1. EXISTING CEILING GRID AND TILE TO REMAIN. PROVIDE NEW CEILING GRID AND
TILE THROUGHOUT REMAINDER OF SPACE TO MATCH EXISTING. CEILING HEIGHT
TO BE CONTINUOUS WITH EXISTING GRID/TILE TO REMAIN.
2. WHERE MULTIPLE SWITCHES ARE SHOWN, PROVIDE (1) GANG BOX WITH A SINGLE
COVERPLATE.
3. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER NEMA AND
IBC. EMERGENCY BATTERY PACKS OR LIGHTS CONNECTED TO AN EMERGENCY
POWER SOURCE ARE REQUIRED IF THE SPACE CONTAINS 50 PERSONS OR MORE.
FIXTURES SHOWN ON PLAN ARE FOR REFERENCE ONLY.
4. LIGHTING PLACEMENT AND QUANTITIES ARE FOR REFERENCE ONLY AND ARE TO
BE PROVIDED BY LIGHTING CONSULTANT AND ELECTRICIAN. ELECTRICAL
CONTRACTOR IS RESPONSIBLE FOR VERIFYING THAT LAY-OUT AND TOTAL
WATTAGE MEETS ASHRAE 90.1 STANDARDS AND LIGHT LEVELS ARE APPROPRIATE
FOR THE USE OF EACH SPACE. OVER 50% OF THE LIGHTING WILL BE REPLACED
WITH NEW, SO ASHRAE WATTAGE REQUIREMENTS WILL NEED TO BE MET.
5. UNLESS NOTED OTHERWISE ALL NEW SWITCHES MUST BE AN OCCUPANCY
SENSOR COMBO UNIT WITH BOTH ULTRASONIC AND INFRARED TECHNOLOGY
WITH A ONE BUTTON OVERRIDE. OCCUPANCY SENSORS ARE TO BE LOCATED
SUCH THAT OCCUPANCY WITHIN ANY PORTION OF INCLUDED AREA IS DETECTED.
PROVIDE CEILING MOUNTED OCCUPANCY SENSORS IN OPEN AREAS AS
REQUIRED.
6. CAN LIGHT FIXTURES TO BE SWITCHED SEPARATELY AND HAVE DIMMERS.
7. ALL DEVICES AND COVERS TO BE WHITE.
8. DECORATIVE FIXTURE(S) SPECIFIED ARE TO BE PURCHASED THRU LOCAL
COMMERCIAL VENDOR TO INSURE COMMERICAL WARRANTIES. PURCHASING
FROM OTHER VENDORS OR AVENUES IS AT THE SUPPLIER'S / EC'S RISK NOT, THE
PARALLEL DESIGN GROUP'S, OWNER'S, OR TENANT'S.
9. IF IN GOOD CONDITION, EXISTING H.V.A.C. DEVICES SALVAGED FROM
DEMOLITION CAN BE SUBSTITUTED FOR NEW. NO NEW HVAC DUCTWORK IS TO
BE INSTALLED PER THIS SHEET.
GENERAL NOTESLEGEND
DIFFUSER, LAY-IN, 2'x2'
DIFFUSER, LAY-IN, 1'x4'
DIFFUSER, LAY-IN, 4"X4'
MECHANICAL NOTES
KEYED NOTES
1. SCOPE INTENT IS FOR EXISTNG MECHANICAL SYSTEMS TO REMAIN. EXISTING FLEX
DUCT AND DIFFUSERS BEING RELOCATED AS NECESSARY PER WALL LAYOUT. NO
MAIN DUCTWORK BEING RELOCATED. MECHANICAL CONTRACTOR IS RESPONSIBLE
FOR NOTIFYING APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED.
2. DIFFUSER LOCATIONS ARE SHOWN ON PLAN FOR REFERENCE ONLY, CONTRACTOR
IS TO PLACE LOCATION OF DIFFUSERS AND RETURN AIR GRILLES AS REQUIRED BY
CODE.
