HomeMy WebLinkAboutE001 - ELECTRICAL SYMBOLSA or AMP
AC
A/C
ACP
ACU
ADD
ADJ
AF
AFC
AFF
AFG
AHU
AIC
AL
AM
AMB
APPROX.
ARCH
ATS
AUTO
AVG
BC
BKR
BHP
BL
BLDG
BR
BTM
C
ºC
CAB
CB or C/B
C/C
CCTV
CKT
CL
CLG
COL
COMM
COMP
CONC
CONST
CONT
CONTR
CR
CT
CU
DB
DC
DEPT
DF
DIST
DM
DO
DRS
DWG
EC
EF
ELEC
ELEV
ELV
EMER
ENCL
EP
EQUIP
EWC
EX
EXH
EXP
EXT
ºF
FA
FAAP
FACP
FC
FCU
FFC
FFS
FHC
FIN
FIXT
FL
FLUOR
FLEX-CONN
FPC
FSS
FTG
FVR
FV
FVNR
G or GND
GALV
GC
GEN
GFCI
GFI
GFP
HGT
HH
HID
HO
HOA
HORZ
HP
HPS
HTR
HV
AMPERE
ALTERNATING CURRENT
AIR CONDITIONING
ACCESS PANEL
AIR CONDITIONING UNIT
ADDITION
ADJUSTABLE
AMPERE FRAME
ABOVE FINISHED CEILING
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMMETER
AMBIENT
APPROXIMATELY
ARCHITECT
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AVERGE
BARE COPPER
BREAKER
BRAKE HORSEPOWER
BUILDING LINE
BUILDING
BRANCH
BOTTOM
CONDUIT
DEGREES CELSIUS
CABINET
CIRCUIT BREAKER
CENTER TO CENTER
CLOSED CIRCUIT TELEVISION
CIRCUIT
CENTER LINE
CEILING
COLUMN
COMMUNICATION
COMPRESSOR
CONCRETE
CONSTRUCTION
CONTINUOUS
CONTRACTOR
CRITICAL
CURRENT TRANSFORMER
COPPER
DIRECT BURIAL
DIRECT CURRENT
DEPARTMENT
DRINKING FOUNTAIN
DISTRIBUTION
DEMAND METER
DRAWOUT
DOCTORS
DRAWING
ELECTRICAL CONTRACTOR
EXHAUST FAN
ELECTRIC
ELEVATOR
ELEVATION
EMERGENCY
ENCLOSURE
ELECTRIC PNEUMATIC
EQUIPMENT
ELECTRIC WATER COOLER
EXPLOSIONPROOF
EXHAUST
EXPANSION
EXTERIOR
DEGREES FAHRENHEIT
FIRE ALARM
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FLAT CABLE
FAN COIL UNIT
FOOD FACILITY CONTRACTOR
FOOD FACILITY SUPPLIER
FIRE HOSE CABINET
FINISH
FIXTURE
FLOOR
FLUORESCENT
FLEXIBLE CONNECTION
FIRE PROTECTION CONTRACTOR
FUSED SAFETY SWITCH
FOOTING
FILMVIEWER
FULL VOLTAGE
FULL VOLTAGE NON REVERSING
GROUND
GALVANIZED
GENERAL CONTRACTOR
GENERATOR
GROUND FAULT CKT. INTERRUPTER
GROUND FAULT INTERRUPTER
GROUND FAULT PROTECTION
HEIGHT
HANDHOLE
HIGH INTENSITY DISCHARGE
HAND OPERATED
HAND-OFF-AUTOMATIC
HORIZONTAL
HORSEPOWER
HIGH PRESSURE SODIUM
HEATER
HIGH VOLTAGE
HZ
IC
ID
INCAN
INCL
ISG
JB
JT
KEC
KT
KVA
KVAR
KW
LAB
LB
LF
LOC
LS
LT
LTG
LV
MATV
MAX
MC
MCB
MCC
MDP
MECH
MH
MIN
MISC
MLO
MTD
MTG HT
MU
OD
OFCI
OFOI
OPNG
OPP
OR
P
PB
PBOX
PE
PF
PH or Ø
PV
PNL
PL
PREFAB
PRES
PT
PTS
PW
PWR
RACU
RAD
RECEPT
REF or REFR
REINF
RGIP
RM
RPM
SA
SC
SG
SHT
SIG
SN
SPEC
SQ
SS
SSSS
STD
STN
STR
SUSP
SW
SWBD
SWGR
TCC
