HomeMy WebLinkAboutA201 REFLECTED CEILING PLAND DDD DD1. REUSE EXISTING CEILING GRID UNLESS OTHERWISE NOTED. EXISTING GRID IS
2'x2' AT 9'-0" A.F.F. REPAIR ANY DAMAGED GRID AND PAINT GRID WHITE AS
REQUIRED.
2. REPLACE ALL DAMAGED OR DIRTY CEILING TILES WITH NEW TO MATCH EXISTING.
PROVIDE LIKE TILES IN INDIVIDUAL ROOMS TO CREATE UNIFORM LOOK.
3. WHERE MULTIPLE SWITCHES ARE SHOWN, PROVIDE (1) GANG BOX WITH A SINGLE
COVERPLATE.
4. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER NEMA AND
IBC. EMERGENCY BATTERY PACKS OR LIGHTS CONNECTED TO AN EMERGENCY
POWER SOURCE ARE REQUIRED IF THE SPACE CONTAINS 50 PERSONS OR MORE.
FIXTURES SHOWN ON PLAN ARE FOR REFERENCE ONLY.
5. LIGHTING PLACEMENT AND QUANTITIES ARE FOR REFERENCE ONLY AND ARE TO
BE PROVIDED BY LIGHTING CONSULTANT AND ELECTRICIAN. ELECTRICAL
CONTRACTOR IS RESPONSIBLE FOR VERIFYING THAT LAY-OUT AND TOTAL
WATTAGE MEETS ASHRAE 90.1 STANDARDS AND LIGHT LEVELS ARE APPROPRIATE
FOR THE USE OF EACH SPACE. OVER 50% OF THE LIGHTING WILL BE REPLACED
WITH NEW, SO ASHRAE WATTAGE REQUIREMENTS WILL NEED TO BE MET.
6. UNLESS NOTED OTHERWISE ALL NEW SWITCHES MUST BE AN OCCUPANCY
SENSOR COMBO UNIT WITH BOTH ULTRASONIC AND INFRARED TECHNOLOGY
WITH A ONE BUTTON OVERRIDE. OCCUPANCY SENSORS ARE TO BE LOCATED
SUCH THAT OCCUPANCY WITHIN ANY PORTION OF INCLUDED AREA IS DETECTED.
PROVIDE CEILING MOUNTED OCCUPANCY SENSORS IN OPEN AREAS AS
REQUIRED.
7. CAN LIGHT FIXTURES TO BE SWITCHED SEPARATELY AND HAVE DIMMERS.
8. ALL EXPOSED ACOUSTICAL CEILING TILE EDGES TO BE FINISHED WITH 4" WHITE
AXIOM TRIM UNLESS NOTED OTHERWISE.
9. ALL DEVICES AND COVERS TO BE WHITE.
10. ALL EXPOSED DECK (INCLUDING SPRINKLERS PIPES) TO BE PAINTED PT1 UNLESS
NOTED OTHERWISE.
11. ALL DRYWALL CEILINGS TO BE PAINTED PT1 UNLESS NOTED OTHERWISE.
12. PAINT 10' BEYOND PERIMETER OF CEILINGS WHERE OPEN DECK IS EXPOSED
BEYOND AND WHERE IT TRANSITIONS FROM OPEN DECK TO ACOUSTICAL TILE.
PAINT EXPOSED DECK WITH DRYFALL PAINT.
13. WHERE PLAN INDICATES EXPOSED DECK AT EXTERIOR WALLS, CONTRACTOR TO
INCLUDE PROVIDING, INSTALLING, AND FINISHING THE DRYWALL ABOVE THE
WINDOW HEADER AT THE EXTERIOR PERIMETER WALLS AS REQUIRED.
14. DECORATIVE FIXTURE(S) SPECIFIED ARE TO BE PURCHASED THRU LOCAL
COMMERCIAL VENDOR TO INSURE COMMERICAL WARRANTIES. PURCHASING
FROM OTHER VENDORS OR AVENUES IS AT THE SUPPLIER'S / EC'S RISK NOT, THE
PARALLEL DESIGN GROUP'S, OWNER'S, OR TENANT'S.
15. IF IN GOOD CONDITION, EXISTING H.V.A.C. DEVICES SALVAGED FROM
DEMOLITION CAN BE SUBSTITUTED FOR NEW. NO NEW HVAC DUCTWORK IS TO
BE INSTALLED PER THIS SHEET.
GENERAL NOTESLEGEND
MECHANICAL NOTES
KEYED NOTES
1. SCOPE INTENT IS FOR EXISTNG MECHANICAL SYSTEMS TO REMAIN. EXISTING FLEX
DUCT AND DIFFUSERS BEING RELOCATED AS NECESSARY PER WALL LAYOUT. NO
MAIN DUCTWORK BEING RELOCATED. MECHANICAL CONTRACTOR IS RESPONSIBLE
FOR NOTIFYING APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED.
2. DIFFUSER LOCATIONS ARE SHOWN ON PLAN FOR REFERENCE ONLY, CONTRACTOR
IS TO PLACE LOCATION OF DIFFUSERS AND RETURN AIR GRILLES AS REQUIRED BY
CODE.
