HomeMy WebLinkAboutE372 Lighting Control DetailsRELEA5E0 FOR CONSTRUCTION
Suhjec� �o compliance with all regula�ions
04 S�a�e antl Local Codes
City of Carmel
r
�un��V l�rc�alols�.
�
DATE: OH�Z5 2O
AS REQUIRED
FORCONTROLOF040VLOAOS
�i 120V/277V • • SWITCHED POWER �i
�i INPUT FEED (SA MAX) �i
�i �l-�� ❑ � 0-10V DIM �i
(60 mA MAX) II
�i RMJS-8T-DV-B �i
i POWPAK DIMMING MODULE i
�i W ITH SA, 0-10 V CONTROL �i
i DIMENSIONS: ii
�i 3.42"[86,9mm] (H) X 2.82"[71,6mm] (W) i
ii X L25"[31.Smm] (D) ii
L-----------------------------------JI
TYPICAL WIRELESS REMOTE, AS REQUIRED
OTHER BUTTON CONFlGURATIONS AVAILABLE
� II
I � � II
�i PJ2-2BRL-GBL-XXX �
i 434 MHZ PICO WIRELESS, LIGHT �i
�i 3 BUTTON CONTROL WITH RAISE/LOWER �i
i 'SEE SPECIFICATION SHEET FOR i
�i DIMENSIONS, ENGRAVING OPTIONS, �i
ii & MOUNTING INSTRUCTIONS i
�I INSTALL ON INNER DOORFRAME, ��
I OPENSIDE4'0"TOTOPOFREMOTE �
`----------------------------II
TVPICAL W IRELE55 SENSOR, AS
RWUIRE�
I � � I
�i LRF2-VCR2B-P-WH I
i 434MHZ WIRELESS �i
�i VACANCY SENSOR �
ii 3.57"[9Q7mm] (DIA) X 1.13"[28,7mm] (D) �i
i MAX 10 PER QSM �i
�i 'DEVICE IS SURFACE-MOUNTED AND i
i BATTERY POWERED, DOES NOT �i
�i REQUIRE POWER FEED �i
�i (OPTION:WITH L-CRMK-WH ii
i RECESS MOUNT KIT FOR i
NON-METALLIC CEILINGS)
MOUNT CENTERED ON CEILING ON FIRM FLAT
SURFACE W HERE POSSIBLE OR STEM MOUNT TO
BELOW BOTTOM LEVEL OF DUCTW ORK (DO NOT LOCATE
ON W RAPPED �UCT WORK)
TYPICAL W IRELESS DAVLIGHT SENSOR,
AS REQUIRED
I � I
ii � i
�i LRF2-DCRB-WH ii
�i 434MHZ WIRELESS i
�i DAYLIGHT SENSOR �i
i 1.6"[40,6mm] (DIA) X 07"[17,8mm] (D) 'i
I MAX 10 PER QSM ii
�i *DEVICE IS SURFACE-MOUNTED AND i
� BATTERY POWERED, DOES NOT 'i
I REQUIRE POWER FEED II
MOUNT CENTERED ON CEILING ON FIRM FLAT
SURFACE W HERE POSSIBLE. OR STEM MOUNT TO
BELOW BOTTOM LEVEL OF DUCTWORK (DO NOT LOCATE
ON WRAPPED DUCT WORK)
THE FOLLOWING LINK RULES MUSi BE OBSERVED FOR PROPER OPERAiION'
ALL OFFICES, CONFERENCE ROOM, HUDDLE ROOMS
AS REOUIRED
FOR CONTROL OF 0-0�V
LOADS
ZONES aa cc, & dd
�i 120V/277V • • SWITCHED POWER �i
�i INPUT FEED (SA MAX) II
i �� ❑ � 0-10V DIM i
(60 mA MAX) ii
�i RMJS-ST-DV-B �i
i POWPAK DIMMING MODULE i
�i WITH SA, 0-10 V CONTROL �i
i DIMENSIONS: ii
�i 3A2"[86,9mm] (H) X 2.82"[71,6mm] (W) i
ii X 125"[31.Smm] (D) i
i i
TYPICAL W IRELESS SENSOR, AS ftWUIRED
I � I
I � � I
i LRF2-OCR2B-P-WH I
�i 434MHZ WIRELESS �i
�i OCCUPANCY/VACANCY SENSOR �
�i 3.57"[90,7mm] (DIA) X 1.13"[28,7mm] (D) �i
i MAX 10 PER QSM �i