TELE
TEMP
TMH
TV
TYP
UC
U/C
UH
UV
V
VAC
VB
VC
VEL
VFD
VM
VOL
VP
VSD/VFC
W/
W/O
WTR
WP
WT
XFMR
Z
HERTZ
INTERCOMMUNICATION
INSIDE DIAMETER
INCANDESCENT
INCLUDE
ISOLATED GROUND SURGE GUARD
JUNCTION BOX
JOINT
KITCHEN EQUIPMENT CONTRACTOR
KITCHENETTE
KILOVOLT AMPERE
KILOVOLT AMPERE REACTIVE
KILOWATT
LABORATORY
POUND
LINEAR FEET
LOCATION
LIFE SAFETY
LIGHT
LIGHTING
LOW VOLTAGE
MASTER ANTENNA TELEVISION
MAXIMUM
MECHANICAL CONTRACTOR
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION PANEL
MECHANICAL
MANHOLE
MINIMUM
MISCELLANEOUS
MAIN LUGS ONLY
MOUNTED
MOUNTING HEIGHT
MEDICINE UNIT
OUTSIDE DIAMETER
OWNER FURNISHED-CONTRACTOR INSTALLED
OWNER FURNISHED-OWNER INSTALLED
OPENING
OPPOSITE
OPERATING ROOM
POLE
PUSHBUTTON
PULL BOX
PNEUMATIC ELECTRIC CONVERTER
POWER FACTOR
PHASE
POST INDICATOR VALVE
PANELBOARD
PILOT LIGHT
PREFABRICATED
PRESSURE
PNEUMATIC TUBE
PNEUMATIC TUBE STATION
PART WINDING
POWER
ROOM AIR CONDITIONING UNIT
RADIATION
RECEPTACLE
REFRIGERATOR
REINFORCED
REMOTE GROUND INDICATING PANEL
ROOM
REVOLUTIONS PER MINUTE
SUPPLY AIR
SHORT CIRCUIT
SURGE GUARD PROTECTION
SHEET
SIGNAL
SOLID NEUTRAL
SPECIFICATIONS
SQUARE
SAFETY SWITCH
SOLID STATE SOFT START
STANDARD
STATION
STRUCTURAL
SUSPENDED
SWITCH
SWITCHBOARD
SWITCHGEAR
TEMPERATURE CONTROL CONTRACTOR
TELECOMMUNICATION
TEMPERATURE
TOP OF MANHOLE
TELEVISION
TYPICAL
UNDER CARPET
UNDER CABINET or UNDER COUNTER
UNIT HEATER
UNIT VENTILATOR
VOLT
VACUUM
VACUUM BREAKER
VACUUM CLEANING
VELOCITY
VARIABLE FREQUENCY DRIVE
VOLTMETER
VOLUME
VAPORPROOF
VARIABLE SPEED DRIVE/CONTROLLER
WITH
WITHOUT
WATER
WEATHERPROOF
WEIGHT
TRANSFORMER
IMPEDANCE
ELECTRICAL ABBREVIATIONS
M
FIRE ALARM SYSTEM
SYMBOL DESCRIPTION
MANUAL SENDING STATION
PIV POST INDICATOR VALVE
SD CEILING SMOKE DETECTOR
TS SPRINKLER SYSTEM TAMPER SWITCH
FS SPRINKLER SYSTEM FLOW SWITCH
SD WALL SMOKE DETECTOR
SD WALL SMOKE DETECTOR WITH SOUNDER BASE
SD
CEILING SMOKE DETECTOR WITH SOUNDER BASE
DD AUTOMATIC DUCT DETECTOR ("X" DENOTES AS FOLLOWS)
RT REMOTE DETECTOR TEST STATION
RI REMOTE DETECTOR INDICATOR STATION
AR FIRE ALARM ADDRESSABLE RELAY
X NONE -PHOTOELECTRIC TYPE
S -SUPPLY
R -RETURN
DR DOOR RELEASE
DU DOOR UNLOCK
J FIREMANS JACK
HD HEAT DETECTOR
FD FLAME DETECTOR
BD BEAM DETECTOR
H WALL HORN ONLY
H WALL HORN STROBE
CEILING HORN ONLY
CEILING HORN STROBE
H
H
S WALL SPEAKER ONLY
