HomeMy WebLinkAboutA004 WALL TYPESA2
A3
WALL PARTITION TYPEPLAN VIEW SECTION VIEWSECTION VIEW
REMARKS
NON-
RATED
REFER TO SCHEDULE BELOW FOR PARTITION WIDTH
NON-
RATED
A
METAL STUD FRAMING @ 16" O.C. MAX.
ONE LAYER 5/8" (TYPE-X) GYPSUM WALL BOARD, EACH SIDE
PROVIDE SOUND ATTENUATION INSULATION AS REQUIRED -SEE SCHEDULE BELOW
METAL RUNNER
ADDITIONAL WALL FINISH (SHOWN DASHED) ON ONE OR BOTH SIDES WHERE OCCURS;
REFER TO FLOOR PLANS AND ROOM FINISH SCHEDULE FOR OCCURRENCE, LOCATION,
AND EXTENT OF WALL COVERAGE. 5/8" MOISTURE RESISTANT GYPSUM WALL BOARD
REPLACES TYPE-X AS SUBSTRATE IN ALL RESTROOMS AND JANITOR'S CLOSETS,TYPICAL
ELIMINATOR TRACK
LINE OF
STRUCTURE
UNDERSIDE OF
STRUCTURE
CEILING GRID
STUD
WIDTH
PART.
WIDTH
FIRE
RATING
UL LISTING
WITH SOUND
ATTENUATION
DESIGNATION
NO SOUND
ATTENUATION
DESIGNATION
NA
NA
3 -3/4"
4 -7/8"3 -5/8"
2 -1/2"
STC:
NO SOUND
WITH SOUND
A2S
A3SB2
B3
B6
B1 B1S
WALL PARTITION TYPE 42" FINISHEDPLAN VIEW SECTION VIEWSECTION VIEW
REMARKS
NON-
RATED
NON-
RATED
NON-
RATED
REFER TO SCHEDULE BELOW FOR PARTITION WIDTH
NON-
RATED
B
METAL STUD FRAMING @ 16" O.C. MAX.
ONE LAYER 5/8" (TYPE-X) GYPSUM WALL BOARD, EACH SIDE
PROVIDE SOUND ATTENUATION INSULATION AS REQUIRED -SEE SCHEDULE BELOW
METAL RUNNER
ADDITIONAL WALL FINISH (SHOWN DASHED) ON ONE OR BOTH SIDES WHERE OCCURS;
REFER TO FLOOR PLANS AND ROOM FINISH SCHEDULE FOR OCCURRENCE, LOCATION,
AND EXTENT OF WALL COVERAGE. 5/8" MOISTURE RESISTANT GYPSUM WALL BOARD
REPLACES TYPE-X AS SUBSTRATE IN ALL RESTROOMS AND JANITOR'S CLOSETS,TYPICAL
METAL RUNNER
LINE OF
STRUCTURE
STUD
WIDTH
PART.
WIDTH
FIRE
RATING
UL LISTING
WITH SOUND
ATTENUATION
DESIGNATION
NO SOUND
ATTENUATION
DESIGNATION
NA
NA
NA
NA
2 -7/8"
3 -3/4"
4 -7/8"
7 -1/4"6"
3 -5/8"
2 -1/2"
1 -5/8"
STC:
NO SOUND
WITH SOUND
B2S
B3S
B6S
B8
NON-
RATED NA9 -1/4"8"
B8S
UNDERSIDE OF
STRUCTURE
C2
C3
C6
C1 C1S
WALL PARTITION TYPE 4"PLAN VIEW SECTION VIEWSECTION VIEW
REMARKS
NON-
RATED
NON-
RATED
NON-
RATED
REFER TO SCHEDULE BELOW FOR PARTITION WIDTH
NON-
RATED
C
METAL STUD FRAMING @ 16" O.C. MAX.
