HomeMy WebLinkAboutE201-12 - FIRST LEVEL LIGHTING PLAN - TENANT 12WDOCOC
OC OC OCOCD OCDOCD OCD
DD DD OC
OC
OC
OC
OCD7 8 8.8 9
C
D
E
F
F.3
F.5
G
G.8
H
J
I
1H1
LIGHTING
CONTROL
RECEPTION
1203WAITING
1201VESTIBULE
1200
TREATMENT
1204
TREATMENT
1205
PHYSICIAN WORK
1207
REHAB
1206
LAUNDRY
1208
PATIENT RESTROOM
1209
STAFF RESTROOM
1210
ELECTRICAL
1160
STAFF BREAK
1211
OFFICE
1212
a b
c
d
c
c
c
NL a
b
F8-EM
F7
1H1-48
1H1-48
NLF8-EM
1H1-48
aF8
1H1-48
aF8
1H1-48
a F8
1H1-48
aF8
1H1-48
aF8
1H1-48
aF8
1H1-48
aF8
1H1-48
aF8
1H1-48
aF8
1H1-48
aF8
1H1-48
aF8-EM
1H1-48
NLF8-EM
1H1-48
F7
1H1-48
F7
1H1-48
F7
1H1-48
F7
1H1-48
F7
1H1-48
F7
1H1-48
F7
1H1-48
F7
1H1-48
F7
1H1-48
F5-EM
1H1-48
NL
F5-EM
1H1-48
NL
FX
1H1-48
FX
1H1-48
F3
1H1-48
F3
1H1-48
F3
1H1-48
F9-EM
1H1-48
F9
1H1-48
a
F10
1H1-48
FX
1H1-48
F3
1H1-48
F5
1H1-48
d
F5
1H1-48
d
F5
1H1-48
d
F9
1H1-48
a
FX
1H1-48
1
TYP.
2
2
22
2 2
22
22
22
22
22
3
2 2
NLF9-EM
1H1-482
F9
1H1-48
a
2
10
Project Number
CERTIFIED BY
ISSUANCE INDEX
DATE:
PROJECT PHASE:7/15/2020 3:06:04 PME201.12
FIRST LEVEL
LIGHTING PLAN -
TENANT 12
2019.00780
7.14.2020
CONSTRUCTION DOCUMENTS
CARMEL MEDICAL
ARTS PAVILION
12174 N. Meridian Street
Carmel, Indiana 46032
1/8" = 1'-0"1 FIRST LEVEL LIGHTING PLAN - TENANT 12
GENERAL NOTES
A. REFER TO DRAWING E001 FOR ELECTRICAL SYMBOLS AND ADDITIONAL GENERAL NOTES.
B. COORDINATE ALL WORK WITH THE OWNER AND THE OTHER TRADES ON THE PROJECT.
C. REFER TO M AND P SERIES DRAWINGS FOR ADDITIONAL ELECTRICAL REQUIREMENTS.
D. PROTECT ALL FINISHES, EQUIPMENT, AND DEVICES DURING THE WORK.
E. REFER TO ARCHITECTURAL SCHEDULES, DETAILS, AND ELEVATIONS FOR ADDITIONAL
INFORMATION ON DEVICE LOCATIONS PRIOR TO ROUGH-IN.
F. COORDINATE ALL WORK WITH THE OWNER'S SYSTEMS VENDORS FOR DEVICES AND
WIRING FOR DATA, I.T. SERVICES, AND SECURITY SYSTEMS.
G. ELECTRICAL SERVICES SHALL NOT ROUTE THROUGH ANY IDF OR MDF ROOM UNLESS
DIRECTLY SERVING THAT \ROOM.
H. CONTRACTOR SHALL VERIFY CORD AND PLUG CONNECTED EQUIPMENT CORD
CONFIGURATION AND PROVIDE MATCHING RECEPTACLE AS REQUIRED.
I. ALL RECEPTACLES WITHIN SIX FEET OF A SINK SHALL BE GFCI TYPE. DEVICES MAY NOT BE
IDENTIFIED AS GFCI ON PLANS, BUT SHALL BE PROVIDED ACCORDING TO THE
REQUIREMENT.
J. ALL SPECIAL TYPE RECEPTACLES SHALL BE NEMA 6-20R UNLESS NOTED OTHERWISE AND
SHALL BE CIRCUITED WITH (2) #10 + (1) #10 NEUTRAL + (1) #10 GROUND. COORDINATE
REQUIREMENTS WITH OWNER SUPPLIED EQUIPMENT PRIOR TO INSTALLATION.
K. COORDINATE INSTALLATION OF LIGHT FIXTURES WITH ARCHITECTURAL REFLECTED
CEILING PLAN, ARCHITECTURAL ELEVATIONS, HVAC EQUIPMENT, DIFFUSERS, DUCTWORK,
PIPING, SUPPORTS, AND STRUCTURE PRIOR TO ROUGH-IN.
L. ALL EXIT SIGNS, EMERGENCY BATTERY LIGHTING UNITS, AND LIGHT FIXTURES SHOWN
WITH EMERGENCY BATTERY BACKUP OR INDICATED AS A NIGHT LIGHT ("NL") SHALL BE
PROVIDED WITH AN UNSWITCHED "HOT" CIRCUIT CONDUCTOR.
M. AT LOCATIONS WITH TWO OR MORE WALL SWITCHES, ALL SWITCHES SHALL BE INSTALLED
GANGED IN A COMMON SWITCH BOX.