�i 'DEVICE IS SURFACE-MOUNTED AND i
�i BATTERY POWERED, DOES NOT I
i REQUIRE POWER FEED �i
I LOCATION TBD �i
I (OPTION:WITH L-CRMK-WH �i
�i RECESS MOUNT KIT FOR i
ii NON-METALLIC CEILINGS) I
MOUNT CENTERED ON CEILING ON FIRM FLAT
SURFACE W HERE POSSIBLE OR STEM MOUNT TO
BELOW BOTTOM LEVEL OF DUCNVORK (DO NOT LOCATE
ON W RAPPED �UCT WORK)
AS RE�UIRED
FOR CONTROL OF PHASE DIMMING LOADS
ZONE bb
�i � ZONE (X) �i
i FIXTURE: i
ii � i
i � �i
III � II
�i MRF2S-6CL-GR �i
�i MAESTRO WIRELESS MULTI-LOCATION/SINGLE-POLE �i
i CL DIMMER i
i 150 W DIMMABLE CFLILED/ 600W i
�i INCANDESENT/HALOGEN i
i (1 GANG US BACKBOX BY OTHERS) �i
L____________________________________
AS REQUIREq FOR CONTROL OF NORMALIEMERGENCV 0-10V LOADS
ZONE dd
I �
i i
II Q � �
— i
� — i
i i
..�� oUa:�,::
i .., i
i i
i O
i O O i
i i
I I
�i LUT-ALCR-D �
� LVS CONTROLS ALCR DEVICE i
�i FOR USE WITH NORMAL AND EMERGENCY i
i 0-10V & ECOSYSTEM LOADS i
�i REFER TO APPLICATION NOTE #628 i
i FOR DETAILED WIRING DIAGRAMS i
i i
� �
GALLEY KITCHEN, PHONE , ACCESSIBLE PHONE MDF
PACKAGE, & WELLNESS ROOMS
WIRING LEGEND:
04 aSCONTROLLINK�SEEWiREDESCRIPTiONBELOW)
.Q QSGONTROLLINK(SEEWIRE�ESGRIPTIONBELOW)
(CONNECT W IRES 1, 3 AN� 4. 00 NOT CONNECT W IRE # 2)
p5 W IRING AS REQUIRED BV CONTROL LINK LENGTH
(REFER TO p5 SMART PANEL POW ER SUPPLV W IRING GUIDE FOR SHADE W IRING NOTES)'.
TOTALCONIROL yyIREGUAGE AVAILABLEFROMWTRONINONE
LINK LENGTH CABLE
PO W ER QERMINAL5182�'.
LESSTHAN6C0l� �PAIRIBAWG�10mm') GRX-CBL3965
(�53 m) OR
OATA�TERMINAL53d6��. GR%�PCBL3Y65
1 PAIR P2AWG (0 5 mm'�, iVJISIE� AN� SHIEL�E�'
POW ER QERMINALS �&P��.
500fl(153m)TO �vaiai2nwc�am�) ppg�g�db�
&OOOf� (BOO mp` OR
P�IIItMINA153CAk GR%�GBL<6L
1 VNH 12 PW G�0 s mmz � yy� � e� Avf] SHIEL�ED'
'ALTERNATEDATAANLVCABLBUSEAPPROVEDDATALINKCABLE�22AWG[O.Smm '�
TVJISTED/SHIELOEOJ FROM BELDEN (MO�EL tl 8481}
"TOTHL LENGTH OF THE OS LINK MUST NOT EXCEED 2,000 fl(600 m).
CONCEPTDRHWINGNOTES�.
CONTROL SVSTEM DRHW ING IS PROVI�E� FOR CONCEPTUHL PURPOSES ONLV PND IS NOT
INTENDEDFORCONSTRUCTION. EXHCTEpIIIPMENTREpUIREMENTS.INCWDINGLOCATIONS
AN� pIIANTITE$ SHOULD BE VEW FlE� IN ACCOROANCE W ITH THE MOST 11P-TO-DATE
LIGHTING/ELECTRICAL REFLECTE� CEILING PLANS, LIGHTING FlXTURE SCHEDULES, PANEL
SCHE�ULES,CONTROLIMENTAN�SPEQFlCATIONS.
LED DIMMMG REOIlIRES AN EXACT MATCH BETW EEN THE LE� ARRAY, DRIVER AND CONTROL.
W TRON CANNOT GIIARANTEE COMPATIBILITV OR PERFORMANCE W ITHOl1T TESTING THIS
COMBINPTION.
