FROM ALL ENCLOSURES. SUCH DEBRIS WCWOES OUST, DIRT, W IRE CLIPPINGS, TAPE, AND WSULATION REMOVED IN ORDER TO MAKE THE CONNECTION. 17 SAFETV AND INDEMNITY A. THE CONTRACTOR SHALL BE SOLELV AND COMPLETELY RESPONSIBLE FOR CONDITIONS OF THE J08 SITE, W CLU�ING SAFETY OF ALL PERSONS AND PROPERTV �URING PERFORMANCE OF THE WORK. THISREQUIREMENTWILLAPPLVCONTINUOUSLYANONOTBELIMITEDTONORMAL W ORKING HOURS. SEE ALSO GENER4L CONOITIONS. B. NO ACT, SERVICE DRAW INGS REVIEW OR CONSTRUCTION REVIEW BV THE ARCHITECT OR ENG W EER, IS INTENDED TO INCLUDE REVIEW OF THE ADE�UACV OF THE CONTRACTOR'S SAFETY MEASURES IN, ON, OR NEAR THE CONSTRUCTION SITE. 1 8 WARRANTIES A. THE WARRANTV PERIOD IS GENERALLV ONE VEAR AFTER DATE OF ACCEPTANCE. 1. DURWG THIS PERIO�, PROVIDE LABOR AND MATERIALS AS REQUIRED TO REPAIR OR REPLACE DEFECTS IN THE ELECTRICAL SVSTEMS AT NO COST TO THE OWNER. PROVIDE CERTIFlCATE W ITH O& M MANUAL SUBMITTAL W HICH GUARANTEES SAME DAY SERVICE RESPONSE TO THE OWNER'S CALL FOR SUCH WARRANTV SERVICE. 2 PROVIDE CERTIFICATES FOR SUCH ITEMS OF EQUIPMENT W HICH HAVE WARRANTIES IN EXCESS OF ONE VEAR. INSERT COPIES IN O& M MANUAL. 3. PROVIDEEMENDEDMANUFACTURERSWARRANTIESTOCOVERONEFULLVEARFROMDATEOF ACCEPTANCE IF STANDARD MANUFACTURERS' WARRANTV ENDS ANV TIME PRIOR TO THAT OATE. RELEA5E0 FOR CONSTRUCTION Suhjec��ocompliancewithallregula�ions SPONSIBILITVFORLAVINGOUTHISWORKANDFORANV 04 S�a�e antl Local Codes 2 SUB-CONTRACTORS BV IMPROPER LOCATION OR City of Carmel r �un��V l�rc�alols�. � DATE: OH�Z5 2O B. THE CONTR4CTOR SHALL PROVIDE PROPER GUARDS FOR PREVENTION OF ACCIDENTS, AND PROVIDE AND MAINTAIN ANV OTHER NECESSARV CONSTRUCTION REpUIRED TO SECURE SAFETY OF LIFE OR PROPERTY TO SECURE SUCH PROTECTION. 12 BVPASSCONNECTIONS A. THE CONTRACTOR SHALL INCW�E ALL COSTS FOR REMOVALS AND RELOCATIONS IN THE CONTRACT. THESECOSTSSHALLINCWOEWORKDESCRIBEDINTHESPEGFICATIONSAN�SHOWN ON THE DRAWINGS W ITH ALLOWANCES FOR NORMAL UNFORESEEN �IFFICULTIES WHEN CONCEALED W ORK HAS BEEN OPENE�. A MINIMUM OF (70) BVPASS CONNECTIONS SHALL BE WCLUOED. EACHBVPASSCONNECTIONSHALLCONSISTOFSOFEETOF4INCHEMTCONDUITWITH 4#5�0 AW G AND iN3 AW G GROUND CONDUCTORS, (2) JUNCTION BOXES, (4) 90 DEGREES BENOS, AND ALL APPURTENANCES AS REQUIRED FOR CONNECTIONS; BVPASS CONNECTIONS W OULD BE INSTALLED 11 FEET HIGH IN CONGESTED AREA, ANo BE SUPPORTED FROM STRUCTURE ABOVE. WCLUDE COST OF CUTTING AND REMOVAL OF FEEDER TO BE BVPASSED. BVPA55 CONNECTION INSTALLATION SHALL BE PRICED ON AN OVERTIME SCHEDULE BASIS. 1.3 SHUTDOWNS A. WHEN WSTALLATION OF A NEW SVSTEM OR RECONNECTION OF AN EXISTING SVSTEM RE�UIRES THE TEMPORARY SHUTDOWN OF AN EXISTMG OPERATING SVSTEM, THE CONNECTION INTO THE EXISTING SVSTEM SHALL BE PERFORMEO AT SUCH TIME AS DESIGNATED BV THE OW NER. A. THEOWNERSHALLBENOTIFIEDOFTHEESTIMATEDDl1RATIONOFTHESHUTDOWNPERIOD(3) W EEKS IN ADVANCE OF THE �ATE THE WORK IS DESIRED TO BE PERFORMED. B. WORK SHALL BE ARRANGED FOR CONTINUOUS PERFORMANCE, INCLUDING OVERTIME, AT NO EXTRA COST TO THE OW NER TO ASSURE THAT EXISTING OPERATING SERVICES W ILL BE SHUT DOWN ONLV DURING THE TIME ACTUALLV REQUIRED TO MAKE NECESSARV CONNECTIONS. fE�HQ�I:��]IJ_tlPP\rplll:ly/F911�RIHRNI1JIy�L1:�Y_FY A. MINIMIZEDISRUPTIONSTOOPERATIONOFBUILDINGSVSTEMSINOCCUPIEDAREAS. B. PROVIDE TEMPORARV CONNECTIONS TO PREVENT LONG DISRUPTIONS. G PROVIDEMULTIPLECREWS,PftEMIUMTIMELABORAN�/ORSHIFTLABORTOREDUCEDURATIONOF WORK AND IMPACT ON THE FACILITV. D. WHEN INSTALLATION OF A NEW SVSTEM REpUIRES THE TEMPORARV SHUTDOW N OF AN EXISTING OPERATING SVSTEM, THE CONNECTION OF THE NEW SVSTEM SHALL BE PERFORMED AT SUCH REGULAR TIME OR AT OVERTIME W HEN DESIGNATED BV THE OW NER. ASSUME ALL CONNECTIONS TO EXISTING OPERATIONAL SVSTEMS W ILL BE ON PREMIUM TIME, PROVIDE A CREDIT FOR ALL W ORK ALLOW ED TO OCCUR ON NORMAL TIME. 1.5 ENGINEERINGBVCONTRACTOR A. THE CONSTRUCTION OF THIS WORK REQUIRES THE CONTRACTOR TO PERFORM CERTAIN DESIGN ACTIVITIES W ITH REGARD TO SEVERAL OF THE CONTRACT SVSTEMS OR SUBSVSTEMS THAT CAN ONLV BE FULLV ASCERTAMED W ITH REGARD TO THE PREVAILING SITE FlELD CONDITIONS DURING CONSTRUCTION ACTIVITIES. ALL SUCH DESIGNS AND RELATED ACTIVITIES SHALL BE THE COMPLETE RESPONSIBILITV OF THE CONTRACTOR. W HERE THESE DESIGN ACTNITIES REQUIRE ENGMEERING IT IS THE RESPONSIBILITV OF THE CONTRACTOR TO ENGAGE THE SERVICE OF A LICENSED INDIANIA STATE PROFESSIONAL ENG W EER EXPERIENCED IN THE AREAS RELATED TO THE DESIGN ACTIVITIES PERFORMED BV THE CONTRACTOR. B. SVSTEMS OR SUBSVSTEMS W HICH REQUIRE ENGINEERING RESPONSIBILITY BV THE CONTRACTOR W C W DE, BUT ARE NOT LIMITED TO: 1. ANV SVSTEM NOT FULLV DETAILED ON THE DRAW INGS. 2 RRE ALARM. 