N. AT LOCATIONS WHERE LIGHT SWITCHES AND ABOVE-COUNTER RECEPTACLES ARE TO BE
MOUNTED ADJACENT TO EACH OTHER, THE DEVICES SHALL BE INSTALLED AT THE SAME
HEIGHT.
O. WHERE OCCUPANCY SENSORS ARE INDICATED ON PLANS, THE ENTIRE ROOM SHALL BE
COVERED. SENSOR MANUFACTURER IS RESPONSIBLE FOR SENSOR LAYOUT.
ADDITIONAL SENSORS REQUIRED DUE TO LACK OF COVERAGE SHALL BE THE
RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. PROVIDE QUANTITIES AS
REQUIRED. CEILING AND WALL MOUNTED SENSORS SHALL BE DUAL-TECHNOLOGY TYPE.
SENSORS SHALL INCLUDED ALL POWER SUPPLIES AND RELAYS NECESSARY TO CONTROL
LIGHT FIXTURES IN ROOM/AREA. SENSORS SHALL OPERATE IN "VACANCY" MODE -
MANUAL ON/AUTO OFF.
P. PROVIDE PULL STRING IN ALL EMPTY CONDUITS.
Q. CONTRACTOR TO PROVIDE ROUGH-INS ONLY FOR DATA, I.T. SERVICES, AND SECURITY
SYSTEMS. DATA, I.T. SERVICES, AND SECURITY SYSTEMS DEVICES AND WIRING TO BE
PROVIDED BY THE OWNERS SYSTEMS VENDORS. PROVIDE ROUGH-INS WITH "RING AND
STRING".
PLAN NOTES
1 EXISTING TO REMAIN.
2 SUSPEND FIXTURE TO HEIGHT DETERMINDED BY ARCHITECT.
3 CONFIRM EXACT LOCATION AND SUSPEND FIXTURE TO HEIGHT DETERMINDED BY
ARCHITECT.
LIGHT FIXTURE SCHEDULE TENANT 12
FIXTURE
TYPE FIXTURE NAME DESCRIPTION VOLTAGE WATTAGE LAMP LUMENS
ACCEPTABLE
MANUFACTURERS
F3 ARCHITECTURAL TROFFER 24"W X 24"L X 4"D DIE FORMED 20 GAUGE COLD ROLLED STEEL HOUSING. DIRECT / INDIRECT
ANGLED RAIL FIXTURE, FROSTED ACRYLIC CENTER OPTIC, 0-10V DIMMING DRIVER (10%-100%).
277 V 43 W LED
3500K
4500 METALUX - RLN
F7 ARCHITECTURAL TROFFER 24"W X 48"L X 4"D DIE FORMED 20 GAUGE COLD ROLLED STEEL HOUSING. DIRECT / INDIRECT
ANGLED RAIL FIXTURE, FROSTED ACRYLIC CENTER OPTIC, 0-10V DIMMING DRIVER (10%-100%).
277 V 48 W LED
3500K
6000 METALUX - RLN
F8 SUSPENDED LINEAR 4"W X 8'L NARROW EXTRUDED ALUMINUM HOUSING, CONTINOUS FLUSH FROSTED ACYRLIC LENS.
0-10V DIMMING DRIVER (10%-100%).
277 V 74 W LED
3500K
7000 FOCAL POINT - SEEM 4
F8-EM SUSPENDED LINEAR 4"W X 8'L NARROW EXTRUDED ALUMINUM HOUSING, CONTINOUS FLUSH FROSTED ACYRLIC LENS.
0-10V DIMMING DRIVER (10%-100%). PROVIDE WITH INTEGRAL 90 MINUTE EMERGENCY BATTERY.
277 V 74 W LED
3500K
7000 FOCAL POINT - SEEM 4
F9 SUSPENDED LINEAR 4"W X 4'L NARROW EXTRUDED ALUMINUM HOUSING, CONTINOUS FLUSH FROSTED ACYRLIC LENS.
0-10V DIMMING DRIVER (10%-100%).
277 V 37 W LED
3500K
3500 FOCAL POINT - SEEM 4
F9-EM SUSPENDED LINEAR 4"W X 4'L NARROW EXTRUDED ALUMINUM HOUSING, CONTINOUS FLUSH FROSTED ACYRLIC LENS.
0-10V DIMMING DRIVER (10%-100%). PROVIDE WITH INTEGRAL 90 MINUTE EMERGENCY BATTERY.
277 V 37 W LED
3500K
3500 FOCAL POINT - SEEM 4
F10 PENDANT LUMINAIRE MACHINED ALUMINUM WITH POWDER COATED FINISH. ARCHITECT TO DETEMINE FINISH COLOR. 277 V 54 W LED 4490 KUZCO LIGHTING - VEGA CH10345
FX EXIT SIGN WHITE LED ELECTRONIC EXIT LIGHT, SINGLE OR DOUBLE FACE AS INDICATED ON DRAWING
DOCUMENTS WITH UNIVERSAL SURFACE MOUNTING CANOPY, END, BACK OR TOP. DIRECTIONAL
ARROW, RED LETTERS "EXIT", NICKEL CADMIUM BATTERY. PROVIDE WITH SELF DIAGNOSTICS AND
CAPABILITY TO POWER REMOTE HEAD.
277 V 2 W LED EVENLITE - RZR3
REVISION SCHEDULE
NO. DESCRIPTION DATE
09/17/20