Domus Structural Engineering, LLC
P.O. Box 6986
Broomfield, CO 80021
530-864-7055
Domusstructural@gmail.com
To: Blue Raven Solar
1403 North Research Way, Building J
Orem, UT. 84097
Subject: Certification Letter
Shea Residence
5115 Hummingbird Cir.
Carmel, IN. 46033
To Whom It May Concern,
Design Criteria:
● Applicable Codes = 2014 Indiana State Building Code, ASCE 7‐10
● Roof Dead Load = 12 psf (MP1)
● Roof Live Load = 20 psf
● Wind Speed = 115 mph (Vult), Exposure C, Risk Category II
●
●
Sincerely,
John Calvert, P.E.
Project Engineer
August 7, 2020
The roof structure of (MP1) consists of composition shingle on roof plywood that is supported by 2x6 rafters @ 16"o.c.. The rafters
support a vaulted ceiling and have a max projected horizontal span of 12'‐0", with a slope of 45 degrees. The rafters are supported
at the ridge by a ridge board and at the eave by a load bearing wall.
The existing roof framing system of (MP1) is judged to be adequate to withstand the loading imposed by the installation of the
solar panels. No reinforcement is necessary.
Ground Snow Load = 20 psf ‐ Roof Snow Load = 14 psf
The spacing of the solar standoffs should be kept at 64" o.c. for landscape and 48" o.c. for portrait orientation, with a staggered
pattern to ensure proper distribution of loads.
A jobsite observation of the condition of the existing framing system was performed by an audit team of Blue Raven Solar as a
request from Domus Structural Engineering. All review is based on these observations and the design criteria listed below and only
deemed valid if provided information is true and accurate.
On the above referenced project, the roof structural framing has been reviewed for additional loading due to the installation of the
solar PV addition to the roof. The structural review only applies to the section of the roof that is directly supporting the solar PV
system and its supporting elements. The observed roof framing is described below. If field conditions differ, contractor to notify
engineer prior to starting construction.
The scope of this report is strictly limited to an evaluation of the fastener attachment, underlying framing and supporting structure
only. The attachment's to the existing structure are required to be in a staggered pattern to ensure proper distribution of loading.
All panels, racking and hardware shall be installed per manufacturer specifications and within specified design limitations. All
waterproofing shall be provided by the manufacturer. Domus Structural Engineering assumes no responsibility for misuse or
improper installation of the solar PV panels or racking.
Please contact me with any further questions or concerns regarding this project.
Note: Seismic check is not required since Ss<.4g and Seismic Design Category (SDC) < B
Attachments: 1 ‐ 5/16" dia. lag screw with 2.5 inch min embedment
depth, at spacing shown above.
Shea Residence, Carmel, IN 1
____________________________________________________________________________________
Domus Structural Engineering, LLC
P.O. Box 6986
Broomfield, CO 80021
530-864-7055
Domusstructural@gmail.com
20 psf
(ASCE7 - Eq 7-1)
1 (ASCE7 - Table 7-2)
1 (ASCE7 - Table 7-3)
1
14.0 psf
(ASCE7 - Eq 7-2)
1
14.0 psf
4.24 psf
3.0 psf
4.00 ft
5.50 ft
22.00 sft
66 lb
4.00
2.00
1.72
4.00
0.28
12.0 psf
17.0 psf
Gravity Loading
PV System Weight
Weight of PV System (Per Blue Raven Solar)
X Standoff Spacing =
Y Standoff Spacing =
Note: PV standoffs are staggered to ensure proper distribution of loading
2x6 Rafters @ 16"o.c.
I = Importance Factor =
Cs = Slope Factor =
Standoff Tributary Area =
ps = Cspf
ps = Sloped Roof Snow Load =
pf = Flat Roof Snow Load =
DL Adjusted to 45 Degree Slope
Roof Snow Load Calculations
pg = Ground Snow Load =
Ce = Exposure Factor =
pf = 0.7 Ce Ct I pg
Ct = Thermal Factor =
Roof Live Load = 20 psf
Roof Plywood
Roof Dead Load (MP1)
Composition Shingle
Note: Roof live load is removed in area's covered by PV array.
