HomeMy WebLinkAboutE601 - ELECTRICAL SCHEDULESExterior Light Fixture Schedule
Qty Label Arrangement Lum. Watts Lum. Lumens LLF Description
1 SA4 SINGLE 166 17664 0.900 GLEON-AF-03-LED-E1-SL4-25ft Pole
1 SA4H SINGLE 166 15087 0.900 GLEON-AF-03-LED-E1-SL4-HSS-25ft Pole
2 SA5 SINGLE 166 19528 0.900 GLEON-AF-03-LED-E1-5MQ-25ft Pole
8 SB1 SINGLE 20.2 1539 0.900 VVB3QFR-40-T5-UNV-XX-X
1 SR1 SINGLE 18.2 1600 0.900 FSM2L-FL-375LF-35K-1C-120-LD1-G1-WH-4FT
7 SR2 SINGLE 36.4 1600 1.800 FSM2L-FL-375LF-35K-1C-120-LD1-G1-WH-8FT
8 SSP SINGLE 20.48 1880 0.900 1045-X-NS-40-B-MV-X-STM-X-18-MH20-MV
4 WP1 SINGLE 34 3478 0.900 GWC-AF-01-LED-E1-SL4-600-HSS
1 WP2 SINGLE 12.2 1397 0.900 XTOR1B-W
23 WP3 CYLINDER UP-DOWN SM 14 1577 0.693 SQL3T240K12DUDXS-X
Project Number
CERTIFIED BY
ISSUANCE INDEX
DATE:
PROJECT PHASE:7/15/2020 3:07:19 PME601
ELECTRICAL
SCHEDULES
2019.00780
7.14.2020
CONSTRUCTION DOCUMENTS
CARMEL MEDICAL
ARTS PAVILION
12174 N. Meridian Street
Carmel, Indiana 46032
Remarks:
X-Ray 56815 VA 95.89% 54479 VA Total Est. Demand Current: 921 A
Receptacle 91120 VA 55.49% 50560 VA Total Conn. Current: 994 A
Lighting 13971 VA 100.00% 13971 VA Total Est. Demand: 765568 VA
HVAC 546430 VA 100.00% 546430 VA Total Conn. Load: 826223 VA
Elevator 118400 VA 85.00% 100640 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Connected Load (Amps): 993.8
Total Connected Load (kVA): 826.2
16
15
14
13
12
11
10
9
8
7 RTU-2 3 200 A 125 A 89.7
6 RTU-1 3 400 A 225 A 160.0
5 ELEVATOR B 3 200 A 200 A 58.0
4 ELEVATOR A 3 200 A 200 A 58.0
3 3H1 3 400 A 400 A 90.5
2 2H1 3 400 A 400 A 87.5
1 1H1 3 400 A 400 A 282.6
Circuit
Number Circuit Description Fixed
Adj.
Inst. L S I G
100%
Rated Poles
Frame
Size
Trip
Rating
Load
(kVA) Remarks:
Thermal Mag Electronic Trip
Breaker Information
General Panel Comments:
Enclosure Type: Ground: Yes Main Rating: 1200A
Mounting: Wire: 4 Main Type: MCB
Supplied From: 480V UTILITY TRANSFORMER Phase: 3 A.I.C. Rating:
Location: Voltage: 480/277 Wye Branch: Normal
Distribution Panel:MDP
TRANSFORMER SCHEDULE
DESIGNATION LOCATION SIZE PHASE PRIMARY VOLTAGE SECONDARY VOLTAGE PRIMARY CONNECTION SECONDARY CONNECTION MOUNTING TYPE COMMENTS
T-1L1 75 kVA 3 480 V 120/208 V DELTA WYE PAD DRY PROVIDED IN CORE AND SHELL
T-2L1 75 kVA 3 480 V 120/208 V DELTA WYE PAD DRY PROVIDED IN CORE AND SHELL
T-3L1 75 kVA 3 480 V 120/208 V DELTA WYE PAD DRY PROVIDED IN CORE AND SHELL
LIGHT FIXTURE SCHEDULE CORE AND SHELL
FIXTURE
TYPE FIXTURE NAME DESCRIPTION VOLTAGE WATTAGE LAMP LUMENS
ACCEPTABLE
MANUFACTURERS
F1 INDUSTRIAL PENDANT 3"W X 48"L X 4"D, COLD ROLLED STEEL HOUSING, BAKED WHITE ENAMEL FINISH, FROSTED LENS,
WIDE DISTRIBUTION, UL WET LOCATION LISTED.
