HomeMy WebLinkAboutM701 Mechanical DetailsF�oW
SA �
INDUSTRIOUS
SVMBOL
O
TS
❑ SIS
M
�
DI
DO
AI
AO
SA
RA
HC
HWR
Cel
C1
C4
CONTROLSLEGEND
NO SCALE
RTU CONTROLS DIAGRAM
NO SCALE
CONTROLS
DESCRIPTION
THERMOSTAT
TEMPERATURE SENSOR
STARTISTOP
MOTORIZED DAMPER
DIGITALINPUT
DIGITAL OUTPUT
ANALOGINPUT
ANAL06 OUTPUT
SUPPLV AIR
RETURN AIR
HEATING COIL
HOT WATER RETURN
HVDRONIC CONTROL VALVE
FIRE ALARM
SHUTDOWN
Q
DEDICATED
CONTROLLER
PROVIDED BV
CORE/SHELL
TO BMS
COMMUNICATION LOOP
C2
C5
ItMYtKNIVKt
TO BMS
COMMUNICATION LOOP
NOTES:
A. OCCUPIED MODE:
1. ON A RISE IN SPACE TEMPERATURE ABOVE THE COOLING SETPOINT, THE DAMPER SHALL MODULATE TO PROVIDE UP TO ITS
MAXIMUM CFM TO MAWTAIN SETPOINT. AS SPACE TEMPERATURE DECREASES, THE DAMPER SHALL MODULATE DOWN TO ITS
MINIMUM COOLING CFM TO MAINTAIN SETPOWT. AS SPACE TEMPERATURE DROPS BELOW HEATIN SETPOWT, HWR VALVE SHALL
MODULATE OPEN(WHERE NOTED).
B. UNOCCUPIED MODE
1. MODULATETO MAINTAIN SETBACKTEMPERATURE.
C. ALARMS:
1. ALARM THE TIME, VAV BOX OESIGNATION ANO DURATION OF ALL VAV OVERRIDES.
SHUT-OFF TERMINAL VAV BOX CONTROLS DIAGRAM
NO SCALE
RTU
CONTROLLER
ROOF
ZONEIVAV
CONTROLLER
ZONEIVAV I CENTR4LBACNET
CONTROLLER INTERFACE
1 ST FLOOR
NOTES'
1. PROVIOE CENTRAL BACNET WTERFACE FOR MONITORING OF ALL RTU'S AND VAV'S. INTERFACE
SHALL INCW DE WALL MOUNTED TOUCHSCREEN, W ITH ABILITV TO VIEW SPACE TEMPERATURE,
SETPOINT, VAV DAMPER POSITION, VAV HEAT STAGING, AND ALL IMEGRAL ALARMS AND POINTS
ASSOCIATED W ITH RTU'S.
SYSTEM LEVEL CONTROLS SCHEMATIC DIAGRAM
NO SCALE
C3
MULTI
STAGE
CONTROLLER
SPACE
TEMPER4TURE
1�1
� SA
ELECTRIC RH COIL
�oW
MED
HIGH
Bo
eo �
BO
AI
AI
BI
OEDICATED
AO CONTROLLER
TO BMS
COMMUNICATION LOOP
NOTES:
A. OCCUPIED MOOE
1. ON A RISE IN SPACE TEMPERATURE ABOVE THE COOLING SETPOINT, THE DAMPER SHALL MODULATE TO PROVIDE UP TO ITS
MAXIMUM CFM TO MAINTAIN SETPOINT. AS SPACE TEMPERATURE DECREASES, THE DAMPER SHALL MODULATE DOWN TO ITS
MINIMUM COOLING CFM TO MAINTAIN SETPOINT. IF TEMPERATURE IS STILL BELOW SETPOINT AT MINIMUM CFM, ELECTRIC HEAT
SHALL ENERGIZE.
B. UNOCCUPIEDMODE:
1. MODULATE TO MAINTAIN SETBACK TEMPERATURE.
G ALARMS'.
1. ALARM THE TIME, VAV BOX DESIGNATION AND OURQTION OF ALL VAV OVERRIOES.
SHUT-OFF TERMINAL VAV BOX WITH ELECTRIC REHEAT CONTROLS DIAGRAM
NO SCALE
COWORKING
880 W MONON GREEN BLVD
CARMEL qTV, IN 460323
OWNERRENANi
INDUSTRIOUS
215PARKAVES,4E1300
NEW YORK, NY 10003
ARCNI7ECTOFRECORD
NORF
325 N LASALLE Si- SOIiE 500
CHICAGO. IL 60654
PEiER-DUBWC.ANORR-COM
312-0242400
MEFENG/NEER
MEENGINEERS
29 WEST 38iH SiREEi, SiH FLOOR
NEW YORK. NY 10018
CONiAQ: BRIAN SHASSIAN
BRIANSHASSIAN@ME-ENGINEER$_COM
JOHN HIGGINS
JOHN.HIGGWS(�MEENGINEERS.COM
�212J 44]-6]]0 PHONE
LIGHi1NGDESIGNER
REGENCY
9261 JOkDAN AVE
CHAiSWORiH, GA
&1�-28a-2�24
ISSUEDATES
REV. DAiE DESCRIPiION
06/OS/2020 DD3
06/18/2020 CDvI
0]/06/2020 CDv2
0]/16/2020 PERMIT
BY CHEGK
ME ME
ME ME
ME ME
ME ME
SEAL 8 SIGNANRE
RELEA5E0 FOR CONSTRUCTI�N
Suhjec��o compliance with allregula�ions
04 S�a�e antl Local Codes
City of Carmel
r
�un��V l�rc�alols�.
�
DATE: OH�Z5�2O
PR0./ECTNAME
CARMEL CITY- 880 MONON GREEN
VROJECiNUMBER
IND880MON
DRAWING TITLE
MECHANICAL DETAILS II
SCALE
7/8„_ ��_�„
SHEETNUMBER
M-701
oF