S WALL SPEAKER STROBE
CEILING SPEAKER STROBES
V WALL VISUAL ONLY
CEILING VISUAL ONLYV
FACP FIRE ALARM CONTROL PANEL
FAAP FIRE ALARM ANNUNCIATOR PANEL
ALL SYMBOLS AND ABBREVIATIONS MAY NOT BE USED ON THIS PROJECT3
ST - 20 AMP, 125VAC, SAFETY TYPE
S -20 AMP, 125VAC, SURGE GUARD PROTECTION TYPE
WP -20 AMP, 125VAC, WEATHERPROOF TYPE
HM - 20 AMP, 125VAC, HORIZONTAL MOUNT TYPE
IG -20 AMP, 125VAC, ISOLATED GROUND TYPE
NONE -20 AMP, 125VAC
ELECTRICAL RECEPTACLES
DUPLEX RECEPTACLE - NORMAL POWER CIRCUIT
DESCRIPTIONSYMBOL
DUPLEX RECEPTACLE - EMERGENCY POWER CIRCUIT
DUPLEX GFCI RECEPTACLE - NORMAL POWER CIRCUIT
DUPLEX GFCI RECEPTACLE - EMERGENCY POWER CIRCUIT
QUADRAPLEX RECEPTACLE -NORMAL POWER CIRCUIT
QUADRAPLEX RECEPTACLE -EMERGENCY POWER CIRCUIT
QUADRAPLEX GFCI RECEPTACLE - NORMAL POWER CIRCUIT
QUADRAPLEX GFCI RECEPTACLE - EMERGENCY POWER CIRCUIT
SIMPLEX RECEPTACLE - NORMAL POWER CIRCUIT
SIMPLEX RECEPTACLE - EMERGENCY POWER CIRCUIT
SPECIAL RECEPTACLE -NORMAL POWER CIRCUIT
SPECIAL RECEPTACLE -EMERGENCY POWER CIRCUIT
DUPLEX RECEPTACLE - TOP SWITCHED
"X" DENOTES AS FOLLOWS:
CEILING DUPLEX RECEPTACLE -NORMAL POWER CIRCUIT
CEILING DUPLEX RECEPTACLE -EMERGENCY POWER CIRCUIT
CEILING QUADRAPLEX RECEPTACLE -NORMAL POWER CIRCUIT
CEILING QUADRAPLEX RECEPTACLE -EMERGENCY POWER CIRCUIT
FLOOR BOX DUPLEX RECEPTACLE -NORMAL POWER CIRCUIT
FLOOR BOX DUPLEX RECEPTACLE -EMERGENCY POWER CIRCUIT
FLOOR BOX QUADRAPLEX RECEPTACLE -NORMAL POWER CIRCUIT
FLOOR BOX QUADRAPLEX RECEPTACLE -EMERGENCY POWER CIRCUIT
FLOOR BOX POWER AND TELECOM
FLOOR BOX BLANK
MULTI-OUTLET ASSEMBLY (POWER AND/OR TELECOM)
ELECTRICAL SWITCHES
DESCRIPTIONSYMBOL
TOGGLE SWITCH -20 AMP, 120/277VAC
TOGGLE SWITCH -3 WAY
4 TOGGLE SWITCH -4 WAY
K TOGGLE SWITCH -KEY OPERATED
T TOGGLE SWITCH -HORSE POWER RATED MANUAL MOTOR
STARTER WITH THERMAL OVERLOAD PROTECTION
P TOGGLE SWITCH - PILOT LIGHT
D DIMMER SWITCH -20 AMP, 120/277VAC
D DIMMER SWITCH -3 WAY3
4D DIMMER SWITCH -4 WAY
OC1 WALL OCCUPANCY SENSOR -1 BUTTON CONTROL
OC2 WALL OCCUPANCY SENSOR -2 BUTTON CONTROL
OC3 WALL OCCUPANCY SENSOR -DUAL RELAY FOR
EXHAUST FAN CONTROL
OC CEILING OCCUPANCY SENSOR
VS1 WALL VACANCY SENSOR -1 BUTTON CONTROL
VS2 WALL VACANCY SENSOR -2 BUTTON CONTROL
LC LOW VOLTAGE LIGHTING CONTROLLER
T 0 -3 HOUR TIMER SWITCH -20 AMP, 120/277VAC
INFORMATION SYSTEMS