3. E�UIPMENTSUPPORTS,NOTFULLVDETAILEDINTHEDRAWINGS. 4. CONDUITHANGERSANDANCHORSNOTSPECIFIEDMTHESEDOCUMENTS,ORCATALOGEDBV THEMANUFACTURER. 5. VIBRATION ISOLATORS AND SEISMIC RESTRAINTS. 6. MISCELLANEOUSSTEELASRWUIRED. ].E�UIPMENTSUPPORTS,HANGERS. 8. PULL BOX AND SPLICE BOX pUANTITIES AND SIZES. G CONTRACTOR'S DESIGN RESPONSIBILITV SHALL INCLUDE SVSTEM DESIGN, ANV REQUIRED CALCULATIONS TO SUPPORT SVSTEM DESIGN, ANV COMPLIANCE DOCUMENTS OR CERTIFICATIONS BY ANV GOVERNING BODV UP TO AND INCLUDING REPLACEMENT OF DESIGN ENGMEER W ITH A DIFFERENT ENGMEER OF RECORO, RETAMED AND PAID BV THE WNTRACTOR, AS DETERM WED BV AUTHORITIES OR ORIGINAL DESIGN ENGINEER. D. CONTRACTOR SHALL COMPLETE ALL CONTROLLED OR SPECIAL INSPECTIONS AND FILE ALL REQUIREDPAPERWORKINATIMELVMANNER. PROFESSIONALENGINEERRETAINEDBV CONTRACTOR TO SERVE AS "SPEqAL INSPECTOR" SHALL MEET ALL REQUIREMENTS FOR SPECIAL INSPECTOR AS DETERMINED BY THE AUTHORITV HAVING JURISDICTION. IJ_1:i�'aJdH�l1[NF`: 2.1 EQUIPMENTAND MATERIALS A. ALLE�UIPMENTANDMATERIALSINSTALLEDSHALLBENEW,UNLESSOTHERWISESPEqFlED. B.ALLMAJOREOUIPMENTCOMPONENTSSHALLHAVE MANUFACTURERS'NAME,A�DRESS,MODEL NUMBER AND SERIAL NUMBER PERMANENTLV ATTACHED IN A CONSPICUOUS LOCATION. C. ALL EpUIPMENT SHALL BE UL LISTED AND BEAR THE UL LABEL. 22 GENERAL SUBMITTAL REQUIREMENTS A COORDINATION AND SE�UENCMG 1. AFTER RECEIPT OF NOTICE TO PROCEED, THE CONTRACTOR SHALL SUBMIT TO THE ARCHITECT A TVPED LIST OF SUBMITTALS AND THE SCHEDULED DATE OF SUBMISSION. LIST SHALL W C W DE SUBMITTAL NUMBER, SECTION NUMBER AN� SCHEDULED DATE OF SUBMISSION. SUBMITTALS SHALL BE GROUPED AND SUBMITTED IN NO MORE THAN TEN COMPLETE PACKAGES. 2. THE CONTRACTOR SHALL NOT SUBMIT ANV SHOP DRAW INGS OR PRODUCT DATA THAT DOES NOT COMPLYWITHTHECONTRACTDOCUMENTS. PRIORTOSUBMITTINGSHOPDRAWINGS,REVIEW SUBMITTAL FOR COMPLIANCE WITH CONTRACT OOCUMENTS ANO PLACE A STAMP OR OTHER CONFIRMATION THEREON W HICH STATES THAT SUeMITTALS HAVE BEEN REVIEW ED. SUBMITTALS W ITHOUT SUCH VERIRCATION W ILL BE RETURNED DISAPPROVED W ITHOUT REVIEW. 3. SUBMITTAL IS FOR WFORMATION AND RECORD, UNLE55 OTHERW ISE INDICATED, AND IS NOT A CHANGEORDERREQUEST. B. PREPARATIONOFSl1BMITTALS: 1. REFERTO DNISION 1 REQUIREMENTS. 2. THE CONTRACTOR SHALL SUBMIT FOR APPROVAL BV THE ARCHITECT DATA OF MATERIALS AND EQUIPMENT TO BE WCORPORATED IN THE WORK. SUBMITTALS SHALL BE SUPPORTED BV DESCRIPTNE MATERIAL, CATALOGS, CUTS, DIAGRQMS, PERFORMANCE CURVES, AND CHARTS PUBLISHED BV THE MANUFACTURER TO SHOW CONFORMANCE TO SPEGFICATION AND DRAW ING REQUIREMENTS; MODEL NUMBERS ALONE W ILL NOT BE ACCEPTABLE. PROVIDE COMPLETE ELECTRICALCHARACTERISTICSFORALLEQUIPMENT. SUBMITPRODUCTSUBMITTALSONITEMS AS OUTL W ED IN SECTIONS HEREINAFTER. 3. PROOUCT SUBMITTALS SHALL BE MA�E BV SPECIFICATION SECTION. ALL ITEMS OF A SECTION, REQUIRWG SUBMISSION, SHALL BE SUBMITTED TOGETHER AT ONE TIME IN A TABBED BINDER OR SEPARATE ELECTRONIC FlLES. IF TWOOR MORE SECTIONS REQUIRE INTER-COOR�INATION (EG., SHORT qRCUIT STUDV, ELECTRICAL ROOM LAVOUTS AND ELECTRICAL SW ITCHBOARDS, PANELBOARD, FIRE ALARM AND FIRE COMMAND CENTER LAYOUT), THEY SHALL BE SUBMITTED AT THE SAME TIME. 4. EACH INDIVIOUAL SUBMITTAL ITEMS SHALL BE MARKED TO SHOW SECTION NUMBER W HICH PERTAWS TO THE ITEM. 5. PROVIDE PERMANENT MARKING IDENTIFVING PROJECT NAME, CONTRACTOR, SUBCONTRACTOR, SUBMITTAL NAME, DATE OF SUBMISSION, SPEQFICATION SECTION, AND INFORMATION TO DISTINGUISH IT FROM OTHER Sl1BMITTALS. 6. SECTION BIN�ERS SHALL BE REPORT COVER TYPE W ITH SOLI� COVER AND 3 METAL FASTENERS. BINDERS SHALL ALSO HAVE A TAB INDICATING SUBMITTAL NUMBER AND SPEQFlCATION SECTION NUMBER. IF PRODUCT SUBMITTALS FOR SECTION EXCEED THE CAPAQTV OF ONE BIN�ER, TW O OR MORE BINDERS SHALL BE USED. IN AODITION, A NOTATION COVER SHALL INDICATE THE NUMBEROFBINDERSFORTHESECTIONANDNUMBEROFTHATBINDER(IE.20R3). BINDERS SHALL HAVE RIGID COVER AND BE OF APPROPRIATE SIZE. IF ELECTRONIC COPV IS PROVIDED FOR REVIEW, CONTRACTOR SHALL PROVIDE (1) HARD COPV OF MAJOR EQUIPMENT PRODUCT DATA (PANELBOARDS. SHOP ORAW INGS, LIGHTING) AND COORDINATION DRAW INGS. ]. SUBMITTALSNOTPRESENTEDINABOl1ND,NEATANOLEGIBLEFASHIONWILL RETURNED`WITHOUTACTIONI' 8. SUBMITTALS SHALL SHOw CONTRACTOR'S EXECUTED REVIEW AN� APPROVAL MARKMG. SUBMITTALS W HICH ARE RECENED FROM SOURCES OTHER THAN THROUGH CONTRACTOR'S OFFICE WILL BE RETURNED' W ITHOUTACTIOM' 9. PROVIDESPACEFORARCHITECT'S"ACTIOM'MARKING. G SUBSTITUTIONS 1. REFERTOTHEGENERALCONDITIONS,WHICHGOVERNS"SUBSTITUTION"OFSPEqRED EQUIPMENT OR MATERIALS. 