HomeMy WebLinkAboutFA000 Fire Alarm Legend1�1
INDUSTRIOUS
COWORKING
1 ST FLOOR
RELEA5E0 FOR CONSTRUCTION
Suhjec� �o compliance with all regula�ions
04 S�a�e antl Local Codes
City of Carmel
r
�un��V l�rc�alols�.
�
DATE: OH�Z5 2O
FAP-A
�I�WI T RTII RETl1RN OUCTS RTU RETURN Dl1CT5 T W�� ��III�
/ �
z a a� x �z s s � n s
INTERCONNECT W ITH FIRE ALARM SVSTEM TO
DE-ENERGRE UPON ACTIVATION OF ANV FIRE
DEVICE
SVSTEM TROUBLE
WATER FLOW
TAMPER
PULL STATION
DUCTSMOKEDETECTOR
SMOKEDETECTOR
ELEVATOR LOBBV SMOKE
ELEVATORLOBBVSMOKE DETECTOR
OTHER THAN EXIT LEVEL
ELEVATOR E�UIPMENT ROOM
SMOKE�ETECTOR
SMOKE�ETECTOR
ELEVATOR EQUIPMENT ROOM
HEAT DETECTOR
�NEW FlREALARMPANEL
FACP I EXISTING LANDLORD FIRE ALARM PANEL
FIRE ALARM RISER DIAGRAM
NOT TO SCALE
NOTES
1. �UANTITV OF DEVICES SHALL BE AS PER PLANS
2. CONTRACTOR SHALL COOR�INATE ALL RRE ALARM
WORK WITH BUIL�ING FACILITIES PERSONNEL
PRIOR TO ANY DISCONNECTIONS, RELOCATIONS
ETC
FIRE ALARM
Q SMOKEOETECTOR
� 30ctl yypLL MOUNTED SPEAKER I STROBE
�30cd CEILINGMOUNTEDSPEAKER/STROBE
..i5cd WqLLMOUNTEDADA5TRO6E
r
„i5ctl CEILINGMOUNTEDADASTROBE
FR FIREALARMRELAV
� FIREISMOKEDAMPER
� MANUAL PULL STATION
Ja I DUCT DETECTOR
V
NOTES:
1. 'X' DENOTES CANDELLA RATING OF STROBE.
SEQUENCE OF OPERATION
FIREALARMPANEL I NOTE
SOME OEVICES SHOW N MAV NOT APPLV TO THIS PROJECT.
FAP-B
RRE ALARM RELAY FOR INTERCONNECTION TO
LANDLORD EXISTING FIRE ALARM SVSTEM
GENERALNOTES
1. REFERTOPLANDRAWINGSFORDEVICE
LOCATIONS.
2. DIVISION 26 SHALL BE RESPONSIBLE FOR
RLING AND OBTAINING APPROVAL OF ALL
APPROPRIATE AUTHORITIES FOR SVSTEM,
WCLU�ING PAVING ALL ASSOCIATED FEES,
WCWOING OBTAINMG SERVICES OF A
STATE LICENSED PROFESSIONAL
EN6INEER. W ORK SHALL NOT BE
CONSIDERED COMPLETE UNLE55 ALL
NECESSARV FlLING, TESTS, AND
INSPECTIONS ARE COMPLETED AND
APPROVED.
3. ALL NEW RRE ALARM DEVICES SHALL BE
FULLV COMPATIBLE WITH THE EXISTING
SVSTEMAND SHALL BE INSTALLED UNDER
DIRECT SUPERVISION OF E%ISTING SVSTEM
SUPPLIER W HO SHALL WARRANTV ALL
WORK FOR (1) VEAF.
4. ALL W IRING SHALL BE TEFLON INSULATEO
AND JACKETEq 2HR RATE�. CABLE SHALL
BE RATED 600 VOLT AND SHALL BE BSA OR
MEA APPROVED. PROVIDE #14 AW G
MINIMUM W IRING FOR ALL SIGNAL AND
INITIATION DEVICES. ROUTE ALL WIRING IN
CONDUIT.