DESCRIPTIONSYMBOL
VOICE AND DATA ONLY OUTLET
WAP -WIRELESS ACCESS
POINT
FLOOR BOX -VOICE AND DATA
CEILING -VOICE AND DATA
TELECOMMUNICATIONS EQUIPMENT RACK
X
R -ROUGH-IN ONLY
# -QUANTITY OF JACK(S) AND CABLE(S)
"X" DENOTES AS FOLLOWS:
LIGHTING
DESCRIPTION
NO SHADING INDICATES NORMAL POWER
SYMBOL
24" x 24" LIGHTING FIXTURE
12" x 48" LIGHTING FIXTURE
HALF SHADED INDICATES LIFE SAFETY POWER
FULL SHADED INDICATES EMERGENCY POWER
12" x 96" LIGHTING FIXTURE
6" x 96" LIGHTING FIXTURE
6" x 48" LIGHTING FIXTURE
6" x 36" LIGHTING FIXTURE
6" x 24" LIGHTING FIXTURE
8" DOWNLIGHT
6" DOWNLIGHT
4" DOWNLIGHT
WALL MOUNTED LIGHT
CEILING EXIT LIGHT (DUAL FACED)
CEILING EXIT LIGHT (SINGLE FACE)
WALL EXIT LIGHT
EXIT LIGHT DIRECTIONAL ARROWS
WALL EMERGENCY BATTERY LIGHT
WALL EXIT WITH EMERGENCY LIGHTS
CEILING EMERGENCY BATTERY LIGHT
WALL EXIT WITH INTERIOR AND
EXTERIOR EMERGENCY LIGHTS
EXTERIOR POLE LIGHT (ONE HEAD)
EXTERIOR POLE LIGHT (TWO HEADS)
EXTERIOR POLE LIGHT (THREE HEADS)
EXTERIOR POLE LIGHT (FOUR HEADS)
EXTERIOR POLE LIGHT (TOP MOUNT)
EXTERIOR BOLLARD
NEUTRAL
GROUND
RACEWAY SYSTEM
DESCRIPTION
PHASE CONDUCTORS
SYMBOL
LIGHT/SCREENED SOLID OR DASHED LINES INDICATE EXISTING TO REMAIN
HEAVY CONTINUOUS LINES INDICATE NEW WORK
LINE SYMBOLS
HEAVY DASHED LINES INDICATE EXISTING TO BE REMOVED
J JUNCTION OR PULL BOX
PUSHBUTTON OR PUSH PLATE
PAD MOUNTED TRANSFORMER
BRANCH PANELBOARD - SURFACE MOUNT
COMBINATION MOTOR CONTROLLER / DISCONNECT
DISCONNECT SWITCH -NON-FUSED
MOTOR CONTROLLER
DISCONNECT SWITCH -FUSED
MOTOR ("X" DENOTES HORSEPOWER)
GROUND CONNECTION
ELECTRIC THERMOSTATT
DESCRIPTION
MOLDED CASE CIRCUIT BREAKER
ELECTRICAL EQUIPMENT
SYMBOL
GROUND POINT
GROUND ROD
X
PC PHOTO CELL
SUSPENDED TRANSFORMER
DISTRIBUTION PANELBOARD
BRANCH PANELBOARD -RECESSED MOUNT
AUTOMATIC TRANSFER SWITCHN E
L
TELECOM TERMINAL BOARD
GROUND BAR
GENERATOR
TV
AV
TV SYSTEM OUTLET
AUDIO/VISUAL CONTROLLER
CLOCK SYSTEM OUTLETC
M
M
MICROPHONE INPUT RECEPTACLE -WALL MOUNTED
SPEAKER -WALL MOUNTED
SPEAKER -CEILING MOUNTED
VOLUME CONTROL
MICROPHONE INPUT RECEPTACLE -CEILING MOUNTED
S
S
V
MTV
CCTV
DR
ES
IC
MI
ML
CR
MD
DC
PB
K
BS
DS
SM
SS
DE
DOOR SECURITY SYSTEM
SYMBOL DESCRIPTION
DOOR BUZZER
SECURITY DOOR ALARM MAGNETIC LOCK
CCTV MONITOR OUTLET
ELECTRIC DOOR OPENER
ELECTRIC DOOR STRIKE
INTERCOM UNIT FLUSH MTD.