2. INDICATE ANV PORTIONS OF W ORK WHICH DEVIATE FROM THE CONTRACT OOCUMENTS. a EXPLAIN THE REASONS FOR THE OEVIATIONS. b SHOW HOW SUCH DEVIATIONS COORDINATE W ITH INTERFAqNG PORTIONS OF OTHER WORK. 3. W HERE SUBSTITUTION OF MATERIALS ALTERS SPACE REQUIREMENTS INDICATED ON THE DRAW INGS, SUBMIT SHOP �RAW INGS INDICATING PROPOSED LAYOUT OF SPACE, ALL EQUIPMENT TO BE INSTALLED THEREIN AN� CLFARANCES BETW EEN EOUIPMENT Q.E., ELECTRICAL ROOMS). ALL CLEARANCES REpUIRED BV THE NATIONAL ELECTRICAL CODE AND APPLICABLE STATE AND LOCAL REGULATIONS MUST BE MAINTAINED. D. REVIEW PROCESS 1. THE ARCHITECT RESERVES THE RIGHT TO REQl11RE A SAMPLE OF ANV EQUIPMENTTO BE SUBMITTED FOR APPROVAL AND TO RETAIN ITS POSSESSION. 2. REFER TO THE IN�IVIDUAL SECTIONS FOR IDENTIFIED EQUIPMENT AND MATERIAL FOR W HICH SUBMITTALS ARE REQUIRED. IN ADDITION, PROVI�E SHOP DRAW INGS AND PROOUCT DATA ON THE FOLLOW ING EQUIPMENT: ELECTRICAL POW ER CONDUCTORS AND CABLES GROUNDING AND BONDING HANGERS AND SUPPORTS RACEWAV AND BOXES VIBRATION AND SEISMIC CONTROLS IDENTIFICATION PANEL BOARDS FUSES LIGHTMG FI%TURES ENCLOSED SW ITCHES AND CIRCUIT BREAKERS RRE ALARM SVSTEM LIGHTING CONTROL DEVICES. DO NOT SUBMIT ON EQUIPMENT OR MATERIALS NOT REQUESTED IN THE SPEqRCATIONS. 3. REVIEWOFSHOPDRAWINGSANDPRODUCTDATABVTHEARCHITECT/ENGMEER,INCWDINGANV REVIEW ANNOTATIONS OR STAMP NOTATIONS, DOES NOT RELIEVE THE CONTRACTOR FROM THE REQUIRED COMPLIANCE W ITH THE CONTRACT DOCUMENTS. 4. THE SHOP DRAW ING AND PRODUCT DATA REVIE W STAMP NOTATION RE�UIREMENTS ARE DEFlNEDAS FOLLOWS: a.NOE%CEPTIONTAKEN"THEREVIEWERDI�NOTOBSERVEANVITEMS WHICHWERENOTIN COMPLIANCE W ITH THE CONTRACT DOCUMENTS. ALL DIMENSIONS, �ETAILS, AN� COORDINATION WITH OTHER TRAOESIS THE RESPONSIBILITV OF THE WNTRACTOR. b. MAKECORRECTIONSNOTE�'."THEREVIEWERINDICATEDITEMS OBSERVEDTHATWERENOT IN COMPLIANCE W ITH THE CONTRACT OOCUMENTS. THE CONTRACTOR SHALL NOT RESUBMIT. BUT SHALL MAKE CORRECTIONS AND PROVIDE CORRECTE� DOCUMENTS W ITH THE "RECORD DRAWINGS" c. REJECTED,REVISEANDRESUBMIT:"THEREVIEWERINDICATEDITEMSOBSERVEDWHICHWERE NOT M COMPLIANCE W ITH THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL RESUBMIT SHOW ING CORRECTIONS OF ALL NOTED ITEMS. DELAVS FOR RESUBMITTAL DOES NOT RELIEVE THE CONTRACTOR FROM MEETING PROJECT SCHEDULES. d. REJECTED"THESUBMISSIONDOESNOTCOMPLYWITHTHECONTRACTREQUIREMENTS. THE ENTIRESUBMITTALMUSTBECORRECTEDANOSUBMITTEDFORREVIEW. DELAVSFOR RESUBMITTAL WES NOT RELIEVE THE CONTRACTOR FROM MEETING PROJECT SCHEDULES. 5. IF SHOP �RQW INGS ARE SIIBMITTED AND RETURNED AS "NO EXCEPTION TAKEN" OR "MAKE CORRECTIONS NOTED" AND MEET CONTR4CT REQUIREMENTS, THE CONTRACTOR SHALL NOT RESUBMIT ANV OTHER SHOP DRAW WGS FOR THESE ITEMS. 6. IF RESUBMITTALS ARE NECESSARV. THEY SHALL BE MADE AS SPECIFlED ABOVE FOR SUBMITTALS. RESUBMITTALS SHALL HIGHLIGHT ALL REVISIONS MADE AND CWER SHALL INCLUDE THE PHRASE "RESUBMITTAL NO. "RESUBMITTAL REQUIREMENTS �O NOT ENTITLE THE CONTRACTOR TO ADOITIONAL TIME AND ARE NOT A CAUSE FOR DELAV OF THE PROJECT. PART3-EXECUTION FiUIN�P]IR�PFY_\E-Y11- A. VISIT TO SITE IS REQUIRED OF ALL BIDDERS PRIOR TO SUBMISSION OF BI�. ALL BID�ERS W ILL BE HEL� TO HAVE FAMILIARIZE� THEMSELVES W ITH ALL DISCERNIBLE CONDITIONS, AND NO E%TRA PAYMENT WILL BE ALLOW ED FOR WORK REQUIRED BECAUSE OF THESE CONDITIONS, WHETHER SPEQFlCALLV MENTIONED OR NOT. B. LINESOFOTHERSERVICESAND/OREQUIPMENTTHATAREDAMAGE�ASARESULTOFTHISWORK SHALL PROMPTLV BE REPAIRED AT NO EXPENSE TO THE OW NER. 3 2 LICENSES, FEES AND PERMITS A. ARRANGE FOR RE�UIRED INSPECTIONS AND PAV ALL LICENSE, PERMIT AND WSPECTION FEES. FURNISH A CERTIFICATE OF FINAL INSPECTIONS AND APPROVALS FROM LOCAL AUTHORITV HAVING JURISDICTION OVER ELECTRICAL WSTALLATION. 