277 V 54 W LED
3500K
5000 METALUX - SNLED
F2-EM STAIRWELL FIXTURE 6"W X 4"D X 48"L STEEL HOUSING, WHITE POWDER COAT FINISH, ACRYLIC DIFFUSER, DAMP
LOCATION LISTED, FIXTURE ON 50% ALL THE TIME AND 100% VIA INTEGRAL OCCUPANCY SENSOR,
PROVIDE WITH 90 MINUTE EMERGENCY BATTERY.
277 V 40 W LED
3500K
4000 METALUX - BCLED
F3 ARCHITECTURAL TROFFER 24"W X 24"L X 4"D DIE FORMED 20 GAUGE COLD ROLLED STEEL HOUSING. DIRECT / INDIRECT
ANGLED RAIL FIXTURE, FROSTED ACRYLIC CENTER OPTIC, 0-10V DIMMING DRIVER (10%-100%).
277 V 43 W LED
3500K
4500 METALUX - RLN
F3-EM ARCHITECTURAL TROFFER 24"W X 24"L X 4"D DIE FORMED 20 GAUGE COLD ROLLED STEEL HOUSING. DIRECT / INDIRECT
ANGLED RAIL FIXTURE, FROSTED ACRYLIC CENTER OPTIC, 0-10V DIMMING DRIVER (10%-100%).
PROVIDE WITH INTEGRAL 90 MINUTE EMERGENCY BATTERY.
277 V 43 W LED
3500K
4500 METALUX - RLN
F4-6 RECESSED LINEAR 2"W X 6'L NARROW EXTRUDED ALUMINUM HOUSING, CONTINOUS FLUSH FROSTED ACYRLIC LENS.
0-10V DIMMING DRIVER (10%-100%).
277 V 36 W LED
3500K
3750 FOCAL POINT - SEEM 2
F4-6-EM RECESSED LINEAR 2"W X 6'L NARROW EXTRUDED ALUMINUM HOUSING, CONTINOUS FLUSH FROSTED ACYRLIC LENS.
0-10V DIMMING DRIVER (10%-100%). PROVIDE WITH INTEGRAL 90 MINUTE EMERGENCY BATTERY.
277 V 36 W LED
3500K
3750 FOCAL POINT - SEEM 2
F5 4" SQUARE DOWNLIGHT 4" APPERTURE X 8" HIGH OPEN DOWNLIGHT, LOW IRIDESCENT SEMI SPECULAR CLEAR ALUMINUM
RELFECTOR, SELF TRIM WITH WHITE FLANGE. 0-10V DIMMING DRIVER.
277 V 20 W LED
3500K
1500 FOCAL POINT - ID+3.5 X 3.5
F5-EM 4" SQUARE DOWNLIGHT 4" APPERTURE X 8" HIGH OPEN DOWNLIGHT, LOW IRIDESCENT SEMI SPECULAR CLEAR ALUMINUM
RELFECTOR, SELF TRIM WITH WHITE LANGE. 0-10V DIMMING DRIVER. PROVIDE WITH INTEGRAL 90
MINUTE EMERGENCY BATTERY.
277 V 20 W LED
3500K
1500 FOCAL POINT - ID+3.5 X 3.5
F6 WALL WASH FIXTURE 9"W X 6.2"T EXTRUDED ALUMINUM HOUSING, CONTINOUS FLUSH FROSTED ACYRLIC LENS. 0-10V
DIMMING DRIVER (10%-100%). LUMEN AND WATTAGE VALUES ARE PER FOOT.