MASTER INTERCOM AND DIRECTORY UNIT
MOTION DETECTOR
CCTV COAXIAL CABLE OUTLET AND POWER OUTLET
SECURITY CARD READER
SECURITY CONTROL PANEL
SECURITY DOOR CONTACTS
SECURITY EXIT PUSH BUTTON
SECURITY KEYPAD
BIOSCAN ACCESS PAD
CAMERA
SECURITY DUTY STATION
SECURITY STAFF STATION
SECURITY MONITOR
SECURITY DOOR EGRESS
NAC FIRE ALARM NOTIFICATION APPLIANCE CONTROL PANEL
WAP
X
X
RECEPTACLE ABOVE COUNTERTOP AT +2" ABOVE
BACKSPLASH TO BOTTOM OF DEVICE. COORDINATE WITH
CASEWORK TO BE INSTALLED.
RECEPTACLE INSTALLED BELOW COUNTERTOP AT +18"
A.F.F. COORDINATE WITH CASEWORK TO BE INSTALLED.
X
RECEPTACLE LEGEND
DESCRIPTIONABBREVIATION ABBREVIATION DESCRIPTION
FXX
FEEDER SIZE. (REFER TO FEEDER SCHEDULE
FOR ADDITIONAL INFORMATION
SCP
24" x 48" LIGHTING FIXTURE
12" x 36" LIGHTING FIXTURE
12" x 24" LIGHTING FIXTURE
12" x 12" LIGHTING FIXTURE
1. PROVIDE SUPPORT WIRES FOR ALL LIGHT FIXTURES.
2. COORDINATE INSTALLATION OF LIGHT FIXTURES WITH ARCHITECTURAL REFLECTED CEILING PLAN, HVAC EQUIPMENT, DUCTWORK,
PIPING AND SUPPORTS.
3. ELECTRICAL CONTRACTOR SHALL VERIFY THE CONDITIONS AT THE PROJECT SITE BEFORE SUBMITTING COST PROPOSAL.
4. ELECTRICAL CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS TO FAMILIARIZE HIMSELF WITH EXTENT OF THE WORK.
5. ALL WORK SHALL CONFORM TO OR EXCEED THE MINIMUM REQUIREMENTS OF THE CURRENT ANSI / NFPA 70 WITH STATE
AMENDMENTS, ENERGY CODE, ANSI / IEEE C2 AND ALL FEDERAL, STATE, LOCAL AND MUNICIPAL CODES AND ORDINANCES. THE
ELECTRICAL SUBCONTRACTOR SHALL COMPLY WITH THE DIRECTIONS OF ALL AUTHORITIES HAVING JURISDICTION.
6. INSTALL WORK USING PROCEDURES DEFINES IN NECA STANDARDS OF INSTALLATION. ALL WORK SHALL PRESENT A NEAT
MECHANICAL APPEARANCE WHEN COMPLETED.
7. REFER TO THE ARCHITECTURAL DRAWINGS FOR CEILING WORK BY THE GENERAL CONTRACTOR. COORDINATE ALL ELECTRICAL
WORK.
8. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL FLOOR, WALL, AND CEILING PENETRATIONS TO COMPLETE HIS WORK.
PROVIDE PROPER FIRESTOPPING/ FIRE SAFEING FOR ALL PENETRATIONS MADE. PROVIDE APPROPRIATE SEALANT (I.E.
FIRESAFEING) TO MAINTAIN CONSTRUCTION INTEGRITY FOR ANY PENETRATIONS THROUGH FLOORS, STRUCTURAL CEILING, AND
FIRE WALLS. REFER TO THE ARCHITECTURAL SPECIFICATIONS FOR REQUIREMENTS.
9. COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES TO ENSURE EFFECTIVE AND EFFICIENT OVERALL INSTALLATION.
10. THE LOCATION OF RECEPTACLES, PHONE / DATA JACKS, AND ROOM EQUIPMENT SHOWN ON THESE DRAWINGS ARE APPROXIMATE.
FINAL LOCATIONS WILL BE DETERMINED WITH THE ARCHITECT DURING THE CONSTRUCTION PHASE.
11. ALL EQUIPMENT SHALL BE SUBMITTED FOR APPROVAL PRIOR TO ORDERING.
12. PHYSICAL SIZES AND LOCATIONS OF ALL MECHANICAL EQUIPMENT SHOWN ON THESE DRAWINGS ARE APPROXIMATE.
COORDINATE ELECTRICAL WORK FOR THIS EQUIPMENT WITH THE OTHER TRADES.
13. ALL BRANCH CIRCUITS SHALL UTILIZE SEPARATE INDEPENDENT NEUTRAL CONDUCTORS. DO NOT COMBINE NEUTRAL
CONDUCTORS.
14. ALL FEEDER NEUTRAL / GROUNDED CONDUCTORS SHALL BE CONSIDERED CURRENT CARRYING. DERATE MULTIPLE CONDUCTORS
IN A RACEWAY ACCORDINGLY WITH NEC TABLES.
15. INSTALL ALL CONDUITS, RACEWAYS, AND CABLE TRAY FOR MAXIMUM HEAD CLEARANCE IN MECHANICAL AREAS.
16. WIRING SHALL BE INSTALLED ABOVE ACCESSIBLE CEILINGS AND WITHIN WALL CAVITIES WHERE POSSIBLE.
17. WIRING THAT IS TO BE INSTALLED IN AREAS WHERE THERE ARE NO CEILINGS SHALL BE INSTALLED EXPOSED. THIS WIRING SHALL
BE INSTALLED NEATLY AND AT RIGHT ANGLES TO STRUCTURE. WIRING SHALL BE INDEPENDENTLY SUPPORTED AS REQUIRED.
WIRING SHALL NOT LAY OVER OTHER TRADES.
18. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR HIS OWN STORING OF ELECTRICAL EQUIPMENT AND MATERIAL.
19. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED FOR ELECTRICAL WORK. ALL
CUTTING, PATCHING, REPAIRING, REPLACEMENT AND REFINISHING, SHALL MATCH THE GENERAL CONSTRUCTION AS NEARLY AS
POSSIBLE. REFER TO THE ARCHITECTURAL SPECIFICATIONS FOR REQUIREMENTS.
20. BLOCKING: ELECTRICAL CONTRACTOR SHALL PROVIDE ALL IN-WALL BLOCKING REQUIRED TO SUPPORT ELECTRICAL EQUIPMENT.
21. WIRING METHOD IN RETURN AIR PLENUM ABOVE CEILING SHALL BE NONCOMBUSTIBLE OR LISTED / LABELED FOR RATING OF
FLAME SPREAD AND SMOKE DEVELOPED INDEX PER INEC ARTICLE 300(C)(1 )
GENERAL NOTES
(APPLY TO ALL ELECTRICAL SHEETS)
1. WHERE OCCUPANCY SENSORS ARE INDICATED ON PLANS, THE ENTIRE ROOM SHALL BE COVERED. MANUFACTURER IS
RESPONSIBLE FOR SENSOR LAYOUT. ADDITIONAL SENSORS REQUIRED DUE TO LACK OF COVERAGE SHALL BE THE
RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. PROVIDE QUANTITY AS REQUIRED. CEILING AND WALL MOUNTED SENSORS
SHALL BE DUAL-TECHNOLOGY TYPE. SENSORS SHALL INCLUDE ALL POWER SUPPLIES AND RELAYS NECESSARY TO CONTROL
LIGHT FIXTURES IN ROOM/AREA. SENSORS SHALL OPERATE IN "VACANCY" MODE -MANUAL ON/AUTO OFF. ACCEPTABLE
MANUFACTURERS ARE: HUBBELL, SENSOR SWITCH, LEVITON, LIGHTOLIER, WATTSTOPPER.
2. ALL LIGHT FIXTURES SHOWN WITH EMERGENCY BATTERY BALLASTS OR BACKUP SHALL HAVE UNSWITCHED "HOT" WIRE
INSTALLED TO FIXTURE FROM INDICATED LIGHTING CIRCUIT.