3 3 W ORKMANSHIP AND CONTRACTOR'S OUALIFICATIONS A. ONLV PROFESSIONAL QUALITV W ORKMANSHIP W ILL BE ACCEPTE�. HAPHAZARD OR POOR INSTALLATION PRACTICE W ILL BE CAUSE PoR REJECTION OF WORK. B. PROVIDEFOREMANINCHARGEOFTHISWORKATALLTIMES. FOREMENFORTHISWORKSHALL HAVE HAO EXPERIENCE IN WSTALLING NOT LESS THAN 5 SUCH ELECTRICAL SVSTEMS OF EQUAL OR GREATER COMPLEXITV. C. W HERE SPECIFlCATIONS CALL PoR AN INSTALLATION TO BE MADE IN ACCORDANCE W ITH MANUFACTURERS' RECOMMENDATIONS, A COPV OF SUCH RECOMMENDATIONS SHALL AT ALL TIMES BE KEPT IN JOB SUPERINTENOENT'S OFFlCE. kEl:iyCtl[�P\r�rllC[�l1.ly:il:LUlyB A. CONTRACTOR SHALL COOROINATE WORK OF THIS OIVISION W ITH OTHER TRADES TO AVOID CONFLICT AND TO PROVI�E ROUGH-INS AND OTHER CONNECTIONS FOR EQUIPMENT FURNISHED UNDER OTHER DNISIONS THAT REQUIRE ELECTRICAL CONNECTIONS. MFORM OTHER TRADES OF REQUIRED CLEARANCES OF ACCESSES FOR OR AROUND ELECTRICAL EQUIPMENT TO MAINTAIN SERVICEABILITY AND CODE COMPLIANCE. B. VERIFV E�UIPMENT DIMENSIONS AND ROUGH-IN REQUIREMENTS FOR DIVISIONS 2 THROUGH 28 W ITH PROVIS10NS SPECIFlED UNDER THIS SECTION OF W ORK, AND REPORT DISCREPANCIES TO THE ARCHITECT IN AMPLE TIME TO PREVENT DELAVS OR UNW ARRANTED CHANGES OF W ORK. 3 5 TESTING A. PROVIDE ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARV TO MAKE REQUIRED TESTS. TESTS SHALL BE COMPLETE AND RESULTS APPROVED BEFORE FINAL INSPECTION IS BEGUN. 3.6 PROGRESS OF WORK A. ORDER PROGRE55 OF ELECTRICAL WORK SO AS TO CONFORM TO PROGRE55 OF W ORK OF OTHER TRADES, AND COMPLETE ENTIRE WSTALLATION AS SOON AS CONDITION OF BWLDING W ILL PERMIT. ASSl1ME ANV COST RESULTING FROM DEFECTNE OR ILL-TIMED WORK PERFORMED 11NDER THIS DIVISION. 3] CUTTING AND PATCHING A. GENERAL: PERFORM CUTTING AND PATCHING IN ACCORDANCE W ITH DIVISION 1 SECTION "CUTTING ANOPATCHING" INADDITIONTOTHEREQUIREMENTSPEGFIEDINDIVISIONI,THEFOLLOWING REQUIREMENTS APPLV: 1. PERFORMCUTTING,FlTTING,ANDPATCHINGOFELECTRICALEQUIPMENTANDMATERIALS REQUIRED TO: a. UNCOVER WORK TO PROVIDE FOR INSTALLATION OF ILL-TIMED WORK. b. REMOVEANDREPLACEDEFECTIVEWORK. a REMOVE AND REPLACE WORK NOT CONFORMING TO REQUIREMENTS OF THE CONTRACT DOCUMENTS. tl. REMOVE SAMPLES OF INSTALLED WORK AS SPECIFlED FOR TESTIN6. e. WSTALLEQUIPMENTANOMATERIALSINNEWLYINSTALLEDSTRUCTURES. C UPON WRITTEN INSTRUCTIONS FROM THE ARCHITECT, UNCOVER AND RESTORE WORK TO PROVIDE FOR ARCHITECT OBSERVATION OF CONCEALED W ORK. 3.8 SLEEVES A. PLACE SLEEVE W FORMS OF WALL$ ROOR SLABS AND PARTITIONS FOR PASSAGE OF ALL CON�UITS, PIPES, AND DUCTS INSTALLED UNDER OIVISIONS 26, 2] AND 28. SLEEVES SHALL BE SET IN PLACE A SUFFICIENT TIME AHEAD OF CONCRETE WORK SO AS NOT TO DELAV THAT WORK. INSTALL SLEEVES AND RACEWAVS THROUGH EXTERIOR WALLS SO AS TO PROVIDE A WATERPROOF INSTALLATION. ALL ROOR PENETRATIONS SHALL BE MADE WATERTIGHT. CONDUITS PASSMG THROUGH WALLS SHALL BE INSTALLED TO PRESERVE INTEGRITV OF THE WALL RATING (LE., FIRE RATING, SOUNO RATING, AIR, ETCJ. ALL PENETR4TION MADE THROUGH EXISTING CONCRETE SLABS OR WALLS SHALL BE %-RAVED AND APPROVE� BV STRUCTURAL ENGINEER PRIOR TO CUTTING 39 QEANUP A. REMOVE ALL MATERIALS, SCRAP, ETC., RELATNE TO ELECTRICAL INSTALLATIONS AND LEAVE PREMISES IN A CLEAN, OROERLV CONDITION. ANV COSTS TO THE OWNER FOR CLEANIIP OF SITE W ILL BE CHARGED TO THE WNTRACTOR. AT COMPLETION, ALL EQUIPMENT, RACEWAVS, ETC., SHALL BE THOROUGHLV CLEANED AN� ALL RESI�UE REMOVE� FROM THE INSIDE AND OUTSIDE SURFACES. DEFACEDFlNISHSHALLBERERNISHED. 3.10TEMPORARYPOWER A. PROVIDE TEMPORARV POWER AS REOUESTED BV THE GENER4L CONTRACTOR AND IN ACCORDANCEWITHOSHAANDLOCALCODEREQUIREMENTS. LIGHTINGANDPOWEROUTLETS SHALL BE PROVIDED THROU6HOUT THE PROJECT. CHECK W ITH CONSTRUCTION MANAGER OR GENERAL CONTRACTOR PRIOR TO BID FOR SPEQAL LIGHTING AND POW ER OUTLETS AND PROVIDE AS NEEOED. 3.11 MINOR CHANGES A. THE OW NER RESERVES THE RIGHT TO MAKE MINOR CHANGES IN THE LOCATIONS OF OUTLETS AND EQUIPMENT UP TO THE TIME OF ELECTRICAL ROUGH-IN W ITHOUT ANV COST TO THE OW NER. SECTION 26 OS 04 - ELECTRICAL DEMOLITION AND RELOCATION PART 1 -GENERAL 1.1 RELATED �OCUMENTS A. THIS SECTION SUPPLEMENTS DIVISION 1, GENERAL REQUIREMENTS. W HERE CONTRADICTIONS OCCUR BETW EEN THIS SECTION AND DNISION 1, THE MORE STRINGENT OF THE TW O SHALL APPLV. THE ARCHITECT SHALL DEQDE WHICH IS MORE STRINGENT. B. REpUIREMENTSOFTHEFOLLOWINGDNISIONSANDSECTIONSAPPLVTOTHISSECTION: 1. DIVISION 26 SECTION 2605 02 "ELECTRICAL REQUIREMENTS" 2. DIVISION 9 SECTION `PAINTING" FOR RELATED REQUIREMENTS. C. REFER TO OTHER DIVISION 26 SECTIONS FOR ADDITIONAL SPEQFlC ELECTRICAL DEMOLITION OR RELOCATION ASSOCIATED W ITH SPEQFIC ITEMS. 