5. E%ACT ROUTING OF FIRE ALARM W IRING TO
BE COORDINATED W FlELD.
6. OUANTITV OF DEVICES ON ONE LOOP
SHALL BE PER MANUFACTURER'S
RECOMMENDATION.
]. LOCATE ALL STROBES 6'-8" TO BOTTOM
ABOVE RNISHED ROOR OR 6" TO CENTER
BELOW FINISHED CEILING, WHICHEVER IS
LOWEST
8. PROVIDESEPARATENOTIFICATION
qRCUITS FOR SPEAKER AN� STROBE
DEVICES. ALL NOTIFICATION CIRCUITS
SHALL BE TWO HOUR PROTECTNE QRCUIT
OR IN CONDUIT PER NFPA ]2.
9. STROBESHALLDELNERAMINIMUMU.L.
19]i LISTED EFFECTNE INTENSITV OF 15
CANDELA (AND SHALL BE COMPATBLE W ITH
BASE BL�G. FIRE ALARM SVSTEM) W ITH NO
MORE THAN A 225MA DRAW. 15 CANDELA
U1. 1971 LISTED/75 CANDELA NEAR AXIS
STROBES (115MA DRAW) SHALL BE UTILRED
FOR SPACE WITH NO DIMENSION GREATER
THAN 20 FEET.
11. COORDINATE EXACT LOCATION AND
QUANTITV OF ALL DUCT TVPE SMOKE
DETECTORS W ITH DIVISION 23. DIVISION 26
SHALL HARD W IRE TO RELAV STARTER.
12. COORDINATE EXACT LOCATION AND
QUANTITV OF ALL FIRE SMOKE DAMPERS
W ITH DIVISION 23.
73. FlRE ALARM CONTRACTOR TO PROVI�E
INTERFACE TO ELECTRICALLV UNLOCK ALL
ELECTRICALLV HEL� DOORS W ITH CARD
READER ACCESS.
14. ALL VISUAL DEVICES SHALL BE
SYNCHRONIZED.
15. PROVIDE END-OF-LINE DEVICES AS
REQUIRED.
1]. DIVISION 26 SHALL FIRE STOP ALL
PENETRATIONS THROUGH FIRE RATED
PARTITIONS AND SLABS.
18. RUN RIGID CONDUIT W HERE NOT
CONCEALED IN CEILINGS AN� W HERE
REQl11RED BV ALL APPLICABLE CODES, ALL
W IRING SHALL BE COLOR CODED AND
IDENTIFlED AT THE FACP.
19. ALL CONDUITS SHALL BE GROUNDED BV
MFANS CONFORMING W ITH THE NATIONAL
ELECTRICAL CODE W ITH A GROUN�
CONDUCTOR EQUAL IN SRE TO THE
LARGEST CONDUCTOR USED IN THE
SYSTEM', BUT IN NO CASE SHALL THE
GROUND CONDUCTOR BE SMALLER THEN
#10 AW G. ALL CONDUITS SHALL BE RIGID
STEEL CONDUIT. ALL CONDUITS AND
JUNCTION BOXES SHALL BE PAINTED RED.
20. REFER TO SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
21. ALL ANNUNCIATING DEVICES SHALL BE
COORDINATED WITH ARCHITECT.
22. TESTING ANO RNAL CONNECTION OF
CONTROL PANELS AND PROGRAMMING OF
THE FIRE ALARM SVSTEM SHALL BE MA�E
BV BASE BUILDING VENDOR.
23. CONTRACTORSHALLSUBMITCOMPLETE
SHOP DRAW INGS FOR THE SVSTEM,
INCWDING W IRING DIAGRAMS, CATALOG
WTS OF ALL DEVICES, SVSTEM RISER
DIAGRAM, AND SEQUENCE OF OPERATION.