ONE LAYER 5/8" (TYPE-X) GYPSUM WALL BOARD, ONE SIDE
PROVIDE SOUND ATTENUATION INSULATION AS REQUIRED -SEE SCHEDULE BELOW
METAL RUNNER
ADDITIONAL WALL FINISH (SHOWN DASHED) ON ONE OR BOTH SIDES WHERE OCCURS;
REFER TO FLOOR PLANS AND ROOM FINISH SCHEDULE FOR OCCURRENCE, LOCATION,
AND EXTENT OF WALL COVERAGE. 5/8" MOISTURE RESISTANT GYPSUM WALL BOARD
REPLACES TYPE-X AS SUBSTRATE IN ALL RESTROOMS AND JANITOR'S CLOSETS,TYPICAL.
METAL RUNNER
LINE OF
STRUCTURE
UNDERSIDE
OF
STRUCTURE
LINE OF
CEILING
STUD
WIDTH
PART.
WIDTH
FIRE
RATING
UL LISTING
WITH SOUND
ATTENUATION
DESIGNATION
NO SOUND
ATTENUATION
DESIGNATION
NA
NA
NA
NA
2 -1/4"
3 -1/8"
4 -1/4"
6 -5/8"6"
3 -5/8"
2 -1/2"
1 -5/8"
STC:
NO SOUND
WITH SOUND
C2S
C3S
C6S
C8 NON-
RATED NA 8 -5/8"8"
C8S
LATERAL BRACING AT 4'-0" O.C. MAX.
E2
E3
E6
E1 E1S
WALL PARTITION TYPE PLAN VIEW SECTION VIEWSECTION VIEW
REMARKS
NON-
RATED
NON-
RATED
NON-
RATED
REFER TO SCHEDULE BELOW FOR PARTITION WIDTH
NON-
RATED
E
METAL STUD FRAMING @ 16" O.C. MAX.
ONE LAYER 5/8" (TYPE-X) GYPSUM WALL BOARD, ONE SIDE
PROVIDE SOUND ATTENUATION INSULATION AS REQUIRED -SEE SCHEDULE BELOW
METAL RUNNER
ADDITIONAL WALL FINISH (SHOWN DASHED) ON ONE OR BOTH SIDES WHERE OCCURS;
REFER TO FLOOR PLANS AND ROOM FINISH SCHEDULE FOR OCCURRENCE, LOCATION,
AND EXTENT OF WALL COVERAGE. 5/8" MOISTURE RESISTANT GYPSUM WALL BOARD
REPLACES TYPE-X AS SUBSTRATE IN ALL RESTROOMS AND JANITOR'S CLOSETS,TYPICAL.
METAL RUNNER
LINE OF
STRUCTURE
UNDERSIDE
OF
STRUCTURE
LINE OF
CEILING
STUD
WIDTH
PART.
WIDTH
FIRE
RATING
UL LISTING
WITH SOUND
ATTENUATION
DESIGNATION
NO SOUND
ATTENUATION
DESIGNATION
NA
NA
NA
NA
2 -1/4"
3 -1/8"
4 -1/4"
6 -5/8"6"
3 -5/8"
2 -1/2"
1 -5/8"
STC:
NO SOUND
WITH SOUND
E2S
E3S
E6S
E8
NON-
RATED NA 8 -5/8"8"
E8S
D2
D3
D6
D1 D1S
WALL PARTITION TYPE4"PLAN VIEW SECTION VIEWSECTION VIEW
REMARKS
NON-
RATED
NON-
RATED
NON-
RATED
REFER TO SCHEDULE BELOW FOR PARTITION WIDTH
NON-
RATED
D
METAL STUD FRAMING @ 16" O.C. MAX.
ONE LAYER 5/8" (TYPE-X) GYPSUM WALL BOARD, EACH SIDE
PROVIDE SOUND ATTENUATION INSULATION AS REQUIRED -SEE SCHEDULE BELOW
METAL RUNNER
ADDITIONAL WALL FINISH (SHOWN DASHED) ON ONE OR BOTH SIDES WHERE OCCURS;
REFER TO FLOOR PLANS AND ROOM FINISH SCHEDULE FOR OCCURRENCE, LOCATION,
AND EXTENT OF WALL COVERAGE. 5/8" MOISTURE RESISTANT GYPSUM WALL BOARD
REPLACES TYPE-X AS SUBSTRATE IN ALL RESTROOMS AND JANITOR'S CLOSETS,TYPICAL
METAL RUNNER
LINE OF
STRUCTURE
UNDERSIDE OF
STRUCTURE
LINE OF
CEILING
STUD
WIDTH
PART.