125UMMARV A. THIS SECTION INCLUDES BASIC REQUIREMENTS FOR DEMOLITION AND RELOCATION OF ELECTRICAL MATERIAL$ WUIPMENT, AN� WSTALLATIONS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING THE SITE PRIOR TO BID TO DETERM W E THE ACTUAL CON�ITIONS, WHICHMIGHTAFFECTTHEBIDORCONTRACTPRICE NOALLOWANCEWILLBEMADE SUBSEQUENTLV RESULTING FROM THE NEGLECT TO VISIT THE SITE AND MAKE SUCH �ETERMINATIONS. B. GENERALLV, ELECTRICAL ITEMS THAT ARE TO BE REPLACED W ITH OTHER EQUIPMENT IN THE SAME LOCATION ARE WORK COVERE� BV THIS SECTION. ALSO COVEREO BV THIS SECTION ARE ELECTRICAL ITEMS THAT ARE TO BE REMOVED M THEIR ENTIRETV OR THAT ARE TO BE RELOCATED TO ANOTHER PLACE. 1.3 UTILITY SERVICES A. MAINTAM EXISTING UTILITY SERVICES. WHERE NECESSARV TO CUT EXISTING CONDUITS, W IRES, CABLES, ETC. OF UTILITV SERVICES OR FIRE PROTECTION SYSTEMS, THEV SHALL BE CUT AND CAPPED AT SUITABLE PLACES OR W HERE �IRECTED BV THE OWNER'S REPRESENTATIVE. B. ELECTRICAL SERVICE IN DEMOLITION AREA SHALL BE REDUCED TO A MINIMUM AND IDENTIFIED TO ELIMINATE UNCERTAINTV ABOUT W HICH qRCUITS ARE ENERGRED. G THE CONTRACTOR SHALL NOTIFV THE OW NER'S REPRESENTATNE IN W RITING OF ANV PLANNED UTILITV WTERRUPTIONS INC W DING INTERRUPTIONS OF POW ER TO COMMUNICATIONS ANO FIRE PROTECTION SVSTEMS AT LEAST 48 HOURS IN ADVANCE OR AS OTHERW ISE SPECIFIED. THE RE�UEST SHALL STATE THE REASON, DATE, BEGINNING TIME, AND EXPECTED DURATION OF SUCH INTERRl1PTIONS. NOINTERRUPTIONSSHALLBEMADEWITHOUTTHEOWNER'SWRITTEN CONCl1RRENCE AND Sl1CH INTERRUPTIONS SHALL BE COORDINATED W ITH THE OWNER TO CAUSE THE LEAST WCONVEMENCE TO THE OWNER'S OPERATIONS. SERVICE INTERRUPTIONS WHICH CANNOT WAIT FOR W RITTEN APPROVAL MAV BE GRANTED W ITH VERBAL APPROVAL FROM THE OWNER'S REPRESENTATIVE. AFTER VERBAL APPROVAL IS GRANTED, WRITTEN CONFIRMATION SHALL BE ISSUE� BV THE CONTRACTOR AS SOON AS PRACTICAL. 14PROTECTNEMEASURES A. PROVIDE THE FOLLOW ING PROTECTNE MEASURES: 1. WHEREVER EXISTING ROOFING SURFACES ARE PENETRATED BV ELECTRICAL CONDUIT, THEV SHALL BE PROTECTED AGAINST WATER INFlLTRATION. WATER LEAKS SHALL BE REPAIRED IMMEDIATELV 11PON DISCOVERV WHEN THEV OCCUR. 2. TEMPORARV PROTECTION AGAWST oAMAGE FOR ALL PORTIONS OF EXISTING STRUCTURES AND 6ROUNDS W HERE WORK IS TO BE DONE MATERIALS HANDLED, AND EQUIPMENT MOVED OR RELOCATED. 3. CONTRACTOR SHALL PATCH AND FlLL OPENINGS IN FLOORS, WALLS AND CEILINGS FOR REMOVED EQUIPMENT OR PIPING W ITH THE SAME MATERIAL, FlRE AND STRUCTURAL INTEGRITV THAT W OULD HAVE EXISTED PRIOR TO THE PENETRATION INCLUDING CONCRETE, BLOCK, GVP WALLBOARq EXTERIOR WALLS, ROOF MEMBRANES, ETG EXCEPT FOR STEEL AND WOOD BEAMS W HICH SHALL HAVE THE OPENINGS CAPPED W ITH SIMILAR MATERIAL. PART2-PRO�l1CT5 2.1 EQUIPMENT AND MATERIALS B. THE CONTRACTOR SHALL PROV IDE ALL E�UIPMENT AND MATERIALS NECESSARV FOR THE REMOVAL OR RELOCATION OF ELECTRICAL EQUIPMENT. C. MATERIALS USED IN RESTORATION OR REPAIRING WORK RELATED TO DEMOLITION AND RELOCATION SHALL CONFORM IN TVPE, QUALITV, AND FUNCTION TO THAT OF THE ORIGINAL EXISTING CONSTRUCTION OR AS OTHERWISE INDICATED. 22 DISPOSAL AND RETENTION A. MATERIALS AND EQUIPMENT RESULTING FROM WORK AND REMOVED FROM THE BUILDING OR STRUCTURES,ORPARTSTHEREOF,SHALLBECOMETHEPROPERTVOFTHECONTRACTORAND SHALL BE REMOVED FROM THE SITE BV THE CONTRACTOR EXCEPT AS FOLLOW: L LIGHT FIXTURES, LAMPS, AND BALLASTS. 2 FlRE, HEAT, AND SMOKE DETECTION DEVICES. 3. TELEPHONESANDTELEPHONEEQUIPMENTOTHERTHANOUTLETDEVICES. 4. FIRE ALARM NOTIFICATION DEVICES AND PULL STATIONS. 5. PAGING SPEAKERS, CLOCKS, AND INTERCOM CALL STATIONS. B. ITEMS REMOVED OR NOTED TO BE RETAWED BY THE OW NER BUT WHICH ARE DECLMED TO BE RETAINED BV THE OWNER SHALL BE REMOVED FROM THE SITE BV THE CONTRACTOR. C. COMBUSTIBLE WASTE MATERIAL AND RUBBISH SHALL NOT BE STORE� OR ALLOW ED TO ACCUMULATE W ITHIN A BUILDING OR ITS VICINITV, BUT SHALL BE KEPT IN A SUITABLE TRASH CONTAINER FOR SUBSEQUENT REMOVAL OR SHALL BE REMOVED FROM THE PREMISES AS RAPIDLV AS PRACTICAL. D. ALL HAZARD WASTE SHALL BE PROPERLV �ISPOSE� OF BV A LICENSED HAZARD WASTE DISPOSAL FACILITY. ITEMS SHALL INCWDE BUT NOT LIMITED TO FWORESCENT LAMPS, DIESEL FUEL, RADIATOR COOLANT, ETC. PART3-EXECUTION A. REMOVE OR RELOCATE ALL ITEMS INDICATED ON THE DRAW IN6S OR AS OTHERW ISE INDICATED. B. WHERETHEORAWINGSINDICATETHATEQUIPMENTISTOBEREPLACEDORWHEREOTHER