TO CONFlRM WNAT PRO�UCTS LUTRON HAS AVAiLABLE OR WNAT iNTERFACES MAY BE
RE�UIRED, CHLL 1-8]�-OIM-LEDB OR CHECN LUTRON'S PRODUCT COMPHTI6ILITY MHTRIX ON-LINE
AT W W W.LUTRON.COM/LED.
TO RE�UEST THE TESTING OF AN LED PRO�UCT BY LUTRON MANUFHCTURERS CAN FILL OUT HN
LED EVALUHTION REQUEST FORM ON�LINE AT W W W. WTRON.COM/LED OR CONTACT
LEDS@WTRON COM.
W TRON CAN GUARANTEE COMPATIBILITY AND PERFORMANCE OF W TRON HL W ME ASERIES
LED DRIVERS USE� WITH APPROPRIATE WTRON CONTROLS. THE H6WME ASERIES LED DRIVER
CAN BE USED ON PRODUCTS UNDER JO WATTS W ITH SUITABLE MOUNTING LOCATIONS. PLEHSE
REFER TO THE SPECIFICATION SUBMITTAL SHEET FOR FURTHER INFORMHTION.
IF USING UNTESTED, NON-LUTRON LED DRIVERS RE�UIRING 0-0OV CONTROL PERFORMHNCE
AN� COMPHTIBILITV CANNOT BE GUARHNTEED BV LUTRON. PRODUCTS FOLLOW ING THE IEC
STANDAR� 60929 NRE MORE LIKELV TO PROVIDE NCCEPTABLE PERFORMANCE RESULTS.
OETERMINATION OF RESl1LT ACCEPTABILITY IS 11P TO THE USER'S DISCRETION.
IF 1151NG UNTESTED, NO&WTRON LED DRIVERS REpIIIRWG PHASE CONTROL, PERFORMANCE
ANO COMPHTIBILITY CANNOT BE GUARANTEED BV LUTRON. N-SERIES OR ELV PROOUCTS
PROVIDING HIGH ENO AND LOW END TRIM PDJUSTMENTS NRE MORE LIKELV TO PROVIDE
ACCEPTABLE PERFORMANCE RESULTS. DETERMINATION OF RESULT HCCEPTABILIN IS UP TO
THE USER'S DISCRETION.
SEPVICE TIRE
COUNT OF SERVICE OESCFIPTION
EHCH IMO�E_NUhIBER�
SERVICE
SPECIFIED �rCOVrvi50�5FRVICESBELOWAREiOBEMCWOE�MSPAFTOFTHiS
vItOJFC15$ .MNr OF W ORK ANO $PECIFlE� INiO iHE W ftIiTEN $PEC DOCUMENiS
PRE-STARTUP SERVICES
o��.E H.��ao.
PPEWiREviSR
(LbCARPrviRE) .00PNiIiY�lOiAiF9iXENOMBEROFN5rt5
��,E�,�.�oH
i�Ns��.a.�oN
��..-��s�.� �.�..�o�.,,.Ro�s���.a���,.A�.oRw�a�.
��xTSEvs �n
STARTUP SUPPORT SERVICES
FnreruP Przovioeo ae*weeu rrve �o�r+s or saoan- ��.aaun. r.orvonv
PFiERHOOR _ Al�nviH��SCOPEOFWOAnp�ORpOppIpCLU�Eti�LRHTOBE
�.AA.�P
asonnsu� n�Pie��-woorv�wcc«e+osiFAionvs.aaPm-no�+oA.��oAhn.
8(sc�Tvis�rl rvEscErvEiEVE�oRa�re��nnrv�.
orvsi.e orvsirewsurtiaouaxwiruFnn�rvawssErvrnrvesoacamEcr
aeerzFFic.io:E Fx�c:io�+wrGriiiei�eoeeicr�i.ii�+?EiwexiA.iNawea+vor
�rvoo.s.EAn���.�Es-�.�,�.A.�oH�.aA�ti�Hoo��.
wnLK*tipOUOti q�N�IONqL*E6lwpw565�PUW,CwvErviORVORU*PON
��P�) C-0UIPIAErvi.