10. PROVIDE MONITORING MOOULES, CONTROL
MODULES, END SW ITCHES, LED STATUS
LIGHTS, SELECTOR SW ITCHES, PRINTED
QRCUIT CAR�S, PROGRAMMING, AND ALL
APPURTENANCES AS REQUIRED.
FlRE ALARM RELAV FOR RTU
SHUTDOWN
FIRE ALARM RELAV FOR RTU
sHuroowN
0
0
a
0
0
NOTES
1. TESTING AND FINAL CONNECTION OF CONTROL PANEL SHALL BE
MADE BV THE BASE BUILDING FIRE ALARM VENDOR SIEMENS
2. CHECK-OUT AND PROGRAMMWG OF THE FlRE ALARM SVSTEM SHALL
BE MAOE BV FlRE ALARM VENDOR SIEMENS
3. RREALARMWIRINGSHALLBEINSTALLEDMCONDUITWHERE
FINISHED CEILINGS ARE NOT PRESENT. ALL FIRE ALARM W IRING
ABOVE FINISHED CEILINGS SHALL BE TEFLON COATED (PLENUM
RATED).
4. COORDINATE INSTALLATION OF FlRE ALARM EQUIPMENT W ITH OS
METRO.
5. CONTRACTORSHALLSUBMITCOMPLETESHOPDRAWINGSFORTHE
SYSTEM, INCLUDING W IRMG DIAGRAMS, CATALOG WTS OF ALL
DEVICES, AND SVSTEM RISER DIAGRAM AND SEQUENCE OF
OPERATION.
6. PROVIDEEND-OFLINEDEVICESASREQl11RED.
7. ALL CONDUITS SHALL BE GROUNDED BV MEANS CONFORMING W ITH
THE NATIONAL ELECTRCIAL CODE W ITH A GROUND CONDUCTOR
WUAL IN SRE TO THE LAR6EST CONDUCTOR USED IN THE SYSTEM;
BUT IN NO CASE SHALL THE GROUND CONDUCTOR BE SMALLER THEN
k10 AWG. ALL CONDUITS SHALL BE RIGID STEEL CONOUIT. ALL
CONDUITS AND JUNCTION BO%ES SHALL BE PAINTED RED.
e. ALL FlRE ALARM SVSTEM W IRING SHALL BE TVJISTED PAIR #14 AWG
MINIMUM, SOLID COPPER, 200 DEG. C, 600V, INSULATED
CONDUCTORS, BS 8 E OR APPROVED AND COLORED RED.
9. RUNRIGIOCONDUITWHERENOTCONCEALEOINCEILINGSAND
WHERE REpUIRED BV ALL APPLICABLE CODES, ALL W IRING SHALL BE
COLOR CODED AND IDENTIFlED AT THE FACP. ALL FlRE ALARM
CABLES SHALL BE APPROVED FOR USE M RRE ALARM SVSTEMS IN
CARMEL CITV INDIANA.
10. ELECTRICAL CONTRACTOR SHALL PERFORM ALL NECESSARV FIRE
DEPARTMENT RLWG. wORK SHALL NOT BE CONSIDERED COMPLETE
UNLESS ALL NECESSARV RLINQ TESTS, AND INSPECTIONS ARE
COMPLETEDANDAPPROVED.
11. ELECTRICAL CONTRQCTOR SHALL FIRE STOP ALL PENETR4TIONS
THROUGH FIRE RATED PARTITIONS AND SLABS.
12. ELECTRICAL CONTRACTOR SHALL INCLUDE IN HIS BID ONE (i) DAV
FOR W ALK-THRUS AND ALL PRETESTING, PRIOR TO RRE
OEPARTMENT INSPECTION AND TESTING.
13. VISUAL ALARM FLASHING STROBE LIGHT SHALL BE MOUNTED @ 80"
A.F F. PER "A D A"REQUIREMENTS STROBE LIGHTS MUST BE
ALTERNATELV W IRED ON A 8 B CIRCUITS AS R W UIRED BV CODE.