EQUIPMENT REpUIRES THE RELOCATION OF EXISTING EOUIPMENT, THE EXISTING EQUIPMENT SHALL BE REMOVED OR RELOCATED AS THOUGH IT WAS SPEqFICALLV NOTE� TO BE REMOVED OR RELOCATED. C. WHEREVER ELECTRICAL MATERIALS HAVE BEEN REMOVED FROM SURFACES OF THE BUILDING OR STRUCTURE, THOSE SURFACES SHALL BE PATCHED AND REPAIRED. D. REMOVE, CUT, ALTER, REPLACE, PATCH, AND REPAIR E%ISTING WORK AS NECESSARV TO INSTALL NEW WORK. UNLESS OTHERW ISE INDICATED OR SPEGFIED, DO NOT CUT, ALTER, OR REMOVE ANV STRUCTURAL MEMBERS, �UCTS, PIPING, OR SERVICE LMES W ITHOUT APPROVAL OF THE OW NER'S REPRESENTATNE. E. EXISTINGWORKOREpUIPMENTTOBEALTERE�OREXTENDEDANDFOUNDTO6EDEFECTNE SHALL BE REPORTED TO THE OWNER'S REPRESENTATIVE BEFORE IT IS DISTURBED OR ANV FURTHER WORK IS PERFORMED ON IT. F. W HERE ELECTRICAL E�UIPMENT IS INDICATED TO BE REMOVED OR RELOCATED, THE WORK SHALL INCLUDE THE COMPLETE DISCONNECTION FROM ITS SOURCE, DISMANTLING AS NECESSARV, AND REMOVAL OR INSTALLATION OF ALL CONOUIT, W IRES, CABLES, ETC. UNLESS NOTED OTHERW ISE, WIRES SHALL BE REMOVED FROM CONDUITS BACK TO THE LAST UTILRATION DEVICE OR TO THE PANELBOARD. NO W IRING SHALL BE REMOVED THAT PREVENTS OPERATION OF OTHER E�UIPMENT NOT SCHEDULED OR INDICATED TO BE REMOVED. G. PERFORM AND SCHEDULE ALL DEMOLITION WORK W ITH OTHER TR4DES AND WORK OF THE W NTRACT AS NECESSARY FOR THE EFFIQENT PROGRESS AND FLOW OF THE W ORK. END OF SECTION 260504 SECTION 260506 - BASIC MATERIAL AND METHODS PART1-GENERAL 1.iRELATEODOCUMENTS A. THIS SECTION Sl1PPLEMENTS DIVISION 1, GENERAL REQUIREMENTS. 12 DESCRIPTION OF WORK A. WORKINCLUDE�INTHISSECTIONCONSISTSOFCONDUITS,WIRESANDOTHERMISCELLANEOUS MATERIALS NOT SPEQFICALLV MENTIONED IN OTHER SECTIONS OF DIVISION 2fi, 2] AND 28 BUT NECESSARV OR REQUIRED FOR EQUIPMENT OR SYSTEM OPERATION OR FUNCTION, AND THE LABORTOINSTALLTHEM. 1.3 SUBMITTALS A. MATERIALS LIST W ITH MANUFACTURER, STVLE, SERIES OR MODEL IDENTIRED. B. MANUFACTURER'S DESCRIPTNE LITERATURE AND/OR SAMPLE IF REQUESTED BV THE ARCHITECT/ENGMEER. PART 2 - PRO�l1CT5 2.7 CONDUIT RACEWAVS: REFER TO SECTION 26 05 33. 22ELECTRICALPOWERCONDUCTORSANDCABLES: REFERTOSECTION260519. 2.3 W IRING DEVICES: REFER TO SECTION 26 2I 26. 24 OUTLET BOXES, JUNCTION AND PULL BOXES A. OUTLET BOXES: HOT-DIPPED GALVANIZED OR SHERARDIZED OF RE�UIRED SIZE, 4" S�UARE MINIMUM, FOR RUSH MOUNTED DEVICES AND LIGHTING FIXTURES. CAST-TVPE F� WITH GASKETED COVERS FOR SURFACEMOUNTED DEVICES. B. JUNCTION ANO PULL BOXES: USE OUTLET BOXES AS JUNCTION BOXES WHEREVER POSSIBLE. LARGER JUNCTION AND PULL BOXES SHALL BE FABRICATED FROM SHEET STEEL, SIZED ACCOR�MG TO CODE, W ITH SCREW-ON COVERS, GALVANIZED WHERE REQUIRED FOR OUT�OOR EXPOSURE. C. ALL EXTERIOR BOXES SHALL BE CAST, GASKETED, WEATHERPROOF TVPE W ITH CAST COVERS. D. REFERTOSECTION260533FORADDITIONALREpUIREMENTS. 25 W IRE CONNECTORS A PoR W IRES THAT ARE #8 AW G AND SMALLER: INSULATED PRESSURE TYPE W ITH LNE SPRING, RATED 105Q 600 VOLT, FOR BUILDMG W IRIN6 ANO 1000 VOLT IN SIGNS OR RXTURES. 8. FOR W IRES THAT ARE N6 AWG AND LARGER: COMPRESSION TVPE W ITH 3M #33 0R EOUAL TAPE INSl1LATION. 2.6 CONDUIT HANGERS A. GALVANIZED STEEL W ITH SPECIAL ACCESSORIES FOR PURPOSE AND ADEQUATE TO SUPPORT LOADIMPOSED. SUPPORTINDIVI�UALCONDUIT1-0l2-WCHANDLARGERANDALLMULTIPLE WNDWTRUNSWITHHANGERS. CLAMPCONDUITSINDIVI�UALLVTOEACHSUPPORT. B. REFER TO SECTION 26 �5 29 FOR ADDITIONAL REpUIREMENTS. 2] CONDUIT SLEEVES A. SLEEVES FOR CONDUIT PENETRATION: HILTI, INC., MODEL CP 682. REFER TO DNISION ] "FIRESTOPPING" FOR ADDITIONAL REpUIREMENTS. PART3-EXECUTION 3.1GENERAL A. PROVIDECOMPLETERACEWAVSVSTEMSFORALLCONDUCTORSMCLUDINGCONTROLWIRINGAND LOW VOLTAGE WIRING UNLE55 OTHERWISE NOTED. & ELECTRICAL SVSTEM LAYOUTS INDICATED ON DRAW INGS ARE GENERALLV DIAGRAMMATIC. BUT SHALL BE FOLLOWED AS CLOSELV AS ACTUAL CONSTRUCTION AND WORK OF OTHER TRA�ES W ILL PERMIT. GOVERN EMACT ROUTING OF RACEWAVS AND LOCATIONS OF OUTLETS BY STRUCTURE AND EQUIPMENT SERVE�. TAKE ALL DIMENSIONS FROM ARCHITECTURAL DRAW INGS. C. ALL HOME RUNS TO PANELBOARDS ARE INDICATED AS STARTIN6 FROM THE OUTLET NEAREST TO THE PANEL AND CONTINUING IN THE GENERAL DIRECTION OF THAT PANEL CONTINUE SUCH CIRCUITS TO PANEL AS THOUGH ROUTES W ERE COMPLETELV INDICATED. D. AVOID CUTTING AND BORING HOLES THROUGH STRl1CTURE OR STRUCTURAL MEMBERS W HEREVER POSSIBLE. OBTAIN PRIOR APPROVAL OF THE ARCHITECT AND CONFORM TO ALL STRUCTURAL REQUIREMENTS W HEN CUTTING OR BORWG STRUCTURE. E FURNISH AND INSTALLALL NECESSARV HARDWARE, HANGERS, BLOCKING, BRACKETS, BRAQNG, RUNNERS, ETC., REQUIRED FOR EQUIPMENT SPECIFIEO UNDER THIS SECTION. 