E Fo �`"��E E
o�;M�;d°noti .,��
a��swm�, o�a�E�.soFn��.e��o���,a��,�s
iliLE2a qCCEPiANCEiESiINOBVnLUiROXCER➢FlEDLI�hiINOCOx}ROL
si. ascse� ooc.z.� nc� mjtiiieiorz �c�:i��c�corv: oi�.�rsw�ru�.�e Acourtreo
POST-STARTUP SERVICES
a����,.o,�,=Ro� �ow,oaP�..Fa�o���.a�H,�E
m aA��,���„s�..a,�NHd�nN���. ��,�.
I�msYsoais� wFItG1'aaeFwien
MAINTENANCE 8 SUPPORT SERVICES
soF.wAaE
a, re,�,��� �
���, wo�Arva�.��EE.ro�>RE���oE��E�sE
vs*�H.szvE-n
. wnnrerw.v ueoaceverenaewi.nnFlr+s.nuniva�
n woen
enHu+ceosii�ca meis"i��a�
asceasi vuNFVFna'�.a�ii� ana.eaH�vcovwaoev'eieeia�zs�ana.s
Eurysceeci�� I�onv�sc�oopqarsom�vwverucEVFsass�e.as�%GORovNrv��.
im%a[
coVFana[ W RN Pza-rvoua aFsrorvs[ nmNalloaN ANxuA�
p-DA`q5CHE0V�E0 PNCEV19rt�p0�➢PWNk
IqiINUm PREVE }piNEMNIx}E
�LSC.�ry AP9JSWWOPnRi90u�VCOVFPAGEVFAR56&RSWo>nRi90N�V
COVEPnG& �p�EMExia/ai5
suaro��v�nn
Uscsi�wwl sr.evuwe�onsrteorerse.rorereevvoms'Eriwe.
o�o.E���o�o ESE..P�.s
G�=«�ow,�° °p�.EaA�,
,�=°Po° .P �, „�oA.,sa� o�aEo
EVI61riOPEPCORMacEVErvirvE
SElS�VCE p
rybGSGwMnwi)
PLEASE GO TO W W W.LUTRON.COM/SERVICES FOR FURTHER INFORMATION.
NOTE: ALL LIGHTING TO BE INTEGRATED W ITH
BWLDWGSVSTEMICONTROLS
QS LINK RULES
THE FOLLOWING LINK RULES MUSi BE OBSERVED FOR PROPER OPERAiION'
• THISISHTOPOLOGY-FREELINK(T-TAP,HOME-RUN,ETC.ISOK)',REFERTOTABLEBELOWFOR
W IRE RUN LIMITS.
. FWIRE�DIFFERENTLYTHANWHATISSHOWN,POWERDRNWUNITREQUIREMENTSNEEDTOBE
CONFIRMED: SEE POW ER DRHW UNITS (PDUs) SPECIFICATION SHEET INCLUOEO IN THIS SUBMITTAL.
• MH%IMUMOF5120UTPUTS(BPLLHSTS.SHqDES.CONTNCTCLO5URE5,ETC).
• MHXIMUMOF1000CCUPANCYSENSORS,1000AYLIGHTSENSORS/RADIOSHHDOWSENSORSNND
moKevanos.
• MHXIMUMOF100�SDEVICES(SUCHHSHGRAFIKEVE�QS,SEETOUCH�aSKEVPAD,SMART
PANEL POW ER SUPPLY �p5P5-Px-10-607, ESN, OR SIVOIA� p5 SHADE / DRAPERY ORNE UNIT).
�UANTUM PROCESSOR COUNTS AS 1 DEVICE PER LINK.
• MHXIMUMOF100ZONES-SUCHPSASIVOIAQSSHHDE/DRHPERVDRIVEUNIT.ORHLIGHTING
ZONE ON A GRAFlK EYE p5 (DOES NOT APPLV TO pUANTl1M SYSTEMS).
. THE100l1TPUT50NAQ5P5-Px-0O�60CHNNOTEXCEEDACOMBWEOLENGTHOF 2,OOOk(600m�.
PANEL LINK RULES
PANEL(5)BHSEDON DHTEDXX.%X.X%FROM
NAMEOFOOC.PROVI�ED SPECIFlER
. PANELSAREDAISKCHAMEDONONEOFTHECONFlGURHBLELMKSPERWTRON'SDRAWING,
HOW EVER THEY DO NOT NAVE TO BE M TNE OR�ER SNOWN.
. 00 NOT HOMERUN OR T-TAP THIS W IRING LINK. ALL CIRCUITS NEEO TO BE LANDED IN THESE
PANELS PER LUTRON'S PHNEL SCHEDULES.