3. FIRE STOP ANY EXISTING DECK PENETRATIONS AS REQUIRED.
4. LOCATE THERMOSTATS WHERE APPROPRIATE PER MECHANICAL DESIGN. ALL
THERMOSTATS TO HAVE LED DISPLAY WITH LOCKOUT CAPABILITY AND LOCK BOX.
VERIFY LOCATIONS WITH TENANT BEFORE INSTALLING.
CEILING TYPE
CEILING HEIGHT
2' x 2' ACOUSTICAL CEILING
MFG: ARMSTRONG
TYPE: MATCH EXISTING
EDGE TYPE: MATCH EXISTING
GRID: 15/16"
NRC RATING: 0.55
FIRE RATING: CLASS A
A
INDICATES NIGHT LIGHT
LOCATION
NL
EXIT LIGHT FIXTURE
EMERGENCY LIGHT
FIXTURE
NEW CEILING GRID,
SUSPENDED, 2'x2'
NEW GYPSUM BOARD CEILING
EXISTING CEILING GRID,
SUSPENDED, 2'x2'
LIGHT SWITCH
LIGHT SWITCH,
3-WAY
LIGHT SWITCH,
DIMMER
LIGHT CIRCUIT
3
D
EL
EXISTING GYPSUM BOARD
CEILING
X
X' -X"
LIGHT FIXTURE, 2'X4', LED
MFG: COOPER LIGHTING
STYLE: 2X4 METALUX LED
EXHAUST FAN
(CONFIRM REQ.
WITH TENANT)
LIGHT FIXTURE, 2'X2', LED
MFG: COOPER LIGHTING
STYLE: 2X2 METALUX LED
('EX' -EXISTING TO BE REUSED)
C1
C2
LIGHT FIXTURE, RECESSED CAN
MFG: CALIBER COMMERCIAL
STYLE: 4SQLFL2XLW
SQUARE CAN LIGHT
LIGHT FIXTURE, RECESSED CAN
MFG: HALO
STYLE: RL3059FS1EWH
UNDERCABINET LIGHTING
MFG: CONTECH
STYLE: LPU2
(CONFIRM WIDTH/QUANTITIES
REQUIRED PER ELEVATION)
UC
LIGHT FIXTURE, RECESSED LINEAR
DIRECT
MFG: LUMENWERX
STYLE: VIA2R-HLO
LIGHT FIXTURE, PENDANT
MFG: LUMENWERX
STYLE: VIA 2 ACOUSTIX 8' LENGTH
FINISH: TBD
D1
P1
ELELEL
C1
C1 UCD1
D1
D1
P1D
D
D
C2 C2 C2
C2 C2 C2
EX
EX
EX
EX
EX
EX
AREA NOT IN CONTRACT
AREA OF WORK
MECHANICAL DIFFUSER RELOCATION1NOT TO SCALE
*REFER TO MECHANICAL NOTES FOR FURTHER INFORMATION
RELOCATE DIFFUSERS AND
FLEX DUCT IF REQUIRED
VAV/
HEAT PUMPEXISTING VAV BOXES OR
HEAT PUMP AND MAIN SUPPLY
DUCTS TO REMAIN
[PROJECT NUMBER][DATE][DRAWN BY][CHECKED BY]ALL DESIGNS, CONCEPTS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THESE DRAWINGS ARE
OWNED BY PARALLEL DESIGN GROUP, INC. AND SHALL NOT BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORP. FOR
ANY REASON WHATSOEVER WITHOUT THE WRITTEN CONSENT
OF PARALLEL DESIGN GROUP INC.
CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS ON THE JOB SITE. PARALLEL DESIGN GROUP INC.
MUST BE NOTIFIED OF ANY DISCREPANCIES OR VARIATIONS
FROM THE DIMENSIONS SHOWN ON THE PLAN.