32RACEWAVS: REFERTOSECTION260533. 3.3 OUTLETS A EXACT LOCATION OF OUTLETS AND EQUIPMENT SHALL BE GOVERNED BV STRUCTURAL CONDITIONS AND OBSTRUCTIONS OR OTHER EQUIPMENT ITEMS. WHEN NECESSARV, RELOCATE OUTLETS SO THAT W HEN FIXTURES OR EQUIPMENT ARE INSTALLED, THEV WILL BE SVMMETRICALLV LOCATE� ACCORDING TO ROOM LAVOUT AND W ILL NOT INTERFERE WITH OTHER WORK OR EQUIPMENT. VERIFV FlNAL LOCATION OF ALL OUTLETS, PANELS, E�UIPMENT, ETC., W ITH THE ARCHITECT/ENG W EER. B. PROVIDEZWGCOATEDORCADMIUM-PLATEDSHEETSTEELOUTLETBOXESNOTLESS THAN 4" OCTAGONAL OR SQUARE, UNLESS OTHERW ISE NOTED. EpUIP FI%TURE OUTLET BOXES W ITH 3/8" NO-BOLT FIXTURE STUDS. WHERE FIXTURES ARE MOUNTED ON OR IN AN ACCESSIBLE TVPE CEILING, PROVIDE A JUNCTION BOX AND EXTEND REXIBLE CONDUIT TO EACH RXTURE. OUTLET BOXES M RNISHED CEILINGS OR WALLS SHALL BE FlTTED WITH APPROPRIATE COVERS, SET TO COME FWSH W ITH THE FINISHED SURFACE W HERE MORE THAN ONE SWITCH OR DEVICE IS LOCATE� ON ONE PO WT, USE GANG BOXES AND COVERS UNLESS OTHERW ISE INDICATED. SECTIONAL SW ITCH BOXES OR UTILITV BOxES wILL NOT BE PERMITTED. PROVIOE TILE BOX OR A 4" SQUARE BOX W ITH TILE RING IN MASONRV WALLS W HICH WILL NOT BE PLASTERED OR FURRED, OR W HERE "DRV-WALC' TYPE MATERIALS ARE APPLIED. THROUGH THE WALL TVPE BOXES ARE NOT PERMITTED. INSTALL MINIMUM 12" LATERAL SEPARATION FOR BACK TO BACK BOXES. G SURFACE-MOUNTED �EVICES ARE TO BE MOUNTED IN CAST TVPE BOXES W ITH GASKETED COVER& (CROUSE-HINDS CONDULETS OR E�UAL). D. OIMENSIONS UNLESS SHOWN ON DRAW INGS ARE 6NEN BELOW AND ARE FROM FlNISHED FLOOR TO CENTER LINE OF OUTLETS UNLESS NOTED OTHERW ISE. ADJUST HEIGHTS OF OUTLETS IN MASONRV WALLS TO CORRESPONO W ITH WNSISTENT BRICK OR BLOCK COURSE. OUTLETS IN BLOCK WALLS SHALL BE INSTALLED IN CORE OF BLOCK. WALL SW ITCHE54' - 0" (TO TOP OF BOH)CONVENIENCE OUTLETS7'-4' (TO BOTTOM OF BOX) -GVP OR e" BLOCK 1'- 6" (TO BOTTOM OF BOX) - 6" BLOCKHALLWAV51' - 6" (TO BOTTOM OF BOX)ABOVE COUNTER W ALL OURETO' - 8" (ABOVE COUNTER TO TOP OF BOX, MAXIMUM 44" AFF, RELD VERIFV HEIGHT OF BACKSPLASH)PANELBOARDS WALL-MOUNTED6'-6" (TO TOP OF BACK BOX)WALL PHONE OUTLET4'-0' (TO TOP OF BOX)TELEPHONE OUTLETS7' -6" (TO BOTTOM OF OUTLET)FIRE ALARM HORNS, SPEAKERSCBLING OR WALLFIRE ALARM PULL STATIONS4' -0" (TO TOP OF DEVICE)RRE ALARM STROBES6' - 8" OR 6" BELOW CEILMG (W HICHEVER IS LOW ER)TELEVISION OUTLETSREFER TONVORARCHITECTURALDRAWING. CONFIRMFINALLOCATIONANDHEIGHTSOFALLOUTLETS, WALL SW ITCHES, AND TELEVISION OUTLETS W ITH ARCHITECTURAL ORAW INGS AND FURNITURE PLANS PRIOR TO INSTALLATION. E OUTLETS EXCEPT OVER COUNTERS, BENCHES, SPECIAL EQUIPMENT, BASEBOARDS, FlN TUBE RADIATORS, ETG, OR AT WAINSCOTTING, SHALL BE AT A HEIGHT TO PREVENT INTERFERENCE TO SERVICE EOUIPMENT, OR AS NOTED ON �R4W INGS. F. REFER TO SECTION 26 �5 34 FOR ADDITIONAL REpUIREMENTS. 3 4 JUNCTION PULL BOXES A. CONSTRUCT JUNCTION OR PULL BOXES NOT OVER 150 CUBIC WCHES IN SIZE SHALL BE STANDARD OUTLET BOXES, AND THOSE OVER 150 CUBIC INCHES SHALL BE CONSTRUCTED THE SAME AS "CABINETS;' W ITH SCREW COVERS OF SAME GAUGE METAL REMOVAL COVERS MUST BE ACCESSIBLE AT ALL TIMES. B. PROVIDE A STANDARD ACCESS PANEL HAVING A HINGED METAL DOOR NEATLV FlTTED INTO A RUSH METAL TRIM, WHERE A JUNCTION BOX OR EQUIPMENT IS LOCATEO ABOVE NON-ACCESSIBLE CEILINGSORBEHINDFINISHEDWALLS. COOR�INATELOCATIONANDTYPEWITHTHEARCHITECT. END OF SECTION 260506 SECTION 260519 - ELECTRICAL POW ER CONDUCTORS AND CABLES PART1-GENERAL 1.iRELATED00CUMENTS A. DRAWINGSANDGENERALPROVISIONSOFCONTRACT,INCLU�INGGENERALANDSIIPPLEMENTARV CONDITIONS ANO DIVISION 1 SPECIFICATION SECTIONS, APPLV TO THIS SECTION. B. REQUIREMENT OF THE FOLLOWING DIVISION 26 SECTIONS APPLV TO THIS SECTION: L ELECTRICALREQUIREMENTS ipbYqril5/fl:�� A. THISSECTIONINCWDESWIRES,CABLES,ANDCONNECTORSFORPOWER,LIGHTING,SIGNAL, CONTROL AND RELATED SVSTEMS RATED 600 VOLTS AND LESS. B. RELATED SECTIONS: THE FOLLOW ING SECTIONS CONTAIN REQUIREMENTS THAT RELATE TO THIS SECTION: 1. DNISION 26 SECTION "ELECTRICAL BOXES AND FITTINGS" FOR CONNECTORS FOR TERMINATING CABLES IN BO%ES AND OTHER ELECTRICAL ENCLOSURES. 