GENERAL LIGHTING NOTES
(APPLY TO ALL ELECTRICAL SHEETS)
GENERAL WIRING DEVICE NOTES
(APPLY TO ALL ELECTRICAL SHEETS)
1. AT LOCATIONS WITH TWO OR MORE WALL SWITCHES, ALL SWITCHES SHALL BE INSTALLED GAGNED IN A COMMON SWITCH BOX.
2. ALL RECEPTACLES SHALL BE TAMPER-RESISTANT TYPE
TELEPHONE AND DATA SYSTEMS NOTES
(APPLY TO ALL ELECTRICAL SHEETS)
1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONDUITS AND OTHER RACEWAYS REQUIRED FOR TELEPHONE AND DATA
SYSTEMS.
2. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL POWER CONNECTIONS FOR THE TELEPHONE AND DATA SYSTEMS
EQUIPMENT.
VOLTAGE DROP NOTES
(APPLY TO ALL ELECTRICAL SHEETS)
1. VOLTAGE DROP IS NOT SHOWN ON THE DRAWINGS. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ADJUSTING ALL
FEEDER AND BRANCH CIRCUIT CONDUCTOR SIZES TO COMPLY THE NATIONAL ELECTRICAL CODE AND ALL STATE AND LOCAL
CODES VOLTAGE DROP REQUIREMENTS.
2. THE ELECTRICAL CONTRACTOR SHALL UPSIZE FEEDER AND BRANCH CIRCUIT CONDUCTORS AS REQUIRED BASED ON ACTUAL
INSTALLED CONDUCTOR LENGHTS.
3. VOLTAGE DROP ON FEEDERS SHALL NOT EXCEED 2 PERCENT.
4. VOLTAGE DROP ON BRANCH CIRCUITS SHALL NOT EXCEED 3 PERCENT.
MECHANICAL EQUIPMENT DISCONNECT NOTES
(APPLY TO ALL ELECTRICAL SHEETS)
1. THE ELECTRICAL CONTRACTOR SHALL VERIFY THE MAXIMUM OVERCURRENT PROTECTION (MCOP) VALUE FOR MECHANICAL
EQUIPMENT WHERE THE EQUIPMENT DISCONNECT IS PROVIDED BY THE EQUIPMENT MANUFACTURER.
2. THE ELECTRICAL CONTRACTOR SHALL ADJUST THE EQUIPMENT CIRCUIT CONDUCTOR AND CIRCUIT BREAKER SIZES AS REQUIRED
TO NOT EXCEED THE EQUIPMENT MCOP.
3. THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL REQUIREMENTS PRIOR TO ORDERING AND INSTALLING PANELBOARDS,
CONDUCTORS, AND CONDUITS.
ARC FLASH STUDY
1. THE CONTRACTOR SHALL INCLUDE IN THE BID A COMPLETE ARC FLASH AND SHORT CIRCUIT STUDY FOR THE PROJECT PERFORMED
BY A LICENSED ENGINEER.
2. ALL EQUIPMENT SHORT CIRCUIT RATINGS SHALL BE ADJUSTED IN ACCORDANCE WITH THE SHORT CIRCUIT STUDY PRIOR TO
ORDERING EQUIPMENT.
3. PROVIDE ARC FLASH LABELS ON ALL EQUIPMENT / PANELBOARDS.
FIRE ALARM SYSTEM
1. THE CONTRACTOR SHALL PROVIDE A FIRE ALARM SYSTEM THAT IS COMPLIANT WITH ALL STATE AND LOCAL CODE REQUIREMENTS.
2. PROVIDE ADDITIONAL SIGNAL DEVICES IN UNITS AS REQUIRED TO COMPLY WITH LOCAL CODES.
3. PROVIDE LOW FREQUENCY SOUNDERS IF REQUIRED BY LOCAL CODES.
Project Number
CERTIFIED BY
ISSUANCE INDEX
DATE:
PROJECT PHASE:7/15/2020 3:05:18 PME001
ELECTRICAL
SYMBOLS
2019.00780
7.14.2020
CONSTRUCTION DOCUMENTS
CARMEL MEDICAL
ARTS PAVILION
12174 N. Meridian Street
Carmel, Indiana 46032
REVISION SCHEDULE
NO. DESCRIPTION DATE
09/17/20