3. FIRE STOP ANY EXISTING DECK PENETRATIONS AS REQUIRED.
4. LOCATE THERMOSTATS WHERE APPROPRIATE PER MECHANICAL DESIGN. ALL
THERMOSTATS TO HAVE LED DISPLAY WITH LOCKOUT CAPABILITY AND LOCK BOX.
VERIFY LOCATIONS WITH TENANT BEFORE INSTALLING.
5. WHERE EXPOSED DECK IS SHOWN, VERIFY WITH DESIGNER AND TENANT IF DUCT
WORK SHOULD BE SPIRAL DUCT.
DIFFUSER, LAY-IN, 2'x2'
DIFFUSER, LAY-IN, 1'x4'
DIFFUSER, LAY-IN, 4"X4'
NOTE: IF IN GOOD CONDITION, EXISTING H.V.A.C. DEVICES AND
CEILING TILES SALVAGED FROM DEMOLITION CAN BE SUBSTITUTED
FOR NEW. NO NEW HVAC DUCTWORK IS TO BE INSTALLED PER THIS
SHEET.
X
X' -X"
CEILING TYPE
CEILING HEIGHT
2' x 2' ACOUSTICAL CEILING (EXISTING TO REMAIN)
MFG: ARMSTRONG
TYPE: DUNE
EXPOSED DECK-PAINT PT1, DRY WALL PAINT
A
INDICATES NIGHT LIGHT
LOCATIONNL
EXIT LIGHT FIXTURE
EMERGENCY LIGHT
FIXTURE
NEW CEILING GRID,
SUSPENDED, 2'x2'
NEW GYPSUM BOARD CEILING
EXISTING CEILING GRID,
SUSPENDED, 2'x2'
LIGHT SWITCH
LIGHT SWITCH,
3-WAY
LIGHT SWITCH,
4-WAY
LIGHT SWITCH,
DIMMER
LIGHT CIRCUIT
3
4
D
EL
EXISTING GYPSUM BOARD
CEILING
LIGHT FIXTURE, WHITE
LUMENWERX VIA3 LINEAR
WALL WASH LED, LENGTHS
VARY; SEE SIZES INDICATED ON
PLAN
D1
LIGHT FIXTURE, PENDANT FIXTURE, LED
MFG: TECH LIGHTING
MFG ID: 700FJPPRSS-LEDS930
MODEL: TLG67148
FINISH: SATIN NICKEL
P1
LIGHT FIXTURE, 24" DIAMETER
PENDANT FIXTURE
MFG: ET2
MFG ID: E31256-BBK
MODEL: 23.5" ET2813708
FINISH: BRUSHED BLACK
P2
LIGHT FIXTURE, 2'X4', LED
MFG: COOPER LIGHTING
STYLE: 2X4 METALUX LED
LIGHT FIXTURE
LED UNDER CABINET LIGHTINGL1
LIGHT FIXTURE, WHITE
LUMENWERX VIA3 LINEAR
SUSPENDED LED
DIRECT/INDIRECT, LENGTHS
VARY; SEE SIZES INDICATED ON
PLAN
D2
B
LIGHT FIXTURE
WALL SCONCE
MFG: BETACALCO
MODEL: STRIPE
FINISH: POWDER COATED
L2
D2 - 12'-0"
D2 - 12'-0"
P1
P2
P2
D1 - 18'-0"D1 - 18'-0"
P1
P2
D2 -7'
-0"D2 -7'-0"D2 -7'
-0"D2 -7'-0"D2 -7'
-0"D2 -7'-0"1
1
1
1
D2 - 12'-0"
L1 L1L1EL EL ELL2
L2
L2
2
AREA NOT IN CONTRACT
AREA OF WORK
MECHANICAL DIFFUSER RELOCATION1NOT TO SCALE
*REFER TO MECHANICAL NOTES FOR FURTHER INFORMATION
RELOCATE DIFFUSERS AND
FLEX DUCT IF REQUIRED
VAV/
HEAT PUMPEXISTING VAV BOXES OR
HEAT PUMP AND MAIN SUPPLY
DUCTS TO REMAIN
[PROJECT NUMBER][DATE][DRAWN BY][CHECKED BY]ALL DESIGNS, CONCEPTS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THESE DRAWINGS ARE
OWNED BY PARALLEL DESIGN GROUP, INC. AND SHALL NOT BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORP. FOR
ANY REASON WHATSOEVER WITHOUT THE WRITTEN CONSENT
OF PARALLEL DESIGN GROUP INC.
CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS ON THE JOB SITE. PARALLEL DESIGN GROUP INC.
MUST BE NOTIFIED OF ANY DISCREPANCIES OR VARIATIONS
FROM THE DIMENSIONS SHOWN ON THE PLAN.
N [ P ][ W ]Indianapolis, IN 46240ParallelDG.com317.721.4399 8940 River Crossing Blvd. Ste 1502020.19007.22.2020BWSB & BDSTRATEGIC CAPITAL PARTNERSINDIANAPOLIS, INDIANA 46240280 E 96TH STREET, SUITE 250A201
REFLECTED
CEILING PLAN
1 PAINT DECK AND DUCT WORK WHITE.
2 PROVIDE SOUND BOOT WITH 2'X2', LAY-IN DIFFUSER.
1/8" = 1'-0"
REFLECTED CEILING PLAN 1 REVISION SCHEDULEMARK DATE DESCRIPTION09/09/20