• THEMHXIMUMWIRELENGTHOFHPHNELLINK152.00Ofl(600m).AM%-RPTRISUSEDTOEXTEND
THE LENGTH OF A LINK ANOTHER 2,000 �I (600 m). A MNXIMUM OF (3) M%-RPTR'S MAV BE USED PER
LINK FOR MHXIMUM LENGTH OF 8,000 ft (2 430 m) PER LINK.
. IF H PHNEL IS MOVED TO ANOTHER LINK.OR THE LOADS ARE NOT W IRED AS SHOWN IN LUTRON
PANEL SCHEDULES WTRON M115T BE NOTIFlED. THIS MFORMATION IS IMPORTANT FOR
PROGRqMMiNG THE SYSTEM.
• UPT032CIRCUITSELECTORSPERLWK
. UPT05125WITCHLEGSORZONESPERLINK
�LT-Oi�l�yl(�$pAIJJ9jQq$JJF�pF,p Qy ��END OF THE LINK
i, r� i tm �sii���i��r rcii�
THE PoLLOWING LOOP RULES MUST BE OBSERVEO PoR PROPER OPERATION'
• THIS IS TOPOLOGY-FREE AND POLPRITV FREE WIRING (T-TqP, HOME-RUN, ETG IS OK .
)
• KEEPALLTHEBALLASTS/MODULESWONEROOMONTHESAMELOOPWHENEVERPOSSiBLE.
. WIREOAYLIGHTSENSORSOCCUPANCVSENSORSANDPERSONALCONTROLSTOTHECLOSEST
ECOSYSTEM BALLAST/SENSOR MOOULE IN THE SHME ROOM.
• ECOSYSTEMLOOPSHRESHOWNONTHELIGHTINGPLANS.IFTHEREISHDISCREPANCY.AND
ROOMS ARE W IRED TO A DIFFERENT LOOP THAN THE ONE SHOW N, W TRON NEEDS TO BE
NOTIFIEO. THIS INFOFMNTION IS IMPORATANT FOR PROGRPMMING THE SYSTEM.
• UPT0658ALLn5T5/MOWLESPERECOSYSTEMLOOP
• UPT0641RCONTROLSPERLOOP
. UPT016DAVLIGHTSENSORSPERLOOP
UP TO 32 OCCUPANT SENSORS PER LOOP
QUANTUM NETWORK
EHRVER/DESKTOP IAPTOP (p MAN ER RTHEB M,N REpUIRES DED CNTED IAN ORIVLANE TSIS THE
RESPONSIBILITV OF THE NETWORK PROVI�ER TO ENSURE THE RELIABILITV HNO SECURITY OF THE
LMN.
CAT5E OR BETT(ER ETHERNET CABLE TO BE Rl1N FOR DEDICATEO LMN TERMINHTED W ITH RJ45
OEETHERNETC�BEDH�ALLNO EXC�E�328FT(100MjPOIMTOPONOTEXCEED6TTOEA L�ENGME
IF LONGER RUNS ARE REQUIRED, MULTI-MODE FIBER OPTIC CHBLE CPN BE USED INSTEH� W ITH
APPROPRIATE FIBER OPTIC CONNECTORS (PROVI�E� BY OTHERS). CONSULT W ITH NETWORK
PROVIDER FOR STANDARO ETHERNET AND FlBER OPTIC W IRMG RULES FOR DISTANCE AND
SEPARATION HS WELL AS FOR PLACEMENT OF SWITCHES. ROUTERS, HUBS ETC.
FOR MORE WFORMATION REGARDING NETW ORK EpUIPMENT REpIIIREMENTS ANO NETW ORK
CONFIGURATION, PLEASE REFER TO THE QUANTUM LIGHTING MANHGEMENT NENJORK
SPECIFICATION SHEET OR CONTqCT LUTRON.
p INPl1TPOWER(NORMAL-EMERGENCV)
❑ INPUTPOWER(NORMAL) � �-WAYRFCOMMUNICATION
� zaiuwctamm�I
Q 3#12NWG(Jmm°) �2�WAYRFCOMMUNICATION
♦ 0.10VSIGNHL2C18HWG(1.Omm�) N 2tti8HWG(10mm')
Q EGOSVSTEMBUS/LOOP'. W 3k18HWG(1-Omm�)
LUTRON CHBLE GW L-21&GR-1
(2#i6CONDl1CTORNON�PLENUM)OR g LUTRONSENSORCHBLEGCBL-522S
C-PC6L216-0L-1�2pi6CONDUCTOR OTHERWISEUSE3#22HWG(�.Omm�)
PLENUMRATEO).OTHERWISEUSE2#16 LUTRONSENSORCHBLEGCBL-522S
AW G(1.5 mm�J BV OTHERS. I OTHERW ISE USE J#22 HW G(1-0 mm �)
❑E CATSEORBETTERCABLEPoRWTRON ❑p OMXCONTROL
NERNORK TERMINHTED W ITH RJ45
CONNECTORS (TO BE PROVIDED BY � OALI LINK
OTHERS). 328 fl(100 m) MAXIMUM RUN.
