HomeMy WebLinkAboutA202_ReflectedCeilingDDD 1. WHERE CEILINGS ARE TEXTURED, ADD NEW LAYER OF SMOOTH 5/8" DRYWALL CEILINGS THROUGHOUT AT 9' -10" +/-A.F.F. 2. REMOVE ALL LIGHT FIXTURES AND PROVIDE 4" SQUARE RECESSED CAN LIGHTING THROUGHOUT. COLOR TEMPERATURE TO BE 3500K. 3. WHERE MULTIPLE SWITCHES ARE SHOWN, PROVIDE (1) GANG BOX WITH A SINGLE COVERPLATE. 4. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED IF THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES SHOWN ON PLAN ARE FOR REFERENCE ONLY. 5. LIGHTING PLACEMENT AND QUANTITIES ARE FOR REFERENCE ONLY AND ARE TO BE PROVIDED BY LIGHTING CONSULTANT AND ELECTRICIAN. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING THAT LAY-OUT AND TOTAL WATTAGE MEETS ASHRAE 90.1 STANDARDS AND LIGHT LEVELS ARE APPROPRIATE FOR THE USE OF EACH SPACE. OVER 50% OF THE LIGHTING WILL BE REPLACED WITH NEW, SO ASHRAE WATTAGE REQUIREMENTS WILL NEED TO BE MET. 6. UNLESS NOTED OTHERWISE ALL NEW SWITCHES MUST BE AN OCCUPANCY SENSOR COMBO UNIT WITH BOTH ULTRASONIC AND INFRARED TECHNOLOGY WITH A ONE BUTTON OVERRIDE. OCCUPANCY SENSORS ARE TO BE LOCATED SUCH THAT OCCUPANCY WITHIN ANY PORTION OF INCLUDED AREA IS DETECTED. PROVIDE CEILING MOUNTED OCCUPANCY SENSORS IN OPEN AREAS AS REQUIRED. 7. ALL DEVICES AND COVERS TO BE WHITE. 8. ALL DRYWALL CEILINGS TO BE PAINTED PT1 UNLESS NOTED OTHERWISE. GENERAL NOTESLEGEND KEYED NOTES X X' -X" CEILING TYPE CEILING HEIGHT GYPSUM BOARD CEILING PAINTED WHITE UNLESS NOTED OTHERWISE ON FINISH PLAN; PROVIDE ALL ACCESS PANELS REQUIRED FOR MAINTENANCE -LOCATIONS SHALL BE APPROVED BY PARALLEL DESIGN GROUP; PROVIDE GYPSUM BOARD VERTICAL SURFACES FOR ALL BULKHEAD CONDITIONS. SEE SECTIONS FOR VERTICAL RETURN DIMENSIONS. A INDICATES NIGHT LIGHT LOCATIONNL EXIT LIGHT FIXTURE EMERGENCY LIGHT FIXTURE NEW GYPSUM BOARD CEILING LIGHT SWITCH LIGHT SWITCH, 3-WAY LIGHT SWITCH, 4-WAY LIGHT SWITCH, DIMMER LIGHT CIRCUIT 3 4 D 4" SQUARE RECESSED CAN LIGHT MFG: HALO MODEL: PRS4 SMF48FS COLOR: WHITE 3500K EL EXISTING GYPSUM BOARD CEILING PENDANT FIXTURE, 24" DIAMETER ($700 MATERIAL ALLOWANCE/FIXTURE) LED UNDER CABINET LIGHTING MFG: HALO MODEL: HU11 C1 P1 L1 LED WALL SCONCES1 PENDANT FIXTURE, 6" -8" DIAMETER ($450 MATERIAL ALLOWANCE/FIXTURE) P2 P1 P1 P1 4' - 6" 4' - 6"7' - 0" 7' - 0"5' - 0" 5' - 0" 5' - 0" 5' - 0"7' - 0"EQ.EQ. EQ. EQ. C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 L1 2 2 2 ELAREA NOT IN CONTRACT AREA OF WORK 1[PROJECT NUMBER][DATE][DRAWN BY][CHECKED BY]ALL DESIGNS, CONCEPTS, ARRANGEMENTS AND PLANS INDICATED OR REPRESENTED BY THESE DRAWINGS ARE OWNED BY PARALLEL DESIGN GROUP, INC. AND SHALL NOT BE USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORP. FOR ANY REASON WHATSOEVER WITHOUT THE WRITTEN CONSENT OF PARALLEL DESIGN GROUP INC. CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS ON THE JOB SITE. PARALLEL DESIGN GROUP INC. MUST BE NOTIFIED OF ANY DISCREPANCIES OR VARIATIONS FROM THE DIMENSIONS SHOWN ON THE PLAN. N [ P ][ W ]8940 River Crossing Blvd. Ste 150Indianapolis, IN 46240ParallelDG.com317.721.4399 2020.16907.30.2020BWSB & BDA202 THIRD FLOOR REFLECTED CEILING PLANPYATT BUILDERS630 3RD AVENUE SOUTHWEST -2ND & 3RD FLOORCARMEL, INDIANA 460321 CONTROL OPEN OFFICE AREA LIGHTING WITH 3-WAY SWITCH AT THIS LOCATION. PROVIDE MULTIPLE SWITCHES AS REQUIRED. MAXIMUM OF 2,500 SQUARE FEET PER SWITCH PER ASHRAE 90.1. 2 CENTER PENDANTS OVER ISLAND. REFER TO FLOOR PLAN AND CONFIRM FINAL LOCATION WITH TENANT. 3/16" = 1'-0" THIRD FLOOR REFLECTED CEILING PLAN 1 MARK DATE DESCRIPTION09/16/20