WIDTH
FIRE
RATING
UL LISTING
WITH SOUND
ATTENUATION
DESIGNATION
NO SOUND
ATTENUATION
DESIGNATION
NA
NA
NA
NA
2 -7/8"
3 -3/4"
4 -7/8"
7 -1/4"6"
3 -5/8"
2 -1/2"
1 -5/8"
STC:
NO SOUND
WITH SOUND
D2S
D3S
D6S
D8 NON-
RATED NA9 -1/4"8"
D8S
LATERAL BRACING AT 4'-0" O.C. MAX.
F2
F3
F6
F1 F1S
WALL PARTITION TYPE PLAN VIEW SECTION VIEWSECTION VIEW
REMARKS
REFER TO SCHEDULE BELOW FOR PARTITION WIDTH
NON-
RATED
F
METAL STUD FRAMING @ 16" O.C. MAX.
ONE LAYER 5/8" (TYPE-X) GYPSUM WALL BOARD, EACH SIDE
PROVIDE SOUND ATTENUATION INSULATION AS REQUIRED -SEE SCHEDULE BELOW
METAL RUNNER
ADDITIONAL WALL FINISH (SHOWN DASHED) ON ONE OR BOTH SIDES WHERE OCCURS;
REFER TO FLOOR PLANS AND ROOM FINISH SCHEDULE FOR OCCURRENCE, LOCATION,
AND EXTENT OF WALL COVERAGE. 5/8" MOISTURE RESISTANT GYPSUM WALL BOARD
REPLACES TYPE-X AS SUBSTRATE IN ALL RESTROOMS AND JANITOR'S CLOSETS,TYPICAL
METAL RUNNER
LINE OF
STRUCTURE
UNDERSIDE OF
STRUCTURE
LINE OF
CEILING
STUD
WIDTH
PART.
WIDTH
FIRE
RATING
UL LISTING
WITH SOUND
ATTENUATION
DESIGNATION
NO SOUND
ATTENUATION
DESIGNATION
NA 2 -7/8"
3 -3/4"
4 -7/8"
7 -1/4"6"
3 -5/8"
2 -1/2"
1 -5/8"
STC:
NO SOUND
WITH SOUND
F2S
F3S
F6S
F8
9 -1/4" 8"
F8S
NON-
RATED NA
NON-
RATED NA
NON-
RATED NA
NON-
RATED NA
WALL TYPES
NOTE:
ALL PLAN DIMENSIONS ARE FROM FACE TO FACE OF FINISHED WALL. NOT
ALL WALL TYPES LISTED ARE NECESSARILY USED ON THIS PROJECT. REFER
TO REFLECTED CEILING PLAN FOR CEILING HEIGHTS.[PROJECT NUMBER][DATE][DRAWN BY][CHECKED BY]ALL DESIGNS, CONCEPTS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THESE DRAWINGS ARE
OWNED BY PARALLEL DESIGN GROUP, INC. AND SHALL NOT BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORP. FOR
ANY REASON WHATSOEVER WITHOUT THE WRITTEN CONSENT
OF PARALLEL DESIGN GROUP INC.
CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS ON THE JOB SITE. PARALLEL DESIGN GROUP INC.
MUST BE NOTIFIED OF ANY DISCREPANCIES OR VARIATIONS
FROM THE DIMENSIONS SHOWN ON THE PLAN.
N [ P ][ W ]Indianapolis, IN 46240ParallelDG.com317.721.4399 8940 River Crossing Blvd. Ste 1502020.19007.22.2020BWSB & BDSTRATEGIC CAPITAL PARTNERSINDIANAPOLIS, INDIANA 46240280 E 96TH STREET, SUITE 250A004
WALL TYPESREVISION SCHEDULEMARK DATE DESCRIPTION09/09/20