Requirements: 100.0% were addressed directly in the COMcheck software
COMcheck Software Version COMcheckWeb
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 90.1 (2007) Standard
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
4.2.2
[PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the lighting and
electrical systems and equipment and
document where exceptions to the
standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
8.4.1.1,
8.4.1.2
[PR6]2
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the electrical systems
and equipment and document where
exceptions are claimed. Feeder
connectors sized in accordance with
approved plans and branch circuits
sized for maximum drop of 3%.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Hobby Horse Barn at Jackson's Grant 05/13/20Report date:
75 ofPage
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
9.4.1.1
[EL1]2
Automatic controls to shut off all
building lighting installed in buildings
>5,000 ft2.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.4.1.2
[EL2]2
Independent lighting controls installed
per approved lighting plans and all
manual controls readily accessible and
visible to occupants.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.4.1.3
[EL3]2
Automatic lighting controls for exterior
lighting installed.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.4.1.4
[EL4]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.4.2
[EL5]3
Ballasted one and three lamp fixtures
with >30 W/lamp have two lamp
tandem wired ballasts when >=2
fixtures in same space on same
control.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.4.3
[EL6]1
Exit signs do not exceed 5 watts per
face.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.4.4
[EL7]1
Exterior grounds lighting over 100 W
provides >60 lm/W unless on motion
sensor or fixture is exempt from scope
of code or from external LPD.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.6.2
[EL8]1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Hobby Horse Barn at Jackson's Grant 05/13/20Report date:
76 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
8.7.1
[FI16]3
Furnished as-built drawings for
electric power systems within 30 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
8.7.2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
9.2.2.3
[FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
9.4.5
[FI19]1
Exterior lighting power is consistent
with what is shown on the approved
lighting plans, demonstrating
proposed watts are less than or equal
to allowed watts.
Complies
Does Not
Not Observable
Not Applicable
See the Exterior Lighting fixture schedule for values.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Hobby Horse Barn at Jackson's Grant 05/13/20Report date:
77 ofPage
MEMORANDUM
Date: May 1, 2020
Recipient: Indiana Department of Homeland Security
Division of Fire and Building Safety
Plan Review Branch
Project Number: 415247
Project Name: Hobby Horse Barn at Jackson’s Grant
Carmel, Indiana
Topic: Building Envelope Energy Code Compliance Check
Regarding the energy code compliance check (ComCheck) for the Hobby Horse Barn at Jackson's Grant project
(415247), the lighting/electrical will comply with the energy code but the envelope will not. Since the building is
not being heated nor air conditioned, the Owner felt that insulating the walls would be a waste of money as well as
detract from the realistic “barn” interior. The building will not be used at all in the winter time and simply rely on
open doors and windows in the summertime for ventilation. It is reasonable to believe that the building envelope
portion of the energy code compliance check assumes that the building will be heated and cooled as well as
occupied throughout the year. This is not the case with this project and, because there is no insulation within the
walls, the building envelope fails the compliance check. It is requested that the building envelope energy code
compliance check be waived.
Submitted by:
Parvin D. Gillim
Project Architect