DL Adjusted to 45 Degree Slope
Point Loads of Standoffs
Miscellaneous
Vaulted Ceiling
Total Roof DL (MP1)
PV Dead Load = 3 psf (Per Blue Raven Solar)
Shea Residence, Carmel, IN 2
___________________________________________________________________________________________
Domus Structural Engineering, LLC
P.O. Box 6986
Broomfield, CO 80021
530-864-7055
Domusstructural@gmail.com
115 mph
C
Hip/Gable
45 degrees
20 ft
19.3 ft
(Eq. 30.3-1)
0.9 (Table 30.3-1)
1 (Fig. 26.8-1)
0.85 (Table 26.6-1)
115 mph (Fig. 26.5-1A)
II (Table 1.5-1)
qh = 25.90
15.54
Zone 1 Zone 2 Zone 3 Positive
GCp = -0.88 -1.08 -1.08 0.84 (Fig. 30.4-1)
Uplift Pressure = -13.61 psf -16.72 psf -16.72 psf 21.7 psf
X Standoff Spacing = 4.00 4.00 2.67
Y Standoff Spacing = 5.50 2.75 2.75
Tributary Area = 22.00 11.00 7.33
Footing Uplift = -299 lb -184 lb -123 lb
Zone 1 Zone 2 Zone 3 Positive
GCp = -0.88 -1.08 -1.08 0.84 (Fig. 30.4-1)
Uplift Pressure = -13.61 psf -16.72 psf -16.72 psf 10.0 psf (Minimum)
X Standoff Spacing = 5.33 5.33 3.56
Y Standoff Spacing = 3.50 1.75 1.75
Tributary Area = 18.67 9.33 6.22
Footing Uplift = -254 lb -156 lb -104 lb
-299 lb
450 lb
Therefore, OK
Fastener =1 - 5/16" dia. lag
Number of Fasteners = 1
Embedment Depth = 2.5
Pullout Capacity Per Inch = 250 lb
Fastener Capacity = 625 lb
w/ F.S. of 1.5 & DOL of 1.6= 667 lb
Therefore, OK
Wind Calculations
Maximum Design Uplift =
Standoff Uplift Capacity =
450 lb capacity > 299 lb demand
Fastener Capacity Check
Standoff Uplift Check
Kz (Exposure Coefficient) =
Kzt (topographic factor) =
Kd (Wind Directionality Factor) =
V (Design Wind Speed) =
Risk Category =
qh = 0.00256 * Kz * Kzt * Kd * V^2
Wind Pressure P = qh*G*Cn
Exposure Category
Per ASCE 7‐10 Components and Cladding
Mean Roof Height
Roof Slope
667.2 lb capacity > 299 lb demand
0.6 * qh =
Standoff Uplift Calculations-Landscape
Input Variables
Wind Speed
Effective Wind Area
Design Wind Pressure Calculations
Roof Shape
Standoff Uplift Calculations-Portrait
Shea Residence, Carmel, IN 3
___________________________________________________________________________________________
Domus Structural Engineering, LLC
P.O. Box 6986
Broomfield, CO 80021
530-864-7055
Domusstructural@gmail.com
(MP1)PASS
Dead Load 17.0 psf
PV Load 4.2 psf
Snow Load 14.0 psf
Governing Load Combo = DL + LL
Total Load 41.2 psf
Fb (psi) = f'b x Cd x Cf x Cr (NDS Table 4.3.1)
900 x 1.25 x 1.3 x 1.15
Allowed Bending Stress = 1681.8 psi
(wL^2) / 8
= 989.117 ft#
= 11869.4 in#
Actual Bending Stress = (Maximum Moment) / S
= 1569.6 psi
L/180 (E = 1600000 psi Per NDS)
= 0.8 in
Deflection Criteria Based on =
(w*L^4) / (185*E*I)
=
= L/450 > L/180 Therefore OK
Allowed Deflection (Live Load) =L/240
0.6 in
(w*L^4) / (185*E*I)
L/924 > L/240 Therefore OK
Member Area = Fv (psi) = 180 psi (NDS Table 4A)
Allowed Shear = Fv * A =Max Shear (V) = w * L / 2 =330 lb
Framing Check
8.3 in^2
Check Shear
w = 55 plf
2x6 Rafters @ 16"o.c.
Member Span = 12' - 0"
1485 lb
Allowed > Actual -- 22.3% Stressed -- Therefore, OK
DF#2
Member Spacing
@ 16"o.c.
Maximum Moment =
Check Deflection
I (in^4)
20.80
Lumber Sp/Gr
Actual Deflection (Live Load) =
Allowed Deflection (Total Load) =
Actual Deflection (Total Load) =
Allowed > Actual -- 93.4% Stressed -- Therefore, OK
Member Properties
Member Size
2x6
S (in^3)
7.56
0.156 in
Continuous Span
0.320 in
Check Bending Stress
(True Dimensions)
Shea Residence, Carmel, IN 4