1.3 SUBMITTALS A. PRODUCT DATA FOR ELECTRICAL W IRE$ CABLES AND CONNECTORS. 1.4 QUALITV ASSURANCE A. REGULATORYREOUIREMENTS: COMPLYWITHPROVISIONSOFTHEFOLLOWINGCODE'. B. NFPA ]0 "NATIONAL ELECTRICAL CODE" 1AONFORM TO APPLICABLE CODES AND REGULATIONS REGARDING TOXIqTV OF COMBUSTION PRODUCTS OF INSULATING MATERIALS. G UL COMPLIANCE: PROVIDE COMPONENTS, W HICH ARE LISTED AND LABELED BV UL UNDER THE FOLLOW ING STANDARDS. 1. ULSTD.44RUBBERINSULATEDWIRESANDCABLES 2 UL SID. 83 THERMOPLASTIC-INSULATED W IRES AND CABLES 3. UL STD. 486A W IRE CONNECTORS AND SOLDERING LUGS FOR USE W ITH COPPER CON�UCTORS 4. UL STD. 854 SERVICE ENTRANCE CABLE D. NEMA/ICEACOMPLIANCE: PROVIDECOMPONENTSWHICHCOMPLYWITHTHEFOLLOWING STANDARDS: 1. WGS:THERMOPLASTIC-INSULATEDWIREANDCABLEFORTHETRANSMISSIONAND�ISTRIBUTION OF ELECTRICAL ENERGV. 2. WC-�: CROSS LMKED THERMOSETTING POLVETHVLENE-INSULATED W IRE AND CABLE FOR THE TR4NSMISSION ANO DISTRIBUTION OF ELECTRICAL ENERGV. E. IEEE COMPLIANCE: PROVIDE COMPONENTS, W HICH COMPLV W ITH THE FOLLOW ING STANDARO. 7. STD. 82: TEST PROCEDURES FOR IMPULSE VOLTAGE TESTS ON INSULATED CONDUCTORS. PART2-PRODUCTS 2.1 W IRES ANO CABLES (600 VOLT COPPER CONDUCTORS) A. GENER4L PROVIDE SUITABLE WIRE AND CABLE FOR THE TEMPERQTURE, CONDITIONS AND LOCATION W HERE INSTALLED. ALL W IRES AND CABLES SHALL BE NEW AND DELNERED TO THE SITE IN UNBROKEN PACKAGES AN� REELS. B. ALL W IRES AND CABLES SHALL BE OF THE SAME MANUFACTURER THROUGHOUT THE ENTIRE PROJECT. G CONDUCTORS: PROVIDESOLIDWNDl1CTOR5FORPOWERANDLIGHTINGCIRCUITS#10AWGAN� SMALLER. PROVI�ESTRANDEDCONDUCTORSFOR#BAWGANDLARGER. D. CONDUCTOR MATERIAL: ALL W IRES AND CABLES SHALL BE COPPER, SINGLE WNDUCTOR RATED AT 60� VOLTS, W HICH CONFORM TO OR EXCEED ICEA SPEQFlCATIONS AND THE FOLLOW ING'. 1. IN SIZES 1/0 AWG TO 4/0: CROSS-LINKED POLVETHYLENE WSULATION TYPE XHHW-2 (]5- 90C) OR THW N. 2 WSIZES250KCMILANDLARGER:TVPEXHHW-2(]SC)ORTHWN. 3. 3 IN SIZES 1 AW G AND SMALLER: ALL CONDUCTORS SHALL HAVE HEATIMOISTURE RESISTANT THERMOPLASTIC W SULATION TVPE TH W N(�SC) EXCEPT AS FOLLOW S: a. WHERECONDUITTEMPERATUREWILLEXCEEO100F,USETYPETHHN(90C). b. b.IN 120 VOLT INCANDESCENT FIXTURES, TVPE SF-2 OR SFF-2 (150 - 200C). c IN WIREWAY OF FLUORESCENT LIGHTING FIXTURES TYPE THHN (90C). E. GROUNDWG CONDUCTORS: SHALL BE OF THE SAME TVPE AS ITS ASSOCIATED PHASE CONDUCTORS F ALL CONDUCTORS SHALL BE LABEL W ITH W IRE SIZE, INSULATION RATING, ETC USING AN ENGRAVED PROCESS, COMPUTER SCAN ON LABELS ARE NOT PERMITTED. G. WLOR COOING FOR PHASE IDENTIFICATION IN ACCORDANCE W ITH TABLE 1 IN PART 3 HEREIN. H. CONNECTORS FOR CONDUCTORS: 1.PROVIDE UL-LISTED FACTORV-FABRICATED, SOLDERLESS METAL CONNECTORS OF SRES, AMPACITV RATINGS, MATERIALS, TYPES AND CLASSES FOR APPLICATIONSANDFORSERVICESINDICATED. USECONNECTORSWITHTEMPERATURERATINGS EQUAL TO OR GREATER THAN THOSE OF THE W IRES UPON W HICH USED. I. SPLICES AND TAPS: 1. N0.10AWGANDSMALLER-CONNECTORSFORSOLIDCONDUCTORSSHALLBE SOLDERLESS, SCREW-ON. SPRING PRESSURE CABLE TYPE, 600 VOLT, 105C W ITH INTEGRAL INSULATION AND UL APPROVEDFORALUMINUMANDCOPPER CONDUCTORS.CONNECTORSFORSTRANDEO CONDUCTORS SHALL BE CRIMP-ON TYPE W ITH INTEGRAL MSULATING COVER. 2 N0.8AWGANDLARGER-HVDRAULICALLVAPPLIEDCRIMPINGSLEEVEORTAP CONNECTORSIZED FOR THE CONDUCTORS. INSULATE THE HVDRAULICALLV APPLIEO CONNECTOR W ITH 90-DEGREE, 600-VOLT INSULATING COVER PROVIDED BV THE CONNECTOR MANUFACTURER. WSULATOR MATERIALS AND INSTALLATION SHALL BE APPROVE� FOR THE SPECIFIC APPLICATION, LOCATION, VOLTAGE, AND TEMPERATURE AND SHALL NOT HAVE AN INSULATION VAW E LESS THAN THE CONDUCTORS BEING JOINED. � � / ♦ 1 � INDUSTRIOUS COWORKING 880 W MONON GREEN BLVD CARMEL qTV, IN 460323 OWNERRENANi INDUSTRIOUS 215PARKAVES,4E1300 NEW YORK, NY 10003 ARCNI7ECTOFRECORD NORF 325 N LASALLE Si- SOIiE 500 CHICAGO. IL 60654 PEiER-DUBWC.ANORR-COM 312-0242400 MEFENG/NEER MEENGINEERS 29 WEST 38iH SiREEi, SiH FLOOR NEW YORK. NY 10018 CONiAQ: BRIAN SHASSIAN BRIANSHASSIAN@ME-ENGINEER$_COM JOHN HIGGINS JOHN.HIGGWS(�MEENGINEERS.COM �212J 44]-6]]0 PHONE LIGHi1NGDESIGNER REGENCY 9261 JOkDAN AVE CHAiSWORiH, GA 800-28d-202a ISSUEDATES REV. DAiE DESCRIPiION 06/OS/2020 DD3 06/18/2020 CDvI 0]/06/2020 CDv2 0]/16/2020 PERMIT SEAL & SIGNATURE BY CHEGK ME ME ME ME ME ME ME ME PR0./ECTNAME CARMEL CITY- 880 MONON GREEN VROJECiNUMBER IND880MON DRAWINGTIiLE ELECTRICAL SPECS I SCALE 7/8„_ ��_�„ SHEETNUMBER E-020 oF