277 V 7 W LED
3500K
650 FOCAL POINT - FWSL
FRH REMOTE HEAD POWERED BY EXIT SIGN 1 W LED EVENLITE - PRWLED1MV
FX EXIT SIGN WHITE LED ELECTRONIC EXIT LIGHT, SINGLE OR DOUBLE FACE AS INDICATED ON DRAWING
DOCUMENTS WITH UNIVERSAL SURFACE MOUNTING CANOPY, END, BACK OR TOP. DIRECTIONAL
ARROW, RED LETTERS "EXIT", NICKEL CADMIUM BATTERY. PROVIDE WITH SELF DIAGNOSTICS AND
CAPABILITY TO POWER REMOTE HEAD.
277 V 2 W LED EVENLITE - RZR3
Remarks:
X-Ray 56815 VA 95.89% 54479 VA Total Est. Demand Current: 290 A
Receptacle 88420 VA 55.65% 49210 VA Total Conn. Current: 340 A
Lighting 12453 VA 100.00% 12453 VA Total Est. Demand: 240921 VA
HVAC 122950 VA 100.00% 122950 VA Total Conn. Load: 282583 VA
Elevator 2400 VA 95.00% 2280 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Load Sumamry:
Total Load: 87.3 kVA 103.0 kVA 92.3 kVA
83 31.5 84
81 PROVISION -- -- 0 40.1 82
79 PROVISION -- -- 0 22.9
3 125 A T-1L1
80
77 PROVISION -- -- 0 0 -- -- PROVISION 78
75 PROVISION -- -- 0 0 -- -- PROVISION 76
73 PROVISION -- -- 0 0 -- -- PROVISION 74
71 PROVISION -- -- 0 0 -- -- PROVISION 72
69 PROVISION -- -- 0 0 -- -- PROVISION 70
67 PROVISION -- -- 0 0 -- -- PROVISION 68
65 PROVISION -- -- 0 0 -- -- PROVISION 66
63 PROVISION -- -- 0 0 -- -- PROVISION 64
61 0 0 1 20 A Spare 62
59 0 0 1 20 A Spare 60
57
Spare 20 A 3
0 0 1 20 A Spare 58
55 0 0 1 20 A Spare 56
53 0 0 1 20 A Spare 54
51
Spare 20 A 3
0 0 1 20 A Spare 52
49 17.7 0 1 20 A Spare 50
47 17.7 2 1 20 A Tenant 12 Lighting 48
45
X-Ray 1113 Main Breaker 80 A 3
17.7 2.4 1 20 A Tenant 11 Lighting 46
43 7 2.5 1 20 A Tenant 11 Lighting 44
41 7 2.4 1 20 A Tenant 11 Lighting 42
39
VAV-117 40 A 3
7 1 40
37 1.4 1 38
35 1.4 1
3 20 A VAV-116
36
33
VAV-115 20 A 3
1.4 3.2 34
31 2.3 3.2 32
29 2.3 3.2
3 20 A VAV-114
30
27
VAV-112,113 20 A 3
2.3 3.6 28
25 2.7 3.6 26
23 2.7 3.6
3 20 A VAV-108
24
21
VAV-111 20 A 3
2.7 4 22
19 3.3 4 20
17 3.3 4
3 20 A VAV-106
18
15
VAV-109,110 20 A 3
3.3 3.6 16
13 4.2 3.6 14
11 4.2 3.6
3 20 A VAV-102,103,104,105
12
9
VAV-101,107 20 A 3
4.2 4.5 1 20 A WH-2 10
7 Core Lighting 20 A 1 1.2 4.5 1 20 A WH-1 8
5 Monument Sign 20 A 1 0.5 2.2 1 20 A UH-3 6
3 East and North Exterior Lighting 20 A 1 0.7 1.5 1 20 A UH-1 4
1 West and South Exterior Lighting 20 A 1 1 1.5 1 20 A UH-1 2
Circuit
Number Circuit Description Trip Poles A B C Poles Trip Circuit Description
Circuit
Number
General Panel Comments:
Enclosure Type: Type 1 Ground: Yes Main Rating: 400A
Mounting: Surface Wire: 4 Main Type: MLO
Supplied From: MDP Phase: 3 A.I.C. Rating:
Location: Voltage: 480/277 Wye Branch: Normal
Branch Panel:1H1
REVISION SCHEDULE
NO. DESCRIPTION DATE
09/17/20