14. COORDINATE COLOR ANO LOCATION OF ALL DEVICES AND CONDUIT
ROUTING WITH ARCHITECT PRIOR TO ANV WORK AND INSTALLATION.
15. REFER TO FLOOR PLAN FOR EXACT Ql1ANTITV OF DEVICES.
i6. ALL DEVICES SHALL BE PROVIDED BV THIS CONTRACTOR.
iZ PRIOR TO SUBMITTING HIS BID, CONTRACTOR SHALL FlELD VERIFV
ALL EXISTING CONOITIONS INCLUDING BUT NOT LIMITED TO
AVAILA&LITY OF CIRCUITSIZONES ETC., AND INFORM THE
ENGINEERIARCHITECT OF ANV DISCREPANCV ANO INCLUDE IN HIS BID
TO INCLUDE THE SAME AS DIRECTED. CLIENT IS NOT RESPONSIBLE
FOR ANV ADDITIONAL COSTS RESULTING FROM VERIFlABLE EXISTING
CONDITIONS DISCOVERED AFfER CONTRACT HAS BEEN AWARDED.
18. PROVIDE A FIRE ALARM CONTROL RELAV FOR CONTROL OF DAMPER
MOTOR POWER FOR ALL FIRE SMOKE DAMPERS. ROUTE POWER VIA
FIRE ALARM REL4V.
n aQa O v�i
d d W W W LL W ly Q U
LL� 0 0 OQmQ y K Q K Q
yU�naQ�n�r_J C� w x � v� w O
Q Q>LL>Q>Z>Z Z � JO Vl F WW � F
ro m m m rc p � tt w � y� d o�
� � w Q w Q w� w N � O O j o J � Q > LL� i w
m m m � m � m m ��-� w¢� � w� N Q� O
>> Q Q>>�z ���� o� azu�o o d
a������o�o a°-°z� ��' ��d" zo �r °o w
�� W'� W'�' W> W> F(aj �=Q w� w0 �O r �m Q� y Q
V� J JC> � 0- Z
r r a�a�awaw>LLo�¢�¢wzj > ��oi�' J �
v� v� F J�¢�a�a rFzz c�a c�N �w F��O"� �
m m?¢?a?w?�'na�zwU����ww a woULL � r
0 0 0
0 0 o i o <
880 W MONON GREEN BLVD
CARMEL qTV, IN 460323
OWNERRENANi
INDUSTRIOUS
215PARKAVES,4E1300
NEW YORK, NY 10003
ARCNI7ECTOFRECORD
NORF
325 N LASALLE Si- SOIiE 500
CHICAGO. IL 60654
PEiER-DUBWC.ANORR-COM
312-0242400
MEFENG/NEER
MEENGINEERS
29 WEST 38iH SiREEi, SiH FLOOR
NEW YORK. NY 10018
CONiAQ: BRIAN SHASSIAN
BRIANSHASSIAN@ME-ENGINEER$_COM
JOHN HIGGINS
JOHN.HIGGWS(�MEENGINEERS.COM
�212J 44]-6]]0 PHONE
LIGHi1NGDESIGNER
REGENCY
9261 JOkDAN AVE
CHAiSwORiH, GA
800-28d-2026
ISSUEDATES
REV. DAiE DESCRIPiION
06/OS/2020 DD3
06/18/2020 CDvI
0]/06/2020 CDv2
0]/16/2020 PERMIT
SEAL & SIGNATURE
BY CHEGK
ME ME
ME ME
ME ME
ME ME
PR0./ECTNAME
CARMEL CITY- 880 MONON GREEN
VROJECiNUMBER
IND880MON
DRAWINGTIiLE
FlREALARM LEGEND
SCALE
7/8„_ ��_�„
SHEETNUMBER
FA-000
oF