QP PHNELLINK(SEEWIREDESCRIPTIONBELOW)
.p PANELLINK(SEEWIRE�ESGRIPTIONBELOW)
(CONNECT W IRES 1, 2, 3 AND 4. DO NOT CONNECT W IRE # 6)
LUTRON CABLE GRX-CBL-46L (5 CONDUCTOR NON-PLENl1M) OR GRX-PW L-46L (5 CONDUCTOR
PLENUM RATEO). OTHERW ISE USE 2#12 AW G(4 mm').1 BELDEN #94fi1 AND BENJEEN PANELS
ADD 1#18 AWG (1 0 mm') FOR EMERGENCY SENSING CNBLE BV OTHERS.
O FIBEROPTICCABLEFORLUTRONNETWORKTERMINATEOWITHAPPROPRIATEFIBEROPTIC
CONNECTORS (TO 8E PROVIDED BV OTHERS). NOTE REpIIIRES DEDICATED FlBER OPTIC LINK
(31NOLEMODE OR MULTIJvIODE).
SWITCHING DETAILS
ITEM MANUF./TYPE MODEL LOCATION COLOR
1 OR 2 GANG WALL PLATE LE GRAND, RADIANT SCREWLESS WALL THROUGHOUT BLACK; WHITE IN
PLATE AMENITV ONLV
3 GANG WALL PLATE LE GRAND, AOORNE 3-GANG SCREWLE55 PHONE ROOM BLACK
WALL PLATE, BLACK INK -
DIM. SW ITCH t SW ITCH +
OUTLET (iX) AW P3GGR4,
(1X) ADPD453LM2, (iX)
ASPD1532M4, (iX)
ARTR152M4
2 BUTTON WIRELESS LUTRON, PICO PJ2-2B-GBL-L01 WI PICO- OFFlCE BLACK
CONTROL WIRELE55 MOUNT-0-BL-CPNS]33
1 GANG. 1 OR 2 PORT LE 6RAND, CLASSIC WP3401 I W P3402 THROUGHOUT BLACK; WHITE IN
KEVSTONE WALLPLATE AMENITY ONLV
MULTISERVICE POKE-THRU LE 6RAND RC4 MULTI SERVICE THROUGHOUT BLACK; WHITE IN
POKE-THRU DEVICE AMENITV ONLV
/ 1
INDUSTRIOUS
COWORKING
880 W MONON GREEN BLVD
CARMEL qTV, IN 460323
OWNERRENANi
INDUSTRIOUS
215PARKAVES,4E1300
NEW YORK, NY 10003
ARCNI7ECTOFRECORD
NORF
325 N LASALLE Si- SOIiE 500
CHICAGO. IL 60654
PEiER-DUBWC.ANORR-COM
312-0242400
MEFENG/NEER
MEENGINEERS
29 WEST 38iH SiREEi, SiH FLOOR
NEW YORK. NY 10018
CONiAQ: BRIAN SHASSIAN
BRIANSHASSIAN@ME-ENGINEER$_COM
JOHN HIGGIN$
JOHN.HIGGWS(�MEENGINEERS.COM
�212J 44]-6]]0 PHONE
LIGHi1NGDESIGNER
REGENCY
9261 JORDAN AVE
rw
CHA S oRiH, Ga
8Up-28d-2026
ISSUEDATES
REV. DAiE DESCRIPiION
06/OS/2020 DD3
06/18/2020 CDvI
0]/06/2020 CDv2
0]/16/2020 PERMIT
SEAL & SIGNATURE
BY CHEGK
ME ME
ME ME
ME ME
ME ME
PR0./ECTNAME
CARMEL CITY- 880 MONON GREEN
VROJECiNUMBER
IND880MON
DRAWING TITLE
LIGHTING CONTROL DETAILS II
SCALE
7/8„_ ��_